Split air conditioner BACnet IP gateway (legacy) · BACnet points list

Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM) BACnet points list

Updated 7 November 2026

Short answer

The Procon BAC-A/50 is an older Mitsubishi Electric UK gateway that links up to 50 Mr. SLIM systems (through Sub I/F boards daisy-chained to its TB12 terminals) to BACnet IP. Each unit address gets the same block of 14 objects (setup _w, state _r, error code and room temperature) named after the unit name typed into the configuration program, plus four system objects. It is the Mr. SLIM sibling of the Procon BAC-IP/50 (CITY MULTI via G-50) and has a smaller object set.

This page lists 18 BACnet objects for the Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
Procon BAC-A/50 (Mr. SLIM)
Equipment
Split air conditioner BACnet IP gateway (legacy)
Equipment type
VRF & split air conditioners
BACnet objects
18 (9 writable)
Transport
BACnet IP
Firmware
Product version 1.05 (PICS 06 Nov 2007)
Default device instance
14
Also known as
BAC-A/50, BACA50, Procon BAC A 50, RM2428
Source document
Procon BAC-A/50 Installation Instructions · rev. 2007-11-07 (v1.00)
Download CSV 18 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Mitsubishi Electric’s current documentation and the live device before use. Not official Mitsubishi Electric information. Terms of use.

BMS integration notes: Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM)

Integration in brief

Wire the Sub I/F boards to TB12, set IP, Device ID and unit names with the PC configuration program, then map each unit's _w (command) and _r (status) objects at 1UUUPP. BV 100024 switches every unit off at once.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 100101nnn_ON_wStart/stop the unitCommand
MO 100104nnn_MD_wCommand the operating modeCommand
AO 100109nnn_SP_wSetpoint commandCommand
MO 100106nnn_FS_wFan speed: 1 low, 2 mid2, 3 mid1, 4 highCommand
BI 100102nnn_ON_rConfirm run statusRead
AI 100108nnn_RARoom temperatureRead
AI 100103nnn_ECodeError code (8000 = no error)Read

Enable & remote start

The Enable Link terminals take a normally-closed volt-free contact (shipped with a wire link). Opening it sends Forced-Off to all units every 5 s; closing it sends one Reset, so later BMS Forced-Off commands (BV 100024) are not overridden.

Network setup

Watch out for

Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

18 of 18 shown
Type
Access
Show
Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM) BACnet Points List
DescriptionStates
BOmin100101nnn_ON_wOn/Off setupCommandInactive=Off, Active=On
BImin100102nnn_ON_rOn/Off stateReadInactive=Off, Active=On
AImin100103nnn_ECodeError code, 4 digits (8000 = no error)Read
MOmin100104nnn_MD_wOperation mode setupCommand1=Cool, 2=Dry, 3=Fan, 4=Heat, 5=Auto, 6=Ventilation
MI100105nnn_MD_rOperation mode stateRead1=Cool, 2=Dry, 3=Fan, 4=Heat, 5=Auto, 6=Ventilation
MOmin100106nnn_FS_wFan speed setupCommand1=Low, 2=Mid2, 3=Mid1, 4=High
MI100107nnn_FS_rFan speed stateRead1=Low, 2=Mid2, 3=Mid1, 4=High
AImin100108nnn_RARoom temperature, 8-39 °C°CRead
AOmin100109nnn_SP_wSetpoint setup (cool/dry 19-30, heat 17-28, auto 19-28)°CCommand
AI100110nnn_SP_rSetpoint state°CRead
BI100111nnn_FL_rFilter sign stateReadInactive=Sign Off, Active=Sign On
BO100112nnn_FL_wFilter sign resetCommandInactive=Clear Sign, Active=No Action
BO100113nnn_LI_wLocal (remote controller) inhibit setupCommandInactive=Off, Active=Inhibit
BI100114nnn_LI_rLocal inhibit stateReadInactive=Off, Active=Inhibited
AV100023Sys_Units_To_ScanNumber of units scanned, 1-50 (applies after restart)Write
BV100024Sys_Forced_Off_CtrlSystem forced off (all units off)WriteInactive=Off, Active=On
BI100025Sys_Enable_Link_StateEnable Link contact presentReadInactive=No Link Present, Active=Link Present
BV100026Sys_New_Setting_CompareWrite commands only when changedWriteInactive=Always write, Active=Write only if different
Object ID lookup: Mitsubishi Electric Procon BAC-A/50 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Procon BAC-A/50 (Mr. SLIM) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM)

How many BACnet points does the Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM) have?

This list has 18 BACnet objects: 3 analog inputs, 1 analog output, 1 analog value, 4 binary inputs, 3 binary outputs, 2 binary values, 2 multi-state inputs, 2 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM) BACnet points are writable?

9 of the 18 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM) BACnet documentation?

The source is Procon BAC-A/50 Installation Instructions, revision 2007-11-07 (v1.00), published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/387.

What are the minimum BACnet points to integrate the Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM)?

Start with BO 100101 nnn_ON_w (Start/stop the unit); MO 100104 nnn_MD_w (Command the operating mode); AO 100109 nnn_SP_w (Setpoint command); MO 100106 nnn_FS_w (Fan speed: 1 low, 2 mid2, 3 mid1, 4 high); BI 100102 nnn_ON_r (Confirm run status); AI 100108 nnn_RA (Room temperature); AI 100103 nnn_ECode (Error code (8000 = no error)).

How do I enable BMS control of the Mitsubishi Electric Procon BAC-A/50 (Mr. SLIM)?

The Enable Link terminals take a normally-closed volt-free contact (shipped with a wire link). Opening it sends Forced-Off to all units every 5 s; closing it sends one Reset, so later BMS Forced-Off commands (BV 100024) are not overridden.

How do I check these points on the real Procon BAC-A/50 (Mr. SLIM)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.