AAON Stratus Unit Manager (Stratus controls) BACnet points list
Updated 12 November 2026
Stratus is AAON's newest unit control platform; the Stratus Unit Manager connects to a BACnet MS/TP trunk or to Ethernet for BACnet IP. Its BACnet map is compact: 57 analog values (temperatures, humidity, airflow, fan and refrigeration modulation, active setpoints, plus writable setpoints at AV 10003-10009), 43 binary values for status, sensor and safety alarms, 4 multistate values for application, mode and occupancy, an occupancy schedule object and a schedule-driven binary input.
This page lists 106 BACnet objects for the AAON Stratus Unit Manager (Stratus controls) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.
- Manufacturer
- AAON
- Model
- Stratus Unit Manager (Stratus controls)
- Equipment
- Rooftop unit / air handler controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 106 (9 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Stratus software 1.3.3
- Also known as
- Stratus, AAON Stratus, Stratus Unit Manager, Stratus BACnet Points Guide, Stratus controller, Stratus Series
- Source document
- Stratus BACnet Points Guide · Rev. A · rev. 2026-11
Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.
BMS integration notes: AAON Stratus Unit Manager (Stratus controls)
Connect the Unit Manager to MS/TP or Ethernet (BACnet IP) and set the baud rate, MAC address and a unique device ID (and BBMD for IP) in Unit Settings. The BAS forces occupancy with MV 10001 or writes the Occupied Schedule, adjusts the occupied and unoccupied setpoints at AV 10004-10007 and can override the supply air setpoint with AV 10003. Read the mode, occupancy and alarm BVs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 10001 | Force Occupancy | Occupancy: auto, force occupied or unoccupied | Write |
| AV 10005 | Occupied Cooling Setpoint | Occupied cooling setpoint, °F | Write |
| AV 10004 | Occupied Heating Setpoint | Occupied heating setpoint, °F | Write |
| AV 10003 | Supply Air Setpoint Override | Supply air setpoint override; rewrite every 5 min | Write |
| MV 2 | HVAC Unit Operating Mode | Current HVAC mode | Read |
| BV 16 | Occupied | Occupied status | Read |
| AV 1 | Mode Based Controlled Temperature | Temperature of the controlled point | Read |
| AV 2 | Supply Air Temperature | Supply air temperature | Read |
| BV 43 | Unit Cannot Run Alarm | Something is blocking unit operation | Read |
Enable & remote start
MV 10001 Force Occupancy (Auto, Force Occupied, Force Unoccupied) or the Occupied Schedule object (Schedule 2, which writes BI 1) set occupancy. BV 10002 can disable economizer operation (inverted logic).
Heartbeat & communication loss
AV 10003 Supply Air Setpoint Override must be written at least every five minutes or it is treated as invalid and the normal control mode takes over the supply air setpoint.
Network setup
- MS/TP: set baud rate, MAC address (masters 0-127) and a unique device ID in Unit Settings; all devices on the trunk need the same baud.
- BACnet IP over the Ethernet port: set the BBMD/network and device ID.
Watch out for
- Writing a low value to AV 10003 disables the override; the footnote says below 40°F and the notes column says below 32°F.
- Setpoints at AV 10004-10009 are shared with the Unit Manager screen, so local changes overwrite BAS values and vice versa.
AAON Stratus Unit Manager (Stratus controls) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | Mode Based Controlled Temperature | Current temperature for the controlled point | °F | Read | |
| AVmin | 2 | Supply Air Temperature | Functional Supply Air temperature | °F | Read | |
| AV | 3 | Supply Air Dewpoint | Functional Supply Air dew point | % | Read | |
| AV | 4 | Outdoor Air Temperature | Functional Outdoor Air temperature | °F | Read | |
| AV | 5 | Outdoor Air Relative Humidity | Functional Outdoor Air Relative Humidity | % | Read | |
| AV | 6 | Outdoor Air Wetbulb | Functional Outdoor Air wet-bulb temperature | °F | Read | |
| AV | 7 | Outdoor Air Dewpoint | Functional Outdoor Air dew point | °F | Read | |
| AV | 8 | Return Air Temperature | Functional Return Air temperature | °F | Read | |
| AV | 9 | Return Air Relative Humidity | Functional Return Air relative humidity | % | Read | |
| AV | 10 | Mixed Air Temperature | Functional Mixed Air temperature | °F | Read | |
| AV | 11 | Mixed Air Relative Humidity | Functional Mixed Air relative humidity | % | Read | |
| AV | 12 | Space Temperature | Functional Space Temperature | °F | Read | |
| AV | 13 | Space Relative Humidity | Functional Space Relative Humidity | % | Read | |
| AV | 14 | Commanded OA Damper Position | Position the Outdoor Air damper should be in | % | Read | |
| AV | 15 | OA Damper Position | Current Outdoor Air damper position | % | Read | |
| AV | 16 | Supply Fan Speed | Current Supply Fan Speed as a percentage from the minimum speed | % | Read | |
| AV | 17 | Return Fan Speed | Current Return Fan Speed as a percentage from the minimum speed | % | Read | |
| AV | 18 | Exhaust Fan Speed | Current Exhaust Fan Speed as a percentage from the minimum speed | % | Read | |
| AV | 19 | Duct Static Pressure Active Setpoint | Duct Static Pressure Control Target | in. w.c. | Read | |
| AV | 20 | Duct Static Pressure | Current Duct Static Pressure | in. w.c. | Read | |
| AV | 21 | Building Pressure Active Setpoint | Building Pressure Control Target | in. w.c. | Read | |
| AV | 22 | Building Pressure | Current Building Pressure | in. w.c. | Read | |
| AV | 23 | Heating Stages Active | Total number of active Heat Stages, including modulating and fixed stages | Read | ||
| AV | 24 | Heating Modulation Percent | Heat Modulation percent | % | Read | |
| AV | 25 | Preheat Stages Active | Total number of active Preheat Stages, including modulating and fixed stages | Read | ||
| AV | 26 | Preheat Modulation Percent | Preheat Modulation percent | % | Read | |
| AV | 27 | Refrigeration Circuits Active | Number of Refrigeration Circuits currently active | Read | ||
| AV | 28 | Refrigeration Circuit A Modulation | Overall percent of operation for the circuit | % | Read | |
| AV | 29 | Refrigeration Circuit B Modulation | Overall percent of operation for the circuit | % | Read | |
| AV | 30 | Refrigeration Circuit C Modulation | Overall percent of operation for the circuit; reserved for future use | % | Read | |
| AV | 31 | Refrigeration Circuit D Modulation | Overall percent of operation for the circuit; reserved for future use | % | Read | |
| AV | 32 | Refrigeration Circuit E Modulation | Overall percent of operation for the circuit; reserved for future use | % | Read | |
| AV | 33 | Refrigeration Circuit F Modulation | Overall percent of operation for the circuit; reserved for future use | % | Read | |
| AV | 34 | Condenser Fan Bank 1 Modulation | Condenser Fan Bank 1 modulation as a percentage from minimum to maximum | % | Read | |
| AV | 35 | Condenser Fan Bank 2 Modulation | Condenser Fan Bank 2 modulation as a percentage from minimum to maximum | % | Read | |
| AV | 36 | Condenser Fan Bank 3 Modulation | Condenser Fan Bank 3 modulation as a percentage from minimum to maximum; reserved for future use | % | Read | |
| AV | 37 | Condenser Fan Bank 4 Modulation | Condenser Fan Bank 4 modulation as a percentage from minimum to maximum; reserved for future use | % | Read | |
| AV | 38 | Condenser Fan Bank 5 Modulation | Condenser Fan Bank 5 modulation as a percentage from minimum to maximum; reserved for future use | % | Read | |
| AV | 39 | Condenser Fan Bank 6 Modulation | Condenser Fan Bank 6 modulation as a percentage from minimum to maximum; reserved for future use | % | Read | |
| AV | 40 | Reheat Position | Reheat Position, which is the same for all operating circuits having reheat | % | Read | |
| AV | 41 | Occupied Cooling Active Setpoint | Active setpoint that may be used to trigger cooling operations | °F | Read | |
| AV | 42 | Occupied Heating Active Setpoint | Active setpoint that may be used to trigger heating operations | °F | Read | |
| AV | 43 | Unoccupied Cooling Active Setpoint | Active setpoint that may be used to trigger cooling operations | °F | Read | |
| AV | 44 | Unoccupied Heating Active Setpoint | Active setpoint that may be used to trigger heating operations | °F | Read | |
| AV | 45 | Active Supply Air Temperature Setpoint | Supply Air Temperature setpoint the unit is trying to maintain | °F | Read | |
| AV | 46 | Measured Outdoor Airflow | Measured Outdoor airflow | CFM | Read | |
| AV | 47 | Measured Supply Airflow | Measured Supply airflow | CFM | Read | |
| AV | 48 | Measured Return Airflow | Measured Return airflow | CFM | Read | |
| AV | 49 | Measured Exhaust Airflow | Measured Exhaust airflow | CFM | Read | |
| AV | 50 | Indoor CO2 | Space CO2, or return CO2 if there is no space value | ppm | Read | |
| AVmin | 10003 | Supply Air Setpoint Override | Supply air setpoint override; write at least every 5 minutes; range 30°F to 140°F | °F | Write | |
| AVmin | 10004 | Occupied Heating Setpoint | Occupied Space Heating setpoint; range 0°F to 109°F | °F | Write | |
| AVmin | 10005 | Occupied Cooling Setpoint | Occupied Space Cooling setpoint; range 1°F to 110°F | °F | Write | |
| AV | 10006 | Unoccupied Heating Setpoint | Unoccupied Space Heating setpoint; range 35°F to 109°F | °F | Write | |
| AV | 10007 | Unoccupied Cooling Setpoint | Unoccupied Space Cooling setpoint; range 36°F to 110°F | °F | Write | |
| AV | 10008 | OA Damper Minimum Position | Outdoor Air damper minimum position during occupied operation; range 0% to 100% | % | Write | |
| AV | 10009 | IAQ CO2 Setpoint | Desired CO2 level for IAQ operation; range 0 to 3000 | ppm | Write | |
| BI | 1 | Schedule Occupied | Commanded occupied by the schedule; written by Schedule 2 | Read | ||
| BV | 3 | Supply Fan Enable | Fan run status | Read | 0=DISABLED, 1=RUNNING | |
| BV | 4 | Return Fan Enable | Fan run status | Read | 0=DISABLED, 1=RUNNING | |
| BV | 5 | Exhaust Fan Enable | Fan run status | Read | 0=DISABLED, 1=RUNNING | |
| BV | 6 | Economizer Enable | OA damper is in economizer control | Read | 0=DISABLED, 1=ENABLED | |
| BV | 7 | Auxiliary Heat Enable | Auxiliary heat is active | Read | 0=DISABLED, 1=ENABLED | |
| BV | 8 | Emergency Heat Enable | Emergency heat is active | Read | 0=DISABLED, 1=ENABLED | |
| BV | 9 | Supply Fan Proof of Airflow | Supply fan is moving air | Read | 0=FALSE, 1=TRUE | |
| BVmin | 16 | Occupied | Occupancy state | Read | 0=UNOCCUPIED, 1=OCCUPIED | |
| BV | 17 | Dirty Filter | True when the filter needs replacing | Read | 0=FALSE, 1=TRUE | |
| BV | 18 | Supply Air Temperature Sensor Status | Faulty sensor detected | Read | 0=FAILED, 1=GOOD | |
| BV | 19 | Supply Air Humidity Sensor Status | Faulty sensor detected | Read | 0=FAILED, 1=GOOD | |
| BV | 20 | Outdoor Air Temperature Sensor Status | Faulty sensor detected | Read | 0=FAILED, 1=GOOD | |
| BV | 21 | Outdoor Air Humidity Sensor Status | Faulty sensor detected | Read | 0=FAILED, 1=GOOD | |
| BV | 22 | Return Air Temperature Sensor Status | Faulty sensor detected | Read | 0=FAILED, 1=GOOD | |
| BV | 23 | Return Air Humidity Sensor Status | Faulty sensor detected | Read | 0=FAILED, 1=GOOD | |
| BV | 24 | Mixed Air Temperature Sensor Status | Faulty sensor detected | Read | 0=FAILED, 1=GOOD | |
| BV | 25 | Mixed Air Humidity Sensor Status | Faulty sensor detected | Read | 0=FAILED, 1=GOOD | |
| BV | 26 | Space Temperature Sensor Status | Faulty sensor detected | Read | 0=FAILED, 1=GOOD | |
| BV | 27 | Space Humidity Sensor Status | Faulty sensor detected | Read | 0=FAILED, 1=GOOD | |
| BV | 28 | OA Cooling Lockout | Too cold outside for active cooling | Read | 0=FALSE, 1=TRUE | |
| BV | 29 | OA Heating Lockout | Too hot outside for active heating | Read | 0=FALSE, 1=TRUE | |
| BV | 30 | Low Supply Air Temperature Fault | Supply air below low limit; unit shuts down | Read | 0=FALSE, 1=TRUE | |
| BV | 31 | High Supply Air Temperature Fault | Supply air above high limit; unit shuts down | Read | 0=FALSE, 1=TRUE | |
| BV | 32 | Circuit 1 Fault | General fault stopping the circuit | Read | 0=FALSE, 1=TRUE | |
| BV | 33 | Circuit 2 Fault | General fault stopping the circuit | Read | 0=FALSE, 1=TRUE | |
| BV | 36 | A2L Airstream Alarm | A2L leak detected; mitigation starts (fail-safe input) | Read | 0=FALSE, 1=TRUE | |
| BV | 37 | A2L Airstream Alarm | A2L leak detected; mitigation starts (fail-safe input) | Read | 0=FALSE, 1=TRUE | |
| BV | 38 | Fire Alarm | Configured fire alarm input (fail-safe) | Read | 0=FALSE, 1=TRUE | |
| BV | 39 | Unit Smoke Detector | Configured smoke detector input (fail-safe) | Read | 0=FALSE, 1=TRUE | |
| BV | 40 | Remote Shutdown | Configured remote shutdown input (fail-safe) | Read | 0=FALSE, 1=TRUE | |
| BV | 41 | Power Input Phase Status | Input phase sequence L1-L2-L3 | Read | 0=REVERSED, 1=TRUE | |
| BV | 42 | Power Input Voltage Status | Input voltage wrong on a phase (phase brownout) | Read | 0=FALSE, 1=TRUE | |
| BVmin | 43 | Unit Cannot Run Alarm | Something is blocking unit operation | Read | 0=FALSE, 1=TRUE | |
| BV | 44 | Mechanical Cooling Alarm | Something is blocking mechanical cooling | Read | 0=FALSE, 1=TRUE | |
| BV | 45 | Mechanical Heating Alarm | Something is blocking mechanical heating | Read | 0=FALSE, 1=TRUE | |
| BV | 46 | Title 24 Alarm A | Fault A, fault detection and diagnostics | Read | 0=FALSE, 1=TRUE | |
| BV | 47 | Title 24 Alarm B | Fault B, fault detection and diagnostics | Read | 0=FALSE, 1=TRUE | |
| BV | 48 | Title 24 Alarm C | Fault C, fault detection and diagnostics | Read | 0=FALSE, 1=TRUE | |
| BV | 49 | Title 24 Alarm D | Fault D, fault detection and diagnostics | Read | 0=FALSE, 1=TRUE | |
| BV | 50 | Title 24 Alarm E | Fault E, fault detection and diagnostics | Read | 0=FALSE, 1=TRUE | |
| BV | 51 | Refrigeration Injection Active | Cold climate heat pump refrigerant injection | Read | 0=FALSE, 1=TRUE | |
| BV | 52 | Defrost Active | Defrost running on at least one circuit | Read | 0=FALSE, 1=TRUE | |
| BV | 10002 | Disabled Economizer Operations | Inverted logic: true disables the economizer | Read | 0=ENABLED, 1=DISABLED | |
| MV | 1 | Application Sequence | Current application sequence | Read | External Supply Air Control, OA Control, Reserved, Return Temperature Control Standard, Space Temperature Control Precision, Space Temperature Control Standard, VAV Control (order as listed; numeric values not printed) | |
| MVmin | 2 | HVAC Unit Operating Mode | Current HVAC unit mode | Read | Cool, Dehum, Heat, Off, Vent (order as listed; numeric values not printed) | |
| MV | 3 | Occupancy | Current occupancy status | Read | Force Occupied, Forced Unoccupied, Occupied, Override Occupied, Remote Input Occupied, Unoccupied (order as listed; numeric values not printed) | |
| MVmin | 10001 | Force Occupancy | Forces occupancy; mirrors UI and Workstation changes | Write | Auto, Force Occupied, Force Unoccupied (order as listed; numeric values not printed) | |
| SCH | 2 | Occupied Schedule | Schedule that controls the occupied state | Write |
No points match these filters.
Object ID lookup: AAON Stratus Unit Manager point IDs by name
AV1Mode Based Controlled TemperatureAV2Supply Air TemperatureAV3Supply Air DewpointAV4Outdoor Air TemperatureAV5Outdoor Air Relative HumidityAV6Outdoor Air WetbulbAV7Outdoor Air DewpointAV8Return Air TemperatureAV9Return Air Relative HumidityAV10Mixed Air TemperatureAV11Mixed Air Relative HumidityAV12Space TemperatureAV13Space Relative HumidityAV14Commanded OA Damper PositionAV15OA Damper PositionAV16Supply Fan SpeedAV17Return Fan SpeedAV18Exhaust Fan SpeedAV19Duct Static Pressure Active SetpointAV20Duct Static PressureAV21Building Pressure Active SetpointAV22Building PressureAV23Heating Stages ActiveAV24Heating Modulation PercentAV25Preheat Stages ActiveAV26Preheat Modulation PercentAV27Refrigeration Circuits ActiveAV28Refrigeration Circuit A ModulationAV29Refrigeration Circuit B ModulationAV30Refrigeration Circuit C ModulationAV31Refrigeration Circuit D ModulationAV32Refrigeration Circuit E ModulationAV33Refrigeration Circuit F ModulationAV34Condenser Fan Bank 1 ModulationAV35Condenser Fan Bank 2 ModulationAV36Condenser Fan Bank 3 ModulationAV37Condenser Fan Bank 4 ModulationAV38Condenser Fan Bank 5 ModulationAV39Condenser Fan Bank 6 ModulationAV40Reheat PositionAV41Occupied Cooling Active SetpointAV42Occupied Heating Active SetpointAV43Unoccupied Cooling Active SetpointAV44Unoccupied Heating Active SetpointAV45Active Supply Air Temperature SetpointAV46Measured Outdoor AirflowAV47Measured Supply AirflowAV48Measured Return AirflowAV49Measured Exhaust AirflowAV50Indoor CO2AV10003Supply Air Setpoint OverrideAV10004Occupied Heating SetpointAV10005Occupied Cooling SetpointAV10006Unoccupied Heating SetpointAV10007Unoccupied Cooling SetpointAV10008OA Damper Minimum PositionAV10009IAQ CO2 SetpointBI1Schedule OccupiedBV3Supply Fan EnableBV4Return Fan EnableBV5Exhaust Fan EnableBV6Economizer EnableBV7Auxiliary Heat EnableBV8Emergency Heat EnableBV9Supply Fan Proof of AirflowBV16OccupiedBV17Dirty FilterBV18Supply Air Temperature Sensor StatusBV19Supply Air Humidity Sensor StatusBV20Outdoor Air Temperature Sensor StatusBV21Outdoor Air Humidity Sensor StatusBV22Return Air Temperature Sensor StatusBV23Return Air Humidity Sensor StatusBV24Mixed Air Temperature Sensor StatusBV25Mixed Air Humidity Sensor StatusBV26Space Temperature Sensor StatusBV27Space Humidity Sensor StatusBV28OA Cooling LockoutBV29OA Heating LockoutBV30Low Supply Air Temperature FaultBV31High Supply Air Temperature FaultBV32Circuit 1 FaultBV33Circuit 2 FaultBV36A2L Airstream AlarmBV37A2L Airstream AlarmBV38Fire AlarmBV39Unit Smoke DetectorBV40Remote ShutdownBV41Power Input Phase StatusBV42Power Input Voltage StatusBV43Unit Cannot Run AlarmBV44Mechanical Cooling AlarmBV45Mechanical Heating AlarmBV46Title 24 Alarm ABV47Title 24 Alarm BBV48Title 24 Alarm CBV49Title 24 Alarm DBV50Title 24 Alarm EBV51Refrigeration Injection ActiveBV52Defrost ActiveBV10002Disabled Economizer OperationsMV1Application SequenceMV2HVAC Unit Operating ModeMV3OccupancyMV10001Force OccupancySCH2Occupied Schedule
Integration notes
- Access is from the guide's R/W column. All analog values below 10000 are read-only; AV 10003-10009 and MV 10001 are writable. BV 10002 is listed as RO although it is described as a command.
- Section 2 is titled Binary Values but its table caption says Binary Inputs; the objects are listed here as BV.
- Multistate state lists are printed without numbers; they are given in the printed order.
- AV 30-33 and AV 36-39 are reserved for future use (the unit currently supports two circuits and two condenser fan banks). AV 3 Supply Air Dewpoint is printed with % units.
- AV 10004-10009 are shared with the Unit Manager setpoints; a change in either place shows in both.
- Source: Stratus BACnet Points Guide Rev. A (software 1.3.3), pages 1-10.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Stratus Unit Manager (Stratus controls) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the AAON Stratus Unit Manager (Stratus controls)
How many BACnet points does the AAON Stratus Unit Manager (Stratus controls) have?
This list has 106 BACnet objects: 57 analog values, 1 binary input, 43 binary values, 1 schedule, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which AAON Stratus Unit Manager (Stratus controls) BACnet points are writable?
9 of the 106 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official AAON Stratus Unit Manager (Stratus controls) BACnet documentation?
The source is Stratus BACnet Points Guide (Rev. A), revision 2026-11, published free by AAON at https://www.aaon.com/hubfs/Controls%20Literature/Stratus%20BACnet%20Points%20Guide%20Rev.%20A.pdf.
What are the minimum BACnet points to integrate the AAON Stratus Unit Manager (Stratus controls)?
Start with MV 10001 Force Occupancy (Occupancy: auto, force occupied or unoccupied); AV 10005 Occupied Cooling Setpoint (Occupied cooling setpoint, °F); AV 10004 Occupied Heating Setpoint (Occupied heating setpoint, °F); AV 10003 Supply Air Setpoint Override (Supply air setpoint override; rewrite every 5 min); MV 2 HVAC Unit Operating Mode (Current HVAC mode); BV 16 Occupied (Occupied status); AV 1 Mode Based Controlled Temperature (Temperature of the controlled point); AV 2 Supply Air Temperature (Supply air temperature); BV 43 Unit Cannot Run Alarm (Something is blocking unit operation).
How do I enable BMS control of the AAON Stratus Unit Manager (Stratus controls)?
MV 10001 Force Occupancy (Auto, Force Occupied, Force Unoccupied) or the Occupied Schedule object (Schedule 2, which writes BI 1) set occupancy. BV 10002 can disable economizer operation (inverted logic).
Does the AAON Stratus Unit Manager (Stratus controls) need a BACnet heartbeat or have a communication timeout?
AV 10003 Supply Air Setpoint Override must be written at least every five minutes or it is treated as invalid and the normal control mode takes over the supply air setpoint.
How do I check these points on the real Stratus Unit Manager (Stratus controls)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More AAON BACnet points lists
- Rooftop unit / air handler controller
AAON Touchscreen Controller
AAON packaged units fitted with the AAON Touchscreen unit controller.
Also known as: AAON Touchscreen, Touch Screen Controller, AAON TS controller - Rooftop unit controller (zoning)
AAON Auto-Zone 3 (AZ 3) Controller
AAON packaged units run by the Auto-Zone 3 controller, alone or with AZ 3 VAV/zone dampers.
Also known as: AZ 3, AZ3, Auto-Zone 3, AAON AZ3, G071000, SS8014, SS8015, Orion AZ3 - General-purpose BACnet I/O controller
AAON BACnet General Controller (BGC)
AAON BGC general-purpose controller with 8 analog inputs, 8 binary inputs, 8 relays and 4 analog outputs.
Also known as: AAON BGC, BGC Controller, AAON BACnet General Controller, G042460, AAON general purpose I/O controller - DX chiller controller
AAON DX Chiller Controller
AAON packaged DX chillers (non-Turbocor compressors) with the Main DX Chiller Controller, refrigerant modules and optional waterside economizer and evaporative condenser modules.
Also known as: AAON DX Chiller Controller, Main DX Chiller Controller, G054280, SS1149, AAON DX chiller BACnet - DX chiller controller
AAON LF Chiller Controller
AAON LF series one- or two-circuit DX chillers with the LF Chiller Main Controller, optional pumping package and waterside economizer.
Also known as: AAON LF Chiller, LF Chiller Main Controller, G059100, SS1131, DT005683-001, LF chiller BACnet - DX chiller controller
AAON Main DX Barrel Chiller Controller
AAON DX barrel chillers with the Main DX Barrel Chiller Controller, up to two barrels and three refrigerant circuits per barrel, with optional pumping, WSE, evaporative condenser and vestibule modules.
Also known as: AAON DX Barrel Chiller, Main DX Barrel Chiller Controller, G070300, SS1140, DX barrel chiller BACnet - Air handler preheat controller
AAON PREHEAT-X Controller
AAON PREHEAT-X controllers that stage and modulate electric (SCR/SSR) preheat on AAON units and air handlers.
Also known as: PREHEAT-X, PREHEATX, Preheat-X, G086640, AAON preheat controller, Orion PREHEAT-X - Rooftop unit / air handler controller (gateway)
AAON SA Controller (via PT-Link II BACnet gateway)
AAON units with the SA (single-zone) controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: SA controller, AAON SA, PT-Link II, PT-Link BACnet5, G114680 - VAV / zone controller
AAON VAV/Zone BACnet Controller (VAVZB)
Pressure-independent and pressure-dependent VAV boxes and zone dampers controlled by the AAON VAV/Zone BACnet controller.
Also known as: VAVZB, VAV/Zone Controller, ASM02426, ASM02427, ASM02661, ASM02662, SS1116, SS1146, G067750 - Rooftop unit / air handler controller
AAON VCB-X Controller
AAON packaged rooftop units, air handlers, DOAS and water-source units controlled by the Orion VCB-X (OE335-26B-VCBX) unit controller.
Also known as: VCBX, VCB-X, Orion VCB-X, OE335-26B-VCBX, V28940, WattMaster VCB-X, AAON VCB-X BACnet - Rooftop unit / air handler controller
AAON VCCX-454 Controller
AAON rooftop units, air handlers, DOAS and self-contained units built for R-454B and controlled by the VCCX-454 unit controller with RM454 refrigerant modules.
Also known as: VCCX-454, VCCX 454, ASM07503, SS1188, AAON VCCX-454 controller, R-454B unit controller - Rooftop unit / air handler controller
AAON VCCX-454-GH Controller (grow house)
AAON R-454B units for indoor agriculture (grow rooms) controlled by the VCCX-454-GH controller.
Also known as: VCCX-454-GH, VCCX454-GH, ASM07792, SS1207, AAON grow house controller, indoor agriculture HVAC controller - Rooftop unit / air handler controller
AAON VCCX2 Controller
AAON rooftop units, air handlers and DOAS units controlled by the VCCX2 (ASM01698) unit controller.
Also known as: VCC-X2, VCCX, VCC-X, ASM01698, Orion VCCX2, SS1088 - Rooftop unit / air handler controller (gateway)
AAON VCM Controller (legacy, via PT-Link II BACnet gateway)
Older AAON units with the legacy VCM controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: VCM, AAON VCM, PT-Link II, PT-Link BACnet5, G114680 - Rooftop unit / air handler controller (gateway)
AAON VCM-X Controller (via PT-Link II BACnet gateway)
AAON rooftop units, air handlers and other equipment with the VCM-X controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: VCM-X, VCMX, PT-Link II, PT-Link BACnet5, G114680
Source: Stratus BACnet Points Guide · Rev. A · rev. 2026-11. Object names, instances and units are reproduced as published; descriptions are our own.