DX chiller controller · BACnet points list
AAON Main DX Barrel Chiller Controller BACnet points list
Updated 12 November 2026
The Main DX Barrel Chiller Controller runs AAON DX chillers built with one or two barrel evaporators and has an on-board BACnet MS/TP port. The object map has 140 read-only analog inputs (water temperatures, pumping, WSE, evaporative condenser and per-circuit refrigerant data), 60 analog values (setpoints, calibration offsets, run command, relay and analog output overrides), 323 read-only binary inputs for status, faults, warnings and lockouts per circuit, and a multistate input for the unit mode.
This page lists 524 BACnet objects for the AAON Main DX Barrel Chiller Controller — 60 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.
- Manufacturer
- AAON
- Model
- Main DX Barrel Chiller Controller
- Equipment
- DX chiller controller
- Equipment type
- Chillers
- BACnet objects
- 524 (60 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- AAON DX Barrel Chiller, G070300, SS1140, DX barrel chiller BACnet
Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.
BMS integration notes: AAON Main DX Barrel Chiller Controller
Connect the on-board MS/TP port and set MAC address, device ID and baud on the LCD. The BAS runs the chiller with AV 81 Auto/Run/Off and reads the unit mode, leaving water temperature and alarm status. Leaving water reset limits are AV 1 and AV 2.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 81 | Auto/Run/Off Command | Chiller command: 0 auto, 1 run, 2 off | Write |
| AV 80 | Reset Unit Lockout { 1 = Reset } | Write 1 to reset a unit lockout | Write |
| MI 1 | Operating Status | Current unit mode | Read |
| BI 8 | Chiller Running On/Off Status | Chiller running | Read |
| AI 4 | Leaving Water Setpoint | Leaving water setpoint in use | Read |
| AI 2 | Entering Water Temperature | Entering water temperature | Read |
| AI 3 | Leaving Water Temperature | Leaving water temperature | Read |
| BI 2 | Proof of Water Flow #1 | Proof of water flow, barrel 1 | Read |
| BI 4 | Emergency Shutdown | Emergency shutdown input | Read |
Enable & remote start
AV 81 Auto/Run/Off Command (0 = Auto, 1 = Run, 2 = Off) runs the chiller from the BAS; BI 1 shows the Run/Stop input and BI 6/7 the barrel disable commands. AV 80 resets a unit lockout.
Network setup
- MAC address, device ID (up to seven digits) and MS/TP baud rate are set on the controller's LCD BACnet screens.
Watch out for
- AV 82-91 switch main board relays and set analog output voltages directly; leave them alone unless the BAS is meant to drive those outputs.
AAON Main DX Barrel Chiller Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Application Version | Read | |||
| AImin | 2 | Entering Water Temperature | Read | |||
| AImin | 3 | Leaving Water Temperature | Read | |||
| AImin | 4 | Leaving Water Setpoint | Read | |||
| AI | 5 | Barrel #1 Leaving Water Temperature | Read | |||
| AI | 6 | Barrel #2 Leaving Water Temperature | Read | |||
| AI | 7 | Barrel Leaving Water Setpoint | Read | |||
| AI | 8 | Outdoor Air Temperature | Read | |||
| AI | 9 | Flow Rate | Read | |||
| AI | 10 | Vestibule #1 Temperature | Read | |||
| AI | 11 | Vestibule #2 Temperature | Read | |||
| AI | 20 | Building Pump Suction Pressure | Read | |||
| AI | 21 | Building Pump Discharge Pressure | Read | |||
| AI | 22 | Building Pump Differential Pressure | Read | |||
| AI | 23 | Building Pump VFD Signal | Read | |||
| AI | 24 | Building Pump Bypass Valve Position | Read | |||
| AI | 30 | Waterside Economizer Primary 3-Way Valve | Read | |||
| AI | 31 | Waterside Economizer Secondary 3-Way Valve | Read | |||
| AI | 32 | Waterside Economizer Heat Exchanger Waterside Outlet | Read | |||
| AI | 33 | Waterside Economizer Heat Exchanger Glycol Side Outlet | Read | |||
| AI | 34 | Waterside Economizer Heat Exchanger Glycol Side Inlet | Read | |||
| AI | 35 | Waterside Economizer Primary Valve Outlet Temperature | Read | |||
| AI | 36 | Waterside Economizer Fan Speed | Read | |||
| AI | 40 | EVAP Sump Temperature #1 | Read | |||
| AI | 41 | EVAP Sump Temperature #2 | Read | |||
| AI | 42 | EVAP Sump Temperature #3 | Read | |||
| AI | 43 | EVAP Pump #1 Amps | Read | |||
| AI | 44 | EVAP Pump #2 Amps | Read | |||
| AI | 45 | EVAP Pump #1 VFD Signal | Read | |||
| AI | 46 | EVAP Pump #2 VFD Signal | Read | |||
| AI | 50 | Superheat Setpoint | Read | |||
| AI | 51 | Head Pressure Setpoint | Read | |||
| AI | 60 | B1:C1 Suction Pressure | Read | |||
| AI | 61 | B1:C1 Discharge Pressure | Read | |||
| AI | 62 | B1:C1 Liquid Line Pressure | Read | |||
| AI | 63 | B1:C1 Calculated Saturation Temp | Read | |||
| AI | 64 | B1:C1 Calculated Discharge Temp | Read | |||
| AI | 65 | B1:C1 Calculated Liquid Line Temp | Read | |||
| AI | 66 | B1:C1 Suction Line Temp | Read | |||
| AI | 67 | B1:C1 Discharge Line Temp | Read | |||
| AI | 68 | B1:C1 Liquid Line Temp | Read | |||
| AI | 69 | B1:C1 Superheat Temp | Read | |||
| AI | 70 | B1:C1 Discharge Superheat Temp | Read | |||
| AI | 71 | B1:C1 Sub-cooling Temp | Read | |||
| AI | 72 | B1:C1 Compressor A1 Percentage | Read | |||
| AI | 73 | B1:C1 Compressor A2 Percentage | Read | |||
| AI | 74 | B1:C1 Condenser Percentage | Read | |||
| AI | 75 | B1:C1 Electronic Expansion Valve Position | Read | |||
| AI | 76 | B1:C1 Compressor 1 Current | Read | |||
| AI | 77 | B1:C1 Compressor 2 Current | Read | |||
| AI | 90 | B2:C1 Suction Pressure | Read | |||
| AI | 91 | B2:C1 Discharge Pressure | Read | |||
| AI | 92 | B2:C1 Liquid Line Pressure | Read | |||
| AI | 93 | B2:C1 Calculated Saturation Temp | Read | |||
| AI | 94 | B2:C1 Calculated Discharge Temp | Read | |||
| AI | 95 | B2:C1 Calculated Liquid Line Temp | Read | |||
| AI | 96 | B2:C1 Suction Line Temp | Read | |||
| AI | 97 | B2:C1 Discharge Line Temp | Read | |||
| AI | 98 | B2:C1 Liquid Line Temp | Read | |||
| AI | 99 | B2:C1 Superheat Temp | Read | |||
| AI | 100 | B2:C1 Discharge Superheat Temp | Read | |||
| AI | 101 | B2:C1 Sub-cooling Temp | Read | |||
| AI | 102 | B2:C1 Compressor A1 Percentage | Read | |||
| AI | 103 | B2:C1 Compressor A2 Percentage | Read | |||
| AI | 104 | B2:C1 Condenser Percentage | Read | |||
| AI | 105 | B2:C1 Electronic Expansion Valve Position | Read | |||
| AI | 106 | B2:C1 Compressor 1 Current | Read | |||
| AI | 107 | B2:C1 Compressor 2 Current | Read | |||
| AI | 120 | B1:C2 Suction Pressure | Read | |||
| AI | 121 | B1:C2 Discharge Pressure | Read | |||
| AI | 122 | B1:C2 Liquid Line Pressure | Read | |||
| AI | 123 | B1:C2 Calculated Saturation Temp | Read | |||
| AI | 124 | B1:C2 Calculated Discharge Temp | Read | |||
| AI | 125 | B1:C2 Calculated Liquid Line Temp | Read | |||
| AI | 126 | B1:C2 Suction Line Temp | Read | |||
| AI | 127 | B1:C2 Discharge Line Temp | Read | |||
| AI | 128 | B1:C2 Liquid Line Temp | Read | |||
| AI | 129 | B1:C2 Superheat Temp | Read | |||
| AI | 130 | B1:C2 Discharge Superheat Temp | Read | |||
| AI | 131 | B1:C2 Sub-cooling Temp | Read | |||
| AI | 132 | B1:C2 Compressor A1 Percentage | Read | |||
| AI | 133 | B1:C2 Compressor A2 Percentage | Read | |||
| AI | 134 | B1:C2 Condenser Percentage | Read | |||
| AI | 135 | B1:C2 Electronic Expansion Valve Position | Read | |||
| AI | 136 | B1:C2 Compressor 1 Current | Read | |||
| AI | 137 | B1:C2 Compressor 2 Current | Read | |||
| AI | 150 | B2:C2 Suction Pressure | Read | |||
| AI | 151 | B2:C2 Discharge Pressure | Read | |||
| AI | 152 | B2:C2 Liquid Line Pressure | Read | |||
| AI | 153 | B2:C2 Calculated Saturation Temp | Read | |||
| AI | 154 | B2:C2 Calculated Discharge Temp | Read | |||
| AI | 155 | B2:C2 Calculated Liquid Line Temp | Read | |||
| AI | 156 | B2:C2 Suction Line Temp | Read | |||
| AI | 157 | B2:C2 Discharge Line Temp | Read | |||
| AI | 158 | B2:C2 Liquid Line Temp | Read | |||
| AI | 159 | B2:C2 Superheat Temp | Read | |||
| AI | 160 | B2:C2 Discharge Superheat Temp | Read | |||
| AI | 161 | B2:C2 Sub-cooling Temp | Read | |||
| AI | 162 | B2:C2 Compressor A1 Percentage | Read | |||
| AI | 163 | B2:C2 Compressor A2 Percentage | Read | |||
| AI | 164 | B2:C2 Condenser Percentage | Read | |||
| AI | 165 | B2:C2 Electronic Expansion Valve Position | Read | |||
| AI | 166 | B2:C2 Compressor 1 Current | Read | |||
| AI | 167 | B2:C2 Compressor 2 Current | Read | |||
| AI | 190 | B1:C3 Suction Pressure | Read | |||
| AI | 191 | B1:C3 Discharge Pressure | Read | |||
| AI | 192 | B1:C3 Liquid Line Pressure | Read | |||
| AI | 193 | B1:C3 Calculated Saturation Temp | Read | |||
| AI | 194 | B1:C3 Calculated Discharge Temp | Read | |||
| AI | 195 | B1:C3 Calculated Liquid Line Temp | Read | |||
| AI | 196 | B1:C3 Suction Line Temp | Read | |||
| AI | 197 | B1:C3 Discharge Line Temp | Read | |||
| AI | 198 | B1:C3 Liquid Line Temp | Read | |||
| AI | 199 | B1:C3 Superheat Temp | Read | |||
| AI | 200 | B1:C3 Discharge Superheat Temp | Read | |||
| AI | 201 | B1:C3 Sub-cooling Temp | Read | |||
| AI | 202 | B1:C3 Compressor A1 Percentage | Read | |||
| AI | 203 | B1:C3 Compressor A2 Percentage | Read | |||
| AI | 204 | B1:C3 Condenser Percentage | Read | |||
| AI | 205 | B1:C3 Electronic Expansion Valve Position | Read | |||
| AI | 206 | B1:C3 Compressor 1 Current | Read | |||
| AI | 207 | B1:C3 Compressor 2 Current | Read | |||
| AI | 220 | B2:C3 Suction Pressure | Read | |||
| AI | 221 | B2:C3 Discharge Pressure | Read | |||
| AI | 222 | B2:C3 Liquid Line Pressure | Read | |||
| AI | 223 | B2:C3 Calculated Saturation Temp | Read | |||
| AI | 224 | B2:C3 Calculated Discharge Temp | Read | |||
| AI | 225 | B2:C3 Calculated Liquid Line Temp | Read | |||
| AI | 226 | B2:C3 Suction Line Temp | Read | |||
| AI | 227 | B2:C3 Discharge Line Temp | Read | |||
| AI | 228 | B2:C3 Liquid Line Temp | Read | |||
| AI | 229 | B2:C3 Superheat Temp | Read | |||
| AI | 230 | B2:C3 Discharge Superheat Temp | Read | |||
| AI | 231 | B2:C3 Sub-cooling Temp | Read | |||
| AI | 232 | B2:C3 Compressor A1 Percentage | Read | |||
| AI | 233 | B2:C3 Compressor A2 Percentage | Read | |||
| AI | 234 | B2:C3 Condenser Percentage | Read | |||
| AI | 235 | B2:C3 Electronic Expansion Valve Position | Read | |||
| AI | 236 | B2:C3 Compressor 1 Current | Read | |||
| AI | 237 | B2:C3 Compressor 2 Current | Read | |||
| AV | 1 | Leaving Water Maximum Reset Limit | Range 35° to 60° | °F | Write | |
| AV | 2 | Leaving Water Minimum Reset Limit | Range 35° to 60° | °F | Write | |
| AV | 3 | Maximum Barrel Setpoint Offset | Range 1° to 10° | °F | Write | |
| AV | 4 | Compressor Stage Window Above | Range 1° to 20° | °F | Write | |
| AV | 5 | Compressor Stage Window Below | Range 1° to 20° | °F | Write | |
| AV | 6 | Low Chilled Water Out Cutoff Temp | Range 25° to 45° | °F | Write | |
| AV | 7 | Ambient Air Lockout Temperature | Range -30° to 40° | °F | Write | |
| AV | 8 | Superheat Setpoint | Range 1° to 20° | °F | Write | |
| AV | 9 | Head Pressure Setpoint | Range 150 psi to 475 psi | psi | Write | |
| AV | 10 | Discharge Pressure Deadband Above | Range 0 psi to 200 psi | psi | Write | |
| AV | 11 | Discharge Pressure Deadband Below | Range 0 psi to 200 psi | psi | Write | |
| AV | 12 | Altitude Above Sea Level | Range 0 to 15,000 Ft | ft | Write | |
| AV | 20 | EVAP Sump Heat Enable Setpoint | Range 38° to 80° | °F | Write | |
| AV | 21 | EVAP Sump Heat Enable Deadband | Range 1° to 10° | °F | Write | |
| AV | 22 | EVAP Maximum Amps | Range 0 Amps to 100 Amps | A | Write | |
| AV | 23 | EVAP Ambient First Stage Enable | Range 35° to 110° | °F | Write | |
| AV | 24 | EVAP Ambient Condenser Lockout | Range -30° to 40° | °F | Write | |
| AV | 30 | Waterside Economizer Enable Deadband | Range 1° to 10° | °F | Write | |
| AV | 31 | Waterside Economizer Freeze Protection Setpoint | Range 0° to 50° | °F | Write | |
| AV | 32 | Waterside Economizer Heat Exchange Inlet Setpoint | Range 0° to 50° | °F | Write | |
| AV | 33 | Waterside Economizer Fan Staging Delay | Range 0 Sec to 30 Sec | s | Write | |
| AV | 34 | Waterside Economizer Startup Delay | Range 0 Sec to 120 Sec | s | Write | |
| AV | 35 | Waterside Economizer Minimum VFD Speed | Range 0% to 50% | % | Write | |
| AV | 36 | Waterside Economizer Minimum Mixing Valve w/Fan On | Range 0% to 95% | % | Write | |
| AV | 37 | Waterside Economizer Primary 3-Way Valve Slow Start | Range 1 Min to 30 Min | min | Write | |
| AV | 38 | Waterside Economizer Primary 3-Way Valve Slow Stop | Range 1 Min to 30 Min | min | Write | |
| AV | 39 | Waterside Economizer Primary Valve Maximum Position | Range 0% to 100% | % | Write | |
| AV | 40 | CPM Reset Alarm History { 1 = Reset } | Write | 0=Log, 1=Reset | ||
| AV | 41 | CPM Maximum Building Pressure | Range 10 psi to 200 psi | psi | Write | |
| AV | 42 | CPM Building Differential Pr. Target | Range 0 psi to 100 psi | psi | Write | |
| AV | 43 | CPM Minimum Suction Pressure | Range 0 psi to 100 psi | psi | Write | |
| AV | 44 | CPM Pump VFD Initial Starting Position | Range 0% to 100% | % | Write | |
| AV | 45 | CPM Pump VFD Minimum Position | Range 0% to 100% | % | Write | |
| AV | 50 | Vestibule 1 Cooling Setpoint | Range 30° to 90° | °F | Write | |
| AV | 51 | Vestibule 1 Heating Setpoint | Range 30° to 90° | °F | Write | |
| AV | 52 | Vestibule 1 Setpoint Deadband | Range 0.1° to 20° | °F | Write | |
| AV | 53 | Vestibule 2 Cooling Setpoint | Range 30° to 90° | °F | Write | |
| AV | 54 | Vestibule 2 Heating Setpoint | Range 30° to 90° | °F | Write | |
| AV | 55 | Vestibule 2 Setpoint Deadband | Range 0.1° to 20° | °F | Write | |
| AV | 60 | Inlet Water Sensor Calibration Offset | Range -100° to 100° | °F | Write | |
| AV | 61 | Outlet Water Sensor Calibration Offset | Range -100° to 100° | °F | Write | |
| AV | 62 | Outdoor Air Sensor Calibration Offset | Range -100° to 100° | °F | Write | |
| AV | 63 | Barrel 1 Temp Sensor Calibration Offset | Range -100° to 100° | °F | Write | |
| AV | 64 | Barrel 2 Temp Sensor Calibration Offset | Range -100° to 100° | °F | Write | |
| AV | 65 | Vestibule 1 Sensor Calibration Offset | Range -100° to 100° | °F | Write | |
| AV | 66 | Vestibule 2 Sensor Calibration Offset | Range -100° to 100° | °F | Write | |
| AV | 70 | Compressor Modulation Rate | Range 1 Sec to 60 Sec | s | Write | |
| AV | 71 | High Outlet Water Temp Failure Time | Range 5 Sec to 600 Sec | s | Write | |
| AVmin | 80 | Reset Unit Lockout { 1 = Reset } | Write | 0=Run, 1=Reset | ||
| AVmin | 81 | Auto/Run/Off Command | Write | 0=Auto, 1=Run, 2=Off | ||
| AV | 82 | Enable/Disable EVAP Drain Valve | Write | 0=Off, 1=On | ||
| AV | 83 | Enable/Disable Main Relay #4 | Write | 0=Off, 1=On | ||
| AV | 84 | Enable/Disable Main Relay #5 | Write | 0=Off, 1=On | ||
| AV | 85 | Enable/Disable Main Relay #6 | Write | 0=Off, 1=On | ||
| AV | 86 | Enable/Disable Main Relay #7 | Write | 0=Off, 1=On | ||
| AV | 87 | Enable/Disable Main Relay #8 | Write | 0=Off, 1=On | ||
| AV | 88 | Set Analog Output #1 Voltage | Range 0 to 100 | Write | ||
| AV | 89 | Set Analog Output #2 Voltage | Range 0 to 100 | Write | ||
| AV | 90 | Set Analog Output #3 Voltage | Range 0 to 100 | Write | ||
| AV | 91 | Set Analog Output #4 Voltage | Range 0 to 100 | Write | ||
| BI | 1 | Run/Stop Input Command | Status | Read | ||
| BImin | 2 | Proof of Water Flow #1 | Status | Read | ||
| BI | 3 | Proof of Water Flow #2 | Status | Read | ||
| BImin | 4 | Emergency Shutdown | Status | Read | ||
| BI | 5 | Phase Loss | Status | Read | ||
| BI | 6 | Barrel #1 Disable Command | Status | Read | ||
| BI | 7 | Barrel #2 Disable Command | Status | Read | ||
| BImin | 8 | Chiller Running On/Off Status | Status | Read | ||
| BI | 9 | Chiller Fully Loaded Status | Status | Read | ||
| BI | 10 | Waterside Economizer Fan Run Status | Status | Read | ||
| BI | 11 | Waterside Economizer at Maximum Capacity | Status | Read | ||
| BI | 12 | Waterside Economizer Secondary Pump Status | Status | Read | ||
| BI | 13 | Waterside Economizer Alarm Not Operating | Alarm | Read | ||
| BI | 14 | Waterside Economizer Alarm Freeze Protection | Alarm | Read | ||
| BI | 15 | Waterside Economizer Alarm Primary Outlet Sensor | Alarm | Read | ||
| BI | 16 | Waterside Economizer Alarm HE Waterside Outlet Sensor | Alarm | Read | ||
| BI | 17 | Waterside Economizer Alarm HE Glycol Inlet Sensor | Alarm | Read | ||
| BI | 18 | Waterside Economizer Alarm HE Glycol Outlet Sensor | Alarm | Read | ||
| BI | 19 | Waterside Economizer Alarm VFD Fault | Alarm | Read | ||
| BI | 20 | Chiller Pumping Module Water Flow Proving | Status | Read | ||
| BI | 21 | Chiller Pumping Module Primary A Pump 1 Status | Status | Read | ||
| BI | 22 | Chiller Pumping Module Primary A Pump 2 Status | Status | Read | ||
| BI | 23 | Chiller Pumping Module Secondary Pump 1 Status | Status | Read | ||
| BI | 24 | Chiller Pumping Module Secondary Pump 2 Status | Status | Read | ||
| BI | 25 | Chiller Pumping Module Primary B Pump 1 Status | Status | Read | ||
| BI | 26 | Chiller Pumping Module Primary B Pump 2 Status | Status | Read | ||
| BI | 27 | Chiller Pumping Module Alarm Primary Pump A1 Locked Out | Alarm | Read | ||
| BI | 28 | Chiller Pumping Module Alarm Primary Pump A2 Locked Out | Alarm | Read | ||
| BI | 29 | Chiller Pumping Module Alarm Secondary Pump 1 Locked Out | Alarm | Read | ||
| BI | 30 | Chiller Pumping Module Alarm Secondary Pump 2 Locked Out | Alarm | Read | ||
| BI | 31 | Chiller Pumping Module Alarm Primary Pump B1 Locked Out | Alarm | Read | ||
| BI | 32 | Chiller Pumping Module Alarm Primary Pump B2 Locked Out | Alarm | Read | ||
| BI | 33 | Chiller Pumping Module Alarm Maximum Pressure Exceeded | Alarm | Read | ||
| BI | 34 | Chiller Pumping Module Alarm Pumps Locked Out | Alarm | Read | ||
| BI | 35 | Chiller Pumping Module Alarm Glycol Feeder Low | Alarm | Read | ||
| BI | 40 | Evaporator Low Sump Input Status | Status | Read | ||
| BI | 41 | Evaporator Pump 1 Pressure Status | Status | Read | ||
| BI | 42 | Evaporator Pump 1 VFD Fault Status | Status | Read | ||
| BI | 43 | Evaporator Pump 2 Pressure Status | Status | Read | ||
| BI | 44 | Evaporator Pump 2 VFD Fault Status | Status | Read | ||
| BI | 45 | Evaporator Condenser Pump 1 | Status | Read | ||
| BI | 46 | Evaporator Condenser Pump 2 | Status | Read | ||
| BI | 47 | Evaporator Sump Heater | Status | Read | ||
| BI | 48 | Evaporator Drain Valve | Status | Read | ||
| BI | 49 | Evaporator Alarm Low Sump Level | Alarm | Read | ||
| BI | 50 | Evaporator Alarm No Pump 1 Pressure Signal | Alarm | Read | ||
| BI | 51 | Evaporator Alarm No Pump 2 Pressure Signal | Alarm | Read | ||
| BI | 52 | Evaporator Alarm Pump 1 VFD Fault | Alarm | Read | ||
| BI | 53 | Evaporator Alarm Pump 2 VFD Fault | Alarm | Read | ||
| BI | 54 | Evaporator Alarm Missing Sump Temperature Sensor #1 | Alarm | Read | ||
| BI | 55 | Evaporator Alarm Missing Sump Temperature Sensor #2 | Alarm | Read | ||
| BI | 56 | Evaporator Alarm Missing Sump Temperature Sensor #3 | Alarm | Read | ||
| BI | 57 | Evaporator Alarm Condenser 1 Lockout | Alarm | Read | ||
| BI | 58 | Evaporator Alarm Condenser 2 Lockout | Alarm | Read | ||
| BI | 59 | Evaporator Alarm Low Sump Temperature | Alarm | Read | ||
| BI | 60 | Evaporator Alarm Pump 1 Low Current | Alarm | Read | ||
| BI | 61 | Evaporator Alarm Pump 1 High Current | Alarm | Read | ||
| BI | 62 | Evaporator Alarm Pump 2 Low Current | Alarm | Read | ||
| BI | 63 | Evaporator Alarm Pump 2 High Current | Alarm | Read | ||
| BI | 70 | B1:C1 Module Enabled | Status | Read | ||
| BI | 71 | B1:C1 Compressor #1 Status | Status | Read | ||
| BI | 72 | B1:C1 Compressor #2 Status | Status | Read | ||
| BI | 73 | B2:C1 Module Enabled | Status | Read | ||
| BI | 74 | B2:C1 Compressor #1 Status | Status | Read | ||
| BI | 75 | B2:C1 Compressor #2 Status | Status | Read | ||
| BI | 76 | B1:C2 Module Enabled | Status | Read | ||
| BI | 77 | B1:C2 Compressor #1 Status | Status | Read | ||
| BI | 78 | B1:C2 Compressor #2 Status | Status | Read | ||
| BI | 79 | B2:C2 Module Enabled | Status | Read | ||
| BI | 80 | B2:C2 Compressor #1 Status | Status | Read | ||
| BI | 81 | B2:C2 Compressor #2 Status | Status | Read | ||
| BI | 82 | B1:C3 Module Enabled | Status | Read | ||
| BI | 83 | B1:C3 Compressor #1 Status | Status | Read | ||
| BI | 84 | B1:C3 Compressor #2 Status | Status | Read | ||
| BI | 85 | B2:C3 Module Enabled | Status | Read | ||
| BI | 86 | B2:C3 Compressor #1 Status | Status | Read | ||
| BI | 87 | B2:C3 Compressor #2 Status | Status | Read | ||
| BI | 90 | B1:C1 Fault Low Suction | Fault | Read | ||
| BI | 91 | B1:C1 Fault Unsafe Suction | Fault | Read | ||
| BI | 92 | B1:C1 Fault Trip High Discharge Pressure | Fault | Read | ||
| BI | 93 | B1:C1 Fault Compressor 1 Not Running | Fault | Read | ||
| BI | 94 | B1:C1 Fault Compressor 2 Not Running | Fault | Read | ||
| BI | 95 | B1:C1 Fault No Suction Line Temperature Sensor | Fault | Read | ||
| BI | 96 | B1:C1 Fault Low Superheat | Fault | Read | ||
| BI | 97 | B1:C1 Fault High Discharge Temperature | Fault | Read | ||
| BI | 98 | B1:C1 Fault High Discharge psi Trip | Fault | Read | ||
| BI | 99 | B1:C1 Fault Compressor 1 False Active | Fault | Read | ||
| BI | 100 | B1:C1 Fault Compressor 2 False Active | Fault | Read | ||
| BI | 101 | B1:C1 Fault No Suction Pressure Sensor | Fault | Read | ||
| BI | 102 | B1:C1 Fault Emergency Shutdown | Fault | Read | ||
| BI | 103 | B1:C1 Fault Modbus Slave Timeout | Fault | Read | ||
| BI | 104 | B1:C1 Fault High Superheat | Fault | Read | ||
| BI | 105 | B1:C1 Fault High Saturation Temperature | Fault | Read | ||
| BI | 106 | B1:C1 Fault Compressor 1 Over Current | Fault | Read | ||
| BI | 107 | B1:C1 Fault Compressor 2 Over Current | Fault | Read | ||
| BI | 108 | B1:C1 Fault Compressor 1 Under Current | Fault | Read | ||
| BI | 109 | B1:C1 Fault Compressor 2 Under Current | Fault | Read | ||
| BI | 110 | B1:C1 Warning Low Suction Pressure | Warning | Read | ||
| BI | 111 | B1:C1 Warning Low Suction Pressure Startup | Warning | Read | ||
| BI | 112 | B1:C1 Warning High Discharge Pressure | Warning | Read | ||
| BI | 113 | B1:C1 Warning No Discharge Pressure Sensor | Warning | Read | ||
| BI | 114 | B1:C1 Warning No Discharge Temperature Sensor | Warning | Read | ||
| BI | 115 | B1:C1 Warning High Superheat | Warning | Read | ||
| BI | 116 | B1:C1 Warning Condenser Fault | Warning | Read | ||
| BI | 117 | B1:C1 Warning No Liquid Line Pressure Sensor | Warning | Read | ||
| BI | 118 | B1:C1 Warning No Liquid Line Temperature Sensor | Warning | Read | ||
| BI | 119 | B1:C1 Warning High Discharge Pressure 2 | Warning | Read | ||
| BI | 120 | B1:C1 Lockout Suction Pressure | Lockout | Read | ||
| BI | 121 | B1:C1 Lockout Low Discharge Pressure | Lockout | Read | ||
| BI | 122 | B1:C1 Lockout Compressor 1 Over Current | Lockout | Read | ||
| BI | 123 | B1:C1 Lockout Compressor 2 Over Current | Lockout | Read | ||
| BI | 124 | B1:C1 Lockout High Discharge Temperature | Lockout | Read | ||
| BI | 125 | B1:C1 Lockout High Discharge Pressure | Lockout | Read | ||
| BI | 126 | B1:C1 Lockout Low Superheat | Lockout | Read | ||
| BI | 127 | B1:C1 Lockout High Superheat | Lockout | Read | ||
| BI | 128 | B1:C1 Lockout High Saturation Temperature | Lockout | Read | ||
| BI | 129 | B1:C1 Lockout Compressor 1 Under Current | Lockout | Read | ||
| BI | 130 | B1:C1 Lockout Compressor 2 Under Current | Lockout | Read | ||
| BI | 131 | B2:C1 Fault Low Suction | Fault | Read | ||
| BI | 132 | B2:C1 Fault Unsafe Suction | Fault | Read | ||
| BI | 133 | B2:C1 Fault Trip High Discharge Pressure | Fault | Read | ||
| BI | 134 | B2:C1 Fault Compressor 1 Not Running | Fault | Read | ||
| BI | 135 | B2:C1 Fault Compressor 2 Not Running | Fault | Read | ||
| BI | 136 | B2:C1 Fault No Suction Line Temperature Sensor | Fault | Read | ||
| BI | 137 | B2:C1 Fault Low Superheat | Fault | Read | ||
| BI | 138 | B2:C1 Fault High Discharge Temperature | Fault | Read | ||
| BI | 139 | B2:C1 Fault High Discharge psi Trip | Fault | Read | ||
| BI | 140 | B2:C1 Fault Compressor 1 False Active | Fault | Read | ||
| BI | 141 | B2:C1 Fault Compressor 2 False Active | Fault | Read | ||
| BI | 142 | B2:C1 Fault No Suction Pressure Sensor | Fault | Read | ||
| BI | 143 | B2:C1 Fault Emergency Shutdown | Fault | Read | ||
| BI | 144 | B2:C1 Fault Modbus Slave Timeout | Fault | Read | ||
| BI | 145 | B2:C1 Fault High Superheat | Fault | Read | ||
| BI | 146 | B2:C1 Fault High Saturation Temperature | Fault | Read | ||
| BI | 147 | B2:C1 Fault Compressor 1 Over Current | Fault | Read | ||
| BI | 148 | B2:C1 Fault Compressor 2 Over Current | Fault | Read | ||
| BI | 149 | B2:C1 Fault Compressor 1 Under Current | Fault | Read | ||
| BI | 150 | B2:C1 Fault Compressor 2 Under Current | Fault | Read | ||
| BI | 151 | B2:C1 Warning Low Suction Pressure | Warning | Read | ||
| BI | 152 | B2:C1 Warning Low Suction Pressure Startup | Warning | Read | ||
| BI | 153 | B2:C1 Warning High Discharge Pressure | Warning | Read | ||
| BI | 154 | B2:C1 Warning No Discharge Pressure Sensor | Warning | Read | ||
| BI | 155 | B2:C1 Warning No Discharge Temperature Sensor | Warning | Read | ||
| BI | 156 | B2:C1 Warning High Superheat | Warning | Read | ||
| BI | 157 | B2:C1 Warning Condenser Fault | Warning | Read | ||
| BI | 158 | B2:C1 Warning No Liquid Line Pressure Sensor | Warning | Read | ||
| BI | 159 | B2:C1 Warning No Liquid Line Temperature Sensor | Warning | Read | ||
| BI | 160 | B2:C1 Warning High Discharge Pressure 2 | Warning | Read | ||
| BI | 161 | B2:C1 Lockout Suction Pressure | Lockout | Read | ||
| BI | 162 | B2:C1 Lockout Low Discharge Pressure | Lockout | Read | ||
| BI | 163 | B2:C1 Lockout Compressor 1 Over Current | Lockout | Read | ||
| BI | 164 | B2:C1 Lockout Compressor 2 Over Current | Lockout | Read | ||
| BI | 165 | B2:C1 Lockout High Discharge Temperature | Lockout | Read | ||
| BI | 166 | B2:C1 Lockout High Discharge Pressure | Lockout | Read | ||
| BI | 167 | B2:C1 Lockout Low Superheat | Lockout | Read | ||
| BI | 168 | B2:C1 Lockout High Superheat | Lockout | Read | ||
| BI | 169 | B2:C1 Lockout High Saturation Temperature | Lockout | Read | ||
| BI | 170 | B2:C1 Lockout Compressor 1 Under Current | Lockout | Read | ||
| BI | 171 | B2:C1 Lockout Compressor 2 Under Current | Lockout | Read | ||
| BI | 172 | B1:C2 Fault Low Suction | Fault | Read | ||
| BI | 173 | B1:C2 Fault Unsafe Suction | Fault | Read | ||
| BI | 174 | B1:C2 Fault Trip High Discharge Pressure | Fault | Read | ||
| BI | 175 | B1:C2 Fault Compressor 1 Not Running | Fault | Read | ||
| BI | 176 | B1:C2 Fault Compressor 2 Not Running | Fault | Read | ||
| BI | 177 | B1:C2 Fault No Suction Line Temperature Sensor | Fault | Read | ||
| BI | 178 | B1:C2 Fault Low Superheat | Fault | Read | ||
| BI | 179 | B1:C2 Fault High Discharge Temperature | Fault | Read | ||
| BI | 180 | B1:C2 Fault High Discharge psi Trip | Fault | Read | ||
| BI | 181 | B1:C2 Fault Compressor 1 False Active | Fault | Read | ||
| BI | 182 | B1:C2 Fault Compressor 2 False Active | Fault | Read | ||
| BI | 183 | B1:C2 Fault No Suction Pressure Sensor | Fault | Read | ||
| BI | 184 | B1:C2 Fault Emergency Shutdown | Fault | Read | ||
| BI | 185 | B1:C2 Fault Modbus Slave Timeout | Fault | Read | ||
| BI | 186 | B1:C2 Fault High Superheat | Fault | Read | ||
| BI | 187 | B1:C2 Fault High Saturation Temperature | Fault | Read | ||
| BI | 188 | B1:C2 Fault Compressor 1 Over Current | Fault | Read | ||
| BI | 189 | B1:C2 Fault Compressor 2 Over Current | Fault | Read | ||
| BI | 190 | B1:C2 Fault Compressor 1 Under Current | Fault | Read | ||
| BI | 191 | B1:C2 Fault Compressor 2 Under Current | Fault | Read | ||
| BI | 192 | B1:C2 Warning Low Suction Pressure | Warning | Read | ||
| BI | 193 | B1:C2 Warning Low Suction Pressure Startup | Warning | Read | ||
| BI | 194 | B1:C2 Warning High Discharge Pressure | Warning | Read | ||
| BI | 195 | B1:C2 Warning No Discharge Pressure Sensor | Warning | Read | ||
| BI | 196 | B1:C2 Warning No Discharge Temperature Sensor | Warning | Read | ||
| BI | 197 | B1:C2 Warning High Superheat | Warning | Read | ||
| BI | 198 | B1:C2 Warning Condenser Fault | Warning | Read | ||
| BI | 199 | B1:C2 Warning No Liquid Line Pressure Sensor | Warning | Read | ||
| BI | 200 | B1:C2 Warning No Liquid Line Temperature Sensor | Warning | Read | ||
| BI | 201 | B1:C2 Warning High Discharge Pressure 2 | Warning | Read | ||
| BI | 202 | B1:C2 Lockout Suction Pressure | Lockout | Read | ||
| BI | 203 | B1:C2 Lockout Low Discharge Pressure | Lockout | Read | ||
| BI | 204 | B1:C2 Lockout Compressor 1 Over Current | Lockout | Read | ||
| BI | 205 | B1:C2 Lockout Compressor 2 Over Current | Lockout | Read | ||
| BI | 206 | B1:C2 Lockout High Discharge Temperature | Lockout | Read | ||
| BI | 207 | B1:C2 Lockout High Discharge Pressure | Lockout | Read | ||
| BI | 208 | B1:C2 Lockout Low Superheat | Lockout | Read | ||
| BI | 209 | B1:C2 Lockout High Superheat | Lockout | Read | ||
| BI | 210 | B1:C2 Lockout High Saturation Temperature | Lockout | Read | ||
| BI | 211 | B1:C2 Lockout Compressor 1 Under Current | Lockout | Read | ||
| BI | 212 | B2:C3 Lockout Compressor 2 Under Current | Lockout | Read | ||
| BI | 213 | B2:C2 Fault Low Suction | Fault | Read | ||
| BI | 214 | B2:C2 Fault Unsafe Suction | Fault | Read | ||
| BI | 215 | B2:C2 Fault Trip High Discharge Pressure | Fault | Read | ||
| BI | 216 | B2:C2 Fault Compressor 1 Not Running | Fault | Read | ||
| BI | 217 | B2:C2 Fault Compressor 2 Not Running | Fault | Read | ||
| BI | 218 | B2:C2 Fault No Suction Line Temperature Sensor | Fault | Read | ||
| BI | 219 | B2:C2 Fault Low Superheat | Fault | Read | ||
| BI | 220 | B2:C2 Fault High Discharge Temperature | Fault | Read | ||
| BI | 221 | B2:C2 Fault High Discharge psi Trip | Fault | Read | ||
| BI | 222 | B2:C2 Fault Compressor 1 False Active | Fault | Read | ||
| BI | 223 | B2:C2 Fault Compressor 2 False Active | Fault | Read | ||
| BI | 224 | B2:C2 Fault No Suction Pressure Sensor | Fault | Read | ||
| BI | 225 | B2:C2 Fault Emergency Shutdown | Fault | Read | ||
| BI | 226 | B2:C2 Fault Modbus Slave Timeout | Fault | Read | ||
| BI | 227 | B2:C2 Fault High Superheat | Fault | Read | ||
| BI | 228 | B2:C2 Fault High Saturation Temperature | Fault | Read | ||
| BI | 229 | B2:C2 Fault Compressor 1 Over Current | Fault | Read | ||
| BI | 230 | B2:C2 Fault Compressor 2 Over Current | Fault | Read | ||
| BI | 231 | B2:C2 Fault Compressor 1 Under Current | Fault | Read | ||
| BI | 232 | B2:C2 Fault Compressor 2 Under Current | Fault | Read | ||
| BI | 233 | B2:C2 Warning Low Suction Pressure | Warning | Read | ||
| BI | 234 | B2:C2 Warning Low Suction Pressure Startup | Warning | Read | ||
| BI | 235 | B2:C2 Warning High Discharge Pressure | Warning | Read | ||
| BI | 236 | B2:C2 Warning No Discharge Pressure Sensor | Warning | Read | ||
| BI | 237 | B2:C2 Warning No Discharge Temperature Sensor | Warning | Read | ||
| BI | 238 | B2:C2 Warning High Superheat | Warning | Read | ||
| BI | 239 | B2:C2 Warning Condenser Fault | Warning | Read | ||
| BI | 240 | B2:C2 Warning No Liquid Line Pressure Sensor | Warning | Read | ||
| BI | 241 | B2:C2 Warning No Liquid Line Temperature Sensor | Warning | Read | ||
| BI | 242 | B2:C2 Warning High Discharge Pressure 2 | Warning | Read | ||
| BI | 243 | B2:C2 Lockout Suction Pressure | Lockout | Read | ||
| BI | 244 | B2:C2 Lockout Low Discharge Pressure | Lockout | Read | ||
| BI | 245 | B2:C2 Lockout Compressor 1 Over Current | Lockout | Read | ||
| BI | 246 | B2:C2 Lockout Compressor 2 Over Current | Lockout | Read | ||
| BI | 247 | B2:C2 Lockout High Discharge Temperature | Lockout | Read | ||
| BI | 248 | B2:C2 Lockout High Discharge Pressure | Lockout | Read | ||
| BI | 249 | B2:C2 Lockout Low Superheat | Lockout | Read | ||
| BI | 250 | B2:C2 Lockout High Superheat | Lockout | Read | ||
| BI | 251 | B2:C2 Lockout High Saturation Temperature | Lockout | Read | ||
| BI | 252 | B2:C2 Lockout Compressor 1 Under Current | Lockout | Read | ||
| BI | 253 | B2:C3 Lockout Compressor 2 Under Current | Lockout | Read | ||
| BI | 254 | B1:C3 Fault Low Suction | Fault | Read | ||
| BI | 255 | B1:C3 Fault Unsafe Suction | Fault | Read | ||
| BI | 256 | B1:C3 Fault Trip High Discharge Pressure | Fault | Read | ||
| BI | 257 | B1:C3 Fault Compressor 1 Not Running | Fault | Read | ||
| BI | 258 | B1:C3 Fault Compressor 2 Not Running | Fault | Read | ||
| BI | 259 | B1:C3 Fault No Suction Line Temperature Sensor | Fault | Read | ||
| BI | 260 | B1:C3 Fault Low Superheat | Fault | Read | ||
| BI | 261 | B1:C3 Fault High Discharge Temperature | Fault | Read | ||
| BI | 262 | B1:C3 Fault High Discharge psi Trip | Fault | Read | ||
| BI | 263 | B1:C3 Fault Compressor 1 False Active | Fault | Read | ||
| BI | 264 | B1:C3 Fault Compressor 2 False Active | Fault | Read | ||
| BI | 265 | B1:C3 Fault No Suction Pressure Sensor | Fault | Read | ||
| BI | 266 | B1:C3 Fault Emergency Shutdown | Fault | Read | ||
| BI | 267 | B1:C3 Fault Modbus Slave Timeout | Fault | Read | ||
| BI | 268 | B1:C3 Fault High Superheat | Fault | Read | ||
| BI | 269 | B1:C3 Fault High Saturation Temperature | Fault | Read | ||
| BI | 270 | B1:C3 Fault Compressor 1 Over Current | Fault | Read | ||
| BI | 271 | B1:C3 Fault Compressor 2 Over Current | Fault | Read | ||
| BI | 272 | B1:C3 Fault Compressor 1 Under Current | Fault | Read | ||
| BI | 273 | B1:C3 Fault Compressor 2 Under Current | Fault | Read | ||
| BI | 274 | B1:C3 Warning Low Suction Pressure | Warning | Read | ||
| BI | 275 | B1:C3 Warning Low Suction Pressure Startup | Warning | Read | ||
| BI | 276 | B1:C3 Warning High Discharge Pressure | Warning | Read | ||
| BI | 277 | B1:C3 Warning No Discharge Pressure Sensor | Warning | Read | ||
| BI | 278 | B1:C3 Warning No Discharge Temperature Sensor | Warning | Read | ||
| BI | 279 | B1:C3 Warning High Superheat | Warning | Read | ||
| BI | 280 | B1:C3 Warning Condenser Fault | Warning | Read | ||
| BI | 281 | B1:C3 Warning No Liquid Line Pressure Sensor | Warning | Read | ||
| BI | 282 | B1:C3 Warning No Liquid Line Temperature Sensor | Warning | Read | ||
| BI | 283 | B1:C3 Warning High Discharge Pressure 2 | Warning | Read | ||
| BI | 284 | B1:C3 Lockout Suction Pressure | Lockout | Read | ||
| BI | 285 | B1:C3 Lockout Low Discharge Pressure | Lockout | Read | ||
| BI | 286 | B1:C3 Lockout Compressor 1 Over Current | Lockout | Read | ||
| BI | 287 | B1:C3 Lockout Compressor 2 Over Current | Lockout | Read | ||
| BI | 288 | B1:C3 Lockout High Discharge Temperature | Lockout | Read | ||
| BI | 289 | B1:C3 Lockout High Discharge Pressure | Lockout | Read | ||
| BI | 290 | B1:C3 Lockout Low Superheat | Lockout | Read | ||
| BI | 291 | B1:C3 Lockout High Superheat | Lockout | Read | ||
| BI | 292 | B1:C3 Lockout High Saturation Temperature | Lockout | Read | ||
| BI | 293 | B1:C3 Lockout Compressor 1 Under Current | Lockout | Read | ||
| BI | 294 | B1:C3 Lockout Compressor 2 Under Current | Lockout | Read | ||
| BI | 295 | B2:C3 Fault Low Suction | Fault | Read | ||
| BI | 296 | B2:C3 Fault Unsafe Suction | Fault | Read | ||
| BI | 297 | B2:C3 Fault Trip High Discharge Pressure | Fault | Read | ||
| BI | 298 | B2:C3 Fault Compressor 1 Not Running | Fault | Read | ||
| BI | 299 | B2:C3 Fault Compressor 2 Not Running | Fault | Read | ||
| BI | 300 | B2:C3 Fault No Suction Line Temperature Sensor | Fault | Read | ||
| BI | 301 | B2:C3 Fault Low Superheat | Fault | Read | ||
| BI | 302 | B2:C3 Fault High Discharge Temperature | Fault | Read | ||
| BI | 303 | B2:C3 Fault High Discharge psi Trip | Fault | Read | ||
| BI | 304 | B2:C3 Fault Compressor 1 False Active | Fault | Read | ||
| BI | 305 | B2:C3 Fault Compressor 2 False Active | Fault | Read | ||
| BI | 306 | B2:C3 Fault No Suction Pressure Sensor | Fault | Read | ||
| BI | 307 | B2:C3 Fault Emergency Shutdown | Fault | Read | ||
| BI | 308 | B2:C3 Fault Modbus Slave Timeout | Fault | Read | ||
| BI | 309 | B2:C3 Fault High Superheat | Fault | Read | ||
| BI | 310 | B2:C3 Fault High Saturation Temperature | Fault | Read | ||
| BI | 311 | B2:C3 Fault Compressor 1 Over Current | Fault | Read | ||
| BI | 312 | B2:C3 Fault Compressor 2 Over Current | Fault | Read | ||
| BI | 313 | B2:C3 Fault Compressor 1 Under Current | Fault | Read | ||
| BI | 314 | B2:C3 Fault Compressor 2 Under Current | Fault | Read | ||
| BI | 315 | B2:C3 Warning Low Suction Pressure | Warning | Read | ||
| BI | 316 | B2:C3 Warning Low Suction Pressure Startup | Warning | Read | ||
| BI | 317 | B2:C3 Warning High Discharge Pressure | Warning | Read | ||
| BI | 318 | B2:C3 Warning No Discharge Pressure Sensor | Warning | Read | ||
| BI | 319 | B2:C3 Warning No Discharge Temperature Sensor | Warning | Read | ||
| BI | 320 | B2:C3 Warning High Superheat | Warning | Read | ||
| BI | 321 | B2:C3 Warning Condenser Fault | Warning | Read | ||
| BI | 322 | B2:C3 Warning No Liquid Line Pressure Sensor | Warning | Read | ||
| BI | 323 | B2:C3 Warning No Liquid Line Temperature Sensor | Warning | Read | ||
| BI | 324 | B2:C3 Warning High Discharge Pressure 2 | Warning | Read | ||
| BI | 325 | B2:C3 Lockout Suction Pressure | Lockout | Read | ||
| BI | 326 | B2:C3 Lockout Low Discharge Pressure | Lockout | Read | ||
| BI | 327 | B2:C3 Lockout Compressor 1 Over Current | Lockout | Read | ||
| BI | 328 | B2:C3 Lockout Compressor 2 Over Current | Lockout | Read | ||
| BI | 329 | B2:C3 Lockout High Discharge Temperature | Lockout | Read | ||
| BI | 330 | B2:C3 Lockout High Discharge Pressure | Lockout | Read | ||
| BI | 331 | B2:C3 Lockout Low Superheat | Lockout | Read | ||
| BI | 332 | B2:C3 Lockout High Superheat | Lockout | Read | ||
| BI | 333 | B2:C3 Lockout High Saturation Temperature | Lockout | Read | ||
| BI | 334 | B2:C3 Lockout Compressor 1 Under Current | Lockout | Read | ||
| BI | 335 | B2:C3 Lockout Compressor 2 Under Current | Lockout | Read | ||
| MImin | 1 | Operating Status | Current unit mode | Read | 1=OFF_MODE, 2=RUN MODE, 3=Holiday OFF MODE, 4=Holiday RUN MODE, 5=Startup Delay, 6=Emergency Shutdown, 7=High Leaving Water |
No points match these filters.
Object ID lookup: AAON Main DX Barrel Chiller Controller point IDs by name
AI1Application VersionAI2Entering Water TemperatureAI3Leaving Water TemperatureAI4Leaving Water SetpointAI5Barrel #1 Leaving Water TemperatureAI6Barrel #2 Leaving Water TemperatureAI7Barrel Leaving Water SetpointAI8Outdoor Air TemperatureAI9Flow RateAI10Vestibule #1 TemperatureAI11Vestibule #2 TemperatureAI20Building Pump Suction PressureAI21Building Pump Discharge PressureAI22Building Pump Differential PressureAI23Building Pump VFD SignalAI24Building Pump Bypass Valve PositionAI30Waterside Economizer Primary 3-Way ValveAI31Waterside Economizer Secondary 3-Way ValveAI32Waterside Economizer Heat Exchanger Waterside OutletAI33Waterside Economizer Heat Exchanger Glycol Side OutletAI34Waterside Economizer Heat Exchanger Glycol Side InletAI35Waterside Economizer Primary Valve Outlet TemperatureAI36Waterside Economizer Fan SpeedAI40EVAP Sump Temperature #1AI41EVAP Sump Temperature #2AI42EVAP Sump Temperature #3AI43EVAP Pump #1 AmpsAI44EVAP Pump #2 AmpsAI45EVAP Pump #1 VFD SignalAI46EVAP Pump #2 VFD SignalAI50Superheat SetpointAI51Head Pressure SetpointAI60B1:C1 Suction PressureAI61B1:C1 Discharge PressureAI62B1:C1 Liquid Line PressureAI63B1:C1 Calculated Saturation TempAI64B1:C1 Calculated Discharge TempAI65B1:C1 Calculated Liquid Line TempAI66B1:C1 Suction Line TempAI67B1:C1 Discharge Line TempAI68B1:C1 Liquid Line TempAI69B1:C1 Superheat TempAI70B1:C1 Discharge Superheat TempAI71B1:C1 Sub-cooling TempAI72B1:C1 Compressor A1 PercentageAI73B1:C1 Compressor A2 PercentageAI74B1:C1 Condenser PercentageAI75B1:C1 Electronic Expansion Valve PositionAI76B1:C1 Compressor 1 CurrentAI77B1:C1 Compressor 2 CurrentAI90B2:C1 Suction PressureAI91B2:C1 Discharge PressureAI92B2:C1 Liquid Line PressureAI93B2:C1 Calculated Saturation TempAI94B2:C1 Calculated Discharge TempAI95B2:C1 Calculated Liquid Line TempAI96B2:C1 Suction Line TempAI97B2:C1 Discharge Line TempAI98B2:C1 Liquid Line TempAI99B2:C1 Superheat TempAI100B2:C1 Discharge Superheat TempAI101B2:C1 Sub-cooling TempAI102B2:C1 Compressor A1 PercentageAI103B2:C1 Compressor A2 PercentageAI104B2:C1 Condenser PercentageAI105B2:C1 Electronic Expansion Valve PositionAI106B2:C1 Compressor 1 CurrentAI107B2:C1 Compressor 2 CurrentAI120B1:C2 Suction PressureAI121B1:C2 Discharge PressureAI122B1:C2 Liquid Line PressureAI123B1:C2 Calculated Saturation TempAI124B1:C2 Calculated Discharge TempAI125B1:C2 Calculated Liquid Line TempAI126B1:C2 Suction Line TempAI127B1:C2 Discharge Line TempAI128B1:C2 Liquid Line TempAI129B1:C2 Superheat TempAI130B1:C2 Discharge Superheat TempAI131B1:C2 Sub-cooling TempAI132B1:C2 Compressor A1 PercentageAI133B1:C2 Compressor A2 PercentageAI134B1:C2 Condenser PercentageAI135B1:C2 Electronic Expansion Valve PositionAI136B1:C2 Compressor 1 CurrentAI137B1:C2 Compressor 2 CurrentAI150B2:C2 Suction PressureAI151B2:C2 Discharge PressureAI152B2:C2 Liquid Line PressureAI153B2:C2 Calculated Saturation TempAI154B2:C2 Calculated Discharge TempAI155B2:C2 Calculated Liquid Line TempAI156B2:C2 Suction Line TempAI157B2:C2 Discharge Line TempAI158B2:C2 Liquid Line TempAI159B2:C2 Superheat TempAI160B2:C2 Discharge Superheat TempAI161B2:C2 Sub-cooling TempAI162B2:C2 Compressor A1 PercentageAI163B2:C2 Compressor A2 PercentageAI164B2:C2 Condenser PercentageAI165B2:C2 Electronic Expansion Valve PositionAI166B2:C2 Compressor 1 CurrentAI167B2:C2 Compressor 2 CurrentAI190B1:C3 Suction PressureAI191B1:C3 Discharge PressureAI192B1:C3 Liquid Line PressureAI193B1:C3 Calculated Saturation TempAI194B1:C3 Calculated Discharge TempAI195B1:C3 Calculated Liquid Line TempAI196B1:C3 Suction Line TempAI197B1:C3 Discharge Line TempAI198B1:C3 Liquid Line TempAI199B1:C3 Superheat TempAI200B1:C3 Discharge Superheat TempAI201B1:C3 Sub-cooling TempAI202B1:C3 Compressor A1 PercentageAI203B1:C3 Compressor A2 PercentageAI204B1:C3 Condenser PercentageAI205B1:C3 Electronic Expansion Valve PositionAI206B1:C3 Compressor 1 CurrentAI207B1:C3 Compressor 2 CurrentAI220B2:C3 Suction PressureAI221B2:C3 Discharge PressureAI222B2:C3 Liquid Line PressureAI223B2:C3 Calculated Saturation TempAI224B2:C3 Calculated Discharge TempAI225B2:C3 Calculated Liquid Line TempAI226B2:C3 Suction Line TempAI227B2:C3 Discharge Line TempAI228B2:C3 Liquid Line TempAI229B2:C3 Superheat TempAI230B2:C3 Discharge Superheat TempAI231B2:C3 Sub-cooling TempAI232B2:C3 Compressor A1 PercentageAI233B2:C3 Compressor A2 PercentageAI234B2:C3 Condenser PercentageAI235B2:C3 Electronic Expansion Valve PositionAI236B2:C3 Compressor 1 CurrentAI237B2:C3 Compressor 2 CurrentAV1Leaving Water Maximum Reset LimitAV2Leaving Water Minimum Reset LimitAV3Maximum Barrel Setpoint OffsetAV4Compressor Stage Window AboveAV5Compressor Stage Window BelowAV6Low Chilled Water Out Cutoff TempAV7Ambient Air Lockout TemperatureAV8Superheat SetpointAV9Head Pressure SetpointAV10Discharge Pressure Deadband AboveAV11Discharge Pressure Deadband BelowAV12Altitude Above Sea LevelAV20EVAP Sump Heat Enable SetpointAV21EVAP Sump Heat Enable DeadbandAV22EVAP Maximum AmpsAV23EVAP Ambient First Stage EnableAV24EVAP Ambient Condenser LockoutAV30Waterside Economizer Enable DeadbandAV31Waterside Economizer Freeze Protection SetpointAV32Waterside Economizer Heat Exchange Inlet SetpointAV33Waterside Economizer Fan Staging DelayAV34Waterside Economizer Startup DelayAV35Waterside Economizer Minimum VFD SpeedAV36Waterside Economizer Minimum Mixing Valve w/Fan OnAV37Waterside Economizer Primary 3-Way Valve Slow StartAV38Waterside Economizer Primary 3-Way Valve Slow StopAV39Waterside Economizer Primary Valve Maximum PositionAV40CPM Reset Alarm History { 1 = Reset }AV41CPM Maximum Building PressureAV42CPM Building Differential Pr. TargetAV43CPM Minimum Suction PressureAV44CPM Pump VFD Initial Starting PositionAV45CPM Pump VFD Minimum PositionAV50Vestibule 1 Cooling SetpointAV51Vestibule 1 Heating SetpointAV52Vestibule 1 Setpoint DeadbandAV53Vestibule 2 Cooling SetpointAV54Vestibule 2 Heating SetpointAV55Vestibule 2 Setpoint DeadbandAV60Inlet Water Sensor Calibration OffsetAV61Outlet Water Sensor Calibration OffsetAV62Outdoor Air Sensor Calibration OffsetAV63Barrel 1 Temp Sensor Calibration OffsetAV64Barrel 2 Temp Sensor Calibration OffsetAV65Vestibule 1 Sensor Calibration OffsetAV66Vestibule 2 Sensor Calibration OffsetAV70Compressor Modulation RateAV71High Outlet Water Temp Failure TimeAV80Reset Unit Lockout { 1 = Reset }AV81Auto/Run/Off CommandAV82Enable/Disable EVAP Drain ValveAV83Enable/Disable Main Relay #4AV84Enable/Disable Main Relay #5AV85Enable/Disable Main Relay #6AV86Enable/Disable Main Relay #7AV87Enable/Disable Main Relay #8AV88Set Analog Output #1 VoltageAV89Set Analog Output #2 VoltageAV90Set Analog Output #3 VoltageAV91Set Analog Output #4 VoltageBI1Run/Stop Input CommandBI2Proof of Water Flow #1BI3Proof of Water Flow #2BI4Emergency ShutdownBI5Phase LossBI6Barrel #1 Disable CommandBI7Barrel #2 Disable CommandBI8Chiller Running On/Off StatusBI9Chiller Fully Loaded StatusBI10Waterside Economizer Fan Run StatusBI11Waterside Economizer at Maximum CapacityBI12Waterside Economizer Secondary Pump StatusBI13Waterside Economizer Alarm Not OperatingBI14Waterside Economizer Alarm Freeze ProtectionBI15Waterside Economizer Alarm Primary Outlet SensorBI16Waterside Economizer Alarm HE Waterside Outlet SensorBI17Waterside Economizer Alarm HE Glycol Inlet SensorBI18Waterside Economizer Alarm HE Glycol Outlet SensorBI19Waterside Economizer Alarm VFD FaultBI20Chiller Pumping Module Water Flow ProvingBI21Chiller Pumping Module Primary A Pump 1 StatusBI22Chiller Pumping Module Primary A Pump 2 StatusBI23Chiller Pumping Module Secondary Pump 1 StatusBI24Chiller Pumping Module Secondary Pump 2 StatusBI25Chiller Pumping Module Primary B Pump 1 StatusBI26Chiller Pumping Module Primary B Pump 2 StatusBI27Chiller Pumping Module Alarm Primary Pump A1 Locked OutBI28Chiller Pumping Module Alarm Primary Pump A2 Locked OutBI29Chiller Pumping Module Alarm Secondary Pump 1 Locked OutBI30Chiller Pumping Module Alarm Secondary Pump 2 Locked OutBI31Chiller Pumping Module Alarm Primary Pump B1 Locked OutBI32Chiller Pumping Module Alarm Primary Pump B2 Locked OutBI33Chiller Pumping Module Alarm Maximum Pressure ExceededBI34Chiller Pumping Module Alarm Pumps Locked OutBI35Chiller Pumping Module Alarm Glycol Feeder LowBI40Evaporator Low Sump Input StatusBI41Evaporator Pump 1 Pressure StatusBI42Evaporator Pump 1 VFD Fault StatusBI43Evaporator Pump 2 Pressure StatusBI44Evaporator Pump 2 VFD Fault StatusBI45Evaporator Condenser Pump 1BI46Evaporator Condenser Pump 2BI47Evaporator Sump HeaterBI48Evaporator Drain ValveBI49Evaporator Alarm Low Sump LevelBI50Evaporator Alarm No Pump 1 Pressure SignalBI51Evaporator Alarm No Pump 2 Pressure SignalBI52Evaporator Alarm Pump 1 VFD FaultBI53Evaporator Alarm Pump 2 VFD FaultBI54Evaporator Alarm Missing Sump Temperature Sensor #1BI55Evaporator Alarm Missing Sump Temperature Sensor #2BI56Evaporator Alarm Missing Sump Temperature Sensor #3BI57Evaporator Alarm Condenser 1 LockoutBI58Evaporator Alarm Condenser 2 LockoutBI59Evaporator Alarm Low Sump TemperatureBI60Evaporator Alarm Pump 1 Low CurrentBI61Evaporator Alarm Pump 1 High CurrentBI62Evaporator Alarm Pump 2 Low CurrentBI63Evaporator Alarm Pump 2 High CurrentBI70B1:C1 Module EnabledBI71B1:C1 Compressor #1 StatusBI72B1:C1 Compressor #2 StatusBI73B2:C1 Module EnabledBI74B2:C1 Compressor #1 StatusBI75B2:C1 Compressor #2 StatusBI76B1:C2 Module EnabledBI77B1:C2 Compressor #1 StatusBI78B1:C2 Compressor #2 StatusBI79B2:C2 Module EnabledBI80B2:C2 Compressor #1 StatusBI81B2:C2 Compressor #2 StatusBI82B1:C3 Module EnabledBI83B1:C3 Compressor #1 StatusBI84B1:C3 Compressor #2 StatusBI85B2:C3 Module EnabledBI86B2:C3 Compressor #1 StatusBI87B2:C3 Compressor #2 StatusBI90B1:C1 Fault Low SuctionBI91B1:C1 Fault Unsafe SuctionBI92B1:C1 Fault Trip High Discharge PressureBI93B1:C1 Fault Compressor 1 Not RunningBI94B1:C1 Fault Compressor 2 Not RunningBI95B1:C1 Fault No Suction Line Temperature SensorBI96B1:C1 Fault Low SuperheatBI97B1:C1 Fault High Discharge TemperatureBI98B1:C1 Fault High Discharge psi TripBI99B1:C1 Fault Compressor 1 False ActiveBI100B1:C1 Fault Compressor 2 False ActiveBI101B1:C1 Fault No Suction Pressure SensorBI102B1:C1 Fault Emergency ShutdownBI103B1:C1 Fault Modbus Slave TimeoutBI104B1:C1 Fault High SuperheatBI105B1:C1 Fault High Saturation TemperatureBI106B1:C1 Fault Compressor 1 Over CurrentBI107B1:C1 Fault Compressor 2 Over CurrentBI108B1:C1 Fault Compressor 1 Under CurrentBI109B1:C1 Fault Compressor 2 Under CurrentBI110B1:C1 Warning Low Suction PressureBI111B1:C1 Warning Low Suction Pressure StartupBI112B1:C1 Warning High Discharge PressureBI113B1:C1 Warning No Discharge Pressure SensorBI114B1:C1 Warning No Discharge Temperature SensorBI115B1:C1 Warning High SuperheatBI116B1:C1 Warning Condenser FaultBI117B1:C1 Warning No Liquid Line Pressure SensorBI118B1:C1 Warning No Liquid Line Temperature SensorBI119B1:C1 Warning High Discharge Pressure 2BI120B1:C1 Lockout Suction PressureBI121B1:C1 Lockout Low Discharge PressureBI122B1:C1 Lockout Compressor 1 Over CurrentBI123B1:C1 Lockout Compressor 2 Over CurrentBI124B1:C1 Lockout High Discharge TemperatureBI125B1:C1 Lockout High Discharge PressureBI126B1:C1 Lockout Low SuperheatBI127B1:C1 Lockout High SuperheatBI128B1:C1 Lockout High Saturation TemperatureBI129B1:C1 Lockout Compressor 1 Under CurrentBI130B1:C1 Lockout Compressor 2 Under CurrentBI131B2:C1 Fault Low SuctionBI132B2:C1 Fault Unsafe SuctionBI133B2:C1 Fault Trip High Discharge PressureBI134B2:C1 Fault Compressor 1 Not RunningBI135B2:C1 Fault Compressor 2 Not RunningBI136B2:C1 Fault No Suction Line Temperature SensorBI137B2:C1 Fault Low SuperheatBI138B2:C1 Fault High Discharge TemperatureBI139B2:C1 Fault High Discharge psi TripBI140B2:C1 Fault Compressor 1 False ActiveBI141B2:C1 Fault Compressor 2 False ActiveBI142B2:C1 Fault No Suction Pressure SensorBI143B2:C1 Fault Emergency ShutdownBI144B2:C1 Fault Modbus Slave TimeoutBI145B2:C1 Fault High SuperheatBI146B2:C1 Fault High Saturation TemperatureBI147B2:C1 Fault Compressor 1 Over CurrentBI148B2:C1 Fault Compressor 2 Over CurrentBI149B2:C1 Fault Compressor 1 Under CurrentBI150B2:C1 Fault Compressor 2 Under CurrentBI151B2:C1 Warning Low Suction PressureBI152B2:C1 Warning Low Suction Pressure StartupBI153B2:C1 Warning High Discharge PressureBI154B2:C1 Warning No Discharge Pressure SensorBI155B2:C1 Warning No Discharge Temperature SensorBI156B2:C1 Warning High SuperheatBI157B2:C1 Warning Condenser FaultBI158B2:C1 Warning No Liquid Line Pressure SensorBI159B2:C1 Warning No Liquid Line Temperature SensorBI160B2:C1 Warning High Discharge Pressure 2BI161B2:C1 Lockout Suction PressureBI162B2:C1 Lockout Low Discharge PressureBI163B2:C1 Lockout Compressor 1 Over CurrentBI164B2:C1 Lockout Compressor 2 Over CurrentBI165B2:C1 Lockout High Discharge TemperatureBI166B2:C1 Lockout High Discharge PressureBI167B2:C1 Lockout Low SuperheatBI168B2:C1 Lockout High SuperheatBI169B2:C1 Lockout High Saturation TemperatureBI170B2:C1 Lockout Compressor 1 Under CurrentBI171B2:C1 Lockout Compressor 2 Under CurrentBI172B1:C2 Fault Low SuctionBI173B1:C2 Fault Unsafe SuctionBI174B1:C2 Fault Trip High Discharge PressureBI175B1:C2 Fault Compressor 1 Not RunningBI176B1:C2 Fault Compressor 2 Not RunningBI177B1:C2 Fault No Suction Line Temperature SensorBI178B1:C2 Fault Low SuperheatBI179B1:C2 Fault High Discharge TemperatureBI180B1:C2 Fault High Discharge psi TripBI181B1:C2 Fault Compressor 1 False ActiveBI182B1:C2 Fault Compressor 2 False ActiveBI183B1:C2 Fault No Suction Pressure SensorBI184B1:C2 Fault Emergency ShutdownBI185B1:C2 Fault Modbus Slave TimeoutBI186B1:C2 Fault High SuperheatBI187B1:C2 Fault High Saturation TemperatureBI188B1:C2 Fault Compressor 1 Over CurrentBI189B1:C2 Fault Compressor 2 Over CurrentBI190B1:C2 Fault Compressor 1 Under CurrentBI191B1:C2 Fault Compressor 2 Under CurrentBI192B1:C2 Warning Low Suction PressureBI193B1:C2 Warning Low Suction Pressure StartupBI194B1:C2 Warning High Discharge PressureBI195B1:C2 Warning No Discharge Pressure SensorBI196B1:C2 Warning No Discharge Temperature SensorBI197B1:C2 Warning High SuperheatBI198B1:C2 Warning Condenser FaultBI199B1:C2 Warning No Liquid Line Pressure SensorBI200B1:C2 Warning No Liquid Line Temperature SensorBI201B1:C2 Warning High Discharge Pressure 2BI202B1:C2 Lockout Suction PressureBI203B1:C2 Lockout Low Discharge PressureBI204B1:C2 Lockout Compressor 1 Over CurrentBI205B1:C2 Lockout Compressor 2 Over CurrentBI206B1:C2 Lockout High Discharge TemperatureBI207B1:C2 Lockout High Discharge PressureBI208B1:C2 Lockout Low SuperheatBI209B1:C2 Lockout High SuperheatBI210B1:C2 Lockout High Saturation TemperatureBI211B1:C2 Lockout Compressor 1 Under CurrentBI212B2:C3 Lockout Compressor 2 Under CurrentBI213B2:C2 Fault Low SuctionBI214B2:C2 Fault Unsafe SuctionBI215B2:C2 Fault Trip High Discharge PressureBI216B2:C2 Fault Compressor 1 Not RunningBI217B2:C2 Fault Compressor 2 Not RunningBI218B2:C2 Fault No Suction Line Temperature SensorBI219B2:C2 Fault Low SuperheatBI220B2:C2 Fault High Discharge TemperatureBI221B2:C2 Fault High Discharge psi TripBI222B2:C2 Fault Compressor 1 False ActiveBI223B2:C2 Fault Compressor 2 False ActiveBI224B2:C2 Fault No Suction Pressure SensorBI225B2:C2 Fault Emergency ShutdownBI226B2:C2 Fault Modbus Slave TimeoutBI227B2:C2 Fault High SuperheatBI228B2:C2 Fault High Saturation TemperatureBI229B2:C2 Fault Compressor 1 Over CurrentBI230B2:C2 Fault Compressor 2 Over CurrentBI231B2:C2 Fault Compressor 1 Under CurrentBI232B2:C2 Fault Compressor 2 Under CurrentBI233B2:C2 Warning Low Suction PressureBI234B2:C2 Warning Low Suction Pressure StartupBI235B2:C2 Warning High Discharge PressureBI236B2:C2 Warning No Discharge Pressure SensorBI237B2:C2 Warning No Discharge Temperature SensorBI238B2:C2 Warning High SuperheatBI239B2:C2 Warning Condenser FaultBI240B2:C2 Warning No Liquid Line Pressure SensorBI241B2:C2 Warning No Liquid Line Temperature SensorBI242B2:C2 Warning High Discharge Pressure 2BI243B2:C2 Lockout Suction PressureBI244B2:C2 Lockout Low Discharge PressureBI245B2:C2 Lockout Compressor 1 Over CurrentBI246B2:C2 Lockout Compressor 2 Over CurrentBI247B2:C2 Lockout High Discharge TemperatureBI248B2:C2 Lockout High Discharge PressureBI249B2:C2 Lockout Low SuperheatBI250B2:C2 Lockout High SuperheatBI251B2:C2 Lockout High Saturation TemperatureBI252B2:C2 Lockout Compressor 1 Under CurrentBI253B2:C3 Lockout Compressor 2 Under CurrentBI254B1:C3 Fault Low SuctionBI255B1:C3 Fault Unsafe SuctionBI256B1:C3 Fault Trip High Discharge PressureBI257B1:C3 Fault Compressor 1 Not RunningBI258B1:C3 Fault Compressor 2 Not RunningBI259B1:C3 Fault No Suction Line Temperature SensorBI260B1:C3 Fault Low SuperheatBI261B1:C3 Fault High Discharge TemperatureBI262B1:C3 Fault High Discharge psi TripBI263B1:C3 Fault Compressor 1 False ActiveBI264B1:C3 Fault Compressor 2 False ActiveBI265B1:C3 Fault No Suction Pressure SensorBI266B1:C3 Fault Emergency ShutdownBI267B1:C3 Fault Modbus Slave TimeoutBI268B1:C3 Fault High SuperheatBI269B1:C3 Fault High Saturation TemperatureBI270B1:C3 Fault Compressor 1 Over CurrentBI271B1:C3 Fault Compressor 2 Over CurrentBI272B1:C3 Fault Compressor 1 Under CurrentBI273B1:C3 Fault Compressor 2 Under CurrentBI274B1:C3 Warning Low Suction PressureBI275B1:C3 Warning Low Suction Pressure StartupBI276B1:C3 Warning High Discharge PressureBI277B1:C3 Warning No Discharge Pressure SensorBI278B1:C3 Warning No Discharge Temperature SensorBI279B1:C3 Warning High SuperheatBI280B1:C3 Warning Condenser FaultBI281B1:C3 Warning No Liquid Line Pressure SensorBI282B1:C3 Warning No Liquid Line Temperature SensorBI283B1:C3 Warning High Discharge Pressure 2BI284B1:C3 Lockout Suction PressureBI285B1:C3 Lockout Low Discharge PressureBI286B1:C3 Lockout Compressor 1 Over CurrentBI287B1:C3 Lockout Compressor 2 Over CurrentBI288B1:C3 Lockout High Discharge TemperatureBI289B1:C3 Lockout High Discharge PressureBI290B1:C3 Lockout Low SuperheatBI291B1:C3 Lockout High SuperheatBI292B1:C3 Lockout High Saturation TemperatureBI293B1:C3 Lockout Compressor 1 Under CurrentBI294B1:C3 Lockout Compressor 2 Under CurrentBI295B2:C3 Fault Low SuctionBI296B2:C3 Fault Unsafe SuctionBI297B2:C3 Fault Trip High Discharge PressureBI298B2:C3 Fault Compressor 1 Not RunningBI299B2:C3 Fault Compressor 2 Not RunningBI300B2:C3 Fault No Suction Line Temperature SensorBI301B2:C3 Fault Low SuperheatBI302B2:C3 Fault High Discharge TemperatureBI303B2:C3 Fault High Discharge psi TripBI304B2:C3 Fault Compressor 1 False ActiveBI305B2:C3 Fault Compressor 2 False ActiveBI306B2:C3 Fault No Suction Pressure SensorBI307B2:C3 Fault Emergency ShutdownBI308B2:C3 Fault Modbus Slave TimeoutBI309B2:C3 Fault High SuperheatBI310B2:C3 Fault High Saturation TemperatureBI311B2:C3 Fault Compressor 1 Over CurrentBI312B2:C3 Fault Compressor 2 Over CurrentBI313B2:C3 Fault Compressor 1 Under CurrentBI314B2:C3 Fault Compressor 2 Under CurrentBI315B2:C3 Warning Low Suction PressureBI316B2:C3 Warning Low Suction Pressure StartupBI317B2:C3 Warning High Discharge PressureBI318B2:C3 Warning No Discharge Pressure SensorBI319B2:C3 Warning No Discharge Temperature SensorBI320B2:C3 Warning High SuperheatBI321B2:C3 Warning Condenser FaultBI322B2:C3 Warning No Liquid Line Pressure SensorBI323B2:C3 Warning No Liquid Line Temperature SensorBI324B2:C3 Warning High Discharge Pressure 2BI325B2:C3 Lockout Suction PressureBI326B2:C3 Lockout Low Discharge PressureBI327B2:C3 Lockout Compressor 1 Over CurrentBI328B2:C3 Lockout Compressor 2 Over CurrentBI329B2:C3 Lockout High Discharge TemperatureBI330B2:C3 Lockout High Discharge PressureBI331B2:C3 Lockout Low SuperheatBI332B2:C3 Lockout High SuperheatBI333B2:C3 Lockout High Saturation TemperatureBI334B2:C3 Lockout Compressor 1 Under CurrentBI335B2:C3 Lockout Compressor 2 Under CurrentMI1Operating Status
Integration notes
- The guide gives no read/write column; AI, BI and MI are shown read-only and AV writable from the object types and the limit ranges.
- Refrigerant points are grouped per barrel and circuit (B1:C1 ... B2:C3), so instance numbers have gaps.
- Points for the chiller pumping module, waterside economizer, evaporative condenser and vestibules report only when fitted.
- Binary input descriptions are the guide's value type column (Status, Alarm, Fault, Warning, Lockout).
- Source: BACnet section, guide pages 81-93.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Main DX Barrel Chiller Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the AAON Main DX Barrel Chiller Controller
How many BACnet points does the AAON Main DX Barrel Chiller Controller have?
This list has 524 BACnet objects: 140 analog inputs, 60 analog values, 323 binary inputs, 1 multi-state input. The exact set on a given unit depends on its firmware, installed options and configuration.
Which AAON Main DX Barrel Chiller Controller BACnet points are writable?
60 of the 524 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official AAON Main DX Barrel Chiller Controller BACnet documentation?
The source is Main DX Barrel Chiller Controller Technical Guide (G070300 Rev. B), revision 2021-11, published free by AAON at https://www.aaon.com/hubfs/Controls%20Literature/G070300_DX-Barrel-B_TGD.pdf.
What are the minimum BACnet points to integrate the AAON Main DX Barrel Chiller Controller?
Start with AV 81 Auto/Run/Off Command (Chiller command: 0 auto, 1 run, 2 off); AV 80 Reset Unit Lockout { 1 = Reset } (Write 1 to reset a unit lockout); MI 1 Operating Status (Current unit mode); BI 8 Chiller Running On/Off Status (Chiller running); AI 4 Leaving Water Setpoint (Leaving water setpoint in use); AI 2 Entering Water Temperature (Entering water temperature); AI 3 Leaving Water Temperature (Leaving water temperature); BI 2 Proof of Water Flow #1 (Proof of water flow, barrel 1); BI 4 Emergency Shutdown (Emergency shutdown input).
How do I enable BMS control of the AAON Main DX Barrel Chiller Controller?
AV 81 Auto/Run/Off Command (0 = Auto, 1 = Run, 2 = Off) runs the chiller from the BAS; BI 1 shows the Run/Stop input and BI 6/7 the barrel disable commands. AV 80 resets a unit lockout.
How do I check these points on the real Main DX Barrel Chiller Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More AAON BACnet points lists
- Rooftop unit / air handler controller
AAON Touchscreen Controller
AAON packaged units fitted with the AAON Touchscreen unit controller.
Also known as: AAON Touchscreen, Touch Screen Controller, AAON TS controller - Rooftop unit controller (zoning)
AAON Auto-Zone 3 (AZ 3) Controller
AAON packaged units run by the Auto-Zone 3 controller, alone or with AZ 3 VAV/zone dampers.
Also known as: AZ 3, AZ3, Auto-Zone 3, AAON AZ3, G071000, SS8014, SS8015, Orion AZ3 - General-purpose BACnet I/O controller
AAON BACnet General Controller (BGC)
AAON BGC general-purpose controller with 8 analog inputs, 8 binary inputs, 8 relays and 4 analog outputs.
Also known as: AAON BGC, BGC Controller, AAON BACnet General Controller, G042460, AAON general purpose I/O controller - DX chiller controller
AAON DX Chiller Controller
AAON packaged DX chillers (non-Turbocor compressors) with the Main DX Chiller Controller, refrigerant modules and optional waterside economizer and evaporative condenser modules.
Also known as: AAON DX Chiller Controller, Main DX Chiller Controller, G054280, SS1149, AAON DX chiller BACnet - DX chiller controller
AAON LF Chiller Controller
AAON LF series one- or two-circuit DX chillers with the LF Chiller Main Controller, optional pumping package and waterside economizer.
Also known as: AAON LF Chiller, LF Chiller Main Controller, G059100, SS1131, DT005683-001, LF chiller BACnet - Air handler preheat controller
AAON PREHEAT-X Controller
AAON PREHEAT-X controllers that stage and modulate electric (SCR/SSR) preheat on AAON units and air handlers.
Also known as: PREHEAT-X, PREHEATX, Preheat-X, G086640, AAON preheat controller, Orion PREHEAT-X - Rooftop unit / air handler controller (gateway)
AAON SA Controller (via PT-Link II BACnet gateway)
AAON units with the SA (single-zone) controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: SA controller, AAON SA, PT-Link II, PT-Link BACnet5, G114680 - Rooftop unit / air handler controller
AAON Stratus Unit Manager (Stratus controls)
AAON units built with Stratus controls (Stratus Unit Manager, software 1.3.3).
Also known as: Stratus, AAON Stratus, Stratus Unit Manager, Stratus BACnet Points Guide, Stratus controller, Stratus Series - VAV / zone controller
AAON VAV/Zone BACnet Controller (VAVZB)
Pressure-independent and pressure-dependent VAV boxes and zone dampers controlled by the AAON VAV/Zone BACnet controller.
Also known as: VAVZB, VAV/Zone Controller, ASM02426, ASM02427, ASM02661, ASM02662, SS1116, SS1146, G067750 - Rooftop unit / air handler controller
AAON VCB-X Controller
AAON packaged rooftop units, air handlers, DOAS and water-source units controlled by the Orion VCB-X (OE335-26B-VCBX) unit controller.
Also known as: VCBX, VCB-X, Orion VCB-X, OE335-26B-VCBX, V28940, WattMaster VCB-X, AAON VCB-X BACnet - Rooftop unit / air handler controller
AAON VCCX-454 Controller
AAON rooftop units, air handlers, DOAS and self-contained units built for R-454B and controlled by the VCCX-454 unit controller with RM454 refrigerant modules.
Also known as: VCCX-454, VCCX 454, ASM07503, SS1188, AAON VCCX-454 controller, R-454B unit controller - Rooftop unit / air handler controller
AAON VCCX-454-GH Controller (grow house)
AAON R-454B units for indoor agriculture (grow rooms) controlled by the VCCX-454-GH controller.
Also known as: VCCX-454-GH, VCCX454-GH, ASM07792, SS1207, AAON grow house controller, indoor agriculture HVAC controller - Rooftop unit / air handler controller
AAON VCCX2 Controller
AAON rooftop units, air handlers and DOAS units controlled by the VCCX2 (ASM01698) unit controller.
Also known as: VCC-X2, VCCX, VCC-X, ASM01698, Orion VCCX2, SS1088 - Rooftop unit / air handler controller (gateway)
AAON VCM Controller (legacy, via PT-Link II BACnet gateway)
Older AAON units with the legacy VCM controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: VCM, AAON VCM, PT-Link II, PT-Link BACnet5, G114680 - Rooftop unit / air handler controller (gateway)
AAON VCM-X Controller (via PT-Link II BACnet gateway)
AAON rooftop units, air handlers and other equipment with the VCM-X controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: VCM-X, VCMX, PT-Link II, PT-Link BACnet5, G114680
Source: Main DX Barrel Chiller Controller Technical Guide · G070300 Rev. B · rev. 2021-11. Object names, instances and units are reproduced as published; descriptions are our own.