Variable frequency drive (inverter) · BACnet points list

Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models) BACnet points list

Updated 7 November 2026

Short answer

Ethernet versions of the FR-E800 serve a fixed BACnet/IP object set: two analog input terminals, monitor and command Analog Values (frequency, current, power, energy, PID, fault history, speed scale, PID commands, a parameter mailbox and accel/decel times), terminal state BIs and BOs, and status and command BVs (run/stop, direction, fault reset). Some terminal objects do nothing on certain model variants.

This page lists 48 BACnet objects for the Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models) — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
FR-E800 inverter (BACnet IP, Ethernet models)
Equipment
Variable frequency drive (inverter)
Equipment type
VFDs & pumps
BACnet objects
48 (17 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
0
Also known as
FR-E800, FR-E800-E, FR-E820, FR-E840, FR-E860, IB-0600871ENG
Source document
FR-E800 Instruction Manual (Communication) · IB-0600871ENG-S · rev. 2026-05
Download CSV 48 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Mitsubishi Electric’s current documentation and the live device before use. Not official Mitsubishi Electric information. Terms of use.

BMS integration notes: Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models)

Integration in brief

Put the inverter in Network operation mode with the Ethernet connector as command source, then write AV 300 Speed scale as the speed command and start/stop with BV 400. Read BV 0, AV 1, AV 2, AV 14 and the fault objects; BV 402 resets a fault.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 400Run/StopStart/stop command (1 = start)Command
AV 300Speed scaleSpeed command as % ratio (speed scale)Command
BV 402Fault resetFault resetCommand
BV 0Inverter runningRunning statusRead
AV 1Output frequencyOutput frequency, HzRead
AV 2Output currentOutput current, ARead
AV 14Output powerOutput power, kWRead
BV 99Fault outputInverter faultRead
AV 200Alarm history 1Latest fault recordRead

Enable & remote start

The inverter must be in Network (NET) operation mode with the Ethernet port as command and speed source; otherwise writes are stored but not applied.

Heartbeat & communication loss

Pr.1432 Ethernet communication check time interval (0.1-999.8 s) trips the inverter with E.EHR if no allowed device talks to it; 9999 disables the check. Command devices are limited to the IP range in Pr.1449-Pr.1454.

Sensors & values from the BMS

AV 311 PID measured value CMD can feed the PID loop from the BMS when Pr.128 and Pr.610 select the network value.

Network setup

Watch out for

Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

48 of 48 shown
Type
Access
Show
Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models) BACnet Points List
DescriptionStates
AI1Terminal 2Terminal 2 analog input, 0-100 % of range%Read
AI2Terminal 4Terminal 4 analog input, 0-100 % of range%Read
AVmin1Output frequencyOutput frequencyHzRead
AVmin2Output currentOutput currentARead
AV3Output voltageOutput voltageVRead
AV6Running speedRunning speedrpmRead
AV8Converter output voltageDC bus (converter output) voltageVRead
AVmin14Output powerOutput powerkWRead
AV17Load meterLoad meter%Read
AV20Cumulative energization timeCumulative energization timehRead
AV23Actual operation timeActual operation timehRead
AV25Cumulative powerCumulative energykWhRead
AV52PID set pointPID set point (monitor)Read
AV54PID deviationPID deviation (monitor)Read
AV67PID measured value2PID measured value 2 (monitor)Read
AVmin200Alarm history 1Latest fault recordRead
AV201Alarm history 2Second latest fault recordRead
AV202Alarm history 3Third latest fault recordRead
AV203Alarm history 4Fourth latest fault recordRead
AVmin300Speed scaleFrequency command as ratio, 0.00-100.00 %%Command
AV310PID set point CMDPID set point from network, 0.00-100.00Command
AV311PID measured value CMDPID measured value from network, 0.00-100.00Command
AV312PID deviation CMDPID deviation from network, -100.00 to 100.00%Command
AV398Mailbox parameterParameter number for mailbox accessWrite
AV399Mailbox valueValue of the mailbox parameterWrite
AV10007Acceleration timePr.7 acceleration timesWrite
AV10008Deceleration timePr.8 deceleration timesWrite
BI0Terminal DI0Terminal DI0 input stateRead0=inactive, 1=active
BI1Terminal DI1Terminal DI1 input stateRead0=inactive, 1=active
BI100Terminal RUNTerminal RUN output stateRead0=inactive, 1=active
BI104Terminal FUTerminal FU output stateRead0=inactive, 1=active
BI105Terminal ABC/RO0Relay A-B-C output stateRead0=inactive, 1=active
BI106Terminal RO1Relay A2-B2-C2 output stateRead0=inactive, 1=active
BI107Terminal SOTerminal SO output stateRead0=inactive, 1=active
BO0Terminal RUN CMDDrives terminal RUN when Y82 is assignedCommand0=inactive, 1=active
BO4Terminal FU CMDDrives terminal FU when Y82 is assignedCommand0=inactive, 1=active
BO5Terminal ABC/RO0 CMDDrives relay A-B-C when Y82 is assignedCommand0=inactive, 1=active
BO6Terminal RO1 CMDDrives relay A2-B2-C2 when Y82 is assignedCommand0=inactive, 1=active
BVmin0Inverter runningRunning (RUN signal)Read
BV11Inverter operation readyReady (RY signal)Read
BV98Alarm outputAlarm (LF signal)Read
BVmin99Fault outputFault (ALM signal)Read
BV200Inverter running reverseRunning in reverseRead
BV300Control input instruction DI0Turns on the STF signalCommand
BV301Control input instruction DI1Turns on the STR signalCommand
BVmin400Run/StopStart/stop commandCommand0=Stop, 1=Start
BV401Forward/ReverseRotation direction commandCommand0=Forward, 1=Reverse
BVmin402Fault resetClears the fault outputCommand
Object ID lookup: Mitsubishi Electric FR-E800 inverter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FR-E800 inverter (BACnet IP, Ethernet models) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models)

How many BACnet points does the Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models) have?

This list has 48 BACnet objects: 2 analog inputs, 25 analog values, 7 binary inputs, 4 binary outputs, 10 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models) BACnet points are writable?

17 of the 48 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models) BACnet documentation?

The source is FR-E800 Instruction Manual (Communication) (IB-0600871ENG-S), revision 2026-05, published free by Mitsubishi Electric at https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600871eng/ib0600871engs.pdf.

What are the minimum BACnet points to integrate the Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models)?

Start with BV 400 Run/Stop (Start/stop command (1 = start)); AV 300 Speed scale (Speed command as % ratio (speed scale)); BV 402 Fault reset (Fault reset); BV 0 Inverter running (Running status); AV 1 Output frequency (Output frequency, Hz); AV 2 Output current (Output current, A); AV 14 Output power (Output power, kW); BV 99 Fault output (Inverter fault); AV 200 Alarm history 1 (Latest fault record).

How do I enable BMS control of the Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models)?

The inverter must be in Network (NET) operation mode with the Ethernet port as command and speed source; otherwise writes are stored but not applied.

Does the Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models) need a BACnet heartbeat or have a communication timeout?

Pr.1432 Ethernet communication check time interval (0.1-999.8 s) trips the inverter with E.EHR if no allowed device talks to it; 9999 disables the check. Command devices are limited to the IP range in Pr.1449-Pr.1454.

Can the BMS supply sensor values to the Mitsubishi Electric FR-E800 inverter (BACnet IP, Ethernet models)?

AV 311 PID measured value CMD can feed the PID loop from the BMS when Pr.128 and Pr.610 select the network value.

How do I check these points on the real FR-E800 inverter (BACnet IP, Ethernet models)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Mitsubishi Electric BACnet points lists

Source: FR-E800 Instruction Manual (Communication) · IB-0600871ENG-S · rev. 2026-05. Object names, instances and units are reproduced as published; descriptions are our own.