Split / VRF indoor unit interface (single unit) · BACnet points list

Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units BACnet points list

Updated 11 November 2026

Short answer

The MelcoBEMS MINI (A1M+) plugs into the CN105 connector of one Mitsubishi Electric indoor unit and serves it on BACnet MS/TP (RS-485) or BACnet IP. For air-to-air units it gives on/off, mode, setpoint, fan speed and vane commands with matching status objects, room temperature, the fault code, and an option to feed a BMS room temperature to the unit.

This page lists 14 BACnet objects for the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
Procon MelcoBEMS MINI (A1M+) - Air-To-Air units
Equipment
Split / VRF indoor unit interface (single unit)
Equipment type
VRF & split air conditioners
BACnet objects
14 (8 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
4.1.1
Also known as
A1M+, MelcoBEMS MINI A1M PLUS, MelcoBEMS MINI (A1M), Procon A1M
Source document
Procon MelcoBEMS MINI (A1M+) Installation Manual (manual 1.0.3, firmware 4.1.1)
Download CSV 14 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Mitsubishi Electric’s current documentation and the live device before use. Not official Mitsubishi Electric information. Terms of use.

BMS integration notes: Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units

Integration in brief

Set DIP switch 7 to BACnet, give the adapter a node address or IP, then write on/off, mode, setpoint and fan speed and read the matching state objects, room temperature and fault code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0Drive OFF/ON SetupUnit on/off commandCommand
MO 3Mode SetupMode command (heat/dry/cool/fan/auto)Command
AV 2SetpointTemperature setpointCommand
MO 5Fan Speed SetupFan speed commandCommand
BI 1Drive OFF/ON StateOn/off statusRead
MI 4Mode StateCurrent modeRead
AI 10Inlet TemperatureRoom (inlet) temperatureRead
AI 11Fault Code4-digit fault code, 8000 = no errorRead

Enable & remote start

No separate enable; the Setup objects command the indoor unit directly.

Sensors & values from the BMS

Set External Temperature ON/OFF Setup (BO 12) to ON and write External Temperature Input (AV 13); the unit then uses that value instead of its own temperature.

Network setup

Watch out for

Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

14 of 14 shown
Type
Access
Show
Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units BACnet Points List
DescriptionStates
BOmin0Drive OFF/ON SetupCommand0=Drive OFF, 1=Drive ON
BImin1Drive OFF/ON StateRead0=Drive OFF, 1=Drive ON
AVmin2Setpoint°C/°FCommand
MOmin3Mode SetupCommand1=Heating, 2=Humidity reduction, 3=Cooling, 4=Ventilation, clean air operation, 5=Auto Operation
MImin4Mode StateRead1=Heating, 2=Humidity reduction, 3=Cooling, 4=Ventilation, clean air operation, 5=Auto Operation
MOmin5Fan Speed SetupCommand1=Auto, 2=Quiet, 3=Weak, 4=Strong, 5=Very strong (SH i)
MI6Fan Speed StateRead1=Auto, 2=Quiet, 3=Weak, 4=Strong, 5=Very strong (SH i)
MO7Air Direction SetupCommand1=Auto, 2=Position 1, 3=Position 2, 4=Position 3, 5=Position 4, 6=Position 5, 7=Swing
MI8Air Direction StateRead1=Auto, 2=Position 1, 3=Position 2, 4=Position 3, 5=Position 4, 6=Position 5, 7=Swing
MO9Temperature UnitsCommand1=ºC, 2=ºF
AImin10Inlet Temperature°C/°FRead
AImin11Fault CodeRead
BO12External Temperature ON/OFF SetupUse AV 13 in place of the unit's own temperatureCommand0=Feature OFF, 1=Feature ON
AV13External Temperature Input°C/°FCommand
Object ID lookup: Mitsubishi Electric MelcoBEMS MINI Air-to-Air point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Procon MelcoBEMS MINI (A1M+) - Air-To-Air units and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units

How many BACnet points does the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units have?

This list has 14 BACnet objects: 2 analog inputs, 2 analog values, 1 binary input, 2 binary outputs, 3 multi-state inputs, 4 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units BACnet points are writable?

8 of the 14 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units BACnet documentation?

The source is Procon MelcoBEMS MINI (A1M+) Installation Manual (manual 1.0.3, firmware 4.1.1), published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5538.

What are the minimum BACnet points to integrate the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units?

Start with BO 0 Drive OFF/ON Setup (Unit on/off command); MO 3 Mode Setup (Mode command (heat/dry/cool/fan/auto)); AV 2 Setpoint (Temperature setpoint); MO 5 Fan Speed Setup (Fan speed command); BI 1 Drive OFF/ON State (On/off status); MI 4 Mode State (Current mode); AI 10 Inlet Temperature (Room (inlet) temperature); AI 11 Fault Code (4-digit fault code, 8000 = no error).

How do I enable BMS control of the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units?

No separate enable; the Setup objects command the indoor unit directly.

Can the BMS supply sensor values to the Mitsubishi Electric Procon MelcoBEMS MINI (A1M+) - Air-To-Air units?

Set External Temperature ON/OFF Setup (BO 12) to ON and write External Temperature Input (AV 13); the unit then uses that value instead of its own temperature.

How do I check these points on the real Procon MelcoBEMS MINI (A1M+) - Air-To-Air units?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Mitsubishi Electric BACnet points lists

Source: Procon MelcoBEMS MINI (A1M+) Installation Manual (manual 1.0.3, firmware 4.1.1). Object names, instances and units are reproduced as published; descriptions are our own.