VRF central controller with BACnet IP · BACnet points list

Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan) BACnet points list

Updated 7 November 2026

Short answer

The AE-200J, AE-50J and EW-50J are the Japan-only central controllers for Mitsubishi Electric commercial air conditioning. With the BACnet license they act as a BACnet IP server and create a fixed set of objects per group, plus blocks for fire control, power-cut recovery, energy apportioning and DT-R / hot water heat pump / brine cooler systems. The manual is in Japanese and the object names are printed in Japanese; the English descriptions are ours. Objects only exist for the functions the connected unit type supports.

This page lists 77 BACnet objects for the Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan) — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
AE-200J / AE-50J / EW-50J BACnet (Japan)
Equipment
VRF central controller with BACnet IP
Equipment type
VRF & split air conditioners
BACnet objects
77 (24 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
AE-200J, AE-50J, EW-50J, AE-200J BACnet, 三菱電機 AE-200J BACnet機能
Source document
三菱電機空調冷熱総合管理システム AE-200J/AE-50J/EW-50J 取扱説明書 BACnet機能編 · WT07918X12
Download CSV 77 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Mitsubishi Electric’s current documentation and the live device before use. Not official Mitsubishi Electric information. Terms of use.

BMS integration notes: Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan)

Integration in brief

Register the BACnet connection license, set up LAN2 and the device number with the BACnet setting tool, then map the per-group objects 01GGPP. Start with on/off, mode, fan speed, setpoint, room temperature and the alarm points. Write only when a value changes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 10101運転/停止(設定)Start/stop the groupCommand
MO 10105運転モード(設定)Command the operating modeCommand
AV 10110室内温度設定値Setpoint for single-setpoint groupsWrite
AV 10124冷房温度設定値Cooling setpoint for dual-setpoint groupsWrite
AV 10125暖房温度設定値Heating setpoint for dual-setpoint groupsWrite
MO 10107風速(設定)Fan speed: 1 low, 2 high, 3 mid2, 4 mid1, 5 autoCommand
BI 10102運転/停止(状態)Confirm run statusRead
AI 10109室内温度計測値Room temperature, °CRead
BI 10103警報信号Group fault alarmRead
BI 10120通信状態M-NET link to the group lostRead

Enable & remote start

No enable point; BO/MO commands take effect directly. DT-R, brine coolers and hot water heat pumps accept commands only when their command source is set to the system controller, which locks out their own remote controllers.

Network setup

Watch out for

Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

77 of 77 shown
Type
Access
Show
Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan) BACnet Points List
DescriptionStates
BOmin10101運転/停止(設定)Start/stop command for the groupCommandInactive=停止, Active=運転
BImin10102運転/停止(状態)Run/stop statusReadInactive=停止, Active=運転
BImin10103警報信号Alarm signal (normal/error)ReadInactive=正常, Active=異常
MI10104異常コードError category codeRead1=正常, 2=その他の異常, 3=冷媒系異常, 4=水系異常, 5=空気系異常, 6=電気系異常, 7=センサー異常, 8=通信異常, 9=システム異常
MOmin10105運転モード(設定)Operating mode commandCommand1=冷房, 2=暖房, 3=送風, 4=自動, 5=ドライ
MI10106運転モード(状態)Operating mode statusRead1=冷房, 2=暖房, 3=送風, 4=自動, 5=ドライ
MOmin10107風速(設定)Fan speed commandCommand1=弱, 2=強, 3=中2, 4=中1, 5=自動
MI10108風速(状態)Fan speed statusRead1=弱, 2=強, 3=中2, 4=中1, 5=自動
AImin10109室内温度計測値Measured room temperature°CRead
AVmin10110室内温度設定値Room temperature setpoint (single setpoint)°CWrite
BI10111フィルターサインFilter signReadInactive=OFF, Active=ON
BV10112フィルターサインリセットFilter sign resetWriteInactive=リセット, Active=無効
BV10113リモコン操作禁止(運転/停止)Prohibit local remote on/offWriteInactive=許可, Active=禁止
BV10114リモコン操作禁止(運転モード)Prohibit local remote mode changeWriteInactive=許可, Active=禁止
BV10115リモコン操作禁止(フィルタリセット)Prohibit local remote filter resetWriteInactive=許可, Active=禁止
BV10116リモコン操作禁止(温度設定値)Prohibit local remote setpoint changeWriteInactive=許可, Active=禁止
BImin10120通信状態M-NET communication stateReadInactive=正常, Active=異常
BV10121緊急停止(個別)Emergency stop, this groupWriteInactive=解除, Active=実行
BV19921緊急停止(一括)Emergency stop, all groupsWriteInactive=解除, Active=実行
MO10122風向(設定)Air direction commandCommand1=水平, 2=下吹き60%, 3=下吹き80%, 4=下吹き100%, 5=スイング
MI10123風向(状態)Air direction statusRead1=水平, 2=下吹き60%, 3=下吹き80%, 4=下吹き100%, 5=スイング
AVmin10124冷房温度設定値Cooling setpoint (dual setpoint)°CWrite
AVmin10125暖房温度設定値Heating setpoint (dual setpoint)°CWrite
AV10126自動1値温度設定値Auto single setpoint°CWrite
MO10132ロスナイ発停・24時間換気(設定)Lossnay start/stop / 24 h ventilation commandCommand1=停止, 2=運転, 3=24時間換気
MI10133ロスナイ発停・24時間換気(状態)Lossnay start/stop / 24 h ventilation statusRead1=停止, 2=運転, 3=24時間換気
MO10135換気モード(設定)Ventilation mode commandCommand1=熱交換, 2=普通, 3=自動
MI10136換気モード(状態)Ventilation mode statusRead1=熱交換, 2=普通, 3=自動
ACC10139グループ按分電力量Apportioned group energy, 0.1 kWh stepskWhRead
ACC610139連動機按分電力量Apportioned energy of interlocked unitkWhRead
ACC410140計量用計測コントローラ電力量1Energy count, channel 1, 0.1 kWh steps (measuring controller 01)kWhRead
ACC410141計量用計測コントローラ電力量2Energy count, channel 2, 0.1 kWh steps (measuring controller 01)kWhRead
ACC410142計量用計測コントローラ電力量3Energy count, channel 3, 0.1 kWh steps (measuring controller 01)kWhRead
ACC410143計量用計測コントローラ電力量4Energy count, channel 4, 0.1 kWh steps (measuring controller 01)kWhRead
ACC410040計量用パルス入力電力量1Energy count, channel 1, 0.1 kWh steps (AE-50J/EW-50J pulse input)kWhRead
ACC410041計量用パルス入力電力量2Energy count, channel 2, 0.1 kWh steps (AE-50J/EW-50J pulse input)kWhRead
ACC410042計量用パルス入力電力量3Energy count, channel 3, 0.1 kWh steps (AE-50J/EW-50J pulse input)kWhRead
ACC410043計量用パルス入力電力量4Energy count, channel 4, 0.1 kWh steps (AE-50J/EW-50J pulse input)kWhRead
ACC10144グループ按分パラメータGroup apportionment parameterRead
ACC610144連動機按分パラメータInterlocked unit apportionment parameterRead
MI10145加湿(状態)Humidifier statusRead1=停止, 2=運転, 3=自動
BI10146ナイトパージ(状態)Night purge statusReadInactive=停止, Active=運転
BI10147サーモON/OFF(状態)Thermo ON/OFF statusReadInactive=OFF, Active=ON
BI10048システム警報信号System alarm signalReadInactive=正常, Active=異常
BI410103計量用計測コントローラ警報信号Measuring controller alarm signalReadInactive=正常, Active=異常
TL10180トレンドログ(室内温度計測値)Trend log of room temperatureRead
TL10183トレンドログ(グループ按分電力量)Trend log of apportioned group energyRead
TL610183トレンドログ(連動機按分電力量)Trend log of interlocked unit apportioned energyRead
TL410184トレンドログ(計量用計測コントローラ電力量1)Trend log of energy channel 1 (measuring controller 01)Read
TL410185トレンドログ(計量用計測コントローラ電力量2)Trend log of energy channel 2 (measuring controller 01)Read
TL410186トレンドログ(計量用計測コントローラ電力量3)Trend log of energy channel 3 (measuring controller 01)Read
TL410187トレンドログ(計量用計測コントローラ電力量4)Trend log of energy channel 4 (measuring controller 01)Read
TL410084トレンドログ(計量用パルス入力電力量1)Trend log of energy channel 1 (AE-50J/EW-50J pulse input)Read
TL410085トレンドログ(計量用パルス入力電力量2)Trend log of energy channel 2 (AE-50J/EW-50J pulse input)Read
TL410086トレンドログ(計量用パルス入力電力量3)Trend log of energy channel 3 (AE-50J/EW-50J pulse input)Read
TL410087トレンドログ(計量用パルス入力電力量4)Trend log of energy channel 4 (AE-50J/EW-50J pulse input)Read
TL10188トレンドログ(グループ按分パラメータ)Trend log of group apportionment parameterRead
TL610188トレンドログ(連動機按分パラメータ)Trend log of interlocked unit apportionment parameterRead
MI210100火災認識状態Fire control state (program 01 shown)Read1=正常, 2=火災中, 3=火災復旧待ち
BV219901火災復旧指令Fire recovery command (all programs)WriteInactive=(火災復旧待ち), Active=復旧
MI310100停電認識状態Power-cut recognition stateRead1=正常, 2=停電中, 3=復電待ち
BV319901復電指令Power restore commandWriteInactive=(復電待ち), Active=復電
BO710101DT-R運転/停止(設定)DT-R / hot water heat pump / brine cooler start/stop commandCommandInactive=停止, Active=運転
BI710102DT-R運転/停止(状態)DT-R / hot water heat pump / brine cooler run statusReadInactive=停止, Active=運転
MO710103DT-R運転モード(設定)DT-R operating mode commandCommand1=暖房, 2=冷房
MI710104DT-R運転モード(状態)DT-R operating mode statusRead1=暖房, 2=冷房
MO710105DT-Rファンモード(設定)DT-R / brine cooler fan mode command (normal/snow)Command1=常時, 2=降雪
MI710106DT-Rファンモード(状態)DT-R / brine cooler fan mode statusRead1=常時, 2=降雪
AV710107DT-R冷房温度設定値Cooling setpoint (hot water temp on hot water heat pump)°CWrite
AV710108DT-R暖房温度設定値Heating setpoint (warm water temp on hot water heat pump)°CWrite
AI710109DT-R入口代表水温計測値Representative inlet water temperature°CRead
AI710110DT-R出口代表水温計測値Representative outlet water temperature°CRead
BI710111DT-R一括異常System collective alarmReadInactive=正常, Active=異常
BI710112DT-R通信状態Communication stateReadInactive=正常, Active=異常
BI710113DT-R重故障Major fault (brine cooler BALV)ReadInactive=正常, Active=異常
AI710114DT-R運転容量状態Operating capacity (brine cooler BALV)%Read
BI910111DT-Rユニット異常状態Unit alarm state (unit 01)ReadInactive=正常, Active=異常
Object ID lookup: Mitsubishi Electric AE-200J / AE-50J / EW-50J point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AE-200J / AE-50J / EW-50J BACnet (Japan) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan)

How many BACnet points does the Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan) have?

This list has 77 BACnet objects: 4 analog inputs, 6 analog values, 13 binary inputs, 2 binary outputs, 9 binary values, 11 multi-state inputs, 7 multi-state outputs, 13 trend logs, 12 accumulators. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan) BACnet points are writable?

24 of the 77 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan) BACnet documentation?

The source is 三菱電機空調冷熱総合管理システム AE-200J/AE-50J/EW-50J 取扱説明書 BACnet機能編 (WT07918X12), published free by Mitsubishi Electric at https://dl.mitsubishielectric.co.jp/dl/ldg/wink/ssl/wink_doc/m_contents/wink/WPAC_IB/wt07918x12.pdf.

What are the minimum BACnet points to integrate the Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan)?

Start with BO 10101 運転/停止(設定) (Start/stop the group); MO 10105 運転モード(設定) (Command the operating mode); AV 10110 室内温度設定値 (Setpoint for single-setpoint groups); AV 10124 冷房温度設定値 (Cooling setpoint for dual-setpoint groups); AV 10125 暖房温度設定値 (Heating setpoint for dual-setpoint groups); MO 10107 風速(設定) (Fan speed: 1 low, 2 high, 3 mid2, 4 mid1, 5 auto); BI 10102 運転/停止(状態) (Confirm run status); AI 10109 室内温度計測値 (Room temperature, °C); BI 10103 警報信号 (Group fault alarm); BI 10120 通信状態 (M-NET link to the group lost).

How do I enable BMS control of the Mitsubishi Electric AE-200J / AE-50J / EW-50J BACnet (Japan)?

No enable point; BO/MO commands take effect directly. DT-R, brine coolers and hot water heat pumps accept commands only when their command source is set to the system controller, which locks out their own remote controllers.

How do I check these points on the real AE-200J / AE-50J / EW-50J BACnet (Japan)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Mitsubishi Electric BACnet points lists

Source: 三菱電機空調冷熱総合管理システム AE-200J/AE-50J/EW-50J 取扱説明書 BACnet機能編 · WT07918X12. Object names, instances and units are reproduced as published; descriptions are our own.