VRF central controller with BACnet IP · BACnet points list

Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50) BACnet points list

Updated 28 October 2026

Short answer

The AE-C400 and EW-C50 centralized controllers (and the BACS-AP50 BM adapter, which behaves like an EW-C) expose the M-NET system to BACnet IP on their LAN2 port. Points are generated per group from a fixed template, plus separate blocks for PI controllers, outdoor units, interlocked units and chillers. The controller only creates objects that the connected unit type supports, so a Lossnay group or a chiller shows a different subset.

This page lists 71 BACnet objects for the Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50) — 28 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
AE-C400 / EW-C50 BACnet (BACS-AP50)
Equipment
VRF central controller with BACnet IP
Equipment type
VRF & split air conditioners
BACnet objects
71 (28 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
AE-C400, AE-C400E, EW-C50, EW-C50E, BACS-AP50, BACS-AP50E, AE-C/EW-C BACnet
Source document
Centralized Controller AE-C400/EW-C50, BM ADAPTER BACS-AP50 Instruction Book <BACnet function> · WT10808X04
Download CSV 71 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50)

Integration in brief

Register the BACnet connection license, set the LAN2 (BACnet) IP and the device number with the BACnet Setting Tool, and wait for the controller to go ONLINE. Then map the per-group objects (01GGPP): On Off, mode, setpoint, room temp and alarm. Write only when a setting changes, never cyclically.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 10101On Off SetupStart/stop the groupWrite
MO 10105Operational Mode SetupCommand the operating modeWrite
AV 10110Set TempSetpoint for single-setpoint groupsWrite
AV 10124Set Temp CoolCooling setpoint for dual-setpoint groupsWrite
AV 10125Set Temp HeatHeating setpoint for dual-setpoint groupsWrite
MO 10107Fan Speed SetupFan speed: 1 low, 2 high, 3 mid2, 4 mid1, 5 autoWrite
BI 10102On Off StateConfirm run statusRead
AI 10109Room TempRoom temperature (water temp on Air To Water groups)Read
BI 10103Alarm SignalGroup fault alarmRead
BI 10120M-NET Communication StateM-NET link to the group lostRead

Enable & remote start

BACnet only runs when the controller is in ONLINE mode, which needs a valid BACnet connection license and consistent BACnet settings. Changing group/interlock settings sends it back to OFFLINE; returning to ONLINE can take up to about 10 minutes on large systems. Local remote-controller lockouts are the Prohibition BVs (13-17) per group.

Network setup

Watch out for

Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

71 of 71 shown
Type
Access
Show
Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50) BACnet Points List
DescriptionStates
BOmin10101On Off SetupStart/stop command for the groupWriteInactive=Stop, Active=Run
BImin10102On Off StateGroup run statusReadInactive=Stop, Active=Run
BImin10103Alarm SignalGroup alarmReadInactive=Normal, Active=Error
MI10104Error CodeError category for the groupRead1=Normal, 2=Other errors, 3=Refrigeration system fault, 4=Water system error, 5=Air system error, 6=Electronic system error, 7=Sensor fault, 8=Communication error, 9=System error
MOmin10105Operational Mode SetupOperating mode commandWrite1=Cool, 2=Heat, 3=Fan, 4=Auto, 5=Dry, 6=Setback
MI10106Operational Mode StateCurrent operating modeRead1=Cool, 2=Heat, 3=Fan, 4=Auto, 5=Dry, 6=Setback
MOmin10107Fan Speed SetupFan speed commandWrite1=Low, 2=High, 3=Mid 2, 4=Mid 1, 5=Auto
MI10108Fan Speed StateCurrent fan speedRead1=Low, 2=High, 3=Mid 2, 4=Mid 1, 5=Auto
AImin10109Room TempRoom temperature (water temp for Air To Water)°F/°CRead
AVmin10110Set TempSingle setpoint (set water temp for Air To Water)°F/°CWrite
BI10111Filter SignFilter signReadInactive=OFF, Active=ON
BV10112Filter Sign ResetResets the filter signWriteInactive=Reset, Active=Void
BV10113Prohibition On OffLocks out local on/offWriteInactive=Permit, Active=Prohibit
BV10114Prohibition ModeLocks out local mode changeWriteInactive=Permit, Active=Prohibit
BV10115Prohibition Filter Sign ResetLocks out local filter sign resetWriteInactive=Permit, Active=Prohibit
BV10116Prohibition Set TemperatureLocks out local setpoint changeWriteInactive=Permit, Active=Prohibit
BV10117Prohibition Fan SpeedLocks out local fan speed changeWriteInactive=Permit, Active=Prohibit
BImin10120M-NET Communication StateM-NET communication statusReadInactive=Normal, Active=Error
BV10121System Forced OffForced off, individual groupWriteInactive=Reset, Active=Execute
BV19921System Forced OffForced off, all groups (collective)WriteInactive=Reset, Active=Execute
MO10122Air Direction SetupVane direction commandWrite1=Horizontal, 2=Downblow 60%, 3=Downblow 80%, 4=Downblow 100%, 5=Swing
MI10123Air Direction StateCurrent vane directionRead1=Horizontal, 2=Downblow 60%, 3=Downblow 80%, 4=Downblow 100%, 5=Swing
AVmin10124Set Temp CoolCooling setpoint (dual setpoint)°F/°CWrite
AVmin10125Set Temp HeatHeating setpoint (dual setpoint)°F/°CWrite
AV10126Set Temp AutoAuto-mode setpoint (single setpoint auto)°F/°CWrite
AV10127Set High Limit Setback TempUpper setback limit°F/°CWrite
AV10128Set Low Limit Setback TempLower setback limit°F/°CWrite
MO10135Ventilation Mode SetupLossnay ventilation mode commandWrite1=Heat Recovery, 2=Bypass, 3=Auto
MI10136Ventilation Mode StateCurrent Lossnay ventilation modeRead1=Heat Recovery, 2=Bypass, 3=Auto
MO10137Air To Water Mode SetupAir To Water mode commandWrite1=Heating, 2=Heating ECO, 3=Hot Water, 4=Anti-freeze, 5=Cooling
MI10138Air To Water Mode StateCurrent Air To Water modeRead1=Heating, 2=Heating ECO, 3=Hot Water, 4=Anti-freeze, 5=Cooling
ACC10139Group Apportioned Electric EnergyApportioned energy per group (needs Charge license)0.1 kWhRead
ACC610139Interlocked Units Apportioned Electric EnergyApportioned energy per interlocked unit0.1 kWhRead
ACC10144Group Apportionment ParameterApportionment parameter per groupRead
ACC610144Interlocked Units Apportionment ParameterApportionment parameter per interlocked unitRead
BI10146Night Purge StateNight purge activeReadInactive=OFF, Active=ON
BI10147Thermo On Off StateThermostat on/off statusReadInactive=OFF, Active=ON
BI10048System Alarm SignalController-level system alarmReadInactive=Normal, Active=Error
AI10149Error Code DetailNumeric error codeRead
BI10150External Heat Source StateExternal heat source statusReadInactive=OFF, Active=ON
BI410103PIcontroller Alarm SignalPI controller alarmReadInactive=Normal, Active=Error
ACC410140PIcontroller Electric Energy 1Metered energy, PI controller channel 10.1 kWhRead
ACC410141PIcontroller Electric Energy 2Metered energy, PI controller channel 20.1 kWhRead
ACC410142PIcontroller Electric Energy 3Metered energy, PI controller channel 30.1 kWhRead
ACC410143PIcontroller Electric Energy 4Metered energy, PI controller channel 40.1 kWhRead
AI510101COPOutdoor unit coefficient of performanceRead
TL10180Trend Log Room TempTrend log of Room TempRead
TL10183Trend Log Group Apportioned Electric EnergyTrend log of group apportioned energyRead
TL610183Trend Log Interlocked Units Apportioned Electric EnergyTrend log of interlocked unit energyRead
TL410184Trend Log PIcontroller Electric Energy 1Trend log of PI controller channel 1Read
TL410185Trend Log PIcontroller Electric Energy 2Trend log of PI controller channel 2Read
TL410186Trend Log PIcontroller Electric Energy 3Trend log of PI controller channel 3Read
TL410187Trend Log PIcontroller Electric Energy 4Trend log of PI controller channel 4Read
TL10188Trend Log Group Apportionment ParameterTrend log of group apportionment parameterRead
TL610188Trend Log Interlocked Units Apportionment ParameterTrend log of interlocked unit parameterRead
BO710101Chiller On Off SetupChiller start/stop commandWriteInactive=OFF, Active=ON
BI710102Chiller On Off StateChiller run statusReadInactive=OFF, Active=ON
MO710103Chiller Operational Mode SetupChiller mode commandWrite1=Heating, 2=Cooling, 3=Anti-freeze, 4=Heating ECO
MI710104Chiller Operational Mode StateCurrent chiller modeRead1=Heating, 2=Cooling, 3=Anti-freeze, 4=Heating ECO
MO710105Chiller Fan Mode SetupChiller fan mode commandWrite1=Normal, 2=Snow
MI710106Chiller Fan Mode StateCurrent chiller fan modeRead1=Normal, 2=Snow
AV710107Chiller Set Temp CoolChiller cooling water setpoint°CWrite
AV710108Chiller Set Temp HeatChiller heating water setpoint°CWrite
AI710109Chiller Representative Inlet Water TempInlet water temperature°CRead
AI710110Chiller Representative Outlet Water TempOutlet water temperature°CRead
BI710111Chiller Representative Alarm SignalChiller system alarmReadInactive=Normal, Active=Error
BI710112Chiller Communication StateChiller communication statusReadInactive=Normal, Active=Error
BV710115Chiller Prohibition On OffLocks out local chiller on/offWriteInactive=Permit, Active=Prohibit
BV710116Chiller Prohibition ModeLocks out local chiller mode changeWriteInactive=Permit, Active=Prohibit
BV710117Chiller Prohibition Set TemperatureLocks out local chiller setpoint changeWriteInactive=Permit, Active=Prohibit
BI910111Chiller Unit Alarm SignalAlarm for an individual chiller unitReadInactive=Normal, Active=Error

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AE-C400 / EW-C50 BACnet (BACS-AP50) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50)

How many BACnet points does the Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50) have?

This list has 71 BACnet objects: 5 analog inputs, 8 analog values, 13 binary inputs, 2 binary outputs, 11 binary values, 8 multi-state inputs, 7 multi-state outputs, 9 trend logs, 8 accumulators. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50) BACnet points are writable?

28 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50) BACnet documentation?

The source is Centralized Controller AE-C400/EW-C50, BM ADAPTER BACS-AP50 Instruction Book <BACnet function> (WT10808X04), published free by Mitsubishi Electric at https://confort.mitsubishielectric.fr/documents/link/26707/stream/1766501797-GTC-BACS-AP50E-NOTICE-UTILISATION-WT10808X03-EN.pdf.

What are the minimum BACnet points to integrate the Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50)?

Start with BO 10101 On Off Setup (Start/stop the group); MO 10105 Operational Mode Setup (Command the operating mode); AV 10110 Set Temp (Setpoint for single-setpoint groups); AV 10124 Set Temp Cool (Cooling setpoint for dual-setpoint groups); AV 10125 Set Temp Heat (Heating setpoint for dual-setpoint groups); MO 10107 Fan Speed Setup (Fan speed: 1 low, 2 high, 3 mid2, 4 mid1, 5 auto); BI 10102 On Off State (Confirm run status); AI 10109 Room Temp (Room temperature (water temp on Air To Water groups)); BI 10103 Alarm Signal (Group fault alarm); BI 10120 M-NET Communication State (M-NET link to the group lost).

How do I enable BMS control of the Mitsubishi Electric AE-C400 / EW-C50 BACnet (BACS-AP50)?

BACnet only runs when the controller is in ONLINE mode, which needs a valid BACnet connection license and consistent BACnet settings. Changing group/interlock settings sends it back to OFFLINE; returning to ONLINE can take up to about 10 minutes on large systems. Local remote-controller lockouts are the Prohibition BVs (13-17) per group.

How do I check these points on the real AE-C400 / EW-C50 BACnet (BACS-AP50)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Mitsubishi Electric BACnet points lists

Source: Centralized Controller AE-C400/EW-C50, BM ADAPTER BACS-AP50 Instruction Book <BACnet function> · WT10808X04. Object names, instances and units are reproduced as published; descriptions are our own.