 "manufacturer": "AAON",
 "manufacturer_slug": "aaon",
 "model": "VCCX-454 Controller",
 "model_slug": "vccx-454",
 "aliases": [
  "VCCX-454",
  "VCCX 454",
  "ASM07503",
  "SS1188",
  "AAON VCCX-454 controller",
  "R-454B unit controller"
 ],
 "equipment_type": "Rooftop unit / air handler controller",
 "applies_to": "AAON rooftop units, air handlers, DOAS and self-contained units built for R-454B and controlled by the VCCX-454 unit controller with RM454 refrigerant modules.",
 "summary": "The VCCX-454 is the unit controller AAON uses on its R-454B equipment. It has an on-board BACnet port that can be set for MS/TP or BACnet IP. The object map has about 350 read-only analog inputs (temperatures, pressures, airflow, RM454 refrigerant module data, power monitor and fan array data), 99 writable analog values (setpoints, overrides and BAS-written sensor values) and about 150 read-only binary inputs (alarms, A2L leak alarms, module and relay status).",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet IP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "AI and BI objects are read-only and AV objects are read/write; of the sensor values, only AV 72, 73 and 75-79 may be written by the BAS.",
  "The table is close to the older VCCX2 map, but refrigerant module points are renamed for RM454 modules and AI 287-351 (fan array, power monitor and capacity data) are new. BI 42 is not listed.",
  "Points for RM454 refrigerant modules, preheater, MODGAS, MHGRV, fan array and power monitor only report data when that hardware is fitted.",
  "AI 2-4 and the RM454-Z warning, fault and drive status points are coded values; the meanings are in the guide's lookup tables.",
  "Analog input units are not printed; analog value units come from the printed limits. AV 70 prints °F limits in the guide although it is a damper position.",
  "Source: Appendix C BACnet guide, guide pages 115-149."
 ],
 "source": {
  "title": "VCCX-454 Controller Technical Guide",
  "doc_number": "ASM07503 Rev. I",
  "revision_date": "2026-08",
  "url": "https://www.aaon.com/hubfs/Controls%20Literature/VCCX-454%20Technical%20Guide%20Rev.%20I.pdf"
 },
 "integration": {
  "summary": "Connect the on-board BACnet port (MS/TP or IP) and set the MAC address, device ID and baud or IP settings on the LCD BACnet screens. The BAS schedules the unit with AV 67 Schedule Force, adjusts the occupied setpoints and supply air setpoints, and can override HVAC mode, fan VFD and OA damper. Alarms are read from the BI objects.",
  "minimum_points": [
   {
    "ref": "AV 67",
    "name": "Schedule Force",
    "why": "Occupancy: 0 auto, 1 occupied, 2 unoccupied"
   },
   {
    "ref": "AV 1",
    "name": "Occupied Cooling Setpoint",
    "why": "Cooling starts one deadband above this"
   },
   {
    "ref": "AV 2",
    "name": "Occupied Heating Setpoint",
    "why": "Heating starts one deadband below this"
   },
   {
    "ref": "AV 10",
    "name": "Supply Air Cooling Setpoint",
    "why": "Discharge air target in cooling"
   },
   {
    "ref": "AI 3",
    "name": "Control Status",
    "why": "Current occupancy status"
   },
   {
    "ref": "AI 4",
    "name": "HVAC Mode",
    "why": "Current operating mode"
   },
   {
    "ref": "AI 5",
    "name": "Control Temperature",
    "why": "Reading from the configured control sensor"
   },
   {
    "ref": "AI 9",
    "name": "Supply Air Temperature",
    "why": "Discharge air temperature"
   },
   {
    "ref": "AI 144",
    "name": "Alarm Status",
    "why": "Summary alarm"
   }
  ],
  "enable": "Occupancy comes from AV 67 Schedule Force (0 = controller schedule, 1 = forced occupied, 2 = forced unoccupied) or the controller's own schedule. AV 68, AV 69, AV 70 and AV 71 override HVAC mode, fan VFD, OA damper and supply setpoint; writing Auto (0, or 65535 for the VFD overrides) hands control back. AV 98 locks out the compressors.",
  "heartbeat": null,
  "remote_sensors": "If the controller is configured for it, the BAS can write AV 72 Space Temperature Value, AV 73 Space Humidity Value, AV 76 Relief Pressure Value, AV 77 Carbon Dioxide Value, AV 78 Outdoor Air Temperature Value and AV 79 Outdoor Air Humidity Value. No refresh timeout is printed in the points table.",
  "setup": [
   "MAC address, device ID (up to seven digits) and baud rate are set on the controller's LCD BACnet screens.",
   "The same port is set to MS/TP or IP (BAC Type) on the LCD settings screens."
  ],
  "gotchas": [
   "Writing an OA damper override between 0 and 100% locks out the compressors; 0 or 100% lets them run.",
   "Many points only report when the matching module (RM454, MHGRV, MODGAS, preheater, fan array, power monitor) is installed."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Application Software Version",
   "description": "Current version of the software in the unit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Control Mode",
   "description": "Configured unit application",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Control Status",
   "description": "Configured Occupied or Unoccupied Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "HVAC Mode",
   "description": "Current Operation Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Control Temperature",
   "description": "Current value of the Control Temperature Sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Mode Cooling Setpoint",
   "description": "Cooling Mode Enable Setpoint Mirror (adjusted by the Space",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Mode Heating Setpoint",
   "description": "Heating Mode Enable Setpoint Mirror (adjust by the Space",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Sensor Slide Adjust Effect",
   "description": "Amount of Current Sensor Slide adjust",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Supply Air Temperature",
   "description": "Current value of the Supply Air Temperature sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Supply Air Setpoint",
   "description": "Current SAT Cooling or Heating Setpoint if there",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Controlling Coil Temp Setpoint",
   "description": "Current calculated Coil Suction Temperature target during Dehumidification Mode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Space Temperature",
   "description": "Current value of the Space Temperature Sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Space Humidity",
   "description": "Current value of the Space Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Return Air Temperature",
   "description": "Current value of the Return Temperature Sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Return Air Humidity",
   "description": "Current value of the Return Air Humidity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Outdoor Air Temperature",
   "description": "Current value of the Outdoor Air Temperature Sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Outdoor Air Humidity",
   "description": "Current value of the Outdoor Humidity Sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "Outdoor Air Wetbulb",
   "description": "Current calculated Outdoor Wetbulb Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Outdoor Air Dewpoint",
   "description": "Current calculated Outdoor Air Dewpoint Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Supply Air Setpoint Reset Voltage",
   "description": "Supply Air Temp Setpoint Reset Input Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Duct Static Pressure",
   "description": "Current Duct Static Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Duct Static Control Signal",
   "description": "Current Duct Static Control Signal (Fan VFD)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "Building Pressure",
   "description": "Current value of the Building Pressure Sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "Building Pressure Control Signal",
   "description": "Current Building Pressure Control Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Outdoor Airflow",
   "description": "Current Outdoor Airflow Measurement",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "Supply Airflow",
   "description": "Current Supply Airflow Measurement",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "Return Airflow",
   "description": "Current Return Airflow Measurement",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "Exhaust Airflow",
   "description": "Current Exhaust Airflow Measurement",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "Carbon Dioxide",
   "description": "Current Indoor CO2 Level",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "Desired Economizer Position",
   "description": "Current Modulating Signal to the Economizer Damper",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "Economizer Feedback Position",
   "description": "Title 24 current position of the feedback",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "Return Damper Position",
   "description": "Current Signal to the Return Air Damper if using",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "Return Bypass Position",
   "description": "Current Signal to the Return Air Bypass Damper",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "Modulating Cooling Position",
   "description": "Current percentage of the Modulating Chilled Water Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "Modulating Heat Position",
   "description": "Current percentage of the Modulating Heating signal (hot Water",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "Preheater Leaving Air Temp #1",
   "description": "Current Preheater Leaving Air Temperature #1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "Preheater Leaving Air Temp #2",
   "description": "Current Preheater Leaving Air Temperature #2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "Preheater Entering Air Temp",
   "description": "Current Entering Air Temp for Preheater",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "Preheater Setpoint Reset Voltage",
   "description": "Current Voltage Reset Input Value for Preheater",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "Preheater SCR Output Signal",
   "description": "Current Modulating Heat Signal for Preheater",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "Preheater PWM Output Signal",
   "description": "Current PWM Output Signal for Preheater",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "Mod Hot Gas Reheat Valve Position",
   "description": "Current position of MHGRV Modulating Hot Gas Reheat Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Mod Gas Heat Valve Position",
   "description": "Current position of MODGAS Modulating Gas Heat Valve Control",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "A1 Compressor Signal",
   "description": "Current Compressor A1 Modulating Cooling Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "A2 Compressor Signal",
   "description": "Current Compressor A2 Modulating Cooling Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "A1 Condenser Signal",
   "description": "Current Condenser A1 Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "A2 Condenser Signal",
   "description": "Current Condenser A2 Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "A1 Suction Pressure",
   "description": "Current Compressor A1 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "A2 Suction Pressure",
   "description": "Current Compressor A2 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "A1 Head Pressure",
   "description": "Current Compressor A1 Head Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "A2 Head Pressure",
   "description": "Current Compressor A2 Head Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "A1 Saturation Temperature",
   "description": "Current Compressor A1 Coil Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "A2 Saturation Temperature",
   "description": "Current Compressor A2 Coil Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "A1 Suction Line Temperature",
   "description": "Current Compressor A1 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "A2 Suction Line Temperature",
   "description": "Current Compressor A1 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "A1 Condenser Suction Temp (Heat Pump)",
   "description": "Current Compressor A1 Suction Line Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "A2 Condenser Suction Temp (Heat Pump)",
   "description": "Current Compressor A2 Suction Line Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "A1 Superheat Temperature",
   "description": "Current Compressor A1 Superheat Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "A2 Superheat Temperature",
   "description": "Current Compressor A2 Superheat Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "Condenser A1 Superheat (Heat Pump)",
   "description": "Current Compressor A1 Superheat Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "Condenser A2 Superheat (Heat Pump)",
   "description": "Current Compressor A2 Superheat Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "A1 Expansion Valve Position",
   "description": "Current position of Compressor A1 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "A2 Expansion Valve Position",
   "description": "Current position of Compressor A2 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 64,
   "name": "Condenser A1 Expansion Valve Position",
   "description": "Current position of Condenser A1 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 65,
   "name": "Condenser A2 Expansion Valve",
   "description": "Current position of Condenser A2 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 66,
   "name": "A1 Discharge Temperature",
   "description": "Current Compressor A1 Discharge Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 67,
   "name": "A2 Discharge Temperature",
   "description": "Current Compressor A2 Discharge Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 68,
   "name": "A1 Leaving Water Temp",
   "description": "Current A1 Leaving Water Temperature for WSHP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 69,
   "name": "B1 Compressor Signal",
   "description": "Current Compressor B1 Modulating Cooling Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 70,
   "name": "B2 Compressor Signal",
   "description": "Current Compressor B2 Modulating Cooling Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 71,
   "name": "B1 Condenser Signal",
   "description": "Current B1 Condenser Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 72,
   "name": "B2 Condenser Signal",
   "description": "Current B2 Condenser Signal or WSE Bypass Valve Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 73,
   "name": "B1 Suction Pressure",
   "description": "Current Compressor B1 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 74,
   "name": "B2 Suction Pressure",
   "description": "Current Compressor B2 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 75,
   "name": "B1 Head Pressure",
   "description": "Current Compressor B1 Head Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 76,
   "name": "B2 Head Pressure",
   "description": "Current Compressor B2 Head Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 77,
   "name": "B1 Saturation Temperature",
   "description": "Current Compressor B1 Coil Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 78,
   "name": "B2 Saturation Temperature",
   "description": "Current Compressor B2 Coil Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 79,
   "name": "B1 Suction Line Temperature",
   "description": "Current Compressor B1 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 80,
   "name": "B2 Suction Line Temperature",
   "description": "Current Compressor B2 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 81,
   "name": "B1 Condenser Suction Temp (Heat Pump)",
   "description": "Current Compressor B1 Suction Line Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 82,
   "name": "B2 Condenser Suction Temp (Heat Pump)",
   "description": "Current Compressor B2 Suction Line Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 83,
   "name": "B1 Superheat Temperature",
   "description": "Current Compressor B1 Superheat Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 84,
   "name": "B2 Superheat Temperature",
   "description": "Current Compressor B2 Superheat Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 85,
   "name": "Condenser B1 Superheat (Heat Pump)",
   "description": "Current Compressor B1 Superheat Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 86,
   "name": "Condenser B2 Superheat (Heat Pump)",
   "description": "Current Compressor B2 Superheat Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 87,
   "name": "B1 Expansion Valve Position",
   "description": "Current position of Compressor B1 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 88,
   "name": "B2 Expansion Valve Position",
   "description": "Current position of Compressor B2 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 89,
   "name": "Condenser B1 Expansion Valve Position",
   "description": "Current position of Condenser B1 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 90,
   "name": "Condenser B2 Expansion Valve Position",
   "description": "Current position of Condenser B2 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 91,
   "name": "B1 Discharge Temperature",
   "description": "Current Compressor B1 Discharge Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 92,
   "name": "B2 Discharge Temperature",
   "description": "Current Compressor B2 Discharge Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 93,
   "name": "B1 Leaving Water Temp",
   "description": "Current B1 Leaving Water Temperature for WSHP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 94,
   "name": "C1 Compressor Signal",
   "description": "Current Compressor C1 Modulating Cooling Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 95,
   "name": "C2 Compressor Signal",
   "description": "Current Compressor C2 Modulating Cooling Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 96,
   "name": "C1 Condenser Signal",
   "description": "Current C1 Condenser Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 97,
   "name": "C2 Condenser Signal",
   "description": "Current C2 Condenser Signal or WSE Bypass Valve Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 98,
   "name": "C1 Suction Pressure",
   "description": "Current Compressor C1 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "C2 Suction Pressure",
   "description": "Current Compressor C2 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 100,
   "name": "C1 Head Pressure",
   "description": "Current Compressor C1 Head Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 101,
   "name": "C2 Head Pressure",
   "description": "Current Compressor C2 Head Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 102,
   "name": "C1 Saturation Temperature",
   "description": "Current Compressor C1 Coil Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 103,
   "name": "C2 Saturation Temperature",
   "description": "Current Compressor C2 Coil Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 104,
   "name": "C1 Suction Line Temperature",
   "description": "Current Compressor C1 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 105,
   "name": "C2 Suction Line Temperature",
   "description": "Current Compressor C2 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 106,
   "name": "C1 Condenser Suction Temp (Heat Pump)",
   "description": "Current Compressor C1 Suction Line Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 107,
   "name": "C2 Condenser Suction Temp (Heat Pump)",
   "description": "Current Compressor C2 Suction Line Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 108,
   "name": "C1 Superheat Temperature",
   "description": "Current Compressor C1 Superheat Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 109,
   "name": "C2 Superheat Temperature",
   "description": "Current Compressor C2 Superheat Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 110,
   "name": "Condenser C1 Superheat (Heat Pump)",
   "description": "Current Compressor C1 Superheat Temperature (Heat pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 111,
   "name": "Condenser C2 Superheat (Heat Pump)",
   "description": "Current Compressor C2 Superheat Temperature (Heat pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 112,
   "name": "C1 Expansion Valve Position",
   "description": "Current position of Compressor C1 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 113,
   "name": "C2 Expansion Valve Position",
   "description": "Current position of Compressor C2 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 114,
   "name": "Condenser C1 Expansion Valve Position",
   "description": "Current position of Condenser C1 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 115,
   "name": "Condenser C2 Expansion Valve Position",
   "description": "Current position of Condenser C2 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 116,
   "name": "C1 Discharge Temperature",
   "description": "Current Compressor C1 Discharge Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 117,
   "name": "C2 Discharge Temperature",
   "description": "Current Compressor C2 Discharge Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 118,
   "name": "C1 Leaving Water Temp",
   "description": "Current C1 Leaving Water Temperature for WSHP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 119,
   "name": "D1 Compressor Signal",
   "description": "Current Compressor D1 Modulating Cooling Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 120,
   "name": "D2 Compressor Signal",
   "description": "Current Compressor D2 Modulating Cooling Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 121,
   "name": "D1 Condenser Signal",
   "description": "Current D1 Condenser Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 122,
   "name": "D2 Condenser Signal",
   "description": "Current D2 Condenser Signal or WSE Bypass Valve Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 123,
   "name": "D1 Suction Pressure",
   "description": "Current Compressor D1 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 124,
   "name": "D2 Suction Pressure",
   "description": "Current Compressor D2 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 125,
   "name": "D1 Head Pressure",
   "description": "Current Compressor D1 Head Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 126,
   "name": "D2 Head Pressure",
   "description": "Current Compressor D2 Head Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 127,
   "name": "D1 Saturation Temperature",
   "description": "Current Compressor D1 Coil Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 128,
   "name": "D2 Saturation Temperature",
   "description": "Current Compressor D2 Coil Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 129,
   "name": "D1 Suction Line Temperature",
   "description": "Current Compressor D1 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 130,
   "name": "D2 Suction Line Temperature",
   "description": "Current Compressor D2 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 131,
   "name": "D1 Condenser Suction Temp (Heat Pump)",
   "description": "Current Compressor D1 Suction Line Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 132,
   "name": "D2 Condenser Suction Temp (Heat Pump)",
   "description": "Current Compressor D2 Suction Line Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 133,
   "name": "D1 Superheat Temperature",
   "description": "Current Compressor D1 Superheat Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 134,
   "name": "D2 Superheat Temperature",
   "description": "Current Compressor D2 Superheat Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 135,
   "name": "Condenser D1 Superheat (Heat Pump)",
   "description": "Current Compressor D1 Superheat Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 136,
   "name": "Condenser D2 Superheat (Heat Pump)",
   "description": "Current Compressor D2 Superheat Temperature (Heat Pump)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 137,
   "name": "D1 Expansion Valve Position",
   "description": "Current position of Compressor D1 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 138,
   "name": "D2 Expansion Valve Position",
   "description": "Current position of Compressor D2 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 139,
   "name": "Condenser D1 Expansion Valve Position",
   "description": "Current position of Condenser D1 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 140,
   "name": "Condenser D2 Expansion Valve Position",
   "description": "Current position of Condenser D2 Expansion Valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 141,
   "name": "D1 Discharge Temperature",
   "description": "Current Compressor D1 Discharge Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 142,
   "name": "D2 Discharge Temperature",
   "description": "Current Compressor D2 Discharge Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 143,
   "name": "D1 Leaving Water Temp",
   "description": "Current D1 Leaving Water Temperature for WSHP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 144,
   "name": "Alarm Status",
   "description": "An alarm condition",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 145,
   "name": "Outdoor Enthalpy",
   "description": "Current outdoor Enthalpy",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 146,
   "name": "Plenum Pressure",
   "description": "Reserved",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 147,
   "name": "Return Fan Speed",
   "description": "Reserved",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 148,
   "name": "Plenum Calculated Setpoint",
   "description": "Reserved",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 149,
   "name": "Return Air Enthalpy Status",
   "description": "Current value of Return Air Enthalpy",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 150,
   "name": "Current Duct Static Setpoint",
   "description": "Status of the duct static setpoint",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 151,
   "name": "RM454-Z 1 Condenser Fan",
   "description": "Current RM454-Z 1 Condenser Fan Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 152,
   "name": "RM454-Z 1 VDC Comp Perc",
   "description": "Current RMR454-Z 1 VFD Compressor Percentage",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 153,
   "name": "RM454-Z 1 Discharge Pressure",
   "description": "Current RM454-1 Discharge Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 154,
   "name": "RM454-Z 1 Suction Pressure",
   "description": "Current RM454-Z 1 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 155,
   "name": "RM454-Z 1 Suction Line Temp",
   "description": "Current RM454-Z 1 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 156,
   "name": "RM454-Z 1 Saturation Temp",
   "description": "Current RM454-Z 1 Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 157,
   "name": "RM454-Z 1 Superheat",
   "description": "Current RM454-Z 1 Superheat Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 158,
   "name": "RM454-Z 1 EEV Position",
   "description": "Current RM454-Z 1 EEV Valve Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 159,
   "name": "RM454-Z 1 Warnings",
   "description": "Current RM454-Z 1 Warnings",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 160,
   "name": "RM454-Z 1 Comp VFD Alarms 1",
   "description": "Current RM454-Z 1 Comp VFD Alarms 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 161,
   "name": "RM454-Z 1 Comp VFD Alarms 2",
   "description": "Current Rm 454-Z 1 Comp VFD Alarms 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 162,
   "name": "RM454-Z 1 Comp VFD Drive Status",
   "description": "Current RM454-Z 1 Comp VFD drive Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 163,
   "name": "RM454-Z 1 Compressor Current",
   "description": "Current reading in Amps that the RM454Z 1 Compressor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 164,
   "name": "RM454-Z 1 Discharge Line Temp",
   "description": "Current RM454-Z 1 discharge line temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 165,
   "name": "RM454-Z 1 Faults",
   "description": "Current RM45-Z 1 Faults",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 166,
   "name": "RM454-Z 1 Lockouts",
   "description": "Current RM454-Z 1 Lockouts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 167,
   "name": "RM454-Z 2 Condenser Fan",
   "description": "Current RM454-Z 2 condenser fan signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 168,
   "name": "RM454-Z 2 VFD Comp Perc",
   "description": "Current RM454-Z 2 VFD Compressor Percentage",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 169,
   "name": "RM454-Z 2 Discharge Pressure",
   "description": "Current RM454-Z 2 discharge pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 170,
   "name": "RM454-Z 2 Suction Pressure",
   "description": "Current RM454-Z 2 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 171,
   "name": "RM454-Z 2 Suction Line Temp",
   "description": "Current RM454-Z 2 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 172,
   "name": "RM454-Z 2 Saturation Temp",
   "description": "Current RM454-Z 2 Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 173,
   "name": "RM454-Z 2 Superheat",
   "description": "Current RM454-Z 2 Superheat temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 174,
   "name": "RM454-Z 2 EEV Position",
   "description": "Current RM454-Z 2 EEV valve position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 175,
   "name": "RM454-Z 2 Warnings",
   "description": "Current RM454-Z 2 Warnings",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 176,
   "name": "RM454-Z 2 Comp VFD Alarms 1",
   "description": "Current RM454-Z 2 Comp VFD Alarms 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 177,
   "name": "RM454-Z 2 Comp VFD Alarms 2",
   "description": "Current RM454-Z 2 Comp VFD Alarms 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 178,
   "name": "RM454-Z 2 Comp VFD Drive Status",
   "description": "Current RM454-Z 2 Comp VFD Drive Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 179,
   "name": "RM454-Z 2 Compressor Current",
   "description": "Current reading in Amps that the RM454Z 2 compressor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 180,
   "name": "RM454-Z 2 Discharge Line Temp",
   "description": "Current RM454-Z 2 discharge line temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 181,
   "name": "RM454-Z 2 Faults",
   "description": "Current RM454-Z 2 Faults",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 182,
   "name": "RM454-Z 2 Lockouts",
   "description": "Current RM454-Z 2 Lockouts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 183,
   "name": "RM454-Z 3 Condenser Fan",
   "description": "Current RM454-Z 3 condenser fan signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 184,
   "name": "RM454-Z 3 Reheat Valve 1",
   "description": "Current RM454-Z 3 Reheat Valve 1 position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 185,
   "name": "RM454-Z 3 Discharge Pressure",
   "description": "Current RM454-Z 3 Discharge Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 186,
   "name": "RM454-Z 3 Suction Pressure",
   "description": "Current RM454-Z 3 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 187,
   "name": "RM454-Z 3 Suction Line Temp",
   "description": "Current RM454-Z 3 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 188,
   "name": "RM454-Z 3 Saturation Temp",
   "description": "Current RM454-Z 3 Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 189,
   "name": "RM454-Z 3 Superheat",
   "description": "Current RM454-Z 3 Superheat temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 190,
   "name": "RM454-Z 3 EEV Position",
   "description": "Current RM454-Z 3 EEV valve position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 191,
   "name": "RM454-Z 3 Suction Pressure 2",
   "description": "Current RM454-Z 3 Suction Pressure 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 192,
   "name": "RM454-Z 3 Suction Line Temp 2",
   "description": "Current RM454-Z 3 Suction Line Temperature 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 193,
   "name": "RM454-Z 3 Saturation Temp 2",
   "description": "Current RM454-Z 3 Saturation Temperature 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 194,
   "name": "RM454-Z 3 Superheat 2",
   "description": "Current RM454-Z 3 Superheat Temperature 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 195,
   "name": "RM454-Z 3 EEV Position 2",
   "description": "Current RM454-Z 3 EEV Valve Position 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 196,
   "name": "RM454-Z 3 Warnings",
   "description": "Current RM454-Z 3 Warnings",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 197,
   "name": "RM454-Z 3 Discharge Line Temp",
   "description": "Current RM454-Z 3 Discharge Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 198,
   "name": "RM454-Z 3 Faults",
   "description": "Current RM454-Z 3 Faults",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 199,
   "name": "RM454-Z 3 Lockouts",
   "description": "Current RM454-Z 3 Lockouts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 200,
   "name": "RM454-Z 4 Condenser Fan",
   "description": "Current RM454-Z 4 Condenser Fan Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 201,
   "name": "RM454-Z 4 VFD Comp Perc",
   "description": "Current RM454-Z 4 VFD Compressor Percentage",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 202,
   "name": "RM454-Z 4 Discharge Pressure",
   "description": "Current RM454-Z 4 Discharge Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 203,
   "name": "RM454-Z 4 Suction Pressure",
   "description": "Current RM454-Z 4 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 204,
   "name": "RM454-Z 4 Suction Line Temp",
   "description": "Current RM454-Z 4 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 205,
   "name": "RM454-Z 4 Saturation Temp",
   "description": "Current RM454-Z 4 Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 206,
   "name": "RM454-Z 4 Superheat",
   "description": "Current RM454-Z 4 Superheat Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 207,
   "name": "RM454-Z 4 EEV Position",
   "description": "Current RM454-Z 4 EEV Valve Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 208,
   "name": "RM454-Z 4 Warnings",
   "description": "Current RM454-Z 4 Warnings",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 209,
   "name": "RM454-Z 4 Comp VFD Alarms 1",
   "description": "Current RM454-Z 4 Comp VFD Alarms 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 210,
   "name": "RM454-Z 4 Comp VFD Alarms 2",
   "description": "Current RM454-Z 4 Comp VFD Alarms 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 211,
   "name": "RM454-Z 4 Comp VFD Drive Status",
   "description": "Current RM454-Z 4 Comp VFD Drive Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 212,
   "name": "RM454-Z 4 Comp VFD Compressor Current",
   "description": "Current reading in Amps that the RM454-Z compressor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 213,
   "name": "RM454-Z 4 Discharge Line Temp",
   "description": "Current RM454-Z 4 Discharge Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 214,
   "name": "RM454-Z 4 Faults",
   "description": "Current RM454-Z 4 Faults",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 215,
   "name": "RM454-Z 4 Lockouts",
   "description": "Current RM454-Z 4 Lockouts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 216,
   "name": "RM454-Z 5 Condenser Fan",
   "description": "Current RM454-Z 5 Condenser Fan Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 217,
   "name": "RM454-Z 5 VFD Comp Perc",
   "description": "Current RM454-Z 5 VFD Compressor Percentage",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 218,
   "name": "RM454-Z 5 Discharge Pressure",
   "description": "Current RM454-Z 5 Discharge Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 219,
   "name": "RM454-Z 5 Suction Pressure",
   "description": "Current RM454-Z 5 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 220,
   "name": "RM454-Z 5 Suction Line Temp",
   "description": "Current RM454-Z 5 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 221,
   "name": "RM454-Z 5 Saturation Temp",
   "description": "Current RM454-Z 5 Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 222,
   "name": "RM454-Z 5 Superheat",
   "description": "Current RM454-Z 5 Superheat Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 223,
   "name": "RM454-Z 5 EEV Position",
   "description": "Current RM454-Z 5 EEV Valve Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 224,
   "name": "RM454-Z 5 Warnings",
   "description": "Current RM454-Z 5 Warnings",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 225,
   "name": "RM454-Z 5 Comp VFD Alarms 1",
   "description": "Current RM454-Z 5 Comp VFD Alarms 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 226,
   "name": "RM454-Z 5 Comp VFD Alarms 2",
   "description": "Current RM454-Z 5 Comp VFD Alarms 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 227,
   "name": "RM454-Z 5 Comp VFD Drive Status",
   "description": "Current RM454-Z 5 Comp VFD Drive Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 228,
   "name": "RM454-Z 5 Compressor Current",
   "description": "Current reading in Amps that the RM454Z 5 compressor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 229,
   "name": "RM454-Z 5 Discharge Line Temp",
   "description": "Current RM454-Z 5 Discharge Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 230,
   "name": "RM454-Z 5 Faults",
   "description": "Current RM454-Z 5 Faults",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 231,
   "name": "RM454-Z 5 Lockouts",
   "description": "Current RM454-Z 5 Lockouts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 232,
   "name": "RM454-Z 6 Condenser Fan",
   "description": "Current RM454-Z 6 Condenser Fan Signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 233,
   "name": "RM454-Z 6 Reheat Valve 1",
   "description": "Current RM454-Z 6 Reheat Valve 1 Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 234,
   "name": "RM454-Z 6 Discharge Pressure",
   "description": "Current RM454-Z 6 Discharge Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 235,
   "name": "RM454-Z 6 Suction Pressure",
   "description": "Current RM454-Z 6 Suction Pressure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 236,
   "name": "RM454-Z 6 Suction Line Temp",
   "description": "Current RM454-Z 6 Suction Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 237,
   "name": "RM454-Z 6 Saturation Temp",
   "description": "Current RM454-Z 6 Saturation Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 238,
   "name": "RM454-Z 6 Superheat",
   "description": "Current RM454-Z 6 Superheat Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 239,
   "name": "RM454-Z 6 EEV Position",
   "description": "Current RM454-Z 6 EEV Valve Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 240,
   "name": "RM454-Z 6 Suction Pressure 2",
   "description": "Current RM454-Z 6 Suction Pressure 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 241,
   "name": "RM454-Z 6 Suction Line Temp 2",
   "description": "Current RM454-Z 6 Suction Line Temperature 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 242,
   "name": "RM454-Z 6 Saturation Temp 2",
   "description": "Current RM454-Z 6 Saturation Temperature 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 243,
   "name": "RM454-Z 6 Superheat 2",
   "description": "Current RM454-Z 6 Superheat Temperature 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 244,
   "name": "RM454-Z 6 EEV Position 2",
   "description": "Current RM454-Z 6 EEV Valve Position 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 245,
   "name": "RM454-Z 6 Warnings",
   "description": "Current RM454-Z 6 Warnings",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 246,
   "name": "RM454-Z 6 Discharge Line Temp",
   "description": "Current RM454-Z 6 Discharge Line Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 247,
   "name": "RM454-Z 6 Faults",
   "description": "Current RM454-Z 6 Faults",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 248,
   "name": "RM454-Z 6 Lockouts",
   "description": "Current RM454-Z 6 Lockouts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 249,
   "name": "Not used",
   "description": "Not used",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 250,
   "name": "Not used",
   "description": "Not used",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 251,
   "name": "Not used",
   "description": "Not used",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 252,
   "name": "Not used",
   "description": "Not used",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 253,
   "name": "SUB 1 Sub Cool 1",
   "description": "Current Subcooling Module 1 Sub Cool 1 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 254,
   "name": "SUB 1 Sub Cool 2",
   "description": "Current Subcooling Module 1 Sub Cool 2 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 255,
   "name": "SUB 1 Sub Cool 3",
   "description": "Current Subcooling Module 1 Sub Cool 3 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 256,
   "name": "SUB 1 Pressure 1",
   "description": "Current Subcooling Module 1 Liquid Line Pressure 1 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 257,
   "name": "SUB 1 Pressure 2",
   "description": "Current Subcooling Module 1 Liquid Line Pressure 2 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 258,
   "name": "SUB 1 Pressure 3",
   "description": "Current Subcooling Module 1 Liquid Line Pressure 3 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 259,
   "name": "SUB 1 Saturation 1",
   "description": "Subcooling Module 1 Saturation Temperature 1 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 260,
   "name": "SUB 1 Saturation 2",
   "description": "Subcooling Module 1 Saturation Temperature 2 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 261,
   "name": "SUB 1 Saturation 3",
   "description": "Subcooling Module 1 Saturation Temperature 3 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 262,
   "name": "SUB 1 Line Temp 1",
   "description": "Subcooling Module 1 Liquid Line Temperature 1 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 263,
   "name": "SUB 1 Line Temp 2",
   "description": "Subcooling Module 1 Liquid Line Temperature 2 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 264,
   "name": "SUB 1 Line Temp 3",
   "description": "Subcooling Module 1 Liquid Line Temperature 3 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 265,
   "name": "SUB 2 Sub Cool 1",
   "description": "Current Subcooling Module 2 Sub Cool 1 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 266,
   "name": "SUB 2 Sub Cool 2",
   "description": "Current Subcooling Module 2 Sub Cool 2 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 267,
   "name": "SUB 2 Sub Cool 3",
   "description": "Current Subcooling Module 2 Sub Cool 3 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 268,
   "name": "SUB 2 Pressure 1",
   "description": "Current Subcooling Module 2 Liquid Line Pressure 1 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 269,
   "name": "SUB 2 Pressure 2",
   "description": "Current Subcooling Module 2 Liquid Line Pressure 2 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 270,
   "name": "SUB 2 Pressure 3",
   "description": "Current Subcooling Module 2 Liquid Line Pressure 3 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 271,
   "name": "SUB 2 Saturation 1",
   "description": "Subcooling Module 2 Saturation Temperature 1 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 272,
   "name": "SUB 2 Saturation 2",
   "description": "Subcooling Module 2 Saturation Temperature 2 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 273,
   "name": "SUB 2 Saturation 3",
   "description": "Subcooling Module 2 Saturation Temperature 3 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 274,
   "name": "SUB 2 Line Temp 1",
   "description": "Subcooling Module 2 Liquid Line Temperature 1 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 275,
   "name": "SUB 2 Line Temp 2",
   "description": "Subcooling Module 2 Liquid Line Temperature 2 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 276,
   "name": "SUB 2 Line Temp 3",
   "description": "Subcooling Module 2 Liquid Line Temperature 3 Reading",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 277,
   "name": "Enter Water Pump",
   "description": "Status of Entering Water Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 278,
   "name": "Return Plenum Press. Status",
   "description": "Current value of the Return Plenum Pressure Sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 279,
   "name": "Return Plenum Control Signal",
   "description": "Current Return Plenum Control Signal (Motorized Exhaust Damper)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 280,
   "name": "Mixed Air Temp",
   "description": "Mixed air temperature sensor status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 281,
   "name": "Actual Heat Rise",
   "description": "Difference between supply air temperature and mixed air temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 282,
   "name": "Calculated Heat Rise",
   "description": "The heat rise limit is determined by how open",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 283,
   "name": "Supply Air Relative Humidity",
   "description": "If an EBUS Supply Air Sensor is being used",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 284,
   "name": "Supply Air Dew Point",
   "description": "If an EBUS Supply Air Sensor is being used",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 285,
   "name": "Space Dew Point",
   "description": "Current value of the calculated Space Dew Point",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 286,
   "name": "Return Dew Point",
   "description": "Current value of the calculated Return Dew Point",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 287,
   "name": "FAC Fan Alarm State Fan 1",
   "description": "Current alarm status of Fan 1 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 288,
   "name": "FAC Fan Alarm State Fan 2",
   "description": "Current alarm status of Fan 2 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 289,
   "name": "FAC Fan Alarm State Fan 3",
   "description": "Current alarm status of Fan 3 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 290,
   "name": "FAC Fan Alarm State Fan 4",
   "description": "Current alarm status of Fan 4 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 291,
   "name": "FAC Fan Alarm State Fan 5",
   "description": "Current alarm status of Fan 5 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 292,
   "name": "FAC Fan Alarm State Fan 6",
   "description": "Current alarm status of Fan 6 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 293,
   "name": "FAC Fan Alarm State Fan 7",
   "description": "Current alarm status of Fan 7 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 294,
   "name": "FAC Fan Alarm State Fan 8",
   "description": "Current alarm status of Fan 8 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 295,
   "name": "FAC Fan Alarm State Fan 9",
   "description": "Current alarm status of Fan 9 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 296,
   "name": "FAC Fan Alarm State Fan 10",
   "description": "Current alarm status of Fan 10 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 297,
   "name": "FAC Fan Alarm State Fan 11",
   "description": "Current alarm status of Fan 11 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 298,
   "name": "FAC Fan Alarm State Fan 12",
   "description": "Current alarm status of Fan 12 of the FAC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 299,
   "name": "Line Frequency",
   "description": "Current Line Frequency from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 300,
   "name": "Line Voltage 1-2",
   "description": "Current Line Voltage 1-2 from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 301,
   "name": "Line Voltage 2-3",
   "description": "Current Line Voltage 2-3 from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 302,
   "name": "Line Voltage 3-1",
   "description": "Current Line Voltage 3-1 from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 303,
   "name": "Average Line Voltage",
   "description": "Current average Line Voltage from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 304,
   "name": "Total Phase A Current",
   "description": "Current Total Phase A Current from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 305,
   "name": "Total Phase B Current",
   "description": "Current Total Phase B Current from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 306,
   "name": "Total Phase C Current",
   "description": "Current Total Phase C Current from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 307,
   "name": "Average Phase Current",
   "description": "Current Average Phase Current from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 308,
   "name": "Phase A Power",
   "description": "Current Phase A Power from the",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 309,
   "name": "Phase B Power",
   "description": "Current Phase B Power from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 310,
   "name": "Phase C Power",
   "description": "Current Phase C Power from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 311,
   "name": "Total System Power",
   "description": "Current Total System Power from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 312,
   "name": "Phase A Reactive Power",
   "description": "Current Phase A Reactive Power from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 313,
   "name": "Phase B Reactive Power",
   "description": "Current Phase B Reactive Power from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 314,
   "name": "Phase C Reactive Power",
   "description": "Current Phase C Reactive C from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 315,
   "name": "Total Reactive Power",
   "description": "Current Total Reactive Power from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 316,
   "name": "Phase A Apparent Power",
   "description": "Current Phase A Apparent power from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 317,
   "name": "Phase B Apparent Power",
   "description": "Current Phase B Apparent Power from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 318,
   "name": "Phase C Apparent Power",
   "description": "Current Phase C Apparent Power from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 319,
   "name": "Total Apparent Power",
   "description": "Current Total Apparent Power from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 320,
   "name": "Phase A Power Factor",
   "description": "Current Phase A Power Factor from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 321,
   "name": "Phase B Power Factor",
   "description": "Current Phase B Power Factor from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 322,
   "name": "Phase C Power Factor",
   "description": "Current Phase C Power Factor from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 323,
   "name": "Total Power Factor",
   "description": "Current Total Power Factor from the Power Monitor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 324,
   "name": "Utilized Cooling Capacity Percent",
   "description": "Current value of the calculated Cooling Capacity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 325,
   "name": "Utilized Heating Capacity Percent",
   "description": "Current value of the calculated Heating Capacity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 326,
   "name": "Active Cooling Stages",
   "description": "Current active Cooling Stages",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 327,
   "name": "Active Heating Stages",
   "description": "Current active Heating Stages",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 328,
   "name": "Motor Current Fan 1",
   "description": "Current Motor Current reading from Fan 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 329,
   "name": "Motor Current Fan 2",
   "description": "Current Motor Current reading from Fan 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 330,
   "name": "Motor Current Fan 3",
   "description": "Current Motor Current reading from Fan 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 331,
   "name": "Motor Current Fan 4",
   "description": "Current Motor Current reading from Fan 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 332,
   "name": "Motor Current Fan 5",
   "description": "Current Motor Current reading from Fan 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 333,
   "name": "Motor Current Fan 6",
   "description": "Current Motor Current reading from Fan 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 334,
   "name": "Motor Current Fan 7",
   "description": "Current Motor Current reading from Fan 7",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 335,
   "name": "Motor Current Fan 8",
   "description": "Current Motor Current reading from Fan 8",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 336,
   "name": "Motor Current Fan 9",
   "description": "Current Motor Current reading from Fan 9",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 337,
   "name": "Motor Current Fan 10",
   "description": "Current Motor Current reading from Fan 10",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 338,
   "name": "Motor Current Fan 11",
   "description": "Current Motor Current reading from Fan 11",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 339,
   "name": "Motor Current Fan 12",
   "description": "Current Motor Current reading from Fan 12",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 340,
   "name": "Motor Speed Percent Fan 1",
   "description": "Current Motor Speed Percentage of Fan 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 341,
   "name": "Motor Speed Percent Fan 2",
   "description": "Current Motor Speed Percentage of Fan 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 342,
   "name": "Motor Speed Percent Fan 3",
   "description": "Current Motor Speed Percentage of Fan 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 343,
   "name": "Motor Speed Percent Fan 4",
   "description": "Current Motor Speed Percentage of Fan 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 344,
   "name": "Motor Speed Percent Fan 5",
   "description": "Current Motor Speed Percentage of Fan 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 345,
   "name": "Motor Speed Percent Fan 6",
   "description": "Current Motor Speed Percentage of Fan 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 346,
   "name": "Motor Speed Percent Fan 7",
   "description": "Current Motor Speed Percentage of Fan 7",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 347,
   "name": "Motor Speed Percent Fan 8",
   "description": "Current Motor Speed Percentage of Fan 8",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 348,
   "name": "Motor Speed Percent Fan 9",
   "description": "Current Motor Speed Percentage of Fan 9",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 349,
   "name": "Motor Speed Percent Fan 10",
   "description": "Current Motor Speed Percentage of Fan 10",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 350,
   "name": "Motor Speed Percent Fan 11",
   "description": "Current Motor Speed Percentage of Fan 11",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 351,
   "name": "Motor Speed Percent Fan 12",
   "description": "Current Motor Speed Percentage of Fan 12",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Occupied Cooling Setpoint",
   "description": "If the control temperature rises one deadband above; range 1°F to 110°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Occupied Heating Setpoint",
   "description": "If the control temperature drops one deadband below; range 1°F to 110°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Hood On Cooling Setpoint",
   "description": "Cooling Mode Enable Setpoint used only in Hood; range 1°F to 110°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Hood On Heating Setpoint",
   "description": "Heating Mode Enable Setpoint used only in Hood; range 1°F to 110°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Unoccupied Cooling Offset",
   "description": "During the Unoccupied Mode of Operation; range 0°F to 30°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Unoccupied Heating Offset",
   "description": "During the Unoccupied Mode of Operation; range 0°F to 30°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Mode Select Deadband",
   "description": "This value is added to and subtracted; range 0°F to 10°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Max Coil Setpoint Reset Limit",
   "description": "Highest that the Coil Temperature resets to during; range 35°F to 70°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Min Coil Setpoint Reset Limit",
   "description": "Lowest that the Coil Temperature resets to during; range 35°F to 70°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Supply Air Cooling Setpoint",
   "description": "Supply Air Cooling Setpoint; range 30°F to 80°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Supply Air Heating Setpoint",
   "description": "Supply Air Cooling Setpoint; range 40°F to 240°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Max SAT Cooling Setpoint Reset Limit",
   "description": "If Supply Air Reset is configured; range 0°F to 100°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Max SAT Heating Setpoint Reset Limit",
   "description": "If Supply Air Reset is configured; range 0°F to 250°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Supply Air Cooling Staging Window",
   "description": "In Cooling Mode; range 1°F to 30°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Supply Air Heating Staging Window",
   "description": "In Heating Mode; range 1°F to 50°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Warm-Up Target Temperature",
   "description": "Morning warm-up target (see AV 89 for cool-down); range 50°F to 90°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Warm-Up Mode Supply Air Setpoint",
   "description": "During Morning Warm-Up; range 40°F to 240°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Cool-Down Mode Supply Air Setpoint",
   "description": "During Morning Cool-Down; range 30°F to 80°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "Mechanical Cooling Outdoor Air Lockout",
   "description": "Mechanical Cooling is locked out when the Outdoor Air; range -30°F to 100°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Mechanical Heating Outdoor Air Lockout",
   "description": "Mechanical Heating is locked out when the Outdoor Air; range -30°F to 150°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "Low Supply Temp Cutoff Alarm",
   "description": "Cooling is disabled if the Supply Air Temperature falls; range 0°F to 100°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "High Supply Temp Cutoff Alarm",
   "description": "Heating is disabled if the Supply Air Temperature rises; range 0°F to 250°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Preheater Cooling Mode Setpoint",
   "description": "If the Preheater is enabled; range 35°F to 90°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Preheater Venting Mode Setpoint",
   "description": "If the Preheater is enabled; range 35°F to 90°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Preheater Heating Mode Setpoint",
   "description": "If the Preheater is enabled; range 35°F to 140°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Outdoor Air Dewpoint Setpoint",
   "description": "On an MUA unit; range 30°F to 80°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Economizer Enable Setpoint",
   "description": "The economizer is enabled if the outdoor drybulb; range -30°F to 80°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Heat Wheel Defrost Enable Setpoint",
   "description": "The unit goes into Heat Wheel Defrost; range 0°F to 50°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "Preheat Enable Setpoint",
   "description": "If the Supply Fan is energized; range -30°F to 105°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Sensor Slide Offset Max Effect",
   "description": "If the space sensor has the optional slide adjustment; range 0°F to 10°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "Space Sensor Calibration Offset",
   "description": "If the Space Temperature Sensor is reading incorrectly; range -100°F to 100°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "Supply Air Sensor Calibration Offset",
   "description": "If the Supply Air Temperature Sensor is reading incorrectly; range -100°F to 100°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "Return Air Sensor Calibration Offset",
   "description": "If the Return Air Temperature Sensor is reading incorrectly; range -100°F to 100°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "Outdoor Air Sensor Calibration Offset",
   "description": "If the Outdoor Air Temperature Sensor is reading incorrectly; range -100°F to 100°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "Carbon Dioxide Sensor Calibration Offset",
   "description": "If the CO2 Sensor is reading incorrectly; range -500 ppm to 500 ppm",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "Low Ambient Protection Setpoint",
   "description": "The temperature at which the Low Ambient Relay activates; range -30°F to 70°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "SAT Cool Setpoint Reset Source Low Limit",
   "description": "If doing Supply Air Setpoint Reset; range -30°F to 150°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "SAT Cool Setpoint Reset Source High Limit",
   "description": "If doing Supply Air Setpoint Reset; range 0°F to 150°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "SAT Heat Setpoint Reset Source Low Limit",
   "description": "If doing Supply Air Setpoint Reset; range -30°F to 150°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "SAT Heat Setpoint Reset Source High Limit",
   "description": "If doing Supply Air Setpoint Reset; range 0°F to 150°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "Control Temperature High Alarm Offset",
   "description": "If the temperature of the controlling sensor rises above; range 0°F to 50°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "Control Temperature Low Alarm Offset",
   "description": "If the temperature of the controlling sensor falls below; range 0°F to 50°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "Heat Pump Compressor Heat Lockout",
   "description": "The Compressor Heat is locked out below this setpoint; range -30°F to 100°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "Maximum Main Fan VFD in SZ VAV Heating Mode",
   "description": "In a single-zone VAV configuration; range 0 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "Minimum Main Fan VFD in Cooling Mode",
   "description": "In a single-zone VAV configuration; range 0 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "Minimum Main Fan VFD in Heating Mode",
   "description": "In a Single Zone VAV configuration; range 0 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "Minimum Main Fan VFD in Vent Mode",
   "description": "The speed at which the VFD operates; range 0 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "Maximum Economizer in Heating Mode",
   "description": "The max position of the Economizer Damper opens; range 0 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "Minimum Economizer Position",
   "description": "The minimum position of the Outdoor Air damper; range 0 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "Maximum Economizer CO2 Reset Limit",
   "description": "The maximum value the Economizer Minimum Position can; range 0 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "Minimum Carbon Dioxide Setpoint",
   "description": "Threshold CO2 level at which the Economizer Min Damper; range 0 ppm to 2000 ppm",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "Maximum Carbon Dioxide Setpoint",
   "description": "CO2 level at which the Economizer Min Damper Position; range 0 ppm to 2000 ppm",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "Indoor Humidity Setpoint Low Reset Limit",
   "description": "On indoor controlled (non-MUA) units; range 0 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "Indoor Humidity Setpoint High Reset Limit",
   "description": "On indoor controlled (non-MUA) units; range 0 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "Duct Static Pressure Setpoint",
   "description": "Current Static Pressure Setpoint; range 0.1 to 3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "Duct Static Pressure Control Deadband",
   "description": "Value above and below the Duct Static Pressure Setpoint; range 0.01 to 0.5",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "Building Pressure Control Setpoint",
   "description": "Building Pressure Setpoint or Exhaust Duct Static Pressure Setpoint; range -0.20 to 3.00",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "Building Pressure Control Deadband",
   "description": "Value above and below the Building Pressure Setpoint; range 0.01 to 0.50",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "Minimum Outdoor CFM Requirement",
   "description": "Minimum Outdoor Airflow CFM Setpoint; range 0.00K to 200K",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "Outdoor CFM Control Deadband",
   "description": "When the OA CFM is within the control deadband; range 10 to 1000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "Single Zone VAV Fan Speed Integral",
   "description": "The Integral Constant for Single Zone VAV Fan Control; range 0 to 10",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "Relay Run-time Hours Warning Limit",
   "description": "If any configured relay's run time exceeds this number; range 0 to 30000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "Cooling Mode Head Pressure Setpoint",
   "description": "Head Pressure Setpoint in the Cooling Mode; range 250 to 450",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "Dehum Mode Head Pressure Setpoint",
   "description": "Head Pressure Setpoint in the Dehumidification Mode; range 250 to 450",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "Superheat Setpoint",
   "description": "Superheat Setpoint; range 1°F to 30°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "Maximum Outdoor CFM Requirement",
   "description": "Maximum Outdoor Airflow CFM Setpoint in High CO2; range 0.10K to 200K",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "Schedule Force",
   "description": "0 = Auto (uses controller's schedule) 1 = Forced; range 0 to 2",
   "units": "",
   "access": "W",
   "states": "0=Auto (controller schedule), 1=Forced Occupied, 2=Forced Unoccupied"
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "HVAC Mode Override",
   "description": "Overrides normal controller operation to force the unit into; range 0 to 6",
   "units": "",
   "access": "W",
   "states": "0=Auto, 1=Vent, 2=Cool, 3=Heat, 4=Vent Dehum, 5=Cool Dehum, 6=Heat Dehum"
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "Fan VFD Override",
   "description": "Override to force the VFD to this percentage speed; range 0% Auto=65535 to 100% Auto=65535",
   "units": "%",
   "access": "W",
   "states": "65535=Auto"
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "Outdoor Air Damper Override",
   "description": "Fixed OA damper position; Auto restores normal control",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "Supply Setpoint Override",
   "description": "This overrides whatever setpoint the Supply Air Temperature; range 0°F to 120°F",
   "units": "°F",
   "access": "W",
   "states": "0=No Override"
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "Space Temperature Value",
   "description": "If the controller is configured for this operation; range 0°F to 120°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "Space Humidity Value",
   "description": "If the controller is configured for this operation; range 0 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "Indoor RH Calibration Offset",
   "description": "If the Space Humidity Sensor is reading incorrectly; range -1 to 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "Relief Fan VFD",
   "description": "Override to force the VFD to this percentage speed; range 0% Auto=65535 to 100% Auto=65535",
   "units": "%",
   "access": "W",
   "states": "65535=Auto"
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "Relief Pressure Value",
   "description": "If the controller is configured for this operation; range -0.5 to 0.5",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "Carbon Dioxide Value",
   "description": "If the controller is configured for this operation; range 0 to 3000",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "Outdoor Air Temperature Value",
   "description": "If the controller is configured for this operation; range -40°F to 150°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "Outdoor Air Humidity Value",
   "description": "If the controller is configured for this operation; range 0 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "Reserved 1",
   "description": "Reserved",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "Reserved 2",
   "description": "Reserved",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "Reserved 3",
   "description": "Reserved",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "Reserved 4",
   "description": "Reserved",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "Enthalpy Enable Setpoint",
   "description": "If configured for Comparative Enthalpy Economizer Control; range 25 BTU/lb. to 35 BTU/lb.",
   "units": "BTU/lb",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "Enthalpy Enable Deadband",
   "description": "The OA Enthalpy must be below the Enthalpy Enable; range 0.3 BTU/lb. to 1.5 BTU/lb.",
   "units": "BTU/lb",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "Maximum Static Setpoint Reset Limit",
   "description": "As the most open VAV damper rises above 80%; range 0.01 “WG to 3.00 “WG",
   "units": "in. w.c.",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "Minimum Static Setpoint Reset Limit",
   "description": "As the most open VAV damper drops below 80%; range 0.01 “WG to 3.00 “WG",
   "units": "in. w.c.",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "Static Setpoint Reset Interval",
   "description": "The Reset Interval is how often the setpoint reset; range 10 min to 60 min",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "Cool-Down Target Temperature",
   "description": "Morning cool-down target (see AV 16 for warm-up); range 50°F to 90°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "Warm-Up Override",
   "description": "Commands the unit into Morning WarmUp Mode; range 0 to 1",
   "units": "",
   "access": "W",
   "states": "1=Command Warm-Up Mode"
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "Cool Down Override",
   "description": "Commands the unit into Morning CoolDown Mode 1=Command Cool-Down; range 0 to 1",
   "units": "",
   "access": "W",
   "states": "1=Command Cool-Down Mode"
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "Return Air High Limit Protection",
   "description": "For voting units or CV units only; range 60 to 100",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "Return Air Low Limit Protection",
   "description": "For voting units or CV units only; range 45 to 70",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "Sump Drain Override",
   "description": "Setting this value to 1 turns the Sump Drain; range 0 to 1",
   "units": "",
   "access": "W",
   "states": "0=Auto, 1=On"
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "Return Plenum Pressure Setpoint",
   "description": "Current Return Plenum Pressure Setpoint; range -0.2\"WG to 0.2\"WG",
   "units": "in. w.c.",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "Return Plenum Pressure Deadband",
   "description": "Value above and below the Return Plenum Pressure Setpoint; range 0.01\"WG to 0.2\"WG",
   "units": "in. w.c.",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "Dehum Lockout Setpoint",
   "description": "If the Outdoor Air temperature is below this setpoint; range -30°F to 60°F",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "Emergency Compressor Lockout",
   "description": "This point can be used to lock out; range 0 to 1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "Supply Air Dew Point Setpoint",
   "description": "When the VCCX-454 is configured for DXDOAS control; range 35 to 80",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Cooling Enabled Status",
   "description": "Status that indicates Mechanical Cooling is enabled based",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Heating Enabled Status",
   "description": "Status that indicates that Mechanical Heating is enabled based",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Economizer Enabled Status",
   "description": "Status that indicates the Economizer is enabled based",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Aux Heat Enabled Status",
   "description": "Heat Pump Auxiliary Heat enabled",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Emergency Heat Enabled Status",
   "description": "Shows the Emergency Heat is enabled based",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Fan Proof of Airflow Status",
   "description": "Proof of Airflow Binary Input Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Exhaust Hood On/Off Status",
   "description": "Exhaust Hood On/Off Binary Input Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Remote Forced Occupied Status",
   "description": "Remote Forced Occupied Mode Binary Input Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "A2L Airstream Leak Detect Status",
   "description": "Alarm active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "A2L Cabinet Leak Detect Status",
   "description": "Alarm active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "Reserved for Future Use",
   "description": "Not Used",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "Bad Supply Air Sensor",
   "description": "Alarm that indicates a failure of the Supply Air",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "Bad Return Air Sensor",
   "description": "Alarm that indicates a failure of the Return Air",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "Bad Outdoor Air Sensor",
   "description": "Failure of the Outdoor Air Temperature Sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "Bad Space Temp Sensor",
   "description": "Failure of the Space Temperature Sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "Bad Carbon Dioxide Sensor",
   "description": "Failure of the CO2 Sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "Bad Building Pressure Sensor",
   "description": "Alarm indicating a missing/failed Building Pressure Sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "Bad Outdoor Airflow Sensor",
   "description": "An Outdoor Airflow Sensor is configured, but not detected",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "Bad Exhaust Airflow Sensor",
   "description": "An Exhaust Airflow Sensor is configured, but not detected",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "Bad Supply Airflow Sensor",
   "description": "A Supply Airflow Sensor is configured, but not detected",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "Bad Return Airflow Sensor",
   "description": "A Return Airflow Sensor is configured, but not detected",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "Mechanical Cooling Alarm",
   "description": "Compressor Relays are enabled but the Supply Air Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "Mechanical Heating Alarm",
   "description": "Heating Mode has been initiated but the Supply Air",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 24,
   "name": "Fan Proving Alarm",
   "description": "This alarm indicates an Airflow failure from the Main",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 25,
   "name": "Dirty Filter Alarm",
   "description": "This alarm indicates that the filters are dirty",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 26,
   "name": "Emergency Shutdown Alarm",
   "description": "This alarm indicates that an Emergency Shutdown has been",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "Relay Runtime Warning",
   "description": "When any of the configured relays exceeds a configured",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "Economizer Missing Alarm",
   "description": "Title 24 operation indicates missing economizer feedback",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 29,
   "name": "Economizer Title 24 Failure A",
   "description": "Title 24 Air Temperature Sensor Failure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 30,
   "name": "Economizer Title 24 Failure B",
   "description": "Title 24 Not Economizing when it should",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 31,
   "name": "Economizer Title 24 Failure C",
   "description": "Title 24 Economizing when it should not",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 32,
   "name": "Economizer Title 24 Failure D",
   "description": "Title 24 Damper Not Modulating",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "Economizer Title 24 Failure E",
   "description": "Title 24 Excess Outdoor Air",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 34,
   "name": "High Supply Temp Cutoff",
   "description": "The Supply Air has risen above the Hi SAT",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 35,
   "name": "Low Supply Temp Cutoff",
   "description": "The Supply Air has fallen below the Low SAT",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 36,
   "name": "High Control Mode Alarm",
   "description": "Occurs when the Controlling Sensor Temperature rises above",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 37,
   "name": "Low Control Mode Alarm",
   "description": "Occurs when the Controlling Sensor Temperature falls below",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 38,
   "name": "Missing Refrigerant Module #1",
   "description": "Refrigerant Module #1 is bad or missing",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 39,
   "name": "Missing Refrigerant Module #2",
   "description": "Refrigerant Module #2 is bad or missing",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 40,
   "name": "Missing Refrigerant Module #3",
   "description": "Refrigerant Module #3 is bad or missing",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 41,
   "name": "Missing Refrigerant Module #4",
   "description": "Refrigerant Module #4 is bad or missing",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 43,
   "name": "Missing Reheat Board",
   "description": "The MHGR board is configured but not detected",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 44,
   "name": "Missing Mod Gas Board",
   "description": "The MODGAS board is configured but not detected",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 45,
   "name": "Missing EM1 Board",
   "description": "EM1 Expansion Board is bad or missing",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 46,
   "name": "Missing 12 Relay Expansion Board",
   "description": "The 12 Relay Expansion Board is configured but not",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 47,
   "name": "On Board Relay 1 Main Fan",
   "description": "Current Status of Main Fan Relay #1 on Main",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 48,
   "name": "On Board Relay 2",
   "description": "Current Status of Configurable Relay #2 on Main Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 49,
   "name": "On Board Relay 3",
   "description": "Current Status of Configurable Relay #3 on Main Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 50,
   "name": "On Board Relay 4",
   "description": "Current Status of Configurable Relay #4 on Main Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 51,
   "name": "On Board Relay 5",
   "description": "Current Status of Configurable Relay #5 on Main Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 52,
   "name": "On Board Relay 6",
   "description": "Current Status of Configurable Relay #6 on Main Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 53,
   "name": "On Board Relay 7",
   "description": "Current Status of Configurable Relay #7 on Main Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 54,
   "name": "On Board Relay 8",
   "description": "Current Status of Configurable Relay #8 on Main Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 55,
   "name": "Expansion Board EM1 Relay 1",
   "description": "Current Status of Configurable Relay #1 on EM1 Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 56,
   "name": "Expansion Board EM1 Relay 2",
   "description": "Current Status of Configurable Relay #2 on EM1 Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 57,
   "name": "Expansion Board EM1 Relay 3",
   "description": "Current Status of Configurable Relay #3 on EM1 Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 58,
   "name": "Expansion Board EM1 Relay 4",
   "description": "Current Status of Configurable Relay #4 on EM1 Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 59,
   "name": "Expansion Board EM1 Relay 5",
   "description": "Current Status of Configurable Relay #5 on EM1 Board",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 60,
   "name": "12 Relay Expansion Board Relay 1",
   "description": "Current Status of Configurable Relay #1 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 61,
   "name": "12 Relay Expansion Board Relay 2",
   "description": "Current Status of Configurable Relay #2 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 62,
   "name": "12 Relay Expansion Board Relay 3",
   "description": "Current Status of Configurable Relay #3 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 63,
   "name": "12 Relay Expansion Board Relay 4",
   "description": "Current Status of Configurable Relay #4 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 64,
   "name": "12 Relay Expansion Board Relay 5",
   "description": "Current Status of Configurable Relay #5 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 65,
   "name": "12 Relay Expansion Board Relay 6",
   "description": "Current Status of Configurable Relay #6 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 66,
   "name": "12 Relay Expansion Board Relay 7",
   "description": "Current Status of Configurable Relay #7 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 67,
   "name": "12 Relay Expansion Board Relay 8",
   "description": "Current Status of Configurable Relay #8 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 68,
   "name": "12 Relay Expansion Board Relay 9",
   "description": "Current Status of Configurable Relay #9 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 69,
   "name": "12 Relay Expansion Board Relay 10",
   "description": "Current Status of Configurable Relay #10 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 70,
   "name": "12 Relay Expansion Board Relay 11",
   "description": "Current Status of Configurable Relay #11 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 71,
   "name": "12 Relay Expansion Board Relay 12",
   "description": "Current Status of Configurable Relay #12 on 12 Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 72,
   "name": "Preheater Enable Status",
   "description": "Status of Preheater Enable Input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 73,
   "name": "Preheater Emergency Shutdown",
   "description": "Status of Preheater Emergency Shutdown Input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 74,
   "name": "Preheater Spare Binary Input #3",
   "description": "Status of Preheater Binary Input #3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 75,
   "name": "MODGAS Enable Status",
   "description": "Status of MODGAS Controller",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 76,
   "name": "MHGR Enable Status",
   "description": "Status of MHGRV Controller",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 77,
   "name": "A1 Compressor Enable",
   "description": "Current Status of Enable Signal to Compressor A1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 78,
   "name": "A2 Compressor Enable",
   "description": "Current Status of Enable Signal to Compressor A2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 79,
   "name": "A1 Compressor Alarms",
   "description": "An RSM alarm is present on the A1 circuit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 80,
   "name": "A2 Compressor Alarms",
   "description": "An RSM alarm is present on the A2 circuit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 81,
   "name": "A1-2 Defrost Switch",
   "description": "Outside Coil A1/A2 Temp Switch for Defrost Mode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 82,
   "name": "A1-2 Water Proof of Flow",
   "description": "A1/A2 Water Proof of Flow Switch",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 83,
   "name": "A1-4 Emergency Shutdown (RM454-D)",
   "description": "Emergency Shutdown Input on Module A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 84,
   "name": "Refrigerant Module 1 Relay 1",
   "description": "Current Status of Compressor A1 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 85,
   "name": "Refrigerant Module 1 Relay 2",
   "description": "Current Status of Compressor A2 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 86,
   "name": "Refrigerant Module 1 Relay 3",
   "description": "Current Status of Condenser 1 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 87,
   "name": "Refrigerant Module 1 Relay 4",
   "description": "Current Status of Relay #4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 88,
   "name": "Refrigerant Module 1 Relay 5",
   "description": "Current Status of Relay #5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 89,
   "name": "B1 Compressor Enable",
   "description": "Current Status of Enable Signal to Compressor B1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 90,
   "name": "B2 Compressor Enable",
   "description": "Current Status of Enable Signal to Compressor B2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 91,
   "name": "B1 Compressor Alarms",
   "description": "An RSM alarm is present on the B1 circuit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 92,
   "name": "B2 Compressor Alarms",
   "description": "An RSM alarm is present on the B2 circuit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 93,
   "name": "B1-2 Defrost Switch",
   "description": "Outside Coil B1/B2 Temp Switch for Defrost Mode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 94,
   "name": "B1-2 Water Proof of Flow",
   "description": "B1/B2 Switch for Water Proof of Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 95,
   "name": "B1-4 Emergency Shutdown (RM454-D)",
   "description": "Emergency Shutdown Input on Module B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 96,
   "name": "Refrigerant Module 2 Relay 1",
   "description": "Current Status of Compressor 1 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 97,
   "name": "Refrigerant Module 2 Relay 2",
   "description": "Current Status of Compressor 2 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 98,
   "name": "Refrigerant Module 2 Relay 3",
   "description": "Current Status of Condenser 1 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 99,
   "name": "Refrigerant Module 2 Relay 4",
   "description": "Current Status of Relay #4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 100,
   "name": "Refrigerant Module 2 Relay 5",
   "description": "Current Status of Relay #5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 101,
   "name": "C1 Compressor Enable",
   "description": "Current Status of Enable Signal to Compressor C1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 102,
   "name": "C2 Compressor Enable",
   "description": "Current Status of Enable Signal to Compressor C2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 103,
   "name": "C1 Compressor Alarms",
   "description": "An RSM alarm is present on the C1 circuit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 104,
   "name": "C2 Compressor Alarms",
   "description": "An RSM alarm is present on the C2 circuit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 105,
   "name": "C1-2 Defrost Switch",
   "description": "Outside Coil C1/C2Temp Switch for Defrost Mode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 106,
   "name": "C1-2 Water Proof of Flow",
   "description": "C1/C2 Switch for Water Proof of Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 107,
   "name": "C1-4 Emergency Shutdown (RM454-D)",
   "description": "Emergency Shutdown Input on Module C",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 108,
   "name": "Refrigerant Module 3 Relay 1",
   "description": "Current Status of Compressor 1 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 109,
   "name": "Refrigerant Module 3 Relay 2",
   "description": "Current Status of Compressor 2 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 110,
   "name": "Refrigerant Module 3 Relay 3",
   "description": "Current Status Condenser 1 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 111,
   "name": "Refrigerant Module 3 Relay 4",
   "description": "Current Status of Relay #4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 112,
   "name": "Refrigerant Module 3 Relay 5",
   "description": "Current Status of Relay #5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 113,
   "name": "D1 Compressor Enable",
   "description": "Current Status of Enable Signal to Compressor D1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 114,
   "name": "D2 Compressor Enable",
   "description": "Current Status of Enable Signal to Compressor D2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 115,
   "name": "D1 Compressor Alarms",
   "description": "An RSM alarm is present on the D1 circuit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 116,
   "name": "D2 Compressor Alarms",
   "description": "An RSM alarm is present on the D2 circuit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 117,
   "name": "D1-2 Defrost Switch",
   "description": "Outside Coil D1/D2 Temp Switch for Defrost Mode",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 118,
   "name": "D1-2 Water Proof of Flow",
   "description": "D1/D2 Switch for Water Proof of Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 119,
   "name": "D1-4 Emergency Shutdown (RM454-D)",
   "description": "Emergency Shutdown Input on Module D",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 120,
   "name": "Refrigerant Module 4 Relay 1",
   "description": "Current Status of Compressor 1 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 121,
   "name": "Refrigerant Module 4 Relay 2",
   "description": "Current Status of Compressor 2 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 122,
   "name": "Refrigerant Module 4 Relay 3",
   "description": "Current Status of Condenser 1 Enable Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 123,
   "name": "Refrigerant Module 4 Relay 4",
   "description": "Current Status of Relay #4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 124,
   "name": "Refrigerant Module 4 Relay 5",
   "description": "Current Status of Relay #5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 125,
   "name": "Preheater Alarm",
   "description": "Preheater Alarm Indicator",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 126,
   "name": "Return Fan Proving Alarm",
   "description": "Exhaust Fan / Return Fan Proof of Flow Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 127,
   "name": "Compressor Running A",
   "description": "Current Run Status of Compressor A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 128,
   "name": "Compressor Running B",
   "description": "Current Run Status of Compressor B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 129,
   "name": "Compressor Running C",
   "description": "Current Run Status of Compressor C",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 130,
   "name": "Compressor Running C2",
   "description": "Current Run Status of Compressor C2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 131,
   "name": "Compressor Running D",
   "description": "Current Run Status of Compressor D",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 132,
   "name": "Compressor Running E",
   "description": "Current Run Status of Compressor E",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 133,
   "name": "Compressor Running E2",
   "description": "Current Run Status of Compressor E2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 134,
   "name": "Compressor Running F",
   "description": "Current Run Status of Compressor F",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 135,
   "name": "Compressor Running F2",
   "description": "Current Run Status of Compressor F2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 136,
   "name": "Return Fan Proving Status",
   "description": "Proof of Return Fan Airflow Binary Input Status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 137,
   "name": "IAQ Mode Active",
   "description": "IAQ Mode is active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 138,
   "name": "Heat Wheel Defrost Active",
   "description": "Heat Wheel Defrost is active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 139,
   "name": "Direct Fire Status",
   "description": "Signal on EM1 binary input 2 from Direct Fire",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 140,
   "name": "Direct Fire Alarm Status",
   "description": "Signal on EM1 binary input 3 that indicates there",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 141,
   "name": "Temp Rise Warning",
   "description": "The heat rise when direct fire heat is active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 142,
   "name": "Temp Rise Alarm",
   "description": "The heat rise when direct fire heat is active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 143,
   "name": "Temp Rise Lockout",
   "description": "Three High Temp Rise alarms occurred within a one",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 144,
   "name": "High CO2 Rise Warning",
   "description": "High return CO2 was detected when running direct fire",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 145,
   "name": "High CO2 Rise Alarm",
   "description": "High return CO2 was detected",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 146,
   "name": "High CO2 Rise Lockout",
   "description": "Three CO2 warning alarms occurred within a one hour",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 147,
   "name": "Ignition Lockout",
   "description": "An active alarm on the Direct Fire Module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 148,
   "name": "Direct Fire Status Lockout",
   "description": "The Direct Fire Status Signal is not active within",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 149,
   "name": "Direct Fire Setpoint Override",
   "description": "The max calculated heat rise is limiting the Supply",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 150,
   "name": "Fan Array Failure",
   "description": "A Fan Array Failure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 151,
   "name": "A2L Leak Detect",
   "description": "An A2L Leak Detected in the Airstream",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 152,
   "name": "A2L Cabinet Leak Detect",
   "description": "An A2L Leak Detected in the Cabinet",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 153,
   "name": "Bad Static Pressure Sensor",
   "description": "The static pressure is missing or otherwise malfunctioning",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/aaon/vccx-454",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}