VRF BACnet IP interface (legacy) · BACnet points list

Mitsubishi Electric PAC-YG31CDA BACnet Interface BACnet points list

Updated 28 October 2026

Short answer

The PAC-YG31CDA is an older Mitsubishi Electric interface that talks to G-50A central controllers over Ethernet and presents each air-conditioner group as a block of BACnet IP objects. Each G-50A and group combination repeats the same template, and the device and notification class instances can be changed in its setting software.

This page lists 22 BACnet objects for the Mitsubishi Electric PAC-YG31CDA BACnet Interface — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
PAC-YG31CDA BACnet Interface
Equipment
VRF BACnet IP interface (legacy)
Equipment type
VRF & split air conditioners
BACnet objects
22 (11 writable)
Transport
BACnet IP
Firmware
Ver. 1.30
Default device instance
3
Also known as
PAC-YG31CDA, G-50A BACnet, BACnet Interface for G-50A
Source document
Mitsubishi Electric Air Conditioning Network System BACnet Interface: PAC-YG31CDA (Ver. 1.30) Operation Manual · WT04221X03 · rev. 2004-03
Download CSV 22 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Mitsubishi Electric PAC-YG31CDA BACnet Interface

Integration in brief

PAC-YG31CDA is BACnet interface software that runs on a PC and talks to up to ten G-50A controllers over Ethernet. Register the BACnet license in each G-50A, enter each G-50A's number and IP address in the software, then map the per-group objects (AAGGPP).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 10101On/Off (setup)Start/stop the groupWrite
MO 10105Operation mode (setup)Command the operating modeWrite
AV 10110Set Temp.Room temperature setpointWrite
MO 10107Fan Speed (setup)Fan speed: 1 low, 2 high, 3 mid2, 4 mid1Write
BI 10102On/Off (state)Confirm run statusRead
AI 10109Room Temp.Room temperature of the groupRead
BI 10103Alarm signalGroup fault alarmRead
BI 10120Communication StateGroup communication faultRead

Enable & remote start

A BACnet license number must be registered in each G-50A (Ver. 2.50 or later). Local remote-controller lockouts are the 'Prohibition of local operation' BVs (13-16) per group.

Network setup

Watch out for

Mitsubishi Electric PAC-YG31CDA BACnet Interface BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

22 of 22 shown
Type
Access
Show
Mitsubishi Electric PAC-YG31CDA BACnet Interface BACnet Points List
DescriptionStates
BOmin10101On/Off (setup)Start/stop command for the groupWriteInactive=Off, Active=On
BImin10102On/Off (state)Group run statusReadInactive=Off, Active=On
BImin10103Alarm signalGroup alarmReadInactive=Normal, Active=Abnormalities
MI10104Error CodeError category for the groupRead1=Normal, 2=Other abnormality, 3=Refrigerant system abnormality, 4=Water system abnormality, 5=Air system abnormality, 6=Electric system abnormality, 7=Sensor abnormality, 8=Communication abnormality, 9=System abnormality
MOmin10105Operation mode (setup)Operating mode commandWrite1=Cool, 2=Heat, 3=Fan, 4=Auto, 5=Dry
MI10106Operation mode (state)Current operating modeRead1=Cool, 2=Heat, 3=Fan, 5=Dry
MOmin10107Fan Speed (setup)Fan speed commandWrite1=Lo, 2=Hi, 3=Mid2, 4=Mid1
MI10108Fan Speed (state)Current fan speedRead1=Lo, 2=Hi, 3=Mid2, 4=Mid1
AImin10109Room Temp.Room temperature°F/°CRead
AVmin10110Set Temp.Setpoint°F/°CWrite
BI10111Filter SignalFilter signReadInactive=OFF, Active=ON
BV10112Filter Signal ResetResets the filter signWriteInactive=RESET, Active=Void
BV10113Prohibition of local operation (On/Off)Locks out local on/offWriteInactive=Permit, Active=Prohibit
BV10114Prohibition of local operation (Mode)Locks out local mode changeWriteInactive=Permit, Active=Prohibit
BV10115Prohibition of local operation (filter reset)Locks out local filter resetWriteInactive=Permit, Active=Prohibit
BV10116Prohibition of local operation (Set Temp.)Locks out local setpoint changeWriteInactive=Permit, Active=Prohibit
BImin10120Communication StateCommunication statusReadInactive=Normal, Active=Abnormalities
BV19921System Forced OffForced off for one G-50A systemWriteInactive=Released, Active=Effective
MO10122Air direction (setup)Vane direction commandWrite1=Horizontal, 2=Down 60%, 3=Down 80%, 4=Down100%, 5=Swing
MI10123Air direction (state)Current vane directionRead1=Horizontal, 2=Down 60%, 3=Down 80%, 4=Down100%, 5=Swing
NC3Notification ClassNotification class for alarmsRead
DEV3DeviceInterface device objectRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PAC-YG31CDA BACnet Interface and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric PAC-YG31CDA BACnet Interface

How many BACnet points does the Mitsubishi Electric PAC-YG31CDA BACnet Interface have?

This list has 22 BACnet objects: 1 analog input, 1 analog value, 4 binary inputs, 1 binary output, 6 binary values, 1 device, 4 multi-state inputs, 3 multi-state outputs, 1 notification class. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric PAC-YG31CDA BACnet Interface BACnet points are writable?

11 of the 22 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Mitsubishi Electric PAC-YG31CDA BACnet Interface BACnet documentation?

The source is Mitsubishi Electric Air Conditioning Network System BACnet Interface: PAC-YG31CDA (Ver. 1.30) Operation Manual (WT04221X03), revision 2004-03, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/2240.

What are the minimum BACnet points to integrate the Mitsubishi Electric PAC-YG31CDA BACnet Interface?

Start with BO 10101 On/Off (setup) (Start/stop the group); MO 10105 Operation mode (setup) (Command the operating mode); AV 10110 Set Temp. (Room temperature setpoint); MO 10107 Fan Speed (setup) (Fan speed: 1 low, 2 high, 3 mid2, 4 mid1); BI 10102 On/Off (state) (Confirm run status); AI 10109 Room Temp. (Room temperature of the group); BI 10103 Alarm signal (Group fault alarm); BI 10120 Communication State (Group communication fault).

How do I enable BMS control of the Mitsubishi Electric PAC-YG31CDA BACnet Interface?

A BACnet license number must be registered in each G-50A (Ver. 2.50 or later). Local remote-controller lockouts are the 'Prohibition of local operation' BVs (13-16) per group.

How do I check these points on the real PAC-YG31CDA BACnet Interface?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Mitsubishi Electric BACnet points lists

Source: Mitsubishi Electric Air Conditioning Network System BACnet Interface: PAC-YG31CDA (Ver. 1.30) Operation Manual · WT04221X03 · rev. 2004-03. Object names, instances and units are reproduced as published; descriptions are our own.