Air-to-water heat pump interface · BACnet points list

Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units BACnet points list

Updated 11 November 2026

Short answer

For air-to-water (Ecodan) systems the MelcoBEMS MINI (A1M+) serves a large object set on BACnet MS/TP or BACnet IP: system on/off, operating mode, DHW and zone setpoints, prohibit and forced-DHW commands, then many read-only analog inputs for temperatures, flow, heat pump frequencies, run hours, error codes, energy produced and consumed, and FTC configuration. Many status values are coded integers in analog inputs rather than binary or multistate objects.

This page lists 259 BACnet objects for the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units
Equipment
Air-to-water heat pump interface
Equipment type
Heat pumps
BACnet objects
259 (27 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
4.1.1
Also known as
A1M+ ATW, MelcoBEMS MINI A1M PLUS Ecodan, Procon A1M+ Ecodan
Source document
Procon MelcoBEMS MINI (A1M+) Installation Manual (manual 1.0.3, firmware 4.1.1)
Download CSV 259 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Mitsubishi Electric’s current documentation and the live device before use. Not official Mitsubishi Electric information. Terms of use.

BMS integration notes: Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units

Integration in brief

Select BACnet with DIP switch 7, then write system on/off, the operating mode, DHW tank and zone setpoints, and read flow, return and tank temperatures plus the error objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0ATW Drive OFF/ON SetupSystem on/off commandCommand
MO 1ATW Mode SetupOperating mode commandCommand
AV 5ATW Tank Setpoint IntDHW tank setpointCommand
AV 6ATW Zone1 HC Target Temperature IntZone 1 target temperatureCommand
MO 3ATW Zone 1 Operation Mode ACZone 1 operation mode (room/flow/curve)Command
AI 51ATW Flow Temperature IntFlow temperatureRead
AI 52ATW Return Temperature IntReturn temperatureRead
AI 53ATW Water Temperature IntWater (tank) temperatureRead
AI 29ATW Refrigerant Error InfoRefrigerant error state, 0 = normalRead

Enable & remote start

No separate enable; the Setup objects command the FTC directly. Prohibit objects (BO 11-15, AV 8) lock functions at the unit's remote controller.

Network setup

Watch out for

Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

259 of 259 shown
Type
BinaryMulti-state
Access
Show
Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units BACnet Points List
DescriptionStates
BOmin0ATW Drive OFF/ON SetupCommand0=System OFF, 1=System ON
MOmin1ATW Mode SetupCommand1=Stop, 2=Hot Water, 3=Heating, 4=Cooling, 5=No voltage contact input (hot water storage), 6=Freeze Stat, 7=Legionella, 8=Heating-Eco, 9=Mode 1, 10=Mode 2, 11=Mode 3, 12=No voltage contact input (heating up)
BO2ATW DHW Mode SetupCommand0=Normal, 1=Eco
MOmin3ATW Zone 1 Operation Mode ACCommand1=Heating Room Temp, 2=Heating Flow Temp, 3=Heating Heat Curve, 4=Cooling Room Temperature (not on 13K model), 5=Cooling Flow Temp, 6=Floor Dryup
MO4ATW Zone 2 Operation Mode ACCommand1=Heating Room Temp, 2=Heating Flow Temp, 3=Heating Heat Curve, 4=Cooling Room Temperature (not on 13K model), 5=Cooling Flow Temp, 6=Floor Dryup
AVmin5ATW Tank Setpoint Int°C/°FCommand
AVmin6ATW Zone1 HC Target Temperature Int°C/°FCommand
AV7ATW Zone2 HC Target Temperature Int°C/°FCommand
AV8ATW MRC OperationProhibitBit packed valueCommand
BO9ATW Forced DHW SetupCommand0=Normal, 1=Force DHW
BO10ATW Holiday SetupCommand0=Normal, 1=Holiday
BO11ATW DHW ON Prohibit SetupCommand0=On, 1=Prohibit
BO12ATW ZONE1 Heating ON SetupCommand0=On, 1=Prohibit
BO13ATW ZONE1 Cooling ON SetupCommand0=On, 1=Prohibit
BO14ATW ZONE2 Heating ON SetupCommand0=On, 1=Prohibit
BO15ATW ZONE2 Cooling ON SetupCommand0=On, 1=Prohibit
BO16ATW Capacity Mode SetupCommand0=COP priority, 1=Capacity priority
AV17ATW Capacity Control Ratio0-100 %%Command
BO18ATW Fan Mode SetupCommand0=Ordinary, 1=Coercion
AV19ATW Current HourCommand
AV20ATW Current MinuteCommand
AV21ATW Outdoor Air Temperature Int°C/°FCommand
AV22ATW Setting Water Temperature Int°C/°FCommand
AV23ATW Therm Target Temperature Int - Zone 1°C/°FCommand
AV24ATW Therm Target Temperature Int - Zone 2°C/°FCommand
MO25ATW HC Control TypeCommand1=Heating, 2=Cooling
AI26ATW Own Refrigerant AddressRead
AI27ATW DefrostRead0=Normal, 1=Standby, 2=Defrost, 3=Waiting Restart
AI28ATW Residual Heat RemovalRead0=Normal, 1=Prepared, 2=Residual Heat Removal
AImin29ATW Refrigerant Error InfoRead0=Normal, 1=Error (System), 2=Error (Startup), 3=Maintenance Error
AI30ATW 7-Segment Display Error Code Digit 1Read0=A, 1=b, 2=E, 3=F, 4=J, 5=L, 6=P, 7=U
AI31ATW 7-Segment Display Error Code Digit 27-segment error code digit (code table in guide)Read
AI32ATW Status Of HeatingReadFTC4: 0=No type, 1=Heating C1, 2=Heating C2, 3=Heating C3; FTC5/6/7: 0=No type, 1=Heating/Cooling A1/B1/C1, 2=Heating/Cooling A2/B2/C2, 3=Heating/Cooling A3/B3/C3
AI33ATW HeatPumpFreq MasterHzRead
AI34ATW HeatPumpFreq Slave1HzRead
AI35ATW HeatPumpFreq Slave2HzRead
AI36ATW HeatPumpFreq Slave3HzRead
AI37ATW HeatPumpFreq Slave4HzRead
AI38ATW HeatPumpFreq Slave5HzRead
AI39ATW HeatPumpFreq Slave6HzRead
AI40ATW Heat Source StatusRead0=H/P, 1=IH, 2=BH, 3=IH + BH, 4=Boiler
AI41ATW Zone1 Temperature Setpoint Int°C/°FRead
AI42ATW Zone2 Temperature Setpoint Int°C/°FRead
AI43ATW Zone1 Flow Temperature Setpoint Int°C/°FRead
AI44ATW Zone2 Flow Temperature Setpoint Int°C/°FRead
AI45ATW Legionella Temperature Setpoint Int°C/°FRead
AI46ATW Dhw Temperaturedrop Int°C/°FRead
AI47ATW Zone1roomtemperature Int°C/°FRead
AI48ATW Zone2roomtemperature Int°C/°FRead
AI49ATW Refrigerant Liquid Temperature Int°C/°FRead
AI50ATW Ambient Temperature Int°C/°FRead
AImin51ATW Flow Temperature Int°C/°FRead
AImin52ATW Return Temperature Int°C/°FRead
AImin53ATW Water Temperature Int°C/°FRead
AI54ATW Flow Temperature Zone1 Int°C/°FRead
AI55ATW Return Temperature Zone1 Int°C/°FRead
AI56ATW Flow Temperature Zone2 Int°C/°FRead
AI57ATW Return Temperature Zone2 Int°C/°FRead
AI58ATW Flow Temperature Boiler Int°C/°FRead
AI59ATW Return Temperature Boiler Int°C/°FRead
AI60ATW Roomthermo1 IN1Read0=OFF, 1=ON
AI61ATW Roomthermo2 IN6Read0=OFF, 1=ON
AI62ATW Flow SW1 IN2Read0=OFF, 1=ON
AI63ATW Flow SW2 IN3Read0=OFF, 1=ON
AI64ATW Flow SW3 IN7Read0=OFF, 1=ON
AI65ATW Demand IN4Read0=OFF, 1=ON
AI66ATW Outdoorthermo IN5Read0=OFF, 1=ON
AI67ATW DipSwitch SW2DIP switch SW2 bitsRead
AI68ATW Heatpump Master ONOFFRead0=Stop, 1=Run
AI69ATW Heatpump Slave ONOFF 0Read0=Stop, 1=Run
AI70ATW Heatpump Slave ONOFF 1Read0=Stop, 1=Run
AI71ATW Heatpump Slave ONOFF 2Read0=Stop, 1=Run
AI72ATW Heatpump Slave ONOFF 3Read0=Stop, 1=Run
AI73ATW Heatpump Slave ONOFF 4Read0=Stop, 1=Run
AI74ATW Heatpump Slave ONOFF 5Read0=Stop, 1=Run
AI75ATW Heatpump Slave ONOFF 6Read0=Stop, 1=Run
AI76ATW Heatpump Slave ONOFF 7Read0=Stop, 1=Run
AI77ATW Heatpump Runtime HourshRead
AI78ATW Heatpump Runtime Hours x100hRead
AI79ATW Heatpump Refaddr1 Runtime Hours x100hRead
AI80ATW Heatpump Refaddr2 Runtime Hours x100hRead
AI81ATW Heatpump Refaddr3 Runtime Hours x100hRead
AI82ATW Heatpump Refaddr4 Runtime Hours x100hRead
AI83ATW Heatpump Refaddr5 Runtime Hours x100hRead
AI84ATW Heatpump Refaddr6 Runtime Hours x100hRead
AI85ATW Boiler ONOFFRead0=Stop, 1=Run
AI86ATW Boosterheater1 ONOFFRead0=Stop, 1=Run
AI87ATW Boosterheater2 ONOFFRead0=Stop, 1=Run
AI88ATW Boosterheater2plus ONOFFRead0=Stop, 1=Run
AI89ATW Immersionheater ONOFFRead0=Stop, 1=Run
AI90ATW Waterpump1 ONOFFRead0=Stop, 1=Run
AI91ATW Waterpump2 ONOFFRead0=Stop, 1=Run
AI92ATW Waterpump3 ONOFFRead0=Stop, 1=Run
AI93ATW 3wayvalve ONOFFRead0=Stop, 1=Run
AI94ATW 2wayvalve2 ONOFFRead0=Stop, 1=Run
AI95ATW MixingvalvestepRead
AI96ATW Ref1 Errcode Upper Digit7-segment error code digit (code table in guide)Read
AI97ATW Ref1 Errcode Lower Digit7-segment error code digit (code table in guide)Read
AI98ATW Ref2 Errcode Upper Digit7-segment error code digit (code table in guide)Read
AI99ATW Ref2 Errcode Lower Digit7-segment error code digit (code table in guide)Read
AI100ATW Ref3 Errcode Upper Digit7-segment error code digit (code table in guide)Read
AI101ATW Ref3 Errcode Lower Digit7-segment error code digit (code table in guide)Read
AI102ATW Ref4 Errcode Upper Digit7-segment error code digit (code table in guide)Read
AI103ATW Ref4 Errcode Lower Digit7-segment error code digit (code table in guide)Read
AI104ATW Ref5 Errcode Upper Digit7-segment error code digit (code table in guide)Read
AI105ATW Ref5 Errcode Lower Digit7-segment error code digit (code table in guide)Read
AI106ATW Ref6 Errcode Upper Digit7-segment error code digit (code table in guide)Read
AI107ATW Ref6 Errcode Lower Digit7-segment error code digit (code table in guide)Read
AI108ATW Heatpump Freq 0HzRead
AI109ATW Heatpump Freq 1HzRead
AI110ATW Heatpump Freq 2HzRead
AI111ATW Heatpump Freq 3HzRead
AI112ATW Heatpump Freq 4HzRead
AI113ATW Heatpump Freq 5HzRead
AI114ATW Heatpump Freq 6HzRead
AI115ATW Heatpump Freq 7HzRead
AI116ATW Heatpump Freq 8HzRead
AI117ATW Heatpump Operation 0Read0=Stop, 1=Run
AI118ATW Heatpump Operation 1Read0=Stop, 1=Run
AI119ATW Heatpump Operation 2Read0=Stop, 1=Run
AI120ATW Heatpump Operation 3Read0=Stop, 1=Run
AI121ATW Heatpump Operation 4Read0=Stop, 1=Run
AI122ATW Heatpump Operation 5Read0=Stop, 1=Run
AI123ATW Heatpump Operation 6Read0=Stop, 1=Run
AI124ATW Heatpump Operation 7Read0=Stop, 1=Run
AI125ATW Heatpump Operation 8Read0=Stop, 1=Run
AI126ATW Heatpump Operation 9Read0=Stop, 1=Run
AI127ATW Heatpump Operation 10Read0=Stop, 1=Run
AI128ATW Heatpump Operation 11Read0=Stop, 1=Run
AI129ATW Heatpump Operation 12Read0=Stop, 1=Run
AI130ATW Heatpump Operation 13Read0=Stop, 1=Run
AI131ATW Heatpump Operation 14Read0=Stop, 1=Run
AI132ATW Heatpump Operation 15Read0=Stop, 1=Run
AI133ATW Heatpump Operation 16Read0=Stop, 1=Run
AI134ATW Heatpump Operation 17Read0=Stop, 1=Run
AI135ATW Heatpump Operation 18Read0=Stop, 1=Run
AI136ATW Heatpump Operation 19Read0=Stop, 1=Run
AI137ATW Heatpump Operation 20Read0=Stop, 1=Run
AI138ATW Heatpump Operation 21Read0=Stop, 1=Run
AI139ATW Heatpump Operation 22Read0=Stop, 1=Run
AI140ATW Externalheater OperationRead0=Stop, 1=Run
AI141ATW Waterpump Operation 0Read0=Stop, 1=Run
AI142ATW Waterpump Operation 1Read0=Stop, 1=Run
AI143ATW Waterpump Operation 2Read0=Stop, 1=Run
AI144ATW Waterpump Operation 3Read0=Stop, 1=Run
AI145ATW Waterpump Operation 4Read0=Stop, 1=Run
AI146ATW Waterpump Operation 5Read0=Stop, 1=Run
AI147ATW Waterpump Operation 6Read0=Stop, 1=Run
AI148ATW Waterpump Operation 7Read0=Stop, 1=Run
AI149ATW Waterpump Operation 8Read0=Stop, 1=Run
AI150ATW Waterpump Operation 9Read0=Stop, 1=Run
AI151ATW Waterpump Operation 10Read0=Stop, 1=Run
AI152ATW Waterpump Operation 11Read0=Stop, 1=Run
AI153ATW Waterpump Operation 12Read0=Stop, 1=Run
AI154ATW Drainpan Operation or Antifreeze piping heater operation ON/OFFRead0=Stop, 1=Run
AI155ATW Evaporating Temperature Int°C/°FRead
AI156ATW Condensing Temperature Int°C/°FRead
AI157ATW Electric Energy 1Electric energy part 1 (0.01 kWh steps)Read
AI158ATW Electric Energy 2Electric energy part 2 (0.01 kWh steps)Read
AI159ATW Electric Energy 3Electric energy part 3 (0.01 kWh steps)Read
AI160ATW Electric Energy 4Electric energy part 4 (0.01 kWh steps)Read
AI161ATW Electric Energy 5Read
AI162ATW Electric Energy 6Read
AI163ATW Electric Energy 7Read
AI164ATW Electric Energy 8Read
AI165ATW Electric Energy 9Read
AI166ATW Electric Energy 10Read
AI167ATW Electric Energy 11Read
AI168ATW Electric Energy 12Read
AI169ATW Electric Energy 13Read
AI170ATW Electric Energy 14Read
AI171ATW Electric Energy 15Read
AI172ATW Electric Energy 16Read
AI173ATW Brine Inlet Temperature Int°C/°FRead
AI174ATW Brine Outlet Temp1 Int°C/°FRead
AI175ATW Brine Outlet Temp2 Int°C/°FRead
AI176ATW Condensing Temp2 Int°C/°FRead
AI177ATW Water Outlet Temp2 Int°C/°FRead
AI178ATW Evaporating Temp2 Int°C/°FRead
AI179ATW PWM Duty Of Waterpump1Duty value in %Read
AI180ATW PWM Duty Feedback Waterpump1Duty value in %Read
AI181ATW 3way Valve 1Read0=OFF (stop), 1=ON (run)
AI182ATW Protocol Version UpperVersion of Protocol is a value in BCD e.gRead
AI183ATW Protocol Version LowerVersion of Protocol is a value in BCD e.gRead
AI184ATW Model Version UpperVersion of Model is a value in BCD e.gRead
AI185ATW Model Version LowerVersion of Model is a value in BCD e.gRead
AI186ATW Capacity Of Supply ElectricityValue x0.1 WRead
AI187ATW Model Profile 1Read0=FTC2B, 1=FTC4, 2=FTC5, 3=FTC6, 128=CAHV1A, 129=CAHV1B, 130=CRHV1A, 131=CRHV1B, 132=EAHV1A, 133=EAHV1B, 134=QAHV1A, 135=QAHV1B, 144=PWFY1
AI188ATW Model Profile 2Read
AI189ATW EnergyConsumptionYearDate of last energy consumption measurement – YearRead
AI190ATW EnergyConsumptionMonthDate of last energy consumption measurement – MonthRead
AI191ATW EnergyConsumptionDayDate of last energy consumption measurement – DayRead
AI192ATW EnergyConsumptionHeatingKwhLast measured heating energy consumption - kWh part of the valueRead
AI193ATW EnergyConsumptionHeatingWhRead
AI194ATW EnergyConsumptionCoolingKwhLast measured cooling energy consumption - kWh part of the valueRead
AI195ATW EnergyConsumptionCoolingWhRead
AI196ATW EnergyConsumptionDHWKwhLast measured DHW energy consumption - kWh part of the valueRead
AI197ATW EnergyConsumptionDHWWhRead
AI198ATW EnergyConsumptionTotalKwhRead
AI199ATW EnergyProducedYearDate of last energy produced measurement – YearRead
AI200ATW EnergyProducedMonthDate of last energy produced measurement – MonthRead
AI201ATW EnergyProducedDayDate of last energy produced measurement – DayRead
AI202ATW EnergyProducedHeatingKwhLast measured heating energy produced - kWh part of the valueRead
AI203ATW EnergyProducedHeatingWhRead
AI204ATW EnergyProducedCoolingKwhLast measured cooling energy produced - kWh part of the valueRead
AI205ATW EnergyProducedCoolingWhRead
AI206ATW EnergyProducedDHWKwhLast measured DHW energy produced - kWh part of the valueRead
AI207ATW EnergyProducedDHWWhRead
AI208ATW EnergyProducedTotalKwhLast measured total energy produced in KwhRead
AI209ATW FlowRate 1L/minRead
AI210ATW Date YearDate(year)Read
AI211ATW Date MonthDate(month)Read
AI212ATW Date DayDate(day)Read
AI213ATW Time HourTime(hour)Read
AI214ATW Time MinTime(minute)Read
AI215ATW Time SecTime(sec)Read
AI216ATW Version Main SWVersion of SoftwareRead
AI217ATW Version SubcodeSub-code Version of SoftwareRead
AI218ATW Demand Leg PreventionRead0=Normal, 1=Legionella Prevention
AI219ATW Type Emergency OpRead0=Normal, 1=Standby, 2=Backup
AI220ATW Zone1 Sensor SettingRead0=Main RC, 1-8=RoomRC1-8, 15=TH1
AI221ATW Zone2 Sensor SettingRead0=Main RC, 1-8=RoomRC1-8, 15=TH1
AI222ATW Freeze Stat Func Outdoor UnitRead0=Normal, 1=Freeze stat
AI223ATW Boiler ProtectionRead0=Normal, 1=Prepared, 2=Protected
AI224ATW Auto Restart PWR FailureRead0=Normal, 1=Standby, 2=IT initial setting standby
AI225ATW Demand of HeaterRead0=No demand, 1=Run, 2=Prohibit
AI226ATW Type Heating CoolingRead0=Type A, 1=Type B, 2=Type C
AI227ATW Zone1 HP Thermo Diff Adj ControlRead0=Normal, 1=discriminating, 2=adjustment ᵅ, 3=ᵝ, 4=ᵞ
AI228ATW Zone2 HP Thermo Diff Adj ControlRead0=Normal, 1=discriminating, 2=adjustment ᵅ, 3=ᵝ, 4=ᵞ
AI229ATW Slave Unit ConnectingSlave Unit Connection StatusRead
AI230ATW Slave Unit Operating StatusSlave Unit Operation StatusRead
AI231ATW HPFREQ4 StatusHzRead
AI232ATW Heatsource Phase DHWRead0=Normal, 1=H/P Phase, 2=Heater Phase
AI233ATW Heatsource TypeRead0=Fixed, 1=Auto
AI234ATW Heatsource Judgement conditionRead
AI235ATW Boiler Operation Hybrid SettingsRead0=Ambient, 1=Cost, 2=CO2
AI236ATW CP BoilerCP boilerRead
AI237ATW CO2 BoilerCO2 boilerRead
AI238ATW Energyprice ElectricityEnergy Price ElectricityRead
AI239ATW OC Connection ErrorOC Connection ErrorRead
AI240ATW RC Connection ErrorRC Connection ErrorRead
AI241ATW Consumed Electric PowerConsumed electric power/energyRead
AI242ATW Produced PowerProduced heat power/energyRead
AI243ATW Calc Func Consumed Electrical EnergyRead0=no function, 1=with function
AI244ATW Calcfunc Produced EnergyRead0=no function, 1=with function
AI245ATW Heatingfunction OnOffRead0=OFF (inactive), 1=ON (active)
AI246ATW Ext Outdoor AmbTempRead0=OFF, 1=ON
AI247ATW Mixtank Water Tempint°C/°FRead
AI248ATW Condensing Tempint°C/°FRead
AI249ATW Dipswitch SW1DipSW setting (SW1) lower byteRead
AI250ATW Dipswitch SW3DipSW setting (SW3) lower byteRead
AI251ATW Dipswitch SW4DipSW setting (SW4) lower byteRead
AI252ATW Dipswitch SW5DipSW setting (SW5) lower byteRead
AI253ATW Dipswitch SW6DipSW setting (SW6) lower byteRead
AI254ATW Flow Rate 2L/minRead
AI255ATW Waterpump4 OnOffRead0=Stop, 1=Run
AI256ATW 2WayValve 2a OnOffRead0=Stop, 1=Run
AI257ATW 2WayValve 2b OnOffRead0=Stop, 1=Run
MO258Temperature UnitsCommand1=ºC, 2=ºF
Object ID lookup: Mitsubishi Electric MelcoBEMS MINI Ecodan point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units

How many BACnet points does the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units have?

This list has 259 BACnet objects: 232 analog inputs, 11 analog values, 11 binary outputs, 5 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units BACnet points are writable?

27 of the 259 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units BACnet documentation?

The source is Procon MelcoBEMS MINI (A1M+) Installation Manual (manual 1.0.3, firmware 4.1.1), published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5538.

What are the minimum BACnet points to integrate the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units?

Start with BO 0 ATW Drive OFF/ON Setup (System on/off command); MO 1 ATW Mode Setup (Operating mode command); AV 5 ATW Tank Setpoint Int (DHW tank setpoint); AV 6 ATW Zone1 HC Target Temperature Int (Zone 1 target temperature); MO 3 ATW Zone 1 Operation Mode AC (Zone 1 operation mode (room/flow/curve)); AI 51 ATW Flow Temperature Int (Flow temperature); AI 52 ATW Return Temperature Int (Return temperature); AI 53 ATW Water Temperature Int (Water (tank) temperature); AI 29 ATW Refrigerant Error Info (Refrigerant error state, 0 = normal).

How do I enable BMS control of the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units?

No separate enable; the Setup objects command the FTC directly. Prohibit objects (BO 11-15, AV 8) lock functions at the unit's remote controller.

How do I check these points on the real Procon MelcoBEMS MINI (A1M+) - Air-To-Water (Ecodan) units?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.