VRF central controller gateway · BACnet points list

Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway) BACnet points list

Updated 7 November 2026

Short answer

The Procon MelcoBEMS2 connects to a Mitsubishi Electric centralised controller over Ethernet and republishes up to 50 air-conditioning groups on BACnet IP (and Modbus). Each group gets the same block of objects: on/off, mode, fan speed, setpoint, vane, filter sign and inhibit commands with matching states, room temperature, error code, energy and run-time totals, hot-water heat pump values and dual setpoints, plus system objects for M-NET and controller status and a global forced-off.

This page lists 71 BACnet objects for the Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway) — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Mitsubishi Electric’s own free documentation, linked below.

Manufacturer
Mitsubishi Electric
Model
Procon MelcoBEMS2 (centralised controller BEMS gateway)
Equipment
VRF central controller gateway
Equipment type
VRF & split air conditioners
BACnet objects
71 (22 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
MelcoBEMS2, MelcoBEMS, Procon MelcoBEMS, MELCOBEMS
Source document
Procon MelcoBEMS2 Installation and Operation Manual (version 1.09)
Download CSV 71 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Mitsubishi Electric’s current documentation and the live device before use. Not official Mitsubishi Electric information. Terms of use.

BMS integration notes: Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway)

Integration in brief

Point the MelcoBEMS2 at the centralised controller's IP address in its web page, set the BACnet device instance and port, then map each group's on/off, mode, setpoint and fan commands with their state objects, room temperature and error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 100101Grp nnn On Off WrGroup on/off commandCommand
MO 100104Operation Mode WrOperation mode commandCommand
AO 100109Grp nnn Setpoint Temperature WrSetpoint commandCommand
MO 100106Fan Speed WrFan speed commandCommand
BI 100102Grp nnn On Off RdOn/off stateRead
MI 100105Operation Mode RdCurrent operation modeRead
AI 100108Grp nnn Room TemperatureRoom temperatureRead
AI 100103Grp nnn (Unit nn) Error Code4-digit error code, 8000 = no errorRead
BI 100026G50 Comms StateCentralised controller link, Active = OKRead

Enable & remote start

Functions to be inhibited locally (on/off, mode, setpoint, filter reset) must first be set on the centralised controller; Local Inhibit Wr then locks them at the remote controller.

Network setup

Watch out for

Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

71 of 71 shown
Type
Other
Access
Show
Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway) BACnet Points List
DescriptionStates
BOmin100101Grp nnn On Off WrOn/off commandCommandInactive=Off, Active=On
BImin100102Grp nnn On Off RdOn/off stateReadInactive=Off, Active=On
AImin100103Grp nnn (Unit nn) Error Code4-digit error code, 8000 = no errorRead
MOmin100104Operation Mode WrOperation mode commandCommand1=Cool, 2=Dry, 3=Fan, 4=Heat, 5=Auto, 6=Heat Recovery, 7=LC_Auto, 8=Bypass, 9=AutoHeat, 10=AutoCool, 11=Heating, 12=Eco-Heating, 13=Hot-Water, 14=Anti-Freeze, 15=Cooling, 16=Setback, 17=Setback Heat, 18=Setback Cool
MImin100105Operation Mode RdOperation mode stateRead1=Cool, 2=Dry, 3=Fan, 4=Heat, 5=Auto, 6=Heat Recovery, 7=LC_Auto, 8=Bypass, 9=AutoHeat, 10=AutoCool, 11=Heating, 12=Eco-Heating, 13=Hot-Water, 14=Anti-Freeze, 15=Cooling, 16=Setback, 17=Setback Heat, 18=Setback Cool
MOmin100106Fan Speed WrFan speed commandCommand1=Low, 2=Mid2 (low medium), 3=Mid1 (high medium), 4=High, 5=Auto
MI100107Fan Speed RdFan speed stateRead1=Low, 2=Mid2 (low medium), 3=Mid1 (high medium), 4=High, 5=Auto
AImin100108Grp nnn Room TemperatureRoom temperature°CRead
AOmin100109Grp nnn Setpoint Temperature WrSetpoint command (cool/dry 19-30, heat 17-28, auto 19-28)°CCommand
AI100110Grp nnn Setpoint Temperature RdSetpoint state°CRead
BI100111Filter Sign RdFilter sign stateReadInactive=Sign Off, Active=Sign On
BO100112Filter Sign WrFilter sign resetCommandInactive=Clear Sign, Active=No Action
BO100113Local Inhibit WrInhibit local remote controllerCommandInactive=Off, Active=Inhibit
BI100114Local Inhibit RdLocal inhibit stateReadInactive=Off, Active=Inhibited
MO100115Air Direction WrVane direction commandCommand1=Horizontal, 2=Diagonal 0 (20%), 3=Diagonal 1, 4=Diagonal 2, 5=Vertical, 6=Swing, 7=Auto
MI100116Air Direction RdVane direction stateRead1=Horizontal, 2=Diagonal 0 (20%), 3=Diagonal 1, 4=Diagonal 2, 5=Vertical, 6=Swing, 7=Auto
MO100117Ventilation WrVentilation command (Lossnay/OA units)Command1=Off, 2=Low, 3=High
MI100118Ventilation RdVentilation state (Lossnay/OA units)Read1=Off, 2=Low, 3=High
AI100119Unit nn Energy DayPrevious day energykWhRead
AI100120Unit nn Energy MonthPrevious month energykWhRead
AI100131Inlet Water Temp RdInlet water temperature (hot water heat pump)°CRead
AI100132Outlet Water Temp RdOutlet water temperature°CRead
AI100133Representative W Temp RdRepresentative water temperature°CRead
AI100134Outdoor Temp RdOutdoor unit temperature°CRead
AO100135Warm Water Setp WrWarm water setpoint command°CCommand
AI100136Warm Water Setp RdWarm water setpoint state°CRead
AO100137Hot Water Setp WrHot water setpoint command°CCommand
AI100138Hot Water Setp RdHot water setpoint state°CRead
BO100139Fan Mode WrFan mode commandCommand
BI100140Fan Mode RdFan mode stateRead
AI100141Unit Cool time previous dayCooling run time, previous dayRead
AI100142Unit Heat time previous dayHeating run time, previous dayRead
AI100143Unit On time previous dayOn time, previous dayRead
AI100144Unit Cool time previous monthCooling run time, previous monthRead
AI100145Unit Heat time previous monthHeating run time, previous monthRead
AI100146Unit On time previous monthOn time, previous monthRead
AI100151Inlet Water Temp ReadInlet water temperature°CRead
AI100152Outlet Water Temp ReadOutlet water temperature°CRead
AI100153Repr. Outlet Temp ReadRepresentative outlet temperature°CRead
AI100154Outdoor Temp ReadOutdoor temperature°CRead
AI100155Repr. Inlet Temp ReadRepresentative inlet temperature°CRead
AI100156Brine Temp ReadBrine temperature°CRead
AO100157Heat Setpoint WriteHeating setpoint command°CCommand
AI100158Heat Setpoint ReadHeating setpoint state°CRead
AO100159Cool Setpoint WriteCooling setpoint command°CCommand
AI100160Cool Setpoint ReadCooling setpoint state°CRead
BO100161Fan Mode WriteFan mode commandCommand
BO100162Fan Mode ReadFan mode state (printed as a Binary Output)Command
BI100163Test Run ReadTest run stateRead
AI100166Cool Setpoint ReadCooling setpoint (dual setpoint) state°CRead
AI100167Heat Setpoint ReadHeating setpoint (dual setpoint) state°CRead
AI100168Auto Setpoint ReadAuto setpoint state°CRead
AI100169Setback cool setpoint ReadSetback cooling setpoint state°CRead
AI100170Setback heat setpoint ReadSetback heating setpoint state°CRead
AO100166Cool Setpoint ReadCooling setpoint (dual setpoint) write object°CCommand
AO100167Heat Setpoint ReadHeating setpoint (dual setpoint) write object°CCommand
AO100168Auto Setpoint ReadAuto setpoint write object°CCommand
AO100169Setback cool setpoint ReadSetback cooling setpoint write object°CCommand
AO100170Setback heat setpoint ReadSetback heating setpoint write object°CCommand
TL100141Unit Cool time previous dayTrend log of AI 1xxx41Read
TL100142Unit Heat time previous dayTrend log of AI 1xxx42Read
TL100143Unit On time previous dayTrend log of AI 1xxx43Read
TL100144Unit Cool time previous monthTrend log of AI 1xxx44Read
TL100145Unit Heat time previous monthTrend log of AI 1xxx45Read
TL100146Unit On time previous monthTrend log of AI 1xxx46Read
AI105122OC/BC Error CodeOutdoor/BC controller error code (name as detected)Read
BI100023MNET Comms StateM-NET communication stateReadInactive=Init, Active=OK
BO100024System Forced Off WrGlobal forced-off commandCommandInactive=Off, Active=On
BI100025System Forced Off RdGlobal forced-off stateReadInactive=Off, Active=On
BImin100026G50 Comms StateLink to the centralised controllerReadInactive=Error, Active=OK
BV100027New Setting CompareWrite handling: always or on change onlyWriteInactive=Write Always, Active=Write COV
Object ID lookup: Mitsubishi Electric Procon MelcoBEMS2 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Procon MelcoBEMS2 (centralised controller BEMS gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway)

How many BACnet points does the Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway) have?

This list has 71 BACnet objects: 31 analog inputs, 10 analog outputs, 8 binary inputs, 7 binary outputs, 1 binary value, 4 multi-state inputs, 4 multi-state outputs, 6 trend logs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway) BACnet points are writable?

22 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway) BACnet documentation?

The source is Procon MelcoBEMS2 Installation and Operation Manual (version 1.09), published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5540.

What are the minimum BACnet points to integrate the Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway)?

Start with BO 100101 Grp nnn On Off Wr (Group on/off command); MO 100104 Operation Mode Wr (Operation mode command); AO 100109 Grp nnn Setpoint Temperature Wr (Setpoint command); MO 100106 Fan Speed Wr (Fan speed command); BI 100102 Grp nnn On Off Rd (On/off state); MI 100105 Operation Mode Rd (Current operation mode); AI 100108 Grp nnn Room Temperature (Room temperature); AI 100103 Grp nnn (Unit nn) Error Code (4-digit error code, 8000 = no error); BI 100026 G50 Comms State (Centralised controller link, Active = OK).

How do I enable BMS control of the Mitsubishi Electric Procon MelcoBEMS2 (centralised controller BEMS gateway)?

Functions to be inhibited locally (on/off, mode, setpoint, filter reset) must first be set on the centralised controller; Local Inhibit Wr then locks them at the remote controller.

How do I check these points on the real Procon MelcoBEMS2 (centralised controller BEMS gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Mitsubishi Electric BACnet points lists

Source: Procon MelcoBEMS2 Installation and Operation Manual (version 1.09). Object names, instances and units are reproduced as published; descriptions are our own.