 "manufacturer": "Mitsubishi Electric",
 "manufacturer_slug": "mitsubishi-electric",
 "model": "FR-F800 inverter (BACnet MS/TP; FR-F800-E BACnet IP)",
 "model_slug": "fr-f800",
 "aliases": [
  "FR-F800",
  "FR-F800-E",
  "FR-F820",
  "FR-F840",
  "FR-F842",
  "FR-F846",
  "FR-F820-E",
  "FR-F840-E",
  "FR-F842-E",
  "FR-F846-E",
  "Mitsubishi FR-F800 BACnet",
  "IB-0600547ENG",
  "IB-0600628ENG"
 ],
 "equipment_type": "Variable frequency drive (HVAC fan and pump)",
 "applies_to": "Mitsubishi Electric FR-F800 fan and pump inverters (FR-F820/F840/F842/F846) on the RS-485 terminals, and FR-F800-E models on the built-in Ethernet port.",
 "summary": "The FR-F800 runs BACnet MS/TP on its RS-485 terminals when Pr.549 = 2; the FR-F800-E Ethernet models also offer BACnet IP. Both manuals print the same fixed object list: terminal inputs and outputs, run/stop, direction and fault reset BVs, the Speed scale frequency command (% of Pr.390), PID setpoint and feedback commands, output monitors, fault history and a mailbox for other parameters. The drive is a B-ASC.",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet IP"
 ],
 "firmware": "PICS firmware revision 2.00 (MS/TP manual); 1.00 in the Ethernet manual PICS",
 "default_device_instance": 0,
 "access_inferred": false,
 "notes": [
  "Points are from the FR-F800 Instruction Manual (Detailed) IB-0600547ENG-G, section 5.12.7 (PDF pp546-550). The FR-A800-E/F800-E Ethernet Function Manual IB-0600628ENG-D (PDF pp85-88) lists the same objects, names and units for BACnet IP; that manual says only FR-F800-E drives support BACnet IP.",
  "The Ethernet manual marks BO 1-6 as R and BV 300-306 as R or blank; the MS/TP manual marks them all C. The MS/TP manual values are used here.",
  "BO 0-6 only drive their terminals when that terminal's function (Pr.190-Pr.196) is 82 or 182.",
  "BV 305 JOG, BV 307 STOP, BV 308 RES and BV 309 CS have no effect at the factory setting; reassign those signals with Pr.185, Pr.186, Pr.188 and Pr.189 to use them.",
  "AV 398/399 mailbox: write a register number to AV 398, then read or write AV 399. Register numbers follow the manual (for example 41000 + parameter number for Pr.0-999).",
  "Writes to C objects stay in the priority array even when the drive refuses them (Write Access Denied) because of the operation mode."
 ],
 "source": {
  "title": "FR-F800 Instruction Manual (Detailed), 5.12.7 BACnet MS/TP protocol, Supported BACnet object; also FR-A800-E/FR-F800-E Ethernet Function Manual, 2.5.7 BACnet/IP",
  "doc_number": "IB-0600547ENG-G (BACnet IP: IB-0600628ENG-D)",
  "revision_date": "2024-10",
  "url": "https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600547eng/ib0600547engg.pdf"
 },
 "integration": {
  "summary": "For MS/TP set Pr.549 = 2, the MAC address in Pr.331, the baud rate in Pr.332 and the device instance in Pr.728/Pr.729. For BACnet IP on an F800-E set 47808 in one of Pr.1427-Pr.1429 and allow the BMS IP range in Pr.1449-Pr.1454. With the drive in Network operation mode and NET as command and speed source, write AV 300 Speed scale and BV 400 Run/Stop, and read BV 0, AV 1, AV 2 and BV 99.",
  "minimum_points": [
   {
    "ref": "BV 400",
    "name": "Run/Stop",
    "why": "Start/stop command (1 = start)"
   },
   {
    "ref": "AV 300",
    "name": "Speed scale",
    "why": "Frequency command, % of Pr.390"
   },
   {
    "ref": "BV 402",
    "name": "Fault reset",
    "why": "Clears the fault output"
   },
   {
    "ref": "BV 0",
    "name": "Inverter running",
    "why": "Running status"
   },
   {
    "ref": "BV 11",
    "name": "Inverter operation ready",
    "why": "Drive ready to run"
   },
   {
    "ref": "AV 1",
    "name": "Output frequency",
    "why": "Output frequency, Hz"
   },
   {
    "ref": "AV 2",
    "name": "Output current",
    "why": "Motor amps"
   },
   {
    "ref": "AV 14",
    "name": "Output power",
    "why": "Output power, kW"
   },
   {
    "ref": "BV 99",
    "name": "Fault output",
    "why": "Any active drive fault"
   },
   {
    "ref": "AV 200",
    "name": "Alarm history 1",
    "why": "Latest fault record"
   }
  ],
  "enable": "BV 400/401 and the AV 300-322 commands can be written at any time but are only applied when the communication operation command source and speed command source are NET (Pr.338/Pr.339) and the drive is in Network operation mode. The start command takes effect after Speed scale is applied.",
  "heartbeat": "The MS/TP section gives no BACnet-specific timeout. For RS-485 terminal communication, Pr.502 sets the action on a communication error (coast, decelerate to stop, or keep running at the Pr.779 frequency) and the LF alarm turns on. On an F800-E, Pr.1432 Ethernet communication check time interval (default 9999 = off) trips E.EHR if the devices in the Pr.1449-Pr.1454 range stop sending; Pr.1431 sets the action on a physical Ethernet loss.",
  "remote_sensors": "AV 311 PID measured value CMD lets the BMS write the PID feedback (and AV 310 the setpoint) when Pr.128 = 60 or 61; AV 321/AV 320 do the same for the second PID when Pr.753 = 60 or 61.",
  "setup": [
   "MS/TP: Pr.549 = 2 (BACnet MS/TP), Pr.331 MAC address 0-127 (default 0), Pr.332 baud rate = setting x 100 bps (96 default, up to 1152).",
   "Pr.726 Auto Baudrate/Max Master: bit 7 turns on auto baud, bits 0-6 are Max Master (default 255). Pr.727 Max Info Frames, default 1.",
   "Device instance = Pr.728 (upper 3 digits) and Pr.729 (lower 4 digits), 0 to 4194302, default 0.",
   "MS/TP is fixed at 8 data bits, no parity, 1 stop bit. The drive has local bias resistors only, so at least one node on the segment must provide network bias.",
   "BACnet IP (FR-F800-E only): set 47808 in one of Pr.1427-Pr.1429 Ethernet function selection and set Pr.1449-Pr.1454 to the BMS IP range; while those are 0, no commands are accepted over Ethernet.",
   "Pr.390 % setting reference frequency (default 60 Hz FM / 50 Hz CA) is the 100 % point for AV 300."
  ],
  "gotchas": [
   "Pr.342 = 0 (default) stores parameters written over the network in EEPROM; set Pr.342 = 1 if the BMS writes parameters often.",
   "The set frequency only changes when AV 300 is written, not when Pr.390 changes, and it is held in RAM.",
   "BACnet IP: do not include other inverters' IP addresses in the Pr.1449-Pr.1454 range, or the drive trips E.EHR.",
   "Segmentation is not supported.",
   "Automatic baud rate recognition writes the detected baud rate to Pr.332 in EEPROM."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "Terminal 1",
   "description": "Terminal 1 input level (range per Pr.73/Pr.267)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Terminal 2",
   "description": "Terminal 2 input level (range per Pr.73/Pr.267)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Terminal 4",
   "description": "Terminal 4 input level (range per Pr.73/Pr.267)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "Terminal FM (CA)",
   "description": "Terminal FM/CA output level, 0-200 %; needs Pr.54 = 85",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "Terminal AM",
   "description": "Terminal AM output level, -200 to 200 %; needs Pr.158 = 86",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Output frequency",
   "description": "Output frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Output current",
   "description": "Output current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Output voltage",
   "description": "Output voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Running speed",
   "description": "Running speed",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Converter output voltage",
   "description": "Converter (DC bus) output voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Output power",
   "description": "Output power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Load meter",
   "description": "Load meter",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Cumulative energization time",
   "description": "Cumulative power-on time",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Actual operation time",
   "description": "Actual run time",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Cumulative power",
   "description": "Cumulative energy",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "PID set point",
   "description": "PID setpoint monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "PID deviation",
   "description": "PID deviation monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "PID measured value2",
   "description": "PID measured value 2 monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "Second PID set point",
   "description": "Second PID setpoint monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "Second PID deviation",
   "description": "Second PID deviation monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "Second PID measured value 2",
   "description": "Second PID measured value 2 monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 200,
   "name": "Alarm history 1",
   "description": "Fault record 1 (latest)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 201,
   "name": "Alarm history 2",
   "description": "Fault record 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 202,
   "name": "Alarm history 3",
   "description": "Fault record 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 203,
   "name": "Alarm history 4",
   "description": "Fault record 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 300,
   "name": "Speed scale",
   "description": "Frequency command as % of Pr.390, 0.00-100.00",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 310,
   "name": "PID set point CMD",
   "description": "PID setpoint when Pr.128 = 60 or 61, 0-100",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 311,
   "name": "PID measured value CMD",
   "description": "PID measured value when Pr.128 = 60 or 61, 0-100",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 312,
   "name": "PID deviation CMD",
   "description": "PID deviation when Pr.128 = 50 or 51, -100 to 100",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 320,
   "name": "Second PID set point CMD",
   "description": "Second PID setpoint when Pr.753 = 60 or 61",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 321,
   "name": "Second PID measured value CMD",
   "description": "Second PID measured value when Pr.753 = 60 or 61",
   "units": "",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 322,
   "name": "Second PID deviation CMD",
   "description": "Second PID deviation when Pr.753 = 50 or 51",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 398,
   "name": "Mailbox parameter",
   "description": "Register number for indirect access",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 399,
   "name": "Mailbox value",
   "description": "Value read or written through the mailbox",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10007,
   "name": "Acceleration time",
   "description": "Pr.7 acceleration time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10008,
   "name": "Deceleration time",
   "description": "Pr.8 deceleration time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "Terminal STF",
   "description": "Input terminal STF state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Terminal STR",
   "description": "Input terminal STR state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Terminal AU",
   "description": "Input terminal AU state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Terminal RT",
   "description": "Input terminal RT state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Terminal RL",
   "description": "Input terminal RL state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Terminal RM",
   "description": "Input terminal RM state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Terminal RH",
   "description": "Input terminal RH state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Terminal JOG",
   "description": "Input terminal JOG state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Terminal MRS",
   "description": "Input terminal MRS state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Terminal STOP",
   "description": "Input terminal STOP state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "Terminal RES",
   "description": "Input terminal RES state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "Terminal CS",
   "description": "Input terminal CS state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 100,
   "name": "Terminal RUN",
   "description": "Output terminal RUN state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 101,
   "name": "Terminal SU",
   "description": "Output terminal SU state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 102,
   "name": "Terminal IPF",
   "description": "Output terminal IPF state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 103,
   "name": "Terminal OL",
   "description": "Output terminal OL state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 104,
   "name": "Terminal FU",
   "description": "Output terminal FU state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 105,
   "name": "Terminal ABC1",
   "description": "Output terminal ABC1 state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 106,
   "name": "Terminal ABC2",
   "description": "Output terminal ABC2 state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 107,
   "name": "Terminal So (SO)",
   "description": "Output terminal So (SO) state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BO",
   "instance": 0,
   "name": "Terminal RUN CMD",
   "description": "Drives output RUN; needs Pr.190 = 82 or 182",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Terminal SU CMD",
   "description": "Drives output SU; needs Pr.191 = 82 or 182",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "Terminal IPF CMD",
   "description": "Drives output IPF; needs Pr.192 = 82 or 182",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BO",
   "instance": 3,
   "name": "Terminal OL CMD",
   "description": "Drives output OL; needs Pr.193 = 82 or 182",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BO",
   "instance": 4,
   "name": "Terminal FU CMD",
   "description": "Drives output FU; needs Pr.194 = 82 or 182",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "Terminal ABC1 CMD",
   "description": "Drives output ABC1; needs Pr.195 = 82 or 182",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BO",
   "instance": 6,
   "name": "Terminal ABC2 CMD",
   "description": "Drives output ABC2; needs Pr.196 = 82 or 182",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "Inverter running",
   "description": "Running (RUN signal)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "Inverter operation ready",
   "description": "Ready to run (RY signal)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 98,
   "name": "Alarm output",
   "description": "Alarm (LF signal)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 99,
   "name": "Fault output",
   "description": "Fault (ALM signal)",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 200,
   "name": "Inverter running reverse",
   "description": "Running in reverse",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 300,
   "name": "Control input instruction AU",
   "description": "Turns on the function set in Pr.184 (terminal AU)",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 301,
   "name": "Control input instruction RT",
   "description": "Turns on the function set in Pr.183 (terminal RT)",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 302,
   "name": "Control input instruction RL",
   "description": "Turns on the function set in Pr.180 (terminal RL)",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 303,
   "name": "Control input instruction RM",
   "description": "Turns on the function set in Pr.181 (terminal RM)",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 304,
   "name": "Control input instruction RH",
   "description": "Turns on the function set in Pr.182 (terminal RH)",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 305,
   "name": "Control input instruction JOG",
   "description": "Turns on the function set in Pr.185 (terminal JOG)",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 306,
   "name": "Control input instruction MRS",
   "description": "Turns on the function set in Pr.187 (terminal MRS)",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 307,
   "name": "Control input instruction STOP",
   "description": "Turns on the function set in Pr.188 (terminal STOP)",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 308,
   "name": "Control input instruction RES",
   "description": "Turns on the function set in Pr.189 (terminal RES)",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 309,
   "name": "Control input instruction CS",
   "description": "Turns on the function set in Pr.186 (terminal CS)",
   "units": "",
   "access": "C",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 400,
   "name": "Run/Stop",
   "description": "Start/stop command",
   "units": "",
   "access": "C",
   "states": "0=Stop, 1=Start"
  },
  {
   "type": "BV",
   "instance": 401,
   "name": "Forward/Reverse",
   "description": "Rotation direction",
   "units": "",
   "access": "C",
   "states": "0=Forward rotation, 1=Reverse rotation"
  },
  {
   "type": "BV",
   "instance": 402,
   "name": "Fault reset",
   "description": "Clears the fault output without resetting the drive",
   "units": "",
   "access": "C",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/mitsubishi-electric/fr-f800",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}