Variable frequency drive (HVAC fan and pump) · BACnet points list

Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP) BACnet points list

Updated 6 November 2026

Short answer

The FR-F800 runs BACnet MS/TP on its RS-485 terminals when Pr.549 = 2; the FR-F800-E Ethernet models also offer BACnet IP. Both manuals print the same fixed object list: terminal inputs and outputs, run/stop, direction and fault reset BVs, the Speed scale frequency command (% of Pr.390), PID setpoint and feedback commands, output monitors, fault history and a mailbox for other parameters. The drive is a B-ASC.

This page lists 81 BACnet objects for the Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP) — 33 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP)
Equipment
Variable frequency drive (HVAC fan and pump)
Equipment type
VFDs & pumps
BACnet objects
81 (33 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
PICS firmware revision 2.00 (MS/TP manual); 1.00 in the Ethernet manual PICS
Default device instance
0
Also known as
FR-F800, FR-F800-E, FR-F820, FR-F840, FR-F842, FR-F846, FR-F820-E, FR-F840-E, FR-F842-E, FR-F846-E, Mitsubishi FR-F800 BACnet, IB-0600547ENG, IB-0600628ENG
Source document
FR-F800 Instruction Manual (Detailed), 5.12.7 BACnet MS/TP protocol, Supported BACnet object; also FR-A800-E/FR-F800-E Ethernet Function Manual, 2.5.7 BACnet/IP · IB-0600547ENG-G (BACnet IP: IB-0600628ENG-D) · rev. 2024-10
Download CSV 81 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Mitsubishi Electric’s current documentation and the live device before use. Not official Mitsubishi Electric information. Terms of use.

BMS integration notes: Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP)

Integration in brief

For MS/TP set Pr.549 = 2, the MAC address in Pr.331, the baud rate in Pr.332 and the device instance in Pr.728/Pr.729. For BACnet IP on an F800-E set 47808 in one of Pr.1427-Pr.1429 and allow the BMS IP range in Pr.1449-Pr.1454. With the drive in Network operation mode and NET as command and speed source, write AV 300 Speed scale and BV 400 Run/Stop, and read BV 0, AV 1, AV 2 and BV 99.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 400Run/StopStart/stop command (1 = start)Command
AV 300Speed scaleFrequency command, % of Pr.390Command
BV 402Fault resetClears the fault outputCommand
BV 0Inverter runningRunning statusRead
BV 11Inverter operation readyDrive ready to runRead
AV 1Output frequencyOutput frequency, HzRead
AV 2Output currentMotor ampsRead
AV 14Output powerOutput power, kWRead
BV 99Fault outputAny active drive faultRead
AV 200Alarm history 1Latest fault recordRead

Enable & remote start

BV 400/401 and the AV 300-322 commands can be written at any time but are only applied when the communication operation command source and speed command source are NET (Pr.338/Pr.339) and the drive is in Network operation mode. The start command takes effect after Speed scale is applied.

Heartbeat & communication loss

The MS/TP section gives no BACnet-specific timeout. For RS-485 terminal communication, Pr.502 sets the action on a communication error (coast, decelerate to stop, or keep running at the Pr.779 frequency) and the LF alarm turns on. On an F800-E, Pr.1432 Ethernet communication check time interval (default 9999 = off) trips E.EHR if the devices in the Pr.1449-Pr.1454 range stop sending; Pr.1431 sets the action on a physical Ethernet loss.

Sensors & values from the BMS

AV 311 PID measured value CMD lets the BMS write the PID feedback (and AV 310 the setpoint) when Pr.128 = 60 or 61; AV 321/AV 320 do the same for the second PID when Pr.753 = 60 or 61.

Network setup

Watch out for

Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

81 of 81 shown
Type
Access
Show
Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP) BACnet Points List
DescriptionStates
AI0Terminal 1Terminal 1 input level (range per Pr.73/Pr.267)%Read
AI1Terminal 2Terminal 2 input level (range per Pr.73/Pr.267)%Read
AI2Terminal 4Terminal 4 input level (range per Pr.73/Pr.267)%Read
AO0Terminal FM (CA)Terminal FM/CA output level, 0-200 %; needs Pr.54 = 85%Command
AO1Terminal AMTerminal AM output level, -200 to 200 %; needs Pr.158 = 86%Command
AVmin1Output frequencyOutput frequencyHzRead
AVmin2Output currentOutput currentARead
AV3Output voltageOutput voltageVRead
AV6Running speedRunning speedrpmRead
AV8Converter output voltageConverter (DC bus) output voltageVRead
AVmin14Output powerOutput powerkWRead
AV17Load meterLoad meter%Read
AV20Cumulative energization timeCumulative power-on timehRead
AV23Actual operation timeActual run timehRead
AV25Cumulative powerCumulative energykWhRead
AV52PID set pointPID setpoint monitorRead
AV54PID deviationPID deviation monitorRead
AV67PID measured value2PID measured value 2 monitorRead
AV92Second PID set pointSecond PID setpoint monitorRead
AV94Second PID deviationSecond PID deviation monitorRead
AV95Second PID measured value 2Second PID measured value 2 monitorRead
AVmin200Alarm history 1Fault record 1 (latest)Read
AV201Alarm history 2Fault record 2Read
AV202Alarm history 3Fault record 3Read
AV203Alarm history 4Fault record 4Read
AVmin300Speed scaleFrequency command as % of Pr.390, 0.00-100.00%Command
AV310PID set point CMDPID setpoint when Pr.128 = 60 or 61, 0-100Command
AV311PID measured value CMDPID measured value when Pr.128 = 60 or 61, 0-100Command
AV312PID deviation CMDPID deviation when Pr.128 = 50 or 51, -100 to 100%Command
AV320Second PID set point CMDSecond PID setpoint when Pr.753 = 60 or 61Command
AV321Second PID measured value CMDSecond PID measured value when Pr.753 = 60 or 61Command
AV322Second PID deviation CMDSecond PID deviation when Pr.753 = 50 or 51%Command
AV398Mailbox parameterRegister number for indirect accessWrite
AV399Mailbox valueValue read or written through the mailboxWrite
AV10007Acceleration timePr.7 acceleration timesWrite
AV10008Deceleration timePr.8 deceleration timesWrite
BI0Terminal STFInput terminal STF stateRead0=Inactive, 1=Active
BI1Terminal STRInput terminal STR stateRead0=Inactive, 1=Active
BI2Terminal AUInput terminal AU stateRead0=Inactive, 1=Active
BI3Terminal RTInput terminal RT stateRead0=Inactive, 1=Active
BI4Terminal RLInput terminal RL stateRead0=Inactive, 1=Active
BI5Terminal RMInput terminal RM stateRead0=Inactive, 1=Active
BI6Terminal RHInput terminal RH stateRead0=Inactive, 1=Active
BI7Terminal JOGInput terminal JOG stateRead0=Inactive, 1=Active
BI8Terminal MRSInput terminal MRS stateRead0=Inactive, 1=Active
BI9Terminal STOPInput terminal STOP stateRead0=Inactive, 1=Active
BI10Terminal RESInput terminal RES stateRead0=Inactive, 1=Active
BI11Terminal CSInput terminal CS stateRead0=Inactive, 1=Active
BI100Terminal RUNOutput terminal RUN stateRead0=Inactive, 1=Active
BI101Terminal SUOutput terminal SU stateRead0=Inactive, 1=Active
BI102Terminal IPFOutput terminal IPF stateRead0=Inactive, 1=Active
BI103Terminal OLOutput terminal OL stateRead0=Inactive, 1=Active
BI104Terminal FUOutput terminal FU stateRead0=Inactive, 1=Active
BI105Terminal ABC1Output terminal ABC1 stateRead0=Inactive, 1=Active
BI106Terminal ABC2Output terminal ABC2 stateRead0=Inactive, 1=Active
BI107Terminal So (SO)Output terminal So (SO) stateRead0=Inactive, 1=Active
BO0Terminal RUN CMDDrives output RUN; needs Pr.190 = 82 or 182Command0=Inactive, 1=Active
BO1Terminal SU CMDDrives output SU; needs Pr.191 = 82 or 182Command0=Inactive, 1=Active
BO2Terminal IPF CMDDrives output IPF; needs Pr.192 = 82 or 182Command0=Inactive, 1=Active
BO3Terminal OL CMDDrives output OL; needs Pr.193 = 82 or 182Command0=Inactive, 1=Active
BO4Terminal FU CMDDrives output FU; needs Pr.194 = 82 or 182Command0=Inactive, 1=Active
BO5Terminal ABC1 CMDDrives output ABC1; needs Pr.195 = 82 or 182Command0=Inactive, 1=Active
BO6Terminal ABC2 CMDDrives output ABC2; needs Pr.196 = 82 or 182Command0=Inactive, 1=Active
BVmin0Inverter runningRunning (RUN signal)Read0=Inactive, 1=Active
BVmin11Inverter operation readyReady to run (RY signal)Read0=Inactive, 1=Active
BV98Alarm outputAlarm (LF signal)Read0=Inactive, 1=Active
BVmin99Fault outputFault (ALM signal)Read0=Inactive, 1=Active
BV200Inverter running reverseRunning in reverseRead0=Inactive, 1=Active
BV300Control input instruction AUTurns on the function set in Pr.184 (terminal AU)Command0=Inactive, 1=Active
BV301Control input instruction RTTurns on the function set in Pr.183 (terminal RT)Command0=Inactive, 1=Active
BV302Control input instruction RLTurns on the function set in Pr.180 (terminal RL)Command0=Inactive, 1=Active
BV303Control input instruction RMTurns on the function set in Pr.181 (terminal RM)Command0=Inactive, 1=Active
BV304Control input instruction RHTurns on the function set in Pr.182 (terminal RH)Command0=Inactive, 1=Active
BV305Control input instruction JOGTurns on the function set in Pr.185 (terminal JOG)Command0=Inactive, 1=Active
BV306Control input instruction MRSTurns on the function set in Pr.187 (terminal MRS)Command0=Inactive, 1=Active
BV307Control input instruction STOPTurns on the function set in Pr.188 (terminal STOP)Command0=Inactive, 1=Active
BV308Control input instruction RESTurns on the function set in Pr.189 (terminal RES)Command0=Inactive, 1=Active
BV309Control input instruction CSTurns on the function set in Pr.186 (terminal CS)Command0=Inactive, 1=Active
BVmin400Run/StopStart/stop commandCommand0=Stop, 1=Start
BV401Forward/ReverseRotation directionCommand0=Forward rotation, 1=Reverse rotation
BVmin402Fault resetClears the fault output without resetting the driveCommand
Object ID lookup: Mitsubishi Electric FR-F800 inverter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP)

How many BACnet points does the Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP) have?

This list has 81 BACnet objects: 3 analog inputs, 2 analog outputs, 31 analog values, 20 binary inputs, 7 binary outputs, 18 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP) BACnet points are writable?

33 of the 81 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP) BACnet documentation?

The source is FR-F800 Instruction Manual (Detailed), 5.12.7 BACnet MS/TP protocol, Supported BACnet object; also FR-A800-E/FR-F800-E Ethernet Function Manual, 2.5.7 BACnet/IP (IB-0600547ENG-G (BACnet IP: IB-0600628ENG-D)), revision 2024-10, published free by Mitsubishi Electric at https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600547eng/ib0600547engg.pdf.

What are the minimum BACnet points to integrate the Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP)?

Start with BV 400 Run/Stop (Start/stop command (1 = start)); AV 300 Speed scale (Frequency command, % of Pr.390); BV 402 Fault reset (Clears the fault output); BV 0 Inverter running (Running status); BV 11 Inverter operation ready (Drive ready to run); AV 1 Output frequency (Output frequency, Hz); AV 2 Output current (Motor amps); AV 14 Output power (Output power, kW); BV 99 Fault output (Any active drive fault); AV 200 Alarm history 1 (Latest fault record).

How do I enable BMS control of the Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP)?

BV 400/401 and the AV 300-322 commands can be written at any time but are only applied when the communication operation command source and speed command source are NET (Pr.338/Pr.339) and the drive is in Network operation mode. The start command takes effect after Speed scale is applied.

Does the Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP) need a BACnet heartbeat or have a communication timeout?

The MS/TP section gives no BACnet-specific timeout. For RS-485 terminal communication, Pr.502 sets the action on a communication error (coast, decelerate to stop, or keep running at the Pr.779 frequency) and the LF alarm turns on. On an F800-E, Pr.1432 Ethernet communication check time interval (default 9999 = off) trips E.EHR if the devices in the Pr.1449-Pr.1454 range stop sending; Pr.1431 sets the action on a physical Ethernet loss.

Can the BMS supply sensor values to the Mitsubishi Electric FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP)?

AV 311 PID measured value CMD lets the BMS write the PID feedback (and AV 310 the setpoint) when Pr.128 = 60 or 61; AV 321/AV 320 do the same for the second PID when Pr.753 = 60 or 61.

How do I check these points on the real FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Mitsubishi Electric BACnet points lists

Source: FR-F800 Instruction Manual (Detailed), 5.12.7 BACnet MS/TP protocol, Supported BACnet object; also FR-A800-E/FR-F800-E Ethernet Function Manual, 2.5.7 BACnet/IP · IB-0600547ENG-G (BACnet IP: IB-0600628ENG-D) · rev. 2024-10. Object names, instances and units are reproduced as published; descriptions are our own.