Energy recovery ventilator interface · BACnet points list

Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Lossnay units BACnet points list

Updated 11 November 2026

Short answer

For Lossnay energy recovery ventilators the MelcoBEMS MINI (A1M+) serves power, mode, ventilation mode, fan speed and setpoint commands on BACnet MS/TP or BACnet IP, plus supply, outdoor and room temperatures, CO2, energy, filter and maintenance signs and a set of capability flags as analog inputs.

This page lists 40 BACnet objects for the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Lossnay units — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
Procon MelcoBEMS MINI (A1M+) - Lossnay units
Equipment
Energy recovery ventilator interface
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
40 (6 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
4.1.1
Also known as
A1M+ Lossnay, MelcoBEMS MINI A1M PLUS Lossnay
Source document
Procon MelcoBEMS MINI (A1M+) Installation Manual (manual 1.0.3, firmware 4.1.1)
Download CSV 40 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Mitsubishi Electric’s current documentation and the live device before use. Not official Mitsubishi Electric information. Terms of use.

BMS integration notes: Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Lossnay units

Integration in brief

Select BACnet with DIP switch 7, then write power, mode, ventilation mode and fan speed, and read temperatures, CO2 and the filter and maintenance signs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0Lossnay Drive OFF/ON SetupPower on/off commandCommand
MO 1Lossnay Mode SetupMode command (heat/cool/fan/auto)Command
MO 2Lossnay Vent Mode SetupVentilation mode (Lossnay/bypass/auto)Command
MO 3Lossnay Fan Speed A SetupFan speed commandCommand
AV 4Lossnay Temperature Setpoint ATemperature setpointCommand
AI 7Lossnay Room Temperature ARoom temperatureRead
AI 8Lossnay Room Co2 LevelRoom CO2 / 10 (254 detecting, 255 no sensor)Read
AI 15Lossnay Filter SignFilter sign, 1 = activeRead
AI 14Lossnay Maintenance SignMaintenance sign, 1 = activeRead

Network setup

Watch out for

Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Lossnay units BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

40 of 40 shown
Type
BinaryMulti-state
Access
Show
Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Lossnay units BACnet Points List
DescriptionStates
BOmin0Lossnay Drive OFF/ON SetupCommand0=Power OFF, 1=Power ON
MOmin1Lossnay Mode SetupCommand1=Heat, 2=Cool, 3=Fan, 4=Auto
MOmin2Lossnay Vent Mode SetupCommand1=Lossnay mode, 2=Bypass mode, 3=Auto mode
MOmin3Lossnay Fan Speed A SetupCommand1=Auto, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4
AVmin4Lossnay Temperature Setpoint A°C/°FCommand
AI5Lossnay Supply Air Temperature A°C/°FRead
AI6Lossnay Outdoor Temperature Int°C/°FRead
AImin7Lossnay Room Temperature A°C/°FRead
AImin8Lossnay Room Co2 LevelCO2 level divided by 10.Read
AI9Lossnay Thermo OnoffRead0=Thermo OFF, 1=Thermo ON
AI10Lossnay Energy Consumption"Value in kWh multiplied by 10.Read
AI11Lossnay Actual Operation ModeRead1=Not auto mode, 2=Determining, 3=Heating, 4=Cooling
AI12Lossnay Auto Fan Speed Control AvailabilityRead0=Not available, 1=Available
AI13Lossnay Night PurgeRead0=Normal operation, 1=In night purge operation
AImin14Lossnay Maintenance SignRead0=Inactive, 1=Active
AImin15Lossnay Filter SignRead0=Inactive, 1=Active
AI16Lossnay Actual Ventilation ModeRead0=Lossnay ventilation, 1=Bypass ventilation
AI17Lossnay Actual Supply Fan SpeedRead1=Stop, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4
AI18Lossnay Actual Extract Fan SpeedRead1=Stop, 2=Speed 1, 3=Speed 2, 4=Speed 3, 5=Speed 4
AI19Lossnay Setpoint 0.5ºC Increments AvailabilityRead0=Not available, 1=Available
AI20Lossnay Heat/Cool or Cool- OnlyRead0=Heat and Cool, 1=Cool only
AI21Lossnay Auto Operation Mode AvailabilityRead0=Not available, 1=Available
AI22Lossnay Heat/Cool or Heat- OnlyRead0=Heat and Cool, 1=Heat only
AI23Lossnay Minimum Cooling Setpoint°C/°FRead
AI24Lossnay Maximum Cooling Setpoint°C/°FRead
AI25Lossnay Minimum Heating Setpoint°C/°FRead
AI26Lossnay Maximum Heating Setpoint°C/°FRead
AI27Lossnay Minimum Auto Setpoint°C/°FRead
AI28Lossnay Maximum Auto Setpoint°C/°FRead
AI29Lossnay Energy Consumption Data AvailableRead0=Not available, 1=Available
AI30Lossnay Number Of Fan SpeedsValues 1 – 4 validRead
AI31Lossnay Bypass Damper Function7-segment error code digit (code table in guide)Read
AI32Lossnay Auto Ventilation Mode AvailableRead0=Not available, 1=Available
AI33Lossnay Operation Mode off Temperature Control UnitRead0=Not available (not connected), 1=Available (connected)
AI34Lossnay Set Temperature on Temperature Control UnitRead0=No set temperature display, 1=RA (Return Air) temperature, 2=SA (Supply Air) temperature
AI35Lossnay Outdoor Temperature SensorRead0=Not equipped, 1=Equipped
AI36Lossnay Return Air Temperature SensorRead0=Not equipped, 1=Equipped
AI37Lossnay Supply Air Temperature SensorRead0=Not equipped, 1=Equipped
AI38Lossnay CO2 SensorRead0=Not equipped, 1=Equipped
MO39Temperature UnitsCommand1=ºC, 2=ºF
Object ID lookup: Mitsubishi Electric MelcoBEMS MINI Lossnay point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Procon MelcoBEMS MINI (A1M+) - Lossnay units and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Lossnay units

How many BACnet points does the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Lossnay units have?

This list has 40 BACnet objects: 34 analog inputs, 1 analog value, 1 binary output, 4 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Lossnay units BACnet points are writable?

6 of the 40 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Lossnay units BACnet documentation?

The source is Procon MelcoBEMS MINI (A1M+) Installation Manual (manual 1.0.3, firmware 4.1.1), published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5538.

What are the minimum BACnet points to integrate the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Lossnay units?

Start with BO 0 Lossnay Drive OFF/ON Setup (Power on/off command); MO 1 Lossnay Mode Setup (Mode command (heat/cool/fan/auto)); MO 2 Lossnay Vent Mode Setup (Ventilation mode (Lossnay/bypass/auto)); MO 3 Lossnay Fan Speed A Setup (Fan speed command); AV 4 Lossnay Temperature Setpoint A (Temperature setpoint); AI 7 Lossnay Room Temperature A (Room temperature); AI 8 Lossnay Room Co2 Level (Room CO2 / 10 (254 detecting, 255 no sensor)); AI 15 Lossnay Filter Sign (Filter sign, 1 = active); AI 14 Lossnay Maintenance Sign (Maintenance sign, 1 = active).

How do I check these points on the real Procon MelcoBEMS MINI (A1M+) - Lossnay units?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Mitsubishi Electric BACnet points lists

Source: Procon MelcoBEMS MINI (A1M+) Installation Manual (manual 1.0.3, firmware 4.1.1). Object names, instances and units are reproduced as published; descriptions are our own.