Rooftop unit / air handler controller · BACnet points list

AAON Stratus Unit Manager (Stratus controls) BACnet points list

Updated 12 November 2026

Short answer

Stratus is AAON's newest unit control platform; the Stratus Unit Manager connects to a BACnet MS/TP trunk or to Ethernet for BACnet IP. Its BACnet map is compact: 57 analog values (temperatures, humidity, airflow, fan and refrigeration modulation, active setpoints, plus writable setpoints at AV 10003-10009), 43 binary values for status, sensor and safety alarms, 4 multistate values for application, mode and occupancy, an occupancy schedule object and a schedule-driven binary input.

This page lists 106 BACnet objects for the AAON Stratus Unit Manager (Stratus controls) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.

Manufacturer
AAON
Model
Stratus Unit Manager (Stratus controls)
Equipment
Rooftop unit / air handler controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
106 (9 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Stratus software 1.3.3
Also known as
Stratus, AAON Stratus, Stratus Unit Manager, Stratus BACnet Points Guide, Stratus controller, Stratus Series
Source document
Stratus BACnet Points Guide · Rev. A · rev. 2026-11
Download CSV 106 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.

BMS integration notes: AAON Stratus Unit Manager (Stratus controls)

Integration in brief

Connect the Unit Manager to MS/TP or Ethernet (BACnet IP) and set the baud rate, MAC address and a unique device ID (and BBMD for IP) in Unit Settings. The BAS forces occupancy with MV 10001 or writes the Occupied Schedule, adjusts the occupied and unoccupied setpoints at AV 10004-10007 and can override the supply air setpoint with AV 10003. Read the mode, occupancy and alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 10001Force OccupancyOccupancy: auto, force occupied or unoccupiedWrite
AV 10005Occupied Cooling SetpointOccupied cooling setpoint, °FWrite
AV 10004Occupied Heating SetpointOccupied heating setpoint, °FWrite
AV 10003Supply Air Setpoint OverrideSupply air setpoint override; rewrite every 5 minWrite
MV 2HVAC Unit Operating ModeCurrent HVAC modeRead
BV 16OccupiedOccupied statusRead
AV 1Mode Based Controlled TemperatureTemperature of the controlled pointRead
AV 2Supply Air TemperatureSupply air temperatureRead
BV 43Unit Cannot Run AlarmSomething is blocking unit operationRead

Enable & remote start

MV 10001 Force Occupancy (Auto, Force Occupied, Force Unoccupied) or the Occupied Schedule object (Schedule 2, which writes BI 1) set occupancy. BV 10002 can disable economizer operation (inverted logic).

Heartbeat & communication loss

AV 10003 Supply Air Setpoint Override must be written at least every five minutes or it is treated as invalid and the normal control mode takes over the supply air setpoint.

Network setup

Watch out for

AAON Stratus Unit Manager (Stratus controls) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

106 of 106 shown
Type
AnalogMulti-stateOther
Access
Show
AAON Stratus Unit Manager (Stratus controls) BACnet Points List
DescriptionStates
AVmin1Mode Based Controlled TemperatureCurrent temperature for the controlled point°FRead
AVmin2Supply Air TemperatureFunctional Supply Air temperature°FRead
AV3Supply Air DewpointFunctional Supply Air dew point%Read
AV4Outdoor Air TemperatureFunctional Outdoor Air temperature°FRead
AV5Outdoor Air Relative HumidityFunctional Outdoor Air Relative Humidity%Read
AV6Outdoor Air WetbulbFunctional Outdoor Air wet-bulb temperature°FRead
AV7Outdoor Air DewpointFunctional Outdoor Air dew point°FRead
AV8Return Air TemperatureFunctional Return Air temperature°FRead
AV9Return Air Relative HumidityFunctional Return Air relative humidity%Read
AV10Mixed Air TemperatureFunctional Mixed Air temperature°FRead
AV11Mixed Air Relative HumidityFunctional Mixed Air relative humidity%Read
AV12Space TemperatureFunctional Space Temperature°FRead
AV13Space Relative HumidityFunctional Space Relative Humidity%Read
AV14Commanded OA Damper PositionPosition the Outdoor Air damper should be in%Read
AV15OA Damper PositionCurrent Outdoor Air damper position%Read
AV16Supply Fan SpeedCurrent Supply Fan Speed as a percentage from the minimum speed%Read
AV17Return Fan SpeedCurrent Return Fan Speed as a percentage from the minimum speed%Read
AV18Exhaust Fan SpeedCurrent Exhaust Fan Speed as a percentage from the minimum speed%Read
AV19Duct Static Pressure Active SetpointDuct Static Pressure Control Targetin. w.c.Read
AV20Duct Static PressureCurrent Duct Static Pressurein. w.c.Read
AV21Building Pressure Active SetpointBuilding Pressure Control Targetin. w.c.Read
AV22Building PressureCurrent Building Pressurein. w.c.Read
AV23Heating Stages ActiveTotal number of active Heat Stages, including modulating and fixed stagesRead
AV24Heating Modulation PercentHeat Modulation percent%Read
AV25Preheat Stages ActiveTotal number of active Preheat Stages, including modulating and fixed stagesRead
AV26Preheat Modulation PercentPreheat Modulation percent%Read
AV27Refrigeration Circuits ActiveNumber of Refrigeration Circuits currently activeRead
AV28Refrigeration Circuit A ModulationOverall percent of operation for the circuit%Read
AV29Refrigeration Circuit B ModulationOverall percent of operation for the circuit%Read
AV30Refrigeration Circuit C ModulationOverall percent of operation for the circuit; reserved for future use%Read
AV31Refrigeration Circuit D ModulationOverall percent of operation for the circuit; reserved for future use%Read
AV32Refrigeration Circuit E ModulationOverall percent of operation for the circuit; reserved for future use%Read
AV33Refrigeration Circuit F ModulationOverall percent of operation for the circuit; reserved for future use%Read
AV34Condenser Fan Bank 1 ModulationCondenser Fan Bank 1 modulation as a percentage from minimum to maximum%Read
AV35Condenser Fan Bank 2 ModulationCondenser Fan Bank 2 modulation as a percentage from minimum to maximum%Read
AV36Condenser Fan Bank 3 ModulationCondenser Fan Bank 3 modulation as a percentage from minimum to maximum; reserved for future use%Read
AV37Condenser Fan Bank 4 ModulationCondenser Fan Bank 4 modulation as a percentage from minimum to maximum; reserved for future use%Read
AV38Condenser Fan Bank 5 ModulationCondenser Fan Bank 5 modulation as a percentage from minimum to maximum; reserved for future use%Read
AV39Condenser Fan Bank 6 ModulationCondenser Fan Bank 6 modulation as a percentage from minimum to maximum; reserved for future use%Read
AV40Reheat PositionReheat Position, which is the same for all operating circuits having reheat%Read
AV41Occupied Cooling Active SetpointActive setpoint that may be used to trigger cooling operations°FRead
AV42Occupied Heating Active SetpointActive setpoint that may be used to trigger heating operations°FRead
AV43Unoccupied Cooling Active SetpointActive setpoint that may be used to trigger cooling operations°FRead
AV44Unoccupied Heating Active SetpointActive setpoint that may be used to trigger heating operations°FRead
AV45Active Supply Air Temperature SetpointSupply Air Temperature setpoint the unit is trying to maintain°FRead
AV46Measured Outdoor AirflowMeasured Outdoor airflowCFMRead
AV47Measured Supply AirflowMeasured Supply airflowCFMRead
AV48Measured Return AirflowMeasured Return airflowCFMRead
AV49Measured Exhaust AirflowMeasured Exhaust airflowCFMRead
AV50Indoor CO2Space CO2, or return CO2 if there is no space valueppmRead
AVmin10003Supply Air Setpoint OverrideSupply air setpoint override; write at least every 5 minutes; range 30°F to 140°F°FWrite
AVmin10004Occupied Heating SetpointOccupied Space Heating setpoint; range 0°F to 109°F°FWrite
AVmin10005Occupied Cooling SetpointOccupied Space Cooling setpoint; range 1°F to 110°F°FWrite
AV10006Unoccupied Heating SetpointUnoccupied Space Heating setpoint; range 35°F to 109°F°FWrite
AV10007Unoccupied Cooling SetpointUnoccupied Space Cooling setpoint; range 36°F to 110°F°FWrite
AV10008OA Damper Minimum PositionOutdoor Air damper minimum position during occupied operation; range 0% to 100%%Write
AV10009IAQ CO2 SetpointDesired CO2 level for IAQ operation; range 0 to 3000ppmWrite
BI1Schedule OccupiedCommanded occupied by the schedule; written by Schedule 2Read
BV3Supply Fan EnableFan run statusRead0=DISABLED, 1=RUNNING
BV4Return Fan EnableFan run statusRead0=DISABLED, 1=RUNNING
BV5Exhaust Fan EnableFan run statusRead0=DISABLED, 1=RUNNING
BV6Economizer EnableOA damper is in economizer controlRead0=DISABLED, 1=ENABLED
BV7Auxiliary Heat EnableAuxiliary heat is activeRead0=DISABLED, 1=ENABLED
BV8Emergency Heat EnableEmergency heat is activeRead0=DISABLED, 1=ENABLED
BV9Supply Fan Proof of AirflowSupply fan is moving airRead0=FALSE, 1=TRUE
BVmin16OccupiedOccupancy stateRead0=UNOCCUPIED, 1=OCCUPIED
BV17Dirty FilterTrue when the filter needs replacingRead0=FALSE, 1=TRUE
BV18Supply Air Temperature Sensor StatusFaulty sensor detectedRead0=FAILED, 1=GOOD
BV19Supply Air Humidity Sensor StatusFaulty sensor detectedRead0=FAILED, 1=GOOD
BV20Outdoor Air Temperature Sensor StatusFaulty sensor detectedRead0=FAILED, 1=GOOD
BV21Outdoor Air Humidity Sensor StatusFaulty sensor detectedRead0=FAILED, 1=GOOD
BV22Return Air Temperature Sensor StatusFaulty sensor detectedRead0=FAILED, 1=GOOD
BV23Return Air Humidity Sensor StatusFaulty sensor detectedRead0=FAILED, 1=GOOD
BV24Mixed Air Temperature Sensor StatusFaulty sensor detectedRead0=FAILED, 1=GOOD
BV25Mixed Air Humidity Sensor StatusFaulty sensor detectedRead0=FAILED, 1=GOOD
BV26Space Temperature Sensor StatusFaulty sensor detectedRead0=FAILED, 1=GOOD
BV27Space Humidity Sensor StatusFaulty sensor detectedRead0=FAILED, 1=GOOD
BV28OA Cooling LockoutToo cold outside for active coolingRead0=FALSE, 1=TRUE
BV29OA Heating LockoutToo hot outside for active heatingRead0=FALSE, 1=TRUE
BV30Low Supply Air Temperature FaultSupply air below low limit; unit shuts downRead0=FALSE, 1=TRUE
BV31High Supply Air Temperature FaultSupply air above high limit; unit shuts downRead0=FALSE, 1=TRUE
BV32Circuit 1 FaultGeneral fault stopping the circuitRead0=FALSE, 1=TRUE
BV33Circuit 2 FaultGeneral fault stopping the circuitRead0=FALSE, 1=TRUE
BV36A2L Airstream AlarmA2L leak detected; mitigation starts (fail-safe input)Read0=FALSE, 1=TRUE
BV37A2L Airstream AlarmA2L leak detected; mitigation starts (fail-safe input)Read0=FALSE, 1=TRUE
BV38Fire AlarmConfigured fire alarm input (fail-safe)Read0=FALSE, 1=TRUE
BV39Unit Smoke DetectorConfigured smoke detector input (fail-safe)Read0=FALSE, 1=TRUE
BV40Remote ShutdownConfigured remote shutdown input (fail-safe)Read0=FALSE, 1=TRUE
BV41Power Input Phase StatusInput phase sequence L1-L2-L3Read0=REVERSED, 1=TRUE
BV42Power Input Voltage StatusInput voltage wrong on a phase (phase brownout)Read0=FALSE, 1=TRUE
BVmin43Unit Cannot Run AlarmSomething is blocking unit operationRead0=FALSE, 1=TRUE
BV44Mechanical Cooling AlarmSomething is blocking mechanical coolingRead0=FALSE, 1=TRUE
BV45Mechanical Heating AlarmSomething is blocking mechanical heatingRead0=FALSE, 1=TRUE
BV46Title 24 Alarm AFault A, fault detection and diagnosticsRead0=FALSE, 1=TRUE
BV47Title 24 Alarm BFault B, fault detection and diagnosticsRead0=FALSE, 1=TRUE
BV48Title 24 Alarm CFault C, fault detection and diagnosticsRead0=FALSE, 1=TRUE
BV49Title 24 Alarm DFault D, fault detection and diagnosticsRead0=FALSE, 1=TRUE
BV50Title 24 Alarm EFault E, fault detection and diagnosticsRead0=FALSE, 1=TRUE
BV51Refrigeration Injection ActiveCold climate heat pump refrigerant injectionRead0=FALSE, 1=TRUE
BV52Defrost ActiveDefrost running on at least one circuitRead0=FALSE, 1=TRUE
BV10002Disabled Economizer OperationsInverted logic: true disables the economizerRead0=ENABLED, 1=DISABLED
MV1Application SequenceCurrent application sequenceReadExternal Supply Air Control, OA Control, Reserved, Return Temperature Control Standard, Space Temperature Control Precision, Space Temperature Control Standard, VAV Control (order as listed; numeric values not printed)
MVmin2HVAC Unit Operating ModeCurrent HVAC unit modeReadCool, Dehum, Heat, Off, Vent (order as listed; numeric values not printed)
MV3OccupancyCurrent occupancy statusReadForce Occupied, Forced Unoccupied, Occupied, Override Occupied, Remote Input Occupied, Unoccupied (order as listed; numeric values not printed)
MVmin10001Force OccupancyForces occupancy; mirrors UI and Workstation changesWriteAuto, Force Occupied, Force Unoccupied (order as listed; numeric values not printed)
SCH2Occupied ScheduleSchedule that controls the occupied stateWrite
Object ID lookup: AAON Stratus Unit Manager point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Stratus Unit Manager (Stratus controls) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AAON Stratus Unit Manager (Stratus controls)

How many BACnet points does the AAON Stratus Unit Manager (Stratus controls) have?

This list has 106 BACnet objects: 57 analog values, 1 binary input, 43 binary values, 1 schedule, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AAON Stratus Unit Manager (Stratus controls) BACnet points are writable?

9 of the 106 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AAON Stratus Unit Manager (Stratus controls) BACnet documentation?

The source is Stratus BACnet Points Guide (Rev. A), revision 2026-11, published free by AAON at https://www.aaon.com/hubfs/Controls%20Literature/Stratus%20BACnet%20Points%20Guide%20Rev.%20A.pdf.

What are the minimum BACnet points to integrate the AAON Stratus Unit Manager (Stratus controls)?

Start with MV 10001 Force Occupancy (Occupancy: auto, force occupied or unoccupied); AV 10005 Occupied Cooling Setpoint (Occupied cooling setpoint, °F); AV 10004 Occupied Heating Setpoint (Occupied heating setpoint, °F); AV 10003 Supply Air Setpoint Override (Supply air setpoint override; rewrite every 5 min); MV 2 HVAC Unit Operating Mode (Current HVAC mode); BV 16 Occupied (Occupied status); AV 1 Mode Based Controlled Temperature (Temperature of the controlled point); AV 2 Supply Air Temperature (Supply air temperature); BV 43 Unit Cannot Run Alarm (Something is blocking unit operation).

How do I enable BMS control of the AAON Stratus Unit Manager (Stratus controls)?

MV 10001 Force Occupancy (Auto, Force Occupied, Force Unoccupied) or the Occupied Schedule object (Schedule 2, which writes BI 1) set occupancy. BV 10002 can disable economizer operation (inverted logic).

Does the AAON Stratus Unit Manager (Stratus controls) need a BACnet heartbeat or have a communication timeout?

AV 10003 Supply Air Setpoint Override must be written at least every five minutes or it is treated as invalid and the normal control mode takes over the supply air setpoint.

How do I check these points on the real Stratus Unit Manager (Stratus controls)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AAON BACnet points lists