VRF BACnet IP gateway (legacy) · BACnet points list

Mitsubishi Electric Procon BAC-IP/50 BACnet points list

Updated 28 October 2026

Short answer

The Procon BAC-IP/50 is a small Mitsubishi Electric UK gateway that connects to a G-50 controller over Ethernet and serves up to 50 units as BACnet IP objects. Each unit address gets the same block of setup (_w) and state (_r) objects, named after the unit name typed into the configuration program. It does not support segmentation and its APDU limit is small, so keep read-multiple requests short.

This page lists 25 BACnet objects for the Mitsubishi Electric Procon BAC-IP/50 — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
Procon BAC-IP/50
Equipment
VRF BACnet IP gateway (legacy)
Equipment type
VRF & split air conditioners
BACnet objects
25 (10 writable)
Transport
BACnet IP
Firmware
v1.34 (manual v1.05, 20/07/2009)
Default device instance
10
Also known as
BAC-IP/50, BACIP50, Procon BAC IP 50
Source document
Procon BAC-IP/50 Installation and User Guide · rev. 2009-07-20
Download CSV 25 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Mitsubishi Electric Procon BAC-IP/50

Integration in brief

Give the BAC-IP/50 and its G-50 separate IP addresses on the same subnet, set the device ID and unit names with the PC configuration program, then map the per-unit _w (command) and _r (status) objects. Only the master unit of each group accepts commands.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 100101nnn_ON_wStart/stop the unitCommand
MO 100104nnn_MD_wCommand the operating modeCommand
AO 100109nnn_SP_wSetpoint commandCommand
MO 100106nnn_FS_wFan speed: 1 low, 2 mid2, 3 mid1, 4 highCommand
BI 100102nnn_ON_rConfirm run statusRead
AI 100108nnn_RARoom temperatureRead
BI 100026Sys_G50_Comms_StateGateway-to-G-50 link statusRead
AI 100103nnn_ECodeError code (8000 = no error)Read

Enable & remote start

The Enable Link terminals take a normally-closed volt-free contact (shipped with a wire link). Opening it sets the G-50 Forced-Off (all units off, remotes disabled) and resends every 5 s; closing it sends one Reset so later BMS Forced-Off commands are not overridden. Local remotes can be inhibited per unit with nnn_LI_w.

Heartbeat & communication loss

No BMS heartbeat. Sys_G50_Comms_State goes inactive when the G-50 is off or unreachable, and Sys_Mnet_State is inactive while M-Net initialises, when the units are effectively offline.

Network setup

Watch out for

Mitsubishi Electric Procon BAC-IP/50 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

25 of 25 shown
Type
Other
Access
Show
Mitsubishi Electric Procon BAC-IP/50 BACnet Points List
DescriptionStates
BOmin100101nnn_ON_wOn/Off setupCommandInactive=Off, Active=On
BImin100102nnn_ON_rOn/Off stateReadInactive=Off, Active=On
AImin100103nnn_ECodeUnit error code, 4 digits (8000 = no error)Read
MOmin100104nnn_MD_wOperation mode setupCommand1=Cool, 2=Dry, 3=Fan, 4=Heat, 5=Auto, 6=Heat Recovery, 7=LC_Auto, 8=Bypass, 9=AutoHeat, 10=AutoCool, 11=Heating, 12=Eco-Heating, 13=Hot-Water, 14=Anti-Freeze, 15=Cooling
MI100105nnn_MD_rOperation mode stateRead1=Cool, 2=Dry, 3=Fan, 4=Heat, 5=Auto, 6=Heat Recovery, 7=LC_Auto, 8=Bypass, 9=AutoHeat, 10=AutoCool, 11=Heating, 12=Eco-Heating, 13=Hot-Water, 14=Anti-Freeze, 15=Cooling
MOmin100106nnn_FS_wFan speed setupCommand1=Low, 2=Mid2, 3=Mid1, 4=High
MI100107nnn_FS_rFan speed stateRead1=Low, 2=Mid2, 3=Mid1, 4=High
AImin100108nnn_RARoom temperature°CRead
AOmin100109nnn_SP_wSetpoint setup°CCommand
AI100110nnn_SP_rSetpoint state°CRead
BI100111nnn_FL_rFilter sign stateReadInactive=Sign Off, Active=Sign On
BO100112nnn_FL_wFilter sign clearCommandInactive=Clear Sign, Active=No Action
BO100113nnn_LI_wLocal remote inhibit setupCommandInactive=Off, Active=Inhibit
BI100114nnn_LI_rLocal remote inhibit stateReadInactive=Off, Active=Inhibited
MO100115nnn_AD_wAir direction setupCommand1=Horizontal, 2=Mid1, 3=Mid2, 4=Vertical, 5=Swing
MI100116nnn_AD_rAir direction stateRead1=Horizontal, 2=Mid1, 3=Mid2, 4=Vertical, 5=Swing
MO100117nnn_VN_wVentilation setup (Lossnay/OA units only)Command1=Off, 2=Low, 3=High
MI100118nnn_VN_rVentilation state (Lossnay/OA units only)Read1=Off, 2=Low, 3=High
AI105122nnn_ECodeOC/BC (outdoor) error code, 8000 = no errorRead
BI100023Sys_Mnet_StateM-Net communication stateReadInactive=Init, Active=Ok
BO100024Sys_Forced_Off_wSystem forced off setupCommandInactive=Off, Active=On
BI100025Sys_Forced_Off_rSystem forced off stateReadInactive=Off, Active=On
BImin100026Sys_G50_Comms_StateBAC-IP/50 to G-50 communication stateReadInactive=Error, Active=Ok
BV100027Sys_New_Setting_CompareWrite only when value changesCommandInactive=Off, Active=On
DEV10DeviceGateway device object (factory default 10, user settable)Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Procon BAC-IP/50 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric Procon BAC-IP/50

How many BACnet points does the Mitsubishi Electric Procon BAC-IP/50 have?

This list has 25 BACnet objects: 4 analog inputs, 1 analog output, 6 binary inputs, 4 binary outputs, 1 binary value, 1 device, 4 multi-state inputs, 4 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric Procon BAC-IP/50 BACnet points are writable?

10 of the 25 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Mitsubishi Electric Procon BAC-IP/50 BACnet documentation?

The source is Procon BAC-IP/50 Installation and User Guide, revision 2009-07-20, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/384.

What are the minimum BACnet points to integrate the Mitsubishi Electric Procon BAC-IP/50?

Start with BO 100101 nnn_ON_w (Start/stop the unit); MO 100104 nnn_MD_w (Command the operating mode); AO 100109 nnn_SP_w (Setpoint command); MO 100106 nnn_FS_w (Fan speed: 1 low, 2 mid2, 3 mid1, 4 high); BI 100102 nnn_ON_r (Confirm run status); AI 100108 nnn_RA (Room temperature); BI 100026 Sys_G50_Comms_State (Gateway-to-G-50 link status); AI 100103 nnn_ECode (Error code (8000 = no error)).

How do I enable BMS control of the Mitsubishi Electric Procon BAC-IP/50?

The Enable Link terminals take a normally-closed volt-free contact (shipped with a wire link). Opening it sets the G-50 Forced-Off (all units off, remotes disabled) and resends every 5 s; closing it sends one Reset so later BMS Forced-Off commands are not overridden. Local remotes can be inhibited per unit with nnn_LI_w.

Does the Mitsubishi Electric Procon BAC-IP/50 need a BACnet heartbeat or have a communication timeout?

No BMS heartbeat. Sys_G50_Comms_State goes inactive when the G-50 is off or unreachable, and Sys_Mnet_State is inactive while M-Net initialises, when the units are effectively offline.

How do I check these points on the real Procon BAC-IP/50?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Mitsubishi Electric BACnet points lists

Source: Procon BAC-IP/50 Installation and User Guide · rev. 2009-07-20. Object names, instances and units are reproduced as published; descriptions are our own.