Rooftop unit / air handler controller · BACnet points list

AAON VCCX-454 Controller BACnet points list

Updated 12 November 2026

Short answer

The VCCX-454 is the unit controller AAON uses on its R-454B equipment. It has an on-board BACnet port that can be set for MS/TP or BACnet IP. The object map has about 350 read-only analog inputs (temperatures, pressures, airflow, RM454 refrigerant module data, power monitor and fan array data), 99 writable analog values (setpoints, overrides and BAS-written sensor values) and about 150 read-only binary inputs (alarms, A2L leak alarms, module and relay status).

This page lists 602 BACnet objects for the AAON VCCX-454 Controller — 99 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.

Manufacturer
AAON
Model
VCCX-454 Controller
Equipment
Rooftop unit / air handler controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
602 (99 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Also known as
VCCX-454, VCCX 454, ASM07503, SS1188, AAON VCCX-454 controller, R-454B unit controller
Source document
VCCX-454 Controller Technical Guide · ASM07503 Rev. I · rev. 2026-08
Download CSV 602 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.

BMS integration notes: AAON VCCX-454 Controller

Integration in brief

Connect the on-board BACnet port (MS/TP or IP) and set the MAC address, device ID and baud or IP settings on the LCD BACnet screens. The BAS schedules the unit with AV 67 Schedule Force, adjusts the occupied setpoints and supply air setpoints, and can override HVAC mode, fan VFD and OA damper. Alarms are read from the BI objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 67Schedule ForceOccupancy: 0 auto, 1 occupied, 2 unoccupiedWrite
AV 1Occupied Cooling SetpointCooling starts one deadband above thisWrite
AV 2Occupied Heating SetpointHeating starts one deadband below thisWrite
AV 10Supply Air Cooling SetpointDischarge air target in coolingWrite
AI 3Control StatusCurrent occupancy statusRead
AI 4HVAC ModeCurrent operating modeRead
AI 5Control TemperatureReading from the configured control sensorRead
AI 9Supply Air TemperatureDischarge air temperatureRead
AI 144Alarm StatusSummary alarmRead

Enable & remote start

Occupancy comes from AV 67 Schedule Force (0 = controller schedule, 1 = forced occupied, 2 = forced unoccupied) or the controller's own schedule. AV 68, AV 69, AV 70 and AV 71 override HVAC mode, fan VFD, OA damper and supply setpoint; writing Auto (0, or 65535 for the VFD overrides) hands control back. AV 98 locks out the compressors.

Sensors & values from the BMS

If the controller is configured for it, the BAS can write AV 72 Space Temperature Value, AV 73 Space Humidity Value, AV 76 Relief Pressure Value, AV 77 Carbon Dioxide Value, AV 78 Outdoor Air Temperature Value and AV 79 Outdoor Air Humidity Value. No refresh timeout is printed in the points table.

Network setup

Watch out for

AAON VCCX-454 Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

602 of 602 shown
Type
Binary
Access
Show
AAON VCCX-454 Controller BACnet Points List
DescriptionStates
AI1Application Software VersionCurrent version of the software in the unitRead
AI2Control ModeConfigured unit applicationRead
AImin3Control StatusConfigured Occupied or Unoccupied StatusRead
AImin4HVAC ModeCurrent Operation StatusRead
AImin5Control TemperatureCurrent value of the Control Temperature SensorRead
AI6Mode Cooling SetpointCooling Mode Enable Setpoint Mirror (adjusted by the SpaceRead
AI7Mode Heating SetpointHeating Mode Enable Setpoint Mirror (adjust by the SpaceRead
AI8Sensor Slide Adjust EffectAmount of Current Sensor Slide adjustRead
AImin9Supply Air TemperatureCurrent value of the Supply Air Temperature sensorRead
AI10Supply Air SetpointCurrent SAT Cooling or Heating Setpoint if thereRead
AI11Controlling Coil Temp SetpointCurrent calculated Coil Suction Temperature target during Dehumidification ModeRead
AI12Space TemperatureCurrent value of the Space Temperature SensorRead
AI13Space HumidityCurrent value of the Space HumidityRead
AI14Return Air TemperatureCurrent value of the Return Temperature SensorRead
AI15Return Air HumidityCurrent value of the Return Air HumidityRead
AI16Outdoor Air TemperatureCurrent value of the Outdoor Air Temperature SensorRead
AI17Outdoor Air HumidityCurrent value of the Outdoor Humidity SensorRead
AI18Outdoor Air WetbulbCurrent calculated Outdoor Wetbulb TemperatureRead
AI19Outdoor Air DewpointCurrent calculated Outdoor Air Dewpoint TemperatureRead
AI20Supply Air Setpoint Reset VoltageSupply Air Temp Setpoint Reset Input SignalRead
AI21Duct Static PressureCurrent Duct Static PressureRead
AI22Duct Static Control SignalCurrent Duct Static Control Signal (Fan VFD)Read
AI23Building PressureCurrent value of the Building Pressure SensorRead
AI24Building Pressure Control SignalCurrent Building Pressure Control SignalRead
AI25Outdoor AirflowCurrent Outdoor Airflow MeasurementRead
AI26Supply AirflowCurrent Supply Airflow MeasurementRead
AI27Return AirflowCurrent Return Airflow MeasurementRead
AI28Exhaust AirflowCurrent Exhaust Airflow MeasurementRead
AI29Carbon DioxideCurrent Indoor CO2 LevelRead
AI30Desired Economizer PositionCurrent Modulating Signal to the Economizer DamperRead
AI31Economizer Feedback PositionTitle 24 current position of the feedbackRead
AI32Return Damper PositionCurrent Signal to the Return Air Damper if usingRead
AI33Return Bypass PositionCurrent Signal to the Return Air Bypass DamperRead
AI34Modulating Cooling PositionCurrent percentage of the Modulating Chilled Water SignalRead
AI35Modulating Heat PositionCurrent percentage of the Modulating Heating signal (hot WaterRead
AI36Preheater Leaving Air Temp #1Current Preheater Leaving Air Temperature #1Read
AI37Preheater Leaving Air Temp #2Current Preheater Leaving Air Temperature #2Read
AI38Preheater Entering Air TempCurrent Entering Air Temp for PreheaterRead
AI39Preheater Setpoint Reset VoltageCurrent Voltage Reset Input Value for PreheaterRead
AI40Preheater SCR Output SignalCurrent Modulating Heat Signal for PreheaterRead
AI41Preheater PWM Output SignalCurrent PWM Output Signal for PreheaterRead
AI42Mod Hot Gas Reheat Valve PositionCurrent position of MHGRV Modulating Hot Gas Reheat ValveRead
AI43Mod Gas Heat Valve PositionCurrent position of MODGAS Modulating Gas Heat Valve ControlRead
AI44A1 Compressor SignalCurrent Compressor A1 Modulating Cooling SignalRead
AI45A2 Compressor SignalCurrent Compressor A2 Modulating Cooling SignalRead
AI46A1 Condenser SignalCurrent Condenser A1 SignalRead
AI47A2 Condenser SignalCurrent Condenser A2 SignalRead
AI48A1 Suction PressureCurrent Compressor A1 Suction PressureRead
AI49A2 Suction PressureCurrent Compressor A2 Suction PressureRead
AI50A1 Head PressureCurrent Compressor A1 Head PressureRead
AI51A2 Head PressureCurrent Compressor A2 Head PressureRead
AI52A1 Saturation TemperatureCurrent Compressor A1 Coil Saturation TemperatureRead
AI53A2 Saturation TemperatureCurrent Compressor A2 Coil Saturation TemperatureRead
AI54A1 Suction Line TemperatureCurrent Compressor A1 Suction Line TemperatureRead
AI55A2 Suction Line TemperatureCurrent Compressor A1 Suction Line TemperatureRead
AI56A1 Condenser Suction Temp (Heat Pump)Current Compressor A1 Suction Line Temperature (Heat Pump)Read
AI57A2 Condenser Suction Temp (Heat Pump)Current Compressor A2 Suction Line Temperature (Heat Pump)Read
AI58A1 Superheat TemperatureCurrent Compressor A1 Superheat TemperatureRead
AI59A2 Superheat TemperatureCurrent Compressor A2 Superheat TemperatureRead
AI60Condenser A1 Superheat (Heat Pump)Current Compressor A1 Superheat Temperature (Heat Pump)Read
AI61Condenser A2 Superheat (Heat Pump)Current Compressor A2 Superheat Temperature (Heat Pump)Read
AI62A1 Expansion Valve PositionCurrent position of Compressor A1 Expansion ValveRead
AI63A2 Expansion Valve PositionCurrent position of Compressor A2 Expansion ValveRead
AI64Condenser A1 Expansion Valve PositionCurrent position of Condenser A1 Expansion ValveRead
AI65Condenser A2 Expansion ValveCurrent position of Condenser A2 Expansion ValveRead
AI66A1 Discharge TemperatureCurrent Compressor A1 Discharge TemperatureRead
AI67A2 Discharge TemperatureCurrent Compressor A2 Discharge TemperatureRead
AI68A1 Leaving Water TempCurrent A1 Leaving Water Temperature for WSHPRead
AI69B1 Compressor SignalCurrent Compressor B1 Modulating Cooling SignalRead
AI70B2 Compressor SignalCurrent Compressor B2 Modulating Cooling SignalRead
AI71B1 Condenser SignalCurrent B1 Condenser SignalRead
AI72B2 Condenser SignalCurrent B2 Condenser Signal or WSE Bypass Valve SignalRead
AI73B1 Suction PressureCurrent Compressor B1 Suction PressureRead
AI74B2 Suction PressureCurrent Compressor B2 Suction PressureRead
AI75B1 Head PressureCurrent Compressor B1 Head PressureRead
AI76B2 Head PressureCurrent Compressor B2 Head PressureRead
AI77B1 Saturation TemperatureCurrent Compressor B1 Coil Saturation TemperatureRead
AI78B2 Saturation TemperatureCurrent Compressor B2 Coil Saturation TemperatureRead
AI79B1 Suction Line TemperatureCurrent Compressor B1 Suction Line TemperatureRead
AI80B2 Suction Line TemperatureCurrent Compressor B2 Suction Line TemperatureRead
AI81B1 Condenser Suction Temp (Heat Pump)Current Compressor B1 Suction Line Temperature (Heat Pump)Read
AI82B2 Condenser Suction Temp (Heat Pump)Current Compressor B2 Suction Line Temperature (Heat Pump)Read
AI83B1 Superheat TemperatureCurrent Compressor B1 Superheat Temperature (Heat Pump)Read
AI84B2 Superheat TemperatureCurrent Compressor B2 Superheat Temperature (Heat Pump)Read
AI85Condenser B1 Superheat (Heat Pump)Current Compressor B1 Superheat Temperature (Heat Pump)Read
AI86Condenser B2 Superheat (Heat Pump)Current Compressor B2 Superheat Temperature (Heat Pump)Read
AI87B1 Expansion Valve PositionCurrent position of Compressor B1 Expansion ValveRead
AI88B2 Expansion Valve PositionCurrent position of Compressor B2 Expansion ValveRead
AI89Condenser B1 Expansion Valve PositionCurrent position of Condenser B1 Expansion ValveRead
AI90Condenser B2 Expansion Valve PositionCurrent position of Condenser B2 Expansion ValveRead
AI91B1 Discharge TemperatureCurrent Compressor B1 Discharge TemperatureRead
AI92B2 Discharge TemperatureCurrent Compressor B2 Discharge TemperatureRead
AI93B1 Leaving Water TempCurrent B1 Leaving Water Temperature for WSHPRead
AI94C1 Compressor SignalCurrent Compressor C1 Modulating Cooling SignalRead
AI95C2 Compressor SignalCurrent Compressor C2 Modulating Cooling SignalRead
AI96C1 Condenser SignalCurrent C1 Condenser SignalRead
AI97C2 Condenser SignalCurrent C2 Condenser Signal or WSE Bypass Valve SignalRead
AI98C1 Suction PressureCurrent Compressor C1 Suction PressureRead
AI99C2 Suction PressureCurrent Compressor C2 Suction PressureRead
AI100C1 Head PressureCurrent Compressor C1 Head PressureRead
AI101C2 Head PressureCurrent Compressor C2 Head PressureRead
AI102C1 Saturation TemperatureCurrent Compressor C1 Coil Saturation TemperatureRead
AI103C2 Saturation TemperatureCurrent Compressor C2 Coil Saturation TemperatureRead
AI104C1 Suction Line TemperatureCurrent Compressor C1 Suction Line TemperatureRead
AI105C2 Suction Line TemperatureCurrent Compressor C2 Suction Line TemperatureRead
AI106C1 Condenser Suction Temp (Heat Pump)Current Compressor C1 Suction Line Temperature (Heat Pump)Read
AI107C2 Condenser Suction Temp (Heat Pump)Current Compressor C2 Suction Line Temperature (Heat Pump)Read
AI108C1 Superheat TemperatureCurrent Compressor C1 Superheat TemperatureRead
AI109C2 Superheat TemperatureCurrent Compressor C2 Superheat TemperatureRead
AI110Condenser C1 Superheat (Heat Pump)Current Compressor C1 Superheat Temperature (Heat pump)Read
AI111Condenser C2 Superheat (Heat Pump)Current Compressor C2 Superheat Temperature (Heat pump)Read
AI112C1 Expansion Valve PositionCurrent position of Compressor C1 Expansion ValveRead
AI113C2 Expansion Valve PositionCurrent position of Compressor C2 Expansion ValveRead
AI114Condenser C1 Expansion Valve PositionCurrent position of Condenser C1 Expansion ValveRead
AI115Condenser C2 Expansion Valve PositionCurrent position of Condenser C2 Expansion ValveRead
AI116C1 Discharge TemperatureCurrent Compressor C1 Discharge TemperatureRead
AI117C2 Discharge TemperatureCurrent Compressor C2 Discharge TemperatureRead
AI118C1 Leaving Water TempCurrent C1 Leaving Water Temperature for WSHPRead
AI119D1 Compressor SignalCurrent Compressor D1 Modulating Cooling SignalRead
AI120D2 Compressor SignalCurrent Compressor D2 Modulating Cooling SignalRead
AI121D1 Condenser SignalCurrent D1 Condenser SignalRead
AI122D2 Condenser SignalCurrent D2 Condenser Signal or WSE Bypass Valve SignalRead
AI123D1 Suction PressureCurrent Compressor D1 Suction PressureRead
AI124D2 Suction PressureCurrent Compressor D2 Suction PressureRead
AI125D1 Head PressureCurrent Compressor D1 Head PressureRead
AI126D2 Head PressureCurrent Compressor D2 Head PressureRead
AI127D1 Saturation TemperatureCurrent Compressor D1 Coil Saturation TemperatureRead
AI128D2 Saturation TemperatureCurrent Compressor D2 Coil Saturation TemperatureRead
AI129D1 Suction Line TemperatureCurrent Compressor D1 Suction Line TemperatureRead
AI130D2 Suction Line TemperatureCurrent Compressor D2 Suction Line TemperatureRead
AI131D1 Condenser Suction Temp (Heat Pump)Current Compressor D1 Suction Line Temperature (Heat Pump)Read
AI132D2 Condenser Suction Temp (Heat Pump)Current Compressor D2 Suction Line Temperature (Heat Pump)Read
AI133D1 Superheat TemperatureCurrent Compressor D1 Superheat TemperatureRead
AI134D2 Superheat TemperatureCurrent Compressor D2 Superheat TemperatureRead
AI135Condenser D1 Superheat (Heat Pump)Current Compressor D1 Superheat Temperature (Heat Pump)Read
AI136Condenser D2 Superheat (Heat Pump)Current Compressor D2 Superheat Temperature (Heat Pump)Read
AI137D1 Expansion Valve PositionCurrent position of Compressor D1 Expansion ValveRead
AI138D2 Expansion Valve PositionCurrent position of Compressor D2 Expansion ValveRead
AI139Condenser D1 Expansion Valve PositionCurrent position of Condenser D1 Expansion ValveRead
AI140Condenser D2 Expansion Valve PositionCurrent position of Condenser D2 Expansion ValveRead
AI141D1 Discharge TemperatureCurrent Compressor D1 Discharge TemperatureRead
AI142D2 Discharge TemperatureCurrent Compressor D2 Discharge TemperatureRead
AI143D1 Leaving Water TempCurrent D1 Leaving Water Temperature for WSHPRead
AImin144Alarm StatusAn alarm conditionRead
AI145Outdoor EnthalpyCurrent outdoor EnthalpyRead
AI146Plenum PressureReservedRead
AI147Return Fan SpeedReservedRead
AI148Plenum Calculated SetpointReservedRead
AI149Return Air Enthalpy StatusCurrent value of Return Air EnthalpyRead
AI150Current Duct Static SetpointStatus of the duct static setpointRead
AI151RM454-Z 1 Condenser FanCurrent RM454-Z 1 Condenser Fan SignalRead
AI152RM454-Z 1 VDC Comp PercCurrent RMR454-Z 1 VFD Compressor PercentageRead
AI153RM454-Z 1 Discharge PressureCurrent RM454-1 Discharge PressureRead
AI154RM454-Z 1 Suction PressureCurrent RM454-Z 1 Suction PressureRead
AI155RM454-Z 1 Suction Line TempCurrent RM454-Z 1 Suction Line TemperatureRead
AI156RM454-Z 1 Saturation TempCurrent RM454-Z 1 Saturation TemperatureRead
AI157RM454-Z 1 SuperheatCurrent RM454-Z 1 Superheat TemperatureRead
AI158RM454-Z 1 EEV PositionCurrent RM454-Z 1 EEV Valve PositionRead
AI159RM454-Z 1 WarningsCurrent RM454-Z 1 WarningsRead
AI160RM454-Z 1 Comp VFD Alarms 1Current RM454-Z 1 Comp VFD Alarms 1Read
AI161RM454-Z 1 Comp VFD Alarms 2Current Rm 454-Z 1 Comp VFD Alarms 2Read
AI162RM454-Z 1 Comp VFD Drive StatusCurrent RM454-Z 1 Comp VFD drive StatusRead
AI163RM454-Z 1 Compressor CurrentCurrent reading in Amps that the RM454Z 1 CompressorRead
AI164RM454-Z 1 Discharge Line TempCurrent RM454-Z 1 discharge line temperatureRead
AI165RM454-Z 1 FaultsCurrent RM45-Z 1 FaultsRead
AI166RM454-Z 1 LockoutsCurrent RM454-Z 1 LockoutsRead
AI167RM454-Z 2 Condenser FanCurrent RM454-Z 2 condenser fan signalRead
AI168RM454-Z 2 VFD Comp PercCurrent RM454-Z 2 VFD Compressor PercentageRead
AI169RM454-Z 2 Discharge PressureCurrent RM454-Z 2 discharge pressureRead
AI170RM454-Z 2 Suction PressureCurrent RM454-Z 2 Suction PressureRead
AI171RM454-Z 2 Suction Line TempCurrent RM454-Z 2 Suction Line TemperatureRead
AI172RM454-Z 2 Saturation TempCurrent RM454-Z 2 Saturation TemperatureRead
AI173RM454-Z 2 SuperheatCurrent RM454-Z 2 Superheat temperatureRead
AI174RM454-Z 2 EEV PositionCurrent RM454-Z 2 EEV valve positionRead
AI175RM454-Z 2 WarningsCurrent RM454-Z 2 WarningsRead
AI176RM454-Z 2 Comp VFD Alarms 1Current RM454-Z 2 Comp VFD Alarms 1Read
AI177RM454-Z 2 Comp VFD Alarms 2Current RM454-Z 2 Comp VFD Alarms 2Read
AI178RM454-Z 2 Comp VFD Drive StatusCurrent RM454-Z 2 Comp VFD Drive StatusRead
AI179RM454-Z 2 Compressor CurrentCurrent reading in Amps that the RM454Z 2 compressorRead
AI180RM454-Z 2 Discharge Line TempCurrent RM454-Z 2 discharge line temperatureRead
AI181RM454-Z 2 FaultsCurrent RM454-Z 2 FaultsRead
AI182RM454-Z 2 LockoutsCurrent RM454-Z 2 LockoutsRead
AI183RM454-Z 3 Condenser FanCurrent RM454-Z 3 condenser fan signalRead
AI184RM454-Z 3 Reheat Valve 1Current RM454-Z 3 Reheat Valve 1 positionRead
AI185RM454-Z 3 Discharge PressureCurrent RM454-Z 3 Discharge PressureRead
AI186RM454-Z 3 Suction PressureCurrent RM454-Z 3 Suction PressureRead
AI187RM454-Z 3 Suction Line TempCurrent RM454-Z 3 Suction Line TemperatureRead
AI188RM454-Z 3 Saturation TempCurrent RM454-Z 3 Saturation TemperatureRead
AI189RM454-Z 3 SuperheatCurrent RM454-Z 3 Superheat temperatureRead
AI190RM454-Z 3 EEV PositionCurrent RM454-Z 3 EEV valve positionRead
AI191RM454-Z 3 Suction Pressure 2Current RM454-Z 3 Suction Pressure 2Read
AI192RM454-Z 3 Suction Line Temp 2Current RM454-Z 3 Suction Line Temperature 2Read
AI193RM454-Z 3 Saturation Temp 2Current RM454-Z 3 Saturation Temperature 2Read
AI194RM454-Z 3 Superheat 2Current RM454-Z 3 Superheat Temperature 2Read
AI195RM454-Z 3 EEV Position 2Current RM454-Z 3 EEV Valve Position 2Read
AI196RM454-Z 3 WarningsCurrent RM454-Z 3 WarningsRead
AI197RM454-Z 3 Discharge Line TempCurrent RM454-Z 3 Discharge Line TemperatureRead
AI198RM454-Z 3 FaultsCurrent RM454-Z 3 FaultsRead
AI199RM454-Z 3 LockoutsCurrent RM454-Z 3 LockoutsRead
AI200RM454-Z 4 Condenser FanCurrent RM454-Z 4 Condenser Fan SignalRead
AI201RM454-Z 4 VFD Comp PercCurrent RM454-Z 4 VFD Compressor PercentageRead
AI202RM454-Z 4 Discharge PressureCurrent RM454-Z 4 Discharge PressureRead
AI203RM454-Z 4 Suction PressureCurrent RM454-Z 4 Suction PressureRead
AI204RM454-Z 4 Suction Line TempCurrent RM454-Z 4 Suction Line TemperatureRead
AI205RM454-Z 4 Saturation TempCurrent RM454-Z 4 Saturation TemperatureRead
AI206RM454-Z 4 SuperheatCurrent RM454-Z 4 Superheat TemperatureRead
AI207RM454-Z 4 EEV PositionCurrent RM454-Z 4 EEV Valve PositionRead
AI208RM454-Z 4 WarningsCurrent RM454-Z 4 WarningsRead
AI209RM454-Z 4 Comp VFD Alarms 1Current RM454-Z 4 Comp VFD Alarms 1Read
AI210RM454-Z 4 Comp VFD Alarms 2Current RM454-Z 4 Comp VFD Alarms 2Read
AI211RM454-Z 4 Comp VFD Drive StatusCurrent RM454-Z 4 Comp VFD Drive StatusRead
AI212RM454-Z 4 Comp VFD Compressor CurrentCurrent reading in Amps that the RM454-Z compressorRead
AI213RM454-Z 4 Discharge Line TempCurrent RM454-Z 4 Discharge Line TemperatureRead
AI214RM454-Z 4 FaultsCurrent RM454-Z 4 FaultsRead
AI215RM454-Z 4 LockoutsCurrent RM454-Z 4 LockoutsRead
AI216RM454-Z 5 Condenser FanCurrent RM454-Z 5 Condenser Fan SignalRead
AI217RM454-Z 5 VFD Comp PercCurrent RM454-Z 5 VFD Compressor PercentageRead
AI218RM454-Z 5 Discharge PressureCurrent RM454-Z 5 Discharge PressureRead
AI219RM454-Z 5 Suction PressureCurrent RM454-Z 5 Suction PressureRead
AI220RM454-Z 5 Suction Line TempCurrent RM454-Z 5 Suction Line TemperatureRead
AI221RM454-Z 5 Saturation TempCurrent RM454-Z 5 Saturation TemperatureRead
AI222RM454-Z 5 SuperheatCurrent RM454-Z 5 Superheat TemperatureRead
AI223RM454-Z 5 EEV PositionCurrent RM454-Z 5 EEV Valve PositionRead
AI224RM454-Z 5 WarningsCurrent RM454-Z 5 WarningsRead
AI225RM454-Z 5 Comp VFD Alarms 1Current RM454-Z 5 Comp VFD Alarms 1Read
AI226RM454-Z 5 Comp VFD Alarms 2Current RM454-Z 5 Comp VFD Alarms 2Read
AI227RM454-Z 5 Comp VFD Drive StatusCurrent RM454-Z 5 Comp VFD Drive StatusRead
AI228RM454-Z 5 Compressor CurrentCurrent reading in Amps that the RM454Z 5 compressorRead
AI229RM454-Z 5 Discharge Line TempCurrent RM454-Z 5 Discharge Line TemperatureRead
AI230RM454-Z 5 FaultsCurrent RM454-Z 5 FaultsRead
AI231RM454-Z 5 LockoutsCurrent RM454-Z 5 LockoutsRead
AI232RM454-Z 6 Condenser FanCurrent RM454-Z 6 Condenser Fan SignalRead
AI233RM454-Z 6 Reheat Valve 1Current RM454-Z 6 Reheat Valve 1 PositionRead
AI234RM454-Z 6 Discharge PressureCurrent RM454-Z 6 Discharge PressureRead
AI235RM454-Z 6 Suction PressureCurrent RM454-Z 6 Suction PressureRead
AI236RM454-Z 6 Suction Line TempCurrent RM454-Z 6 Suction Line TemperatureRead
AI237RM454-Z 6 Saturation TempCurrent RM454-Z 6 Saturation TemperatureRead
AI238RM454-Z 6 SuperheatCurrent RM454-Z 6 Superheat TemperatureRead
AI239RM454-Z 6 EEV PositionCurrent RM454-Z 6 EEV Valve PositionRead
AI240RM454-Z 6 Suction Pressure 2Current RM454-Z 6 Suction Pressure 2Read
AI241RM454-Z 6 Suction Line Temp 2Current RM454-Z 6 Suction Line Temperature 2Read
AI242RM454-Z 6 Saturation Temp 2Current RM454-Z 6 Saturation Temperature 2Read
AI243RM454-Z 6 Superheat 2Current RM454-Z 6 Superheat Temperature 2Read
AI244RM454-Z 6 EEV Position 2Current RM454-Z 6 EEV Valve Position 2Read
AI245RM454-Z 6 WarningsCurrent RM454-Z 6 WarningsRead
AI246RM454-Z 6 Discharge Line TempCurrent RM454-Z 6 Discharge Line TemperatureRead
AI247RM454-Z 6 FaultsCurrent RM454-Z 6 FaultsRead
AI248RM454-Z 6 LockoutsCurrent RM454-Z 6 LockoutsRead
AI249Not usedNot usedRead
AI250Not usedNot usedRead
AI251Not usedNot usedRead
AI252Not usedNot usedRead
AI253SUB 1 Sub Cool 1Current Subcooling Module 1 Sub Cool 1 ReadingRead
AI254SUB 1 Sub Cool 2Current Subcooling Module 1 Sub Cool 2 ReadingRead
AI255SUB 1 Sub Cool 3Current Subcooling Module 1 Sub Cool 3 ReadingRead
AI256SUB 1 Pressure 1Current Subcooling Module 1 Liquid Line Pressure 1 ReadingRead
AI257SUB 1 Pressure 2Current Subcooling Module 1 Liquid Line Pressure 2 ReadingRead
AI258SUB 1 Pressure 3Current Subcooling Module 1 Liquid Line Pressure 3 ReadingRead
AI259SUB 1 Saturation 1Subcooling Module 1 Saturation Temperature 1 ReadingRead
AI260SUB 1 Saturation 2Subcooling Module 1 Saturation Temperature 2 ReadingRead
AI261SUB 1 Saturation 3Subcooling Module 1 Saturation Temperature 3 ReadingRead
AI262SUB 1 Line Temp 1Subcooling Module 1 Liquid Line Temperature 1 ReadingRead
AI263SUB 1 Line Temp 2Subcooling Module 1 Liquid Line Temperature 2 ReadingRead
AI264SUB 1 Line Temp 3Subcooling Module 1 Liquid Line Temperature 3 ReadingRead
AI265SUB 2 Sub Cool 1Current Subcooling Module 2 Sub Cool 1 ReadingRead
AI266SUB 2 Sub Cool 2Current Subcooling Module 2 Sub Cool 2 ReadingRead
AI267SUB 2 Sub Cool 3Current Subcooling Module 2 Sub Cool 3 ReadingRead
AI268SUB 2 Pressure 1Current Subcooling Module 2 Liquid Line Pressure 1 ReadingRead
AI269SUB 2 Pressure 2Current Subcooling Module 2 Liquid Line Pressure 2 ReadingRead
AI270SUB 2 Pressure 3Current Subcooling Module 2 Liquid Line Pressure 3 ReadingRead
AI271SUB 2 Saturation 1Subcooling Module 2 Saturation Temperature 1 ReadingRead
AI272SUB 2 Saturation 2Subcooling Module 2 Saturation Temperature 2 ReadingRead
AI273SUB 2 Saturation 3Subcooling Module 2 Saturation Temperature 3 ReadingRead
AI274SUB 2 Line Temp 1Subcooling Module 2 Liquid Line Temperature 1 ReadingRead
AI275SUB 2 Line Temp 2Subcooling Module 2 Liquid Line Temperature 2 ReadingRead
AI276SUB 2 Line Temp 3Subcooling Module 2 Liquid Line Temperature 3 ReadingRead
AI277Enter Water PumpStatus of Entering Water TemperatureRead
AI278Return Plenum Press. StatusCurrent value of the Return Plenum Pressure SensorRead
AI279Return Plenum Control SignalCurrent Return Plenum Control Signal (Motorized Exhaust Damper)Read
AI280Mixed Air TempMixed air temperature sensor statusRead
AI281Actual Heat RiseDifference between supply air temperature and mixed air temperatureRead
AI282Calculated Heat RiseThe heat rise limit is determined by how openRead
AI283Supply Air Relative HumidityIf an EBUS Supply Air Sensor is being usedRead
AI284Supply Air Dew PointIf an EBUS Supply Air Sensor is being usedRead
AI285Space Dew PointCurrent value of the calculated Space Dew PointRead
AI286Return Dew PointCurrent value of the calculated Return Dew PointRead
AI287FAC Fan Alarm State Fan 1Current alarm status of Fan 1 of the FACRead
AI288FAC Fan Alarm State Fan 2Current alarm status of Fan 2 of the FACRead
AI289FAC Fan Alarm State Fan 3Current alarm status of Fan 3 of the FACRead
AI290FAC Fan Alarm State Fan 4Current alarm status of Fan 4 of the FACRead
AI291FAC Fan Alarm State Fan 5Current alarm status of Fan 5 of the FACRead
AI292FAC Fan Alarm State Fan 6Current alarm status of Fan 6 of the FACRead
AI293FAC Fan Alarm State Fan 7Current alarm status of Fan 7 of the FACRead
AI294FAC Fan Alarm State Fan 8Current alarm status of Fan 8 of the FACRead
AI295FAC Fan Alarm State Fan 9Current alarm status of Fan 9 of the FACRead
AI296FAC Fan Alarm State Fan 10Current alarm status of Fan 10 of the FACRead
AI297FAC Fan Alarm State Fan 11Current alarm status of Fan 11 of the FACRead
AI298FAC Fan Alarm State Fan 12Current alarm status of Fan 12 of the FACRead
AI299Line FrequencyCurrent Line Frequency from the Power MonitorRead
AI300Line Voltage 1-2Current Line Voltage 1-2 from the Power MonitorRead
AI301Line Voltage 2-3Current Line Voltage 2-3 from the Power MonitorRead
AI302Line Voltage 3-1Current Line Voltage 3-1 from the Power MonitorRead
AI303Average Line VoltageCurrent average Line Voltage from the Power MonitorRead
AI304Total Phase A CurrentCurrent Total Phase A Current from the Power MonitorRead
AI305Total Phase B CurrentCurrent Total Phase B Current from the Power MonitorRead
AI306Total Phase C CurrentCurrent Total Phase C Current from the Power MonitorRead
AI307Average Phase CurrentCurrent Average Phase Current from the Power MonitorRead
AI308Phase A PowerCurrent Phase A Power from theRead
AI309Phase B PowerCurrent Phase B Power from the Power MonitorRead
AI310Phase C PowerCurrent Phase C Power from the Power MonitorRead
AI311Total System PowerCurrent Total System Power from the Power MonitorRead
AI312Phase A Reactive PowerCurrent Phase A Reactive Power from the Power MonitorRead
AI313Phase B Reactive PowerCurrent Phase B Reactive Power from the Power MonitorRead
AI314Phase C Reactive PowerCurrent Phase C Reactive C from the Power MonitorRead
AI315Total Reactive PowerCurrent Total Reactive Power from the Power MonitorRead
AI316Phase A Apparent PowerCurrent Phase A Apparent power from the Power MonitorRead
AI317Phase B Apparent PowerCurrent Phase B Apparent Power from the Power MonitorRead
AI318Phase C Apparent PowerCurrent Phase C Apparent Power from the Power MonitorRead
AI319Total Apparent PowerCurrent Total Apparent Power from the Power MonitorRead
AI320Phase A Power FactorCurrent Phase A Power Factor from the Power MonitorRead
AI321Phase B Power FactorCurrent Phase B Power Factor from the Power MonitorRead
AI322Phase C Power FactorCurrent Phase C Power Factor from the Power MonitorRead
AI323Total Power FactorCurrent Total Power Factor from the Power MonitorRead
AI324Utilized Cooling Capacity PercentCurrent value of the calculated Cooling CapacityRead
AI325Utilized Heating Capacity PercentCurrent value of the calculated Heating CapacityRead
AI326Active Cooling StagesCurrent active Cooling StagesRead
AI327Active Heating StagesCurrent active Heating StagesRead
AI328Motor Current Fan 1Current Motor Current reading from Fan 1Read
AI329Motor Current Fan 2Current Motor Current reading from Fan 2Read
AI330Motor Current Fan 3Current Motor Current reading from Fan 3Read
AI331Motor Current Fan 4Current Motor Current reading from Fan 4Read
AI332Motor Current Fan 5Current Motor Current reading from Fan 5Read
AI333Motor Current Fan 6Current Motor Current reading from Fan 6Read
AI334Motor Current Fan 7Current Motor Current reading from Fan 7Read
AI335Motor Current Fan 8Current Motor Current reading from Fan 8Read
AI336Motor Current Fan 9Current Motor Current reading from Fan 9Read
AI337Motor Current Fan 10Current Motor Current reading from Fan 10Read
AI338Motor Current Fan 11Current Motor Current reading from Fan 11Read
AI339Motor Current Fan 12Current Motor Current reading from Fan 12Read
AI340Motor Speed Percent Fan 1Current Motor Speed Percentage of Fan 1Read
AI341Motor Speed Percent Fan 2Current Motor Speed Percentage of Fan 2Read
AI342Motor Speed Percent Fan 3Current Motor Speed Percentage of Fan 3Read
AI343Motor Speed Percent Fan 4Current Motor Speed Percentage of Fan 4Read
AI344Motor Speed Percent Fan 5Current Motor Speed Percentage of Fan 5Read
AI345Motor Speed Percent Fan 6Current Motor Speed Percentage of Fan 6Read
AI346Motor Speed Percent Fan 7Current Motor Speed Percentage of Fan 7Read
AI347Motor Speed Percent Fan 8Current Motor Speed Percentage of Fan 8Read
AI348Motor Speed Percent Fan 9Current Motor Speed Percentage of Fan 9Read
AI349Motor Speed Percent Fan 10Current Motor Speed Percentage of Fan 10Read
AI350Motor Speed Percent Fan 11Current Motor Speed Percentage of Fan 11Read
AI351Motor Speed Percent Fan 12Current Motor Speed Percentage of Fan 12Read
AVmin1Occupied Cooling SetpointIf the control temperature rises one deadband above; range 1°F to 110°F°FWrite
AVmin2Occupied Heating SetpointIf the control temperature drops one deadband below; range 1°F to 110°F°FWrite
AV3Hood On Cooling SetpointCooling Mode Enable Setpoint used only in Hood; range 1°F to 110°F°FWrite
AV4Hood On Heating SetpointHeating Mode Enable Setpoint used only in Hood; range 1°F to 110°F°FWrite
AV5Unoccupied Cooling OffsetDuring the Unoccupied Mode of Operation; range 0°F to 30°F°FWrite
AV6Unoccupied Heating OffsetDuring the Unoccupied Mode of Operation; range 0°F to 30°F°FWrite
AV7Mode Select DeadbandThis value is added to and subtracted; range 0°F to 10°F°FWrite
AV8Max Coil Setpoint Reset LimitHighest that the Coil Temperature resets to during; range 35°F to 70°F°FWrite
AV9Min Coil Setpoint Reset LimitLowest that the Coil Temperature resets to during; range 35°F to 70°F°FWrite
AVmin10Supply Air Cooling SetpointSupply Air Cooling Setpoint; range 30°F to 80°F°FWrite
AV11Supply Air Heating SetpointSupply Air Cooling Setpoint; range 40°F to 240°F°FWrite
AV12Max SAT Cooling Setpoint Reset LimitIf Supply Air Reset is configured; range 0°F to 100°F°FWrite
AV13Max SAT Heating Setpoint Reset LimitIf Supply Air Reset is configured; range 0°F to 250°F°FWrite
AV14Supply Air Cooling Staging WindowIn Cooling Mode; range 1°F to 30°F°FWrite
AV15Supply Air Heating Staging WindowIn Heating Mode; range 1°F to 50°F°FWrite
AV16Warm-Up Target TemperatureMorning warm-up target (see AV 89 for cool-down); range 50°F to 90°F°FWrite
AV17Warm-Up Mode Supply Air SetpointDuring Morning Warm-Up; range 40°F to 240°F°FWrite
AV18Cool-Down Mode Supply Air SetpointDuring Morning Cool-Down; range 30°F to 80°F°FWrite
AV19Mechanical Cooling Outdoor Air LockoutMechanical Cooling is locked out when the Outdoor Air; range -30°F to 100°F°FWrite
AV20Mechanical Heating Outdoor Air LockoutMechanical Heating is locked out when the Outdoor Air; range -30°F to 150°F°FWrite
AV21Low Supply Temp Cutoff AlarmCooling is disabled if the Supply Air Temperature falls; range 0°F to 100°F°FWrite
AV22High Supply Temp Cutoff AlarmHeating is disabled if the Supply Air Temperature rises; range 0°F to 250°F°FWrite
AV23Preheater Cooling Mode SetpointIf the Preheater is enabled; range 35°F to 90°F°FWrite
AV24Preheater Venting Mode SetpointIf the Preheater is enabled; range 35°F to 90°F°FWrite
AV25Preheater Heating Mode SetpointIf the Preheater is enabled; range 35°F to 140°F°FWrite
AV26Outdoor Air Dewpoint SetpointOn an MUA unit; range 30°F to 80°F°FWrite
AV27Economizer Enable SetpointThe economizer is enabled if the outdoor drybulb; range -30°F to 80°F°FWrite
AV28Heat Wheel Defrost Enable SetpointThe unit goes into Heat Wheel Defrost; range 0°F to 50°F°FWrite
AV29Preheat Enable SetpointIf the Supply Fan is energized; range -30°F to 105°F°FWrite
AV30Sensor Slide Offset Max EffectIf the space sensor has the optional slide adjustment; range 0°F to 10°F°FWrite
AV31Space Sensor Calibration OffsetIf the Space Temperature Sensor is reading incorrectly; range -100°F to 100°F°FWrite
AV32Supply Air Sensor Calibration OffsetIf the Supply Air Temperature Sensor is reading incorrectly; range -100°F to 100°F°FWrite
AV33Return Air Sensor Calibration OffsetIf the Return Air Temperature Sensor is reading incorrectly; range -100°F to 100°F°FWrite
AV34Outdoor Air Sensor Calibration OffsetIf the Outdoor Air Temperature Sensor is reading incorrectly; range -100°F to 100°F°FWrite
AV35Carbon Dioxide Sensor Calibration OffsetIf the CO2 Sensor is reading incorrectly; range -500 ppm to 500 ppmppmWrite
AV36Low Ambient Protection SetpointThe temperature at which the Low Ambient Relay activates; range -30°F to 70°F°FWrite
AV37SAT Cool Setpoint Reset Source Low LimitIf doing Supply Air Setpoint Reset; range -30°F to 150°F°FWrite
AV38SAT Cool Setpoint Reset Source High LimitIf doing Supply Air Setpoint Reset; range 0°F to 150°F°FWrite
AV39SAT Heat Setpoint Reset Source Low LimitIf doing Supply Air Setpoint Reset; range -30°F to 150°F°FWrite
AV40SAT Heat Setpoint Reset Source High LimitIf doing Supply Air Setpoint Reset; range 0°F to 150°F°FWrite
AV41Control Temperature High Alarm OffsetIf the temperature of the controlling sensor rises above; range 0°F to 50°F°FWrite
AV42Control Temperature Low Alarm OffsetIf the temperature of the controlling sensor falls below; range 0°F to 50°F°FWrite
AV43Heat Pump Compressor Heat LockoutThe Compressor Heat is locked out below this setpoint; range -30°F to 100°F°FWrite
AV44Maximum Main Fan VFD in SZ VAV Heating ModeIn a single-zone VAV configuration; range 0 to 100Write
AV45Minimum Main Fan VFD in Cooling ModeIn a single-zone VAV configuration; range 0 to 100Write
AV46Minimum Main Fan VFD in Heating ModeIn a Single Zone VAV configuration; range 0 to 100Write
AV47Minimum Main Fan VFD in Vent ModeThe speed at which the VFD operates; range 0 to 100Write
AV48Maximum Economizer in Heating ModeThe max position of the Economizer Damper opens; range 0 to 100Write
AV49Minimum Economizer PositionThe minimum position of the Outdoor Air damper; range 0 to 100Write
AV50Maximum Economizer CO2 Reset LimitThe maximum value the Economizer Minimum Position can; range 0 to 100Write
AV51Minimum Carbon Dioxide SetpointThreshold CO2 level at which the Economizer Min Damper; range 0 ppm to 2000 ppmppmWrite
AV52Maximum Carbon Dioxide SetpointCO2 level at which the Economizer Min Damper Position; range 0 ppm to 2000 ppmppmWrite
AV53Indoor Humidity Setpoint Low Reset LimitOn indoor controlled (non-MUA) units; range 0 to 100Write
AV54Indoor Humidity Setpoint High Reset LimitOn indoor controlled (non-MUA) units; range 0 to 100Write
AV55Duct Static Pressure SetpointCurrent Static Pressure Setpoint; range 0.1 to 3Write
AV56Duct Static Pressure Control DeadbandValue above and below the Duct Static Pressure Setpoint; range 0.01 to 0.5Write
AV57Building Pressure Control SetpointBuilding Pressure Setpoint or Exhaust Duct Static Pressure Setpoint; range -0.20 to 3.00Write
AV58Building Pressure Control DeadbandValue above and below the Building Pressure Setpoint; range 0.01 to 0.50Write
AV59Minimum Outdoor CFM RequirementMinimum Outdoor Airflow CFM Setpoint; range 0.00K to 200KWrite
AV60Outdoor CFM Control DeadbandWhen the OA CFM is within the control deadband; range 10 to 1000Write
AV61Single Zone VAV Fan Speed IntegralThe Integral Constant for Single Zone VAV Fan Control; range 0 to 10Write
AV62Relay Run-time Hours Warning LimitIf any configured relay's run time exceeds this number; range 0 to 30000Write
AV63Cooling Mode Head Pressure SetpointHead Pressure Setpoint in the Cooling Mode; range 250 to 450Write
AV64Dehum Mode Head Pressure SetpointHead Pressure Setpoint in the Dehumidification Mode; range 250 to 450Write
AV65Superheat SetpointSuperheat Setpoint; range 1°F to 30°F°FWrite
AV66Maximum Outdoor CFM RequirementMaximum Outdoor Airflow CFM Setpoint in High CO2; range 0.10K to 200KWrite
AVmin67Schedule Force0 = Auto (uses controller's schedule) 1 = Forced; range 0 to 2Write0=Auto (controller schedule), 1=Forced Occupied, 2=Forced Unoccupied
AV68HVAC Mode OverrideOverrides normal controller operation to force the unit into; range 0 to 6Write0=Auto, 1=Vent, 2=Cool, 3=Heat, 4=Vent Dehum, 5=Cool Dehum, 6=Heat Dehum
AV69Fan VFD OverrideOverride to force the VFD to this percentage speed; range 0% Auto=65535 to 100% Auto=65535%Write65535=Auto
AV70Outdoor Air Damper OverrideFixed OA damper position; Auto restores normal control%Write
AV71Supply Setpoint OverrideThis overrides whatever setpoint the Supply Air Temperature; range 0°F to 120°F°FWrite0=No Override
AV72Space Temperature ValueIf the controller is configured for this operation; range 0°F to 120°F°FWrite
AV73Space Humidity ValueIf the controller is configured for this operation; range 0 to 100Write
AV74Indoor RH Calibration OffsetIf the Space Humidity Sensor is reading incorrectly; range -1 to 1Write
AV75Relief Fan VFDOverride to force the VFD to this percentage speed; range 0% Auto=65535 to 100% Auto=65535%Write65535=Auto
AV76Relief Pressure ValueIf the controller is configured for this operation; range -0.5 to 0.5Write
AV77Carbon Dioxide ValueIf the controller is configured for this operation; range 0 to 3000Write
AV78Outdoor Air Temperature ValueIf the controller is configured for this operation; range -40°F to 150°F°FWrite
AV79Outdoor Air Humidity ValueIf the controller is configured for this operation; range 0 to 100Write
AV80Reserved 1ReservedWrite
AV81Reserved 2ReservedWrite
AV82Reserved 3ReservedWrite
AV83Reserved 4ReservedWrite
AV84Enthalpy Enable SetpointIf configured for Comparative Enthalpy Economizer Control; range 25 BTU/lb. to 35 BTU/lb.BTU/lbWrite
AV85Enthalpy Enable DeadbandThe OA Enthalpy must be below the Enthalpy Enable; range 0.3 BTU/lb. to 1.5 BTU/lb.BTU/lbWrite
AV86Maximum Static Setpoint Reset LimitAs the most open VAV damper rises above 80%; range 0.01 “WG to 3.00 “WGin. w.c.Write
AV87Minimum Static Setpoint Reset LimitAs the most open VAV damper drops below 80%; range 0.01 “WG to 3.00 “WGin. w.c.Write
AV88Static Setpoint Reset IntervalThe Reset Interval is how often the setpoint reset; range 10 min to 60 minminWrite
AV89Cool-Down Target TemperatureMorning cool-down target (see AV 16 for warm-up); range 50°F to 90°F°FWrite
AV90Warm-Up OverrideCommands the unit into Morning WarmUp Mode; range 0 to 1Write1=Command Warm-Up Mode
AV91Cool Down OverrideCommands the unit into Morning CoolDown Mode 1=Command Cool-Down; range 0 to 1Write1=Command Cool-Down Mode
AV92Return Air High Limit ProtectionFor voting units or CV units only; range 60 to 100Write
AV93Return Air Low Limit ProtectionFor voting units or CV units only; range 45 to 70Write
AV94Sump Drain OverrideSetting this value to 1 turns the Sump Drain; range 0 to 1Write0=Auto, 1=On
AV95Return Plenum Pressure SetpointCurrent Return Plenum Pressure Setpoint; range -0.2"WG to 0.2"WGin. w.c.Write
AV96Return Plenum Pressure DeadbandValue above and below the Return Plenum Pressure Setpoint; range 0.01"WG to 0.2"WGin. w.c.Write
AV97Dehum Lockout SetpointIf the Outdoor Air temperature is below this setpoint; range -30°F to 60°F°FWrite
AV98Emergency Compressor LockoutThis point can be used to lock out; range 0 to 1Write
AV99Supply Air Dew Point SetpointWhen the VCCX-454 is configured for DXDOAS control; range 35 to 80Write
BI1Cooling Enabled StatusStatus that indicates Mechanical Cooling is enabled basedRead
BI2Heating Enabled StatusStatus that indicates that Mechanical Heating is enabled basedRead
BI3Economizer Enabled StatusStatus that indicates the Economizer is enabled basedRead
BI4Aux Heat Enabled StatusHeat Pump Auxiliary Heat enabledRead
BI5Emergency Heat Enabled StatusShows the Emergency Heat is enabled basedRead
BI6Fan Proof of Airflow StatusProof of Airflow Binary Input StatusRead
BI7Exhaust Hood On/Off StatusExhaust Hood On/Off Binary Input StatusRead
BI8Remote Forced Occupied StatusRemote Forced Occupied Mode Binary Input StatusRead
BI9A2L Airstream Leak Detect StatusAlarm activeRead
BI10A2L Cabinet Leak Detect StatusAlarm activeRead
BI11Reserved for Future UseNot UsedRead
BI12Bad Supply Air SensorAlarm that indicates a failure of the Supply AirRead
BI13Bad Return Air SensorAlarm that indicates a failure of the Return AirRead
BI14Bad Outdoor Air SensorFailure of the Outdoor Air Temperature SensorRead
BI15Bad Space Temp SensorFailure of the Space Temperature SensorRead
BI16Bad Carbon Dioxide SensorFailure of the CO2 SensorRead
BI17Bad Building Pressure SensorAlarm indicating a missing/failed Building Pressure SensorRead
BI18Bad Outdoor Airflow SensorAn Outdoor Airflow Sensor is configured, but not detectedRead
BI19Bad Exhaust Airflow SensorAn Exhaust Airflow Sensor is configured, but not detectedRead
BI20Bad Supply Airflow SensorA Supply Airflow Sensor is configured, but not detectedRead
BI21Bad Return Airflow SensorA Return Airflow Sensor is configured, but not detectedRead
BI22Mechanical Cooling AlarmCompressor Relays are enabled but the Supply Air TemperatureRead
BI23Mechanical Heating AlarmHeating Mode has been initiated but the Supply AirRead
BI24Fan Proving AlarmThis alarm indicates an Airflow failure from the MainRead
BI25Dirty Filter AlarmThis alarm indicates that the filters are dirtyRead
BI26Emergency Shutdown AlarmThis alarm indicates that an Emergency Shutdown has beenRead
BI27Relay Runtime WarningWhen any of the configured relays exceeds a configuredRead
BI28Economizer Missing AlarmTitle 24 operation indicates missing economizer feedbackRead
BI29Economizer Title 24 Failure ATitle 24 Air Temperature Sensor FailureRead
BI30Economizer Title 24 Failure BTitle 24 Not Economizing when it shouldRead
BI31Economizer Title 24 Failure CTitle 24 Economizing when it should notRead
BI32Economizer Title 24 Failure DTitle 24 Damper Not ModulatingRead
BI33Economizer Title 24 Failure ETitle 24 Excess Outdoor AirRead
BI34High Supply Temp CutoffThe Supply Air has risen above the Hi SATRead
BI35Low Supply Temp CutoffThe Supply Air has fallen below the Low SATRead
BI36High Control Mode AlarmOccurs when the Controlling Sensor Temperature rises aboveRead
BI37Low Control Mode AlarmOccurs when the Controlling Sensor Temperature falls belowRead
BI38Missing Refrigerant Module #1Refrigerant Module #1 is bad or missingRead
BI39Missing Refrigerant Module #2Refrigerant Module #2 is bad or missingRead
BI40Missing Refrigerant Module #3Refrigerant Module #3 is bad or missingRead
BI41Missing Refrigerant Module #4Refrigerant Module #4 is bad or missingRead
BI43Missing Reheat BoardThe MHGR board is configured but not detectedRead
BI44Missing Mod Gas BoardThe MODGAS board is configured but not detectedRead
BI45Missing EM1 BoardEM1 Expansion Board is bad or missingRead
BI46Missing 12 Relay Expansion BoardThe 12 Relay Expansion Board is configured but notRead
BI47On Board Relay 1 Main FanCurrent Status of Main Fan Relay #1 on MainRead
BI48On Board Relay 2Current Status of Configurable Relay #2 on Main BoardRead
BI49On Board Relay 3Current Status of Configurable Relay #3 on Main BoardRead
BI50On Board Relay 4Current Status of Configurable Relay #4 on Main BoardRead
BI51On Board Relay 5Current Status of Configurable Relay #5 on Main BoardRead
BI52On Board Relay 6Current Status of Configurable Relay #6 on Main BoardRead
BI53On Board Relay 7Current Status of Configurable Relay #7 on Main BoardRead
BI54On Board Relay 8Current Status of Configurable Relay #8 on Main BoardRead
BI55Expansion Board EM1 Relay 1Current Status of Configurable Relay #1 on EM1 BoardRead
BI56Expansion Board EM1 Relay 2Current Status of Configurable Relay #2 on EM1 BoardRead
BI57Expansion Board EM1 Relay 3Current Status of Configurable Relay #3 on EM1 BoardRead
BI58Expansion Board EM1 Relay 4Current Status of Configurable Relay #4 on EM1 BoardRead
BI59Expansion Board EM1 Relay 5Current Status of Configurable Relay #5 on EM1 BoardRead
BI6012 Relay Expansion Board Relay 1Current Status of Configurable Relay #1 on 12 RelayRead
BI6112 Relay Expansion Board Relay 2Current Status of Configurable Relay #2 on 12 RelayRead
BI6212 Relay Expansion Board Relay 3Current Status of Configurable Relay #3 on 12 RelayRead
BI6312 Relay Expansion Board Relay 4Current Status of Configurable Relay #4 on 12 RelayRead
BI6412 Relay Expansion Board Relay 5Current Status of Configurable Relay #5 on 12 RelayRead
BI6512 Relay Expansion Board Relay 6Current Status of Configurable Relay #6 on 12 RelayRead
BI6612 Relay Expansion Board Relay 7Current Status of Configurable Relay #7 on 12 RelayRead
BI6712 Relay Expansion Board Relay 8Current Status of Configurable Relay #8 on 12 RelayRead
BI6812 Relay Expansion Board Relay 9Current Status of Configurable Relay #9 on 12 RelayRead
BI6912 Relay Expansion Board Relay 10Current Status of Configurable Relay #10 on 12 RelayRead
BI7012 Relay Expansion Board Relay 11Current Status of Configurable Relay #11 on 12 RelayRead
BI7112 Relay Expansion Board Relay 12Current Status of Configurable Relay #12 on 12 RelayRead
BI72Preheater Enable StatusStatus of Preheater Enable InputRead
BI73Preheater Emergency ShutdownStatus of Preheater Emergency Shutdown InputRead
BI74Preheater Spare Binary Input #3Status of Preheater Binary Input #3Read
BI75MODGAS Enable StatusStatus of MODGAS ControllerRead
BI76MHGR Enable StatusStatus of MHGRV ControllerRead
BI77A1 Compressor EnableCurrent Status of Enable Signal to Compressor A1Read
BI78A2 Compressor EnableCurrent Status of Enable Signal to Compressor A2Read
BI79A1 Compressor AlarmsAn RSM alarm is present on the A1 circuitRead
BI80A2 Compressor AlarmsAn RSM alarm is present on the A2 circuitRead
BI81A1-2 Defrost SwitchOutside Coil A1/A2 Temp Switch for Defrost ModeRead
BI82A1-2 Water Proof of FlowA1/A2 Water Proof of Flow SwitchRead
BI83A1-4 Emergency Shutdown (RM454-D)Emergency Shutdown Input on Module ARead
BI84Refrigerant Module 1 Relay 1Current Status of Compressor A1 Enable RelayRead
BI85Refrigerant Module 1 Relay 2Current Status of Compressor A2 Enable RelayRead
BI86Refrigerant Module 1 Relay 3Current Status of Condenser 1 Enable RelayRead
BI87Refrigerant Module 1 Relay 4Current Status of Relay #4Read
BI88Refrigerant Module 1 Relay 5Current Status of Relay #5Read
BI89B1 Compressor EnableCurrent Status of Enable Signal to Compressor B1Read
BI90B2 Compressor EnableCurrent Status of Enable Signal to Compressor B2Read
BI91B1 Compressor AlarmsAn RSM alarm is present on the B1 circuitRead
BI92B2 Compressor AlarmsAn RSM alarm is present on the B2 circuitRead
BI93B1-2 Defrost SwitchOutside Coil B1/B2 Temp Switch for Defrost ModeRead
BI94B1-2 Water Proof of FlowB1/B2 Switch for Water Proof of FlowRead
BI95B1-4 Emergency Shutdown (RM454-D)Emergency Shutdown Input on Module BRead
BI96Refrigerant Module 2 Relay 1Current Status of Compressor 1 Enable RelayRead
BI97Refrigerant Module 2 Relay 2Current Status of Compressor 2 Enable RelayRead
BI98Refrigerant Module 2 Relay 3Current Status of Condenser 1 Enable RelayRead
BI99Refrigerant Module 2 Relay 4Current Status of Relay #4Read
BI100Refrigerant Module 2 Relay 5Current Status of Relay #5Read
BI101C1 Compressor EnableCurrent Status of Enable Signal to Compressor C1Read
BI102C2 Compressor EnableCurrent Status of Enable Signal to Compressor C2Read
BI103C1 Compressor AlarmsAn RSM alarm is present on the C1 circuitRead
BI104C2 Compressor AlarmsAn RSM alarm is present on the C2 circuitRead
BI105C1-2 Defrost SwitchOutside Coil C1/C2Temp Switch for Defrost ModeRead
BI106C1-2 Water Proof of FlowC1/C2 Switch for Water Proof of FlowRead
BI107C1-4 Emergency Shutdown (RM454-D)Emergency Shutdown Input on Module CRead
BI108Refrigerant Module 3 Relay 1Current Status of Compressor 1 Enable RelayRead
BI109Refrigerant Module 3 Relay 2Current Status of Compressor 2 Enable RelayRead
BI110Refrigerant Module 3 Relay 3Current Status Condenser 1 Enable RelayRead
BI111Refrigerant Module 3 Relay 4Current Status of Relay #4Read
BI112Refrigerant Module 3 Relay 5Current Status of Relay #5Read
BI113D1 Compressor EnableCurrent Status of Enable Signal to Compressor D1Read
BI114D2 Compressor EnableCurrent Status of Enable Signal to Compressor D2Read
BI115D1 Compressor AlarmsAn RSM alarm is present on the D1 circuitRead
BI116D2 Compressor AlarmsAn RSM alarm is present on the D2 circuitRead
BI117D1-2 Defrost SwitchOutside Coil D1/D2 Temp Switch for Defrost ModeRead
BI118D1-2 Water Proof of FlowD1/D2 Switch for Water Proof of FlowRead
BI119D1-4 Emergency Shutdown (RM454-D)Emergency Shutdown Input on Module DRead
BI120Refrigerant Module 4 Relay 1Current Status of Compressor 1 Enable RelayRead
BI121Refrigerant Module 4 Relay 2Current Status of Compressor 2 Enable RelayRead
BI122Refrigerant Module 4 Relay 3Current Status of Condenser 1 Enable RelayRead
BI123Refrigerant Module 4 Relay 4Current Status of Relay #4Read
BI124Refrigerant Module 4 Relay 5Current Status of Relay #5Read
BI125Preheater AlarmPreheater Alarm IndicatorRead
BI126Return Fan Proving AlarmExhaust Fan / Return Fan Proof of Flow AlarmRead
BI127Compressor Running ACurrent Run Status of Compressor ARead
BI128Compressor Running BCurrent Run Status of Compressor BRead
BI129Compressor Running CCurrent Run Status of Compressor CRead
BI130Compressor Running C2Current Run Status of Compressor C2Read
BI131Compressor Running DCurrent Run Status of Compressor DRead
BI132Compressor Running ECurrent Run Status of Compressor ERead
BI133Compressor Running E2Current Run Status of Compressor E2Read
BI134Compressor Running FCurrent Run Status of Compressor FRead
BI135Compressor Running F2Current Run Status of Compressor F2Read
BI136Return Fan Proving StatusProof of Return Fan Airflow Binary Input StatusRead
BI137IAQ Mode ActiveIAQ Mode is activeRead
BI138Heat Wheel Defrost ActiveHeat Wheel Defrost is activeRead
BI139Direct Fire StatusSignal on EM1 binary input 2 from Direct FireRead
BI140Direct Fire Alarm StatusSignal on EM1 binary input 3 that indicates thereRead
BI141Temp Rise WarningThe heat rise when direct fire heat is activeRead
BI142Temp Rise AlarmThe heat rise when direct fire heat is activeRead
BI143Temp Rise LockoutThree High Temp Rise alarms occurred within a oneRead
BI144High CO2 Rise WarningHigh return CO2 was detected when running direct fireRead
BI145High CO2 Rise AlarmHigh return CO2 was detectedRead
BI146High CO2 Rise LockoutThree CO2 warning alarms occurred within a one hourRead
BI147Ignition LockoutAn active alarm on the Direct Fire ModuleRead
BI148Direct Fire Status LockoutThe Direct Fire Status Signal is not active withinRead
BI149Direct Fire Setpoint OverrideThe max calculated heat rise is limiting the SupplyRead
BI150Fan Array FailureA Fan Array FailureRead
BI151A2L Leak DetectAn A2L Leak Detected in the AirstreamRead
BI152A2L Cabinet Leak DetectAn A2L Leak Detected in the CabinetRead
BI153Bad Static Pressure SensorThe static pressure is missing or otherwise malfunctioningRead
Object ID lookup: AAON VCCX-454 Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VCCX-454 Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AAON VCCX-454 Controller

How many BACnet points does the AAON VCCX-454 Controller have?

This list has 602 BACnet objects: 351 analog inputs, 99 analog values, 152 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AAON VCCX-454 Controller BACnet points are writable?

99 of the 602 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AAON VCCX-454 Controller BACnet documentation?

The source is VCCX-454 Controller Technical Guide (ASM07503 Rev. I), revision 2026-08, published free by AAON at https://www.aaon.com/hubfs/Controls%20Literature/VCCX-454%20Technical%20Guide%20Rev.%20I.pdf.

What are the minimum BACnet points to integrate the AAON VCCX-454 Controller?

Start with AV 67 Schedule Force (Occupancy: 0 auto, 1 occupied, 2 unoccupied); AV 1 Occupied Cooling Setpoint (Cooling starts one deadband above this); AV 2 Occupied Heating Setpoint (Heating starts one deadband below this); AV 10 Supply Air Cooling Setpoint (Discharge air target in cooling); AI 3 Control Status (Current occupancy status); AI 4 HVAC Mode (Current operating mode); AI 5 Control Temperature (Reading from the configured control sensor); AI 9 Supply Air Temperature (Discharge air temperature); AI 144 Alarm Status (Summary alarm).

How do I enable BMS control of the AAON VCCX-454 Controller?

Occupancy comes from AV 67 Schedule Force (0 = controller schedule, 1 = forced occupied, 2 = forced unoccupied) or the controller's own schedule. AV 68, AV 69, AV 70 and AV 71 override HVAC mode, fan VFD, OA damper and supply setpoint; writing Auto (0, or 65535 for the VFD overrides) hands control back. AV 98 locks out the compressors.

Can the BMS supply sensor values to the AAON VCCX-454 Controller?

If the controller is configured for it, the BAS can write AV 72 Space Temperature Value, AV 73 Space Humidity Value, AV 76 Relief Pressure Value, AV 77 Carbon Dioxide Value, AV 78 Outdoor Air Temperature Value and AV 79 Outdoor Air Humidity Value. No refresh timeout is printed in the points table.

How do I check these points on the real VCCX-454 Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AAON BACnet points lists

Source: VCCX-454 Controller Technical Guide · ASM07503 Rev. I · rev. 2026-08. Object names, instances and units are reproduced as published; descriptions are our own.