VRF BACnet IP gateway · BACnet points list

Mitsubishi Electric BAC-HD150 BM Adapter BACnet points list

Updated 28 October 2026

Short answer

The BAC-HD150 sits on the M-NET bus of a CITY MULTI system and serves BACnet IP objects for each indoor unit group. Every group gets the same block of control and status objects, so the point list is one template repeated per group. Which objects actually respond depends on the group type and on BAC-HD150 Setting Tool options such as dual setpoint and Old Model Compatibility Mode.

This page lists 31 BACnet objects for the Mitsubishi Electric BAC-HD150 BM Adapter — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
BAC-HD150 BM Adapter
Equipment
VRF BACnet IP gateway
Equipment type
VRF & split air conditioners
BACnet objects
31 (19 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
BAC-HD150, BAC-HD/150, BACHD150, BM ADAPTER, CMCN BACnet points list, MEAPP0002
Source document
Air-conditioner Control System BM ADAPTER BAC-HD150 Instruction Book · WT05542X04
Download CSV 31 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Mitsubishi Electric BAC-HD150 BM Adapter

Integration in brief

Set the BAC-HD150 IP addresses and groups with the BAC-HD150 Setting Tool, then map the same block of objects for each indoor unit group (instance MMGGPP). For a basic job you need On Off Setup/State, Operational Mode Setup/State, Set Temp (or Set Temp Cool/Heat for dual-setpoint groups), Room Temp and Alarm Signal. Space out requests: at least 200 ms per property.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 10101On Off SetupStart/stop the groupWrite
MO 10105Operational Mode SetupCommand the operating modeWrite
AV 10110Set TempSetpoint for single-setpoint groupsWrite
AV 10124Set Temp CoolCooling setpoint for dual-setpoint groupsWrite
AV 10125Set Temp HeatHeating setpoint for dual-setpoint groupsWrite
MO 10107Fan Speed SetupFan speed: 1 low, 2 high, 3 mid2, 4 mid1Write
BI 10102On Off StateConfirm run statusRead
AI 10109Room TempRoom temperature (water temp on BU/AU groups)Read
BI 10103Alarm SignalGroup fault alarmRead
BI 10120M-NET Communication StateM-NET link to the group lostRead

Enable & remote start

No enable point is described; the BMS commands groups directly. Remote controller lockouts are separate Prohibition BVs (on/off, mode, filter reset, set temperature) per group, and System Forced Off works per group (MM GG 21) or for all groups (999921).

Network setup

Watch out for

Mitsubishi Electric BAC-HD150 BM Adapter BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

31 of 31 shown
Type
Access
Show
Mitsubishi Electric BAC-HD150 BM Adapter BACnet Points List
DescriptionStates
BOmin10101On Off SetupStart/stop command for the groupWriteInactive=Stop, Active=Run
BImin10102On Off StateGroup run statusReadInactive=Stop, Active=Run
BImin10103Alarm SignalGroup alarmReadInactive=Normal, Active=Error
MI10104Error CodeError category for the groupRead1=Normal, 2=Other errors, 3=Refrigeration system fault, 4=Water system error, 5=Air system error, 6=Electronic system error, 7=Sensor fault, 8=Communication error, 9=System error
MOmin10105Operational Mode SetupOperating mode commandWrite1=Cooling, 2=Heating, 3=Fan, 4=Auto, 5=Dry, 6=Setback
MI10106Operational Mode StateCurrent operating modeRead1=Cooling, 2=Heating, 3=Fan, 4=Auto, 5=Dry, 6=Setback
MOmin10107Fan Speed SetupFan speed commandWrite1=Low, 2=High, 3=Mid 2, 4=Mid 1
MI10108Fan Speed StateCurrent fan speedRead1=Low, 2=High, 3=Mid 2, 4=Mid 1
AImin10109Room TempRoom temperature (water temp for BU/AU groups)°F/°CRead
AVmin10110Set TempSingle setpoint (set water temp for BU/AU groups)°F/°CWrite
BI10111Filter SignFilter sign (circulating water exchange sign for BU/AU)ReadInactive=OFF, Active=ON
BV10112Filter Sign ResetResets the filter signWriteInactive=Reset, Active=Void
BV10113Prohibition On OffLocks out local on/offWriteInactive=Permit, Active=Prohibit
BV10114Prohibition ModeLocks out local mode changeWriteInactive=Permit, Active=Prohibit
BV10115Prohibition Filter Sign ResetLocks out local filter sign resetWriteInactive=Permit, Active=Prohibit
BV10116Prohibition Set TemperatureLocks out local setpoint changeWriteInactive=Permit, Active=Prohibit
BImin10120M-NET Communication StateM-NET communication statusReadInactive=Normal, Active=Error
BV10121System Forced OffForced off, individual groupWriteInactive=Reset, Active=Execute
BV999921System Forced OffForced off, all groups (bundle)WriteInactive=Reset, Active=Execute
MO10122Air Direction SetupVane direction commandWrite1=Horizontal, 2=Downblow 60%, 3=Downblow 80%, 4=Downblow 100%, 5=Swing
MI10123Air Direction StateCurrent vane directionRead1=Horizontal, 2=Downblow 60%, 3=Downblow 80%, 4=Downblow 100%, 5=Swing
AVmin10124Set Temp CoolCooling setpoint (dual setpoint groups)°F/°CWrite
AVmin10125Set Temp HeatHeating setpoint (dual setpoint groups)°F/°CWrite
AV10126Set Temp AutoAuto-mode setpoint (single setpoint auto)°F/°CWrite
AV10127Set High Limit Setback TempUpper setback limit°F/°CWrite
AV10128Set Low Limit Setback TempLower setback limit°F/°CWrite
MO10135Ventilation Mode SetupLossnay ventilation mode commandWrite1=Heat exchange, 2=Bypass, 3=Auto
MI10136Ventilation Mode StateCurrent Lossnay ventilation modeRead1=Heat exchange, 2=Bypass, 3=Auto
MO10137Air To Water Mode SetupAir To Water (PWFY) mode commandWrite1=Heating, 2=Heating ECO, 3=Hot Water, 4=Antifreeze, 5=Cooling
MI10138Air To Water Mode StateCurrent Air To Water modeRead1=Heating, 2=Heating ECO, 3=Hot Water, 4=Antifreeze, 5=Cooling
BI19981Expansion Controller Communication StateExpansion controller comms statusReadInactive=Normal, Active=Error

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BAC-HD150 BM Adapter and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric BAC-HD150 BM Adapter

How many BACnet points does the Mitsubishi Electric BAC-HD150 BM Adapter have?

This list has 31 BACnet objects: 1 analog input, 6 analog values, 5 binary inputs, 1 binary output, 7 binary values, 6 multi-state inputs, 5 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric BAC-HD150 BM Adapter BACnet points are writable?

19 of the 31 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Mitsubishi Electric BAC-HD150 BM Adapter BACnet documentation?

The source is Air-conditioner Control System BM ADAPTER BAC-HD150 Instruction Book (WT05542X04), published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/373.

What are the minimum BACnet points to integrate the Mitsubishi Electric BAC-HD150 BM Adapter?

Start with BO 10101 On Off Setup (Start/stop the group); MO 10105 Operational Mode Setup (Command the operating mode); AV 10110 Set Temp (Setpoint for single-setpoint groups); AV 10124 Set Temp Cool (Cooling setpoint for dual-setpoint groups); AV 10125 Set Temp Heat (Heating setpoint for dual-setpoint groups); MO 10107 Fan Speed Setup (Fan speed: 1 low, 2 high, 3 mid2, 4 mid1); BI 10102 On Off State (Confirm run status); AI 10109 Room Temp (Room temperature (water temp on BU/AU groups)); BI 10103 Alarm Signal (Group fault alarm); BI 10120 M-NET Communication State (M-NET link to the group lost).

How do I enable BMS control of the Mitsubishi Electric BAC-HD150 BM Adapter?

No enable point is described; the BMS commands groups directly. Remote controller lockouts are separate Prohibition BVs (on/off, mode, filter reset, set temperature) per group, and System Forced Off works per group (MM GG 21) or for all groups (999921).

How do I check these points on the real BAC-HD150 BM Adapter?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Mitsubishi Electric BACnet points lists

Source: Air-conditioner Control System BM ADAPTER BAC-HD150 Instruction Book · WT05542X04. Object names, instances and units are reproduced as published; descriptions are our own.