DX chiller controller · BACnet points list

AAON Main DX Barrel Chiller Controller BACnet points list

Updated 12 November 2026

Short answer

The Main DX Barrel Chiller Controller runs AAON DX chillers built with one or two barrel evaporators and has an on-board BACnet MS/TP port. The object map has 140 read-only analog inputs (water temperatures, pumping, WSE, evaporative condenser and per-circuit refrigerant data), 60 analog values (setpoints, calibration offsets, run command, relay and analog output overrides), 323 read-only binary inputs for status, faults, warnings and lockouts per circuit, and a multistate input for the unit mode.

This page lists 524 BACnet objects for the AAON Main DX Barrel Chiller Controller — 60 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.

Manufacturer
AAON
Model
Main DX Barrel Chiller Controller
Equipment
DX chiller controller
Equipment type
Chillers
BACnet objects
524 (60 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
AAON DX Barrel Chiller, G070300, SS1140, DX barrel chiller BACnet
Source document
Main DX Barrel Chiller Controller Technical Guide · G070300 Rev. B · rev. 2021-11
Download CSV 524 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.

BMS integration notes: AAON Main DX Barrel Chiller Controller

Integration in brief

Connect the on-board MS/TP port and set MAC address, device ID and baud on the LCD. The BAS runs the chiller with AV 81 Auto/Run/Off and reads the unit mode, leaving water temperature and alarm status. Leaving water reset limits are AV 1 and AV 2.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 81Auto/Run/Off CommandChiller command: 0 auto, 1 run, 2 offWrite
AV 80Reset Unit Lockout { 1 = Reset }Write 1 to reset a unit lockoutWrite
MI 1Operating StatusCurrent unit modeRead
BI 8Chiller Running On/Off StatusChiller runningRead
AI 4Leaving Water SetpointLeaving water setpoint in useRead
AI 2Entering Water TemperatureEntering water temperatureRead
AI 3Leaving Water TemperatureLeaving water temperatureRead
BI 2Proof of Water Flow #1Proof of water flow, barrel 1Read
BI 4Emergency ShutdownEmergency shutdown inputRead

Enable & remote start

AV 81 Auto/Run/Off Command (0 = Auto, 1 = Run, 2 = Off) runs the chiller from the BAS; BI 1 shows the Run/Stop input and BI 6/7 the barrel disable commands. AV 80 resets a unit lockout.

Network setup

Watch out for

AAON Main DX Barrel Chiller Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

524 of 524 shown
Type
BinaryMulti-state
Access
Show
AAON Main DX Barrel Chiller Controller BACnet Points List
DescriptionStates
AI1Application VersionRead
AImin2Entering Water TemperatureRead
AImin3Leaving Water TemperatureRead
AImin4Leaving Water SetpointRead
AI5Barrel #1 Leaving Water TemperatureRead
AI6Barrel #2 Leaving Water TemperatureRead
AI7Barrel Leaving Water SetpointRead
AI8Outdoor Air TemperatureRead
AI9Flow RateRead
AI10Vestibule #1 TemperatureRead
AI11Vestibule #2 TemperatureRead
AI20Building Pump Suction PressureRead
AI21Building Pump Discharge PressureRead
AI22Building Pump Differential PressureRead
AI23Building Pump VFD SignalRead
AI24Building Pump Bypass Valve PositionRead
AI30Waterside Economizer Primary 3-Way ValveRead
AI31Waterside Economizer Secondary 3-Way ValveRead
AI32Waterside Economizer Heat Exchanger Waterside OutletRead
AI33Waterside Economizer Heat Exchanger Glycol Side OutletRead
AI34Waterside Economizer Heat Exchanger Glycol Side InletRead
AI35Waterside Economizer Primary Valve Outlet TemperatureRead
AI36Waterside Economizer Fan SpeedRead
AI40EVAP Sump Temperature #1Read
AI41EVAP Sump Temperature #2Read
AI42EVAP Sump Temperature #3Read
AI43EVAP Pump #1 AmpsRead
AI44EVAP Pump #2 AmpsRead
AI45EVAP Pump #1 VFD SignalRead
AI46EVAP Pump #2 VFD SignalRead
AI50Superheat SetpointRead
AI51Head Pressure SetpointRead
AI60B1:C1 Suction PressureRead
AI61B1:C1 Discharge PressureRead
AI62B1:C1 Liquid Line PressureRead
AI63B1:C1 Calculated Saturation TempRead
AI64B1:C1 Calculated Discharge TempRead
AI65B1:C1 Calculated Liquid Line TempRead
AI66B1:C1 Suction Line TempRead
AI67B1:C1 Discharge Line TempRead
AI68B1:C1 Liquid Line TempRead
AI69B1:C1 Superheat TempRead
AI70B1:C1 Discharge Superheat TempRead
AI71B1:C1 Sub-cooling TempRead
AI72B1:C1 Compressor A1 PercentageRead
AI73B1:C1 Compressor A2 PercentageRead
AI74B1:C1 Condenser PercentageRead
AI75B1:C1 Electronic Expansion Valve PositionRead
AI76B1:C1 Compressor 1 CurrentRead
AI77B1:C1 Compressor 2 CurrentRead
AI90B2:C1 Suction PressureRead
AI91B2:C1 Discharge PressureRead
AI92B2:C1 Liquid Line PressureRead
AI93B2:C1 Calculated Saturation TempRead
AI94B2:C1 Calculated Discharge TempRead
AI95B2:C1 Calculated Liquid Line TempRead
AI96B2:C1 Suction Line TempRead
AI97B2:C1 Discharge Line TempRead
AI98B2:C1 Liquid Line TempRead
AI99B2:C1 Superheat TempRead
AI100B2:C1 Discharge Superheat TempRead
AI101B2:C1 Sub-cooling TempRead
AI102B2:C1 Compressor A1 PercentageRead
AI103B2:C1 Compressor A2 PercentageRead
AI104B2:C1 Condenser PercentageRead
AI105B2:C1 Electronic Expansion Valve PositionRead
AI106B2:C1 Compressor 1 CurrentRead
AI107B2:C1 Compressor 2 CurrentRead
AI120B1:C2 Suction PressureRead
AI121B1:C2 Discharge PressureRead
AI122B1:C2 Liquid Line PressureRead
AI123B1:C2 Calculated Saturation TempRead
AI124B1:C2 Calculated Discharge TempRead
AI125B1:C2 Calculated Liquid Line TempRead
AI126B1:C2 Suction Line TempRead
AI127B1:C2 Discharge Line TempRead
AI128B1:C2 Liquid Line TempRead
AI129B1:C2 Superheat TempRead
AI130B1:C2 Discharge Superheat TempRead
AI131B1:C2 Sub-cooling TempRead
AI132B1:C2 Compressor A1 PercentageRead
AI133B1:C2 Compressor A2 PercentageRead
AI134B1:C2 Condenser PercentageRead
AI135B1:C2 Electronic Expansion Valve PositionRead
AI136B1:C2 Compressor 1 CurrentRead
AI137B1:C2 Compressor 2 CurrentRead
AI150B2:C2 Suction PressureRead
AI151B2:C2 Discharge PressureRead
AI152B2:C2 Liquid Line PressureRead
AI153B2:C2 Calculated Saturation TempRead
AI154B2:C2 Calculated Discharge TempRead
AI155B2:C2 Calculated Liquid Line TempRead
AI156B2:C2 Suction Line TempRead
AI157B2:C2 Discharge Line TempRead
AI158B2:C2 Liquid Line TempRead
AI159B2:C2 Superheat TempRead
AI160B2:C2 Discharge Superheat TempRead
AI161B2:C2 Sub-cooling TempRead
AI162B2:C2 Compressor A1 PercentageRead
AI163B2:C2 Compressor A2 PercentageRead
AI164B2:C2 Condenser PercentageRead
AI165B2:C2 Electronic Expansion Valve PositionRead
AI166B2:C2 Compressor 1 CurrentRead
AI167B2:C2 Compressor 2 CurrentRead
AI190B1:C3 Suction PressureRead
AI191B1:C3 Discharge PressureRead
AI192B1:C3 Liquid Line PressureRead
AI193B1:C3 Calculated Saturation TempRead
AI194B1:C3 Calculated Discharge TempRead
AI195B1:C3 Calculated Liquid Line TempRead
AI196B1:C3 Suction Line TempRead
AI197B1:C3 Discharge Line TempRead
AI198B1:C3 Liquid Line TempRead
AI199B1:C3 Superheat TempRead
AI200B1:C3 Discharge Superheat TempRead
AI201B1:C3 Sub-cooling TempRead
AI202B1:C3 Compressor A1 PercentageRead
AI203B1:C3 Compressor A2 PercentageRead
AI204B1:C3 Condenser PercentageRead
AI205B1:C3 Electronic Expansion Valve PositionRead
AI206B1:C3 Compressor 1 CurrentRead
AI207B1:C3 Compressor 2 CurrentRead
AI220B2:C3 Suction PressureRead
AI221B2:C3 Discharge PressureRead
AI222B2:C3 Liquid Line PressureRead
AI223B2:C3 Calculated Saturation TempRead
AI224B2:C3 Calculated Discharge TempRead
AI225B2:C3 Calculated Liquid Line TempRead
AI226B2:C3 Suction Line TempRead
AI227B2:C3 Discharge Line TempRead
AI228B2:C3 Liquid Line TempRead
AI229B2:C3 Superheat TempRead
AI230B2:C3 Discharge Superheat TempRead
AI231B2:C3 Sub-cooling TempRead
AI232B2:C3 Compressor A1 PercentageRead
AI233B2:C3 Compressor A2 PercentageRead
AI234B2:C3 Condenser PercentageRead
AI235B2:C3 Electronic Expansion Valve PositionRead
AI236B2:C3 Compressor 1 CurrentRead
AI237B2:C3 Compressor 2 CurrentRead
AV1Leaving Water Maximum Reset LimitRange 35° to 60°°FWrite
AV2Leaving Water Minimum Reset LimitRange 35° to 60°°FWrite
AV3Maximum Barrel Setpoint OffsetRange 1° to 10°°FWrite
AV4Compressor Stage Window AboveRange 1° to 20°°FWrite
AV5Compressor Stage Window BelowRange 1° to 20°°FWrite
AV6Low Chilled Water Out Cutoff TempRange 25° to 45°°FWrite
AV7Ambient Air Lockout TemperatureRange -30° to 40°°FWrite
AV8Superheat SetpointRange 1° to 20°°FWrite
AV9Head Pressure SetpointRange 150 psi to 475 psipsiWrite
AV10Discharge Pressure Deadband AboveRange 0 psi to 200 psipsiWrite
AV11Discharge Pressure Deadband BelowRange 0 psi to 200 psipsiWrite
AV12Altitude Above Sea LevelRange 0 to 15,000 FtftWrite
AV20EVAP Sump Heat Enable SetpointRange 38° to 80°°FWrite
AV21EVAP Sump Heat Enable DeadbandRange 1° to 10°°FWrite
AV22EVAP Maximum AmpsRange 0 Amps to 100 AmpsAWrite
AV23EVAP Ambient First Stage EnableRange 35° to 110°°FWrite
AV24EVAP Ambient Condenser LockoutRange -30° to 40°°FWrite
AV30Waterside Economizer Enable DeadbandRange 1° to 10°°FWrite
AV31Waterside Economizer Freeze Protection SetpointRange 0° to 50°°FWrite
AV32Waterside Economizer Heat Exchange Inlet SetpointRange 0° to 50°°FWrite
AV33Waterside Economizer Fan Staging DelayRange 0 Sec to 30 SecsWrite
AV34Waterside Economizer Startup DelayRange 0 Sec to 120 SecsWrite
AV35Waterside Economizer Minimum VFD SpeedRange 0% to 50%%Write
AV36Waterside Economizer Minimum Mixing Valve w/Fan OnRange 0% to 95%%Write
AV37Waterside Economizer Primary 3-Way Valve Slow StartRange 1 Min to 30 MinminWrite
AV38Waterside Economizer Primary 3-Way Valve Slow StopRange 1 Min to 30 MinminWrite
AV39Waterside Economizer Primary Valve Maximum PositionRange 0% to 100%%Write
AV40CPM Reset Alarm History { 1 = Reset }Write0=Log, 1=Reset
AV41CPM Maximum Building PressureRange 10 psi to 200 psipsiWrite
AV42CPM Building Differential Pr. TargetRange 0 psi to 100 psipsiWrite
AV43CPM Minimum Suction PressureRange 0 psi to 100 psipsiWrite
AV44CPM Pump VFD Initial Starting PositionRange 0% to 100%%Write
AV45CPM Pump VFD Minimum PositionRange 0% to 100%%Write
AV50Vestibule 1 Cooling SetpointRange 30° to 90°°FWrite
AV51Vestibule 1 Heating SetpointRange 30° to 90°°FWrite
AV52Vestibule 1 Setpoint DeadbandRange 0.1° to 20°°FWrite
AV53Vestibule 2 Cooling SetpointRange 30° to 90°°FWrite
AV54Vestibule 2 Heating SetpointRange 30° to 90°°FWrite
AV55Vestibule 2 Setpoint DeadbandRange 0.1° to 20°°FWrite
AV60Inlet Water Sensor Calibration OffsetRange -100° to 100°°FWrite
AV61Outlet Water Sensor Calibration OffsetRange -100° to 100°°FWrite
AV62Outdoor Air Sensor Calibration OffsetRange -100° to 100°°FWrite
AV63Barrel 1 Temp Sensor Calibration OffsetRange -100° to 100°°FWrite
AV64Barrel 2 Temp Sensor Calibration OffsetRange -100° to 100°°FWrite
AV65Vestibule 1 Sensor Calibration OffsetRange -100° to 100°°FWrite
AV66Vestibule 2 Sensor Calibration OffsetRange -100° to 100°°FWrite
AV70Compressor Modulation RateRange 1 Sec to 60 SecsWrite
AV71High Outlet Water Temp Failure TimeRange 5 Sec to 600 SecsWrite
AVmin80Reset Unit Lockout { 1 = Reset }Write0=Run, 1=Reset
AVmin81Auto/Run/Off CommandWrite0=Auto, 1=Run, 2=Off
AV82Enable/Disable EVAP Drain ValveWrite0=Off, 1=On
AV83Enable/Disable Main Relay #4Write0=Off, 1=On
AV84Enable/Disable Main Relay #5Write0=Off, 1=On
AV85Enable/Disable Main Relay #6Write0=Off, 1=On
AV86Enable/Disable Main Relay #7Write0=Off, 1=On
AV87Enable/Disable Main Relay #8Write0=Off, 1=On
AV88Set Analog Output #1 VoltageRange 0 to 100Write
AV89Set Analog Output #2 VoltageRange 0 to 100Write
AV90Set Analog Output #3 VoltageRange 0 to 100Write
AV91Set Analog Output #4 VoltageRange 0 to 100Write
BI1Run/Stop Input CommandStatusRead
BImin2Proof of Water Flow #1StatusRead
BI3Proof of Water Flow #2StatusRead
BImin4Emergency ShutdownStatusRead
BI5Phase LossStatusRead
BI6Barrel #1 Disable CommandStatusRead
BI7Barrel #2 Disable CommandStatusRead
BImin8Chiller Running On/Off StatusStatusRead
BI9Chiller Fully Loaded StatusStatusRead
BI10Waterside Economizer Fan Run StatusStatusRead
BI11Waterside Economizer at Maximum CapacityStatusRead
BI12Waterside Economizer Secondary Pump StatusStatusRead
BI13Waterside Economizer Alarm Not OperatingAlarmRead
BI14Waterside Economizer Alarm Freeze ProtectionAlarmRead
BI15Waterside Economizer Alarm Primary Outlet SensorAlarmRead
BI16Waterside Economizer Alarm HE Waterside Outlet SensorAlarmRead
BI17Waterside Economizer Alarm HE Glycol Inlet SensorAlarmRead
BI18Waterside Economizer Alarm HE Glycol Outlet SensorAlarmRead
BI19Waterside Economizer Alarm VFD FaultAlarmRead
BI20Chiller Pumping Module Water Flow ProvingStatusRead
BI21Chiller Pumping Module Primary A Pump 1 StatusStatusRead
BI22Chiller Pumping Module Primary A Pump 2 StatusStatusRead
BI23Chiller Pumping Module Secondary Pump 1 StatusStatusRead
BI24Chiller Pumping Module Secondary Pump 2 StatusStatusRead
BI25Chiller Pumping Module Primary B Pump 1 StatusStatusRead
BI26Chiller Pumping Module Primary B Pump 2 StatusStatusRead
BI27Chiller Pumping Module Alarm Primary Pump A1 Locked OutAlarmRead
BI28Chiller Pumping Module Alarm Primary Pump A2 Locked OutAlarmRead
BI29Chiller Pumping Module Alarm Secondary Pump 1 Locked OutAlarmRead
BI30Chiller Pumping Module Alarm Secondary Pump 2 Locked OutAlarmRead
BI31Chiller Pumping Module Alarm Primary Pump B1 Locked OutAlarmRead
BI32Chiller Pumping Module Alarm Primary Pump B2 Locked OutAlarmRead
BI33Chiller Pumping Module Alarm Maximum Pressure ExceededAlarmRead
BI34Chiller Pumping Module Alarm Pumps Locked OutAlarmRead
BI35Chiller Pumping Module Alarm Glycol Feeder LowAlarmRead
BI40Evaporator Low Sump Input StatusStatusRead
BI41Evaporator Pump 1 Pressure StatusStatusRead
BI42Evaporator Pump 1 VFD Fault StatusStatusRead
BI43Evaporator Pump 2 Pressure StatusStatusRead
BI44Evaporator Pump 2 VFD Fault StatusStatusRead
BI45Evaporator Condenser Pump 1StatusRead
BI46Evaporator Condenser Pump 2StatusRead
BI47Evaporator Sump HeaterStatusRead
BI48Evaporator Drain ValveStatusRead
BI49Evaporator Alarm Low Sump LevelAlarmRead
BI50Evaporator Alarm No Pump 1 Pressure SignalAlarmRead
BI51Evaporator Alarm No Pump 2 Pressure SignalAlarmRead
BI52Evaporator Alarm Pump 1 VFD FaultAlarmRead
BI53Evaporator Alarm Pump 2 VFD FaultAlarmRead
BI54Evaporator Alarm Missing Sump Temperature Sensor #1AlarmRead
BI55Evaporator Alarm Missing Sump Temperature Sensor #2AlarmRead
BI56Evaporator Alarm Missing Sump Temperature Sensor #3AlarmRead
BI57Evaporator Alarm Condenser 1 LockoutAlarmRead
BI58Evaporator Alarm Condenser 2 LockoutAlarmRead
BI59Evaporator Alarm Low Sump TemperatureAlarmRead
BI60Evaporator Alarm Pump 1 Low CurrentAlarmRead
BI61Evaporator Alarm Pump 1 High CurrentAlarmRead
BI62Evaporator Alarm Pump 2 Low CurrentAlarmRead
BI63Evaporator Alarm Pump 2 High CurrentAlarmRead
BI70B1:C1 Module EnabledStatusRead
BI71B1:C1 Compressor #1 StatusStatusRead
BI72B1:C1 Compressor #2 StatusStatusRead
BI73B2:C1 Module EnabledStatusRead
BI74B2:C1 Compressor #1 StatusStatusRead
BI75B2:C1 Compressor #2 StatusStatusRead
BI76B1:C2 Module EnabledStatusRead
BI77B1:C2 Compressor #1 StatusStatusRead
BI78B1:C2 Compressor #2 StatusStatusRead
BI79B2:C2 Module EnabledStatusRead
BI80B2:C2 Compressor #1 StatusStatusRead
BI81B2:C2 Compressor #2 StatusStatusRead
BI82B1:C3 Module EnabledStatusRead
BI83B1:C3 Compressor #1 StatusStatusRead
BI84B1:C3 Compressor #2 StatusStatusRead
BI85B2:C3 Module EnabledStatusRead
BI86B2:C3 Compressor #1 StatusStatusRead
BI87B2:C3 Compressor #2 StatusStatusRead
BI90B1:C1 Fault Low SuctionFaultRead
BI91B1:C1 Fault Unsafe SuctionFaultRead
BI92B1:C1 Fault Trip High Discharge PressureFaultRead
BI93B1:C1 Fault Compressor 1 Not RunningFaultRead
BI94B1:C1 Fault Compressor 2 Not RunningFaultRead
BI95B1:C1 Fault No Suction Line Temperature SensorFaultRead
BI96B1:C1 Fault Low SuperheatFaultRead
BI97B1:C1 Fault High Discharge TemperatureFaultRead
BI98B1:C1 Fault High Discharge psi TripFaultRead
BI99B1:C1 Fault Compressor 1 False ActiveFaultRead
BI100B1:C1 Fault Compressor 2 False ActiveFaultRead
BI101B1:C1 Fault No Suction Pressure SensorFaultRead
BI102B1:C1 Fault Emergency ShutdownFaultRead
BI103B1:C1 Fault Modbus Slave TimeoutFaultRead
BI104B1:C1 Fault High SuperheatFaultRead
BI105B1:C1 Fault High Saturation TemperatureFaultRead
BI106B1:C1 Fault Compressor 1 Over CurrentFaultRead
BI107B1:C1 Fault Compressor 2 Over CurrentFaultRead
BI108B1:C1 Fault Compressor 1 Under CurrentFaultRead
BI109B1:C1 Fault Compressor 2 Under CurrentFaultRead
BI110B1:C1 Warning Low Suction PressureWarningRead
BI111B1:C1 Warning Low Suction Pressure StartupWarningRead
BI112B1:C1 Warning High Discharge PressureWarningRead
BI113B1:C1 Warning No Discharge Pressure SensorWarningRead
BI114B1:C1 Warning No Discharge Temperature SensorWarningRead
BI115B1:C1 Warning High SuperheatWarningRead
BI116B1:C1 Warning Condenser FaultWarningRead
BI117B1:C1 Warning No Liquid Line Pressure SensorWarningRead
BI118B1:C1 Warning No Liquid Line Temperature SensorWarningRead
BI119B1:C1 Warning High Discharge Pressure 2WarningRead
BI120B1:C1 Lockout Suction PressureLockoutRead
BI121B1:C1 Lockout Low Discharge PressureLockoutRead
BI122B1:C1 Lockout Compressor 1 Over CurrentLockoutRead
BI123B1:C1 Lockout Compressor 2 Over CurrentLockoutRead
BI124B1:C1 Lockout High Discharge TemperatureLockoutRead
BI125B1:C1 Lockout High Discharge PressureLockoutRead
BI126B1:C1 Lockout Low SuperheatLockoutRead
BI127B1:C1 Lockout High SuperheatLockoutRead
BI128B1:C1 Lockout High Saturation TemperatureLockoutRead
BI129B1:C1 Lockout Compressor 1 Under CurrentLockoutRead
BI130B1:C1 Lockout Compressor 2 Under CurrentLockoutRead
BI131B2:C1 Fault Low SuctionFaultRead
BI132B2:C1 Fault Unsafe SuctionFaultRead
BI133B2:C1 Fault Trip High Discharge PressureFaultRead
BI134B2:C1 Fault Compressor 1 Not RunningFaultRead
BI135B2:C1 Fault Compressor 2 Not RunningFaultRead
BI136B2:C1 Fault No Suction Line Temperature SensorFaultRead
BI137B2:C1 Fault Low SuperheatFaultRead
BI138B2:C1 Fault High Discharge TemperatureFaultRead
BI139B2:C1 Fault High Discharge psi TripFaultRead
BI140B2:C1 Fault Compressor 1 False ActiveFaultRead
BI141B2:C1 Fault Compressor 2 False ActiveFaultRead
BI142B2:C1 Fault No Suction Pressure SensorFaultRead
BI143B2:C1 Fault Emergency ShutdownFaultRead
BI144B2:C1 Fault Modbus Slave TimeoutFaultRead
BI145B2:C1 Fault High SuperheatFaultRead
BI146B2:C1 Fault High Saturation TemperatureFaultRead
BI147B2:C1 Fault Compressor 1 Over CurrentFaultRead
BI148B2:C1 Fault Compressor 2 Over CurrentFaultRead
BI149B2:C1 Fault Compressor 1 Under CurrentFaultRead
BI150B2:C1 Fault Compressor 2 Under CurrentFaultRead
BI151B2:C1 Warning Low Suction PressureWarningRead
BI152B2:C1 Warning Low Suction Pressure StartupWarningRead
BI153B2:C1 Warning High Discharge PressureWarningRead
BI154B2:C1 Warning No Discharge Pressure SensorWarningRead
BI155B2:C1 Warning No Discharge Temperature SensorWarningRead
BI156B2:C1 Warning High SuperheatWarningRead
BI157B2:C1 Warning Condenser FaultWarningRead
BI158B2:C1 Warning No Liquid Line Pressure SensorWarningRead
BI159B2:C1 Warning No Liquid Line Temperature SensorWarningRead
BI160B2:C1 Warning High Discharge Pressure 2WarningRead
BI161B2:C1 Lockout Suction PressureLockoutRead
BI162B2:C1 Lockout Low Discharge PressureLockoutRead
BI163B2:C1 Lockout Compressor 1 Over CurrentLockoutRead
BI164B2:C1 Lockout Compressor 2 Over CurrentLockoutRead
BI165B2:C1 Lockout High Discharge TemperatureLockoutRead
BI166B2:C1 Lockout High Discharge PressureLockoutRead
BI167B2:C1 Lockout Low SuperheatLockoutRead
BI168B2:C1 Lockout High SuperheatLockoutRead
BI169B2:C1 Lockout High Saturation TemperatureLockoutRead
BI170B2:C1 Lockout Compressor 1 Under CurrentLockoutRead
BI171B2:C1 Lockout Compressor 2 Under CurrentLockoutRead
BI172B1:C2 Fault Low SuctionFaultRead
BI173B1:C2 Fault Unsafe SuctionFaultRead
BI174B1:C2 Fault Trip High Discharge PressureFaultRead
BI175B1:C2 Fault Compressor 1 Not RunningFaultRead
BI176B1:C2 Fault Compressor 2 Not RunningFaultRead
BI177B1:C2 Fault No Suction Line Temperature SensorFaultRead
BI178B1:C2 Fault Low SuperheatFaultRead
BI179B1:C2 Fault High Discharge TemperatureFaultRead
BI180B1:C2 Fault High Discharge psi TripFaultRead
BI181B1:C2 Fault Compressor 1 False ActiveFaultRead
BI182B1:C2 Fault Compressor 2 False ActiveFaultRead
BI183B1:C2 Fault No Suction Pressure SensorFaultRead
BI184B1:C2 Fault Emergency ShutdownFaultRead
BI185B1:C2 Fault Modbus Slave TimeoutFaultRead
BI186B1:C2 Fault High SuperheatFaultRead
BI187B1:C2 Fault High Saturation TemperatureFaultRead
BI188B1:C2 Fault Compressor 1 Over CurrentFaultRead
BI189B1:C2 Fault Compressor 2 Over CurrentFaultRead
BI190B1:C2 Fault Compressor 1 Under CurrentFaultRead
BI191B1:C2 Fault Compressor 2 Under CurrentFaultRead
BI192B1:C2 Warning Low Suction PressureWarningRead
BI193B1:C2 Warning Low Suction Pressure StartupWarningRead
BI194B1:C2 Warning High Discharge PressureWarningRead
BI195B1:C2 Warning No Discharge Pressure SensorWarningRead
BI196B1:C2 Warning No Discharge Temperature SensorWarningRead
BI197B1:C2 Warning High SuperheatWarningRead
BI198B1:C2 Warning Condenser FaultWarningRead
BI199B1:C2 Warning No Liquid Line Pressure SensorWarningRead
BI200B1:C2 Warning No Liquid Line Temperature SensorWarningRead
BI201B1:C2 Warning High Discharge Pressure 2WarningRead
BI202B1:C2 Lockout Suction PressureLockoutRead
BI203B1:C2 Lockout Low Discharge PressureLockoutRead
BI204B1:C2 Lockout Compressor 1 Over CurrentLockoutRead
BI205B1:C2 Lockout Compressor 2 Over CurrentLockoutRead
BI206B1:C2 Lockout High Discharge TemperatureLockoutRead
BI207B1:C2 Lockout High Discharge PressureLockoutRead
BI208B1:C2 Lockout Low SuperheatLockoutRead
BI209B1:C2 Lockout High SuperheatLockoutRead
BI210B1:C2 Lockout High Saturation TemperatureLockoutRead
BI211B1:C2 Lockout Compressor 1 Under CurrentLockoutRead
BI212B2:C3 Lockout Compressor 2 Under CurrentLockoutRead
BI213B2:C2 Fault Low SuctionFaultRead
BI214B2:C2 Fault Unsafe SuctionFaultRead
BI215B2:C2 Fault Trip High Discharge PressureFaultRead
BI216B2:C2 Fault Compressor 1 Not RunningFaultRead
BI217B2:C2 Fault Compressor 2 Not RunningFaultRead
BI218B2:C2 Fault No Suction Line Temperature SensorFaultRead
BI219B2:C2 Fault Low SuperheatFaultRead
BI220B2:C2 Fault High Discharge TemperatureFaultRead
BI221B2:C2 Fault High Discharge psi TripFaultRead
BI222B2:C2 Fault Compressor 1 False ActiveFaultRead
BI223B2:C2 Fault Compressor 2 False ActiveFaultRead
BI224B2:C2 Fault No Suction Pressure SensorFaultRead
BI225B2:C2 Fault Emergency ShutdownFaultRead
BI226B2:C2 Fault Modbus Slave TimeoutFaultRead
BI227B2:C2 Fault High SuperheatFaultRead
BI228B2:C2 Fault High Saturation TemperatureFaultRead
BI229B2:C2 Fault Compressor 1 Over CurrentFaultRead
BI230B2:C2 Fault Compressor 2 Over CurrentFaultRead
BI231B2:C2 Fault Compressor 1 Under CurrentFaultRead
BI232B2:C2 Fault Compressor 2 Under CurrentFaultRead
BI233B2:C2 Warning Low Suction PressureWarningRead
BI234B2:C2 Warning Low Suction Pressure StartupWarningRead
BI235B2:C2 Warning High Discharge PressureWarningRead
BI236B2:C2 Warning No Discharge Pressure SensorWarningRead
BI237B2:C2 Warning No Discharge Temperature SensorWarningRead
BI238B2:C2 Warning High SuperheatWarningRead
BI239B2:C2 Warning Condenser FaultWarningRead
BI240B2:C2 Warning No Liquid Line Pressure SensorWarningRead
BI241B2:C2 Warning No Liquid Line Temperature SensorWarningRead
BI242B2:C2 Warning High Discharge Pressure 2WarningRead
BI243B2:C2 Lockout Suction PressureLockoutRead
BI244B2:C2 Lockout Low Discharge PressureLockoutRead
BI245B2:C2 Lockout Compressor 1 Over CurrentLockoutRead
BI246B2:C2 Lockout Compressor 2 Over CurrentLockoutRead
BI247B2:C2 Lockout High Discharge TemperatureLockoutRead
BI248B2:C2 Lockout High Discharge PressureLockoutRead
BI249B2:C2 Lockout Low SuperheatLockoutRead
BI250B2:C2 Lockout High SuperheatLockoutRead
BI251B2:C2 Lockout High Saturation TemperatureLockoutRead
BI252B2:C2 Lockout Compressor 1 Under CurrentLockoutRead
BI253B2:C3 Lockout Compressor 2 Under CurrentLockoutRead
BI254B1:C3 Fault Low SuctionFaultRead
BI255B1:C3 Fault Unsafe SuctionFaultRead
BI256B1:C3 Fault Trip High Discharge PressureFaultRead
BI257B1:C3 Fault Compressor 1 Not RunningFaultRead
BI258B1:C3 Fault Compressor 2 Not RunningFaultRead
BI259B1:C3 Fault No Suction Line Temperature SensorFaultRead
BI260B1:C3 Fault Low SuperheatFaultRead
BI261B1:C3 Fault High Discharge TemperatureFaultRead
BI262B1:C3 Fault High Discharge psi TripFaultRead
BI263B1:C3 Fault Compressor 1 False ActiveFaultRead
BI264B1:C3 Fault Compressor 2 False ActiveFaultRead
BI265B1:C3 Fault No Suction Pressure SensorFaultRead
BI266B1:C3 Fault Emergency ShutdownFaultRead
BI267B1:C3 Fault Modbus Slave TimeoutFaultRead
BI268B1:C3 Fault High SuperheatFaultRead
BI269B1:C3 Fault High Saturation TemperatureFaultRead
BI270B1:C3 Fault Compressor 1 Over CurrentFaultRead
BI271B1:C3 Fault Compressor 2 Over CurrentFaultRead
BI272B1:C3 Fault Compressor 1 Under CurrentFaultRead
BI273B1:C3 Fault Compressor 2 Under CurrentFaultRead
BI274B1:C3 Warning Low Suction PressureWarningRead
BI275B1:C3 Warning Low Suction Pressure StartupWarningRead
BI276B1:C3 Warning High Discharge PressureWarningRead
BI277B1:C3 Warning No Discharge Pressure SensorWarningRead
BI278B1:C3 Warning No Discharge Temperature SensorWarningRead
BI279B1:C3 Warning High SuperheatWarningRead
BI280B1:C3 Warning Condenser FaultWarningRead
BI281B1:C3 Warning No Liquid Line Pressure SensorWarningRead
BI282B1:C3 Warning No Liquid Line Temperature SensorWarningRead
BI283B1:C3 Warning High Discharge Pressure 2WarningRead
BI284B1:C3 Lockout Suction PressureLockoutRead
BI285B1:C3 Lockout Low Discharge PressureLockoutRead
BI286B1:C3 Lockout Compressor 1 Over CurrentLockoutRead
BI287B1:C3 Lockout Compressor 2 Over CurrentLockoutRead
BI288B1:C3 Lockout High Discharge TemperatureLockoutRead
BI289B1:C3 Lockout High Discharge PressureLockoutRead
BI290B1:C3 Lockout Low SuperheatLockoutRead
BI291B1:C3 Lockout High SuperheatLockoutRead
BI292B1:C3 Lockout High Saturation TemperatureLockoutRead
BI293B1:C3 Lockout Compressor 1 Under CurrentLockoutRead
BI294B1:C3 Lockout Compressor 2 Under CurrentLockoutRead
BI295B2:C3 Fault Low SuctionFaultRead
BI296B2:C3 Fault Unsafe SuctionFaultRead
BI297B2:C3 Fault Trip High Discharge PressureFaultRead
BI298B2:C3 Fault Compressor 1 Not RunningFaultRead
BI299B2:C3 Fault Compressor 2 Not RunningFaultRead
BI300B2:C3 Fault No Suction Line Temperature SensorFaultRead
BI301B2:C3 Fault Low SuperheatFaultRead
BI302B2:C3 Fault High Discharge TemperatureFaultRead
BI303B2:C3 Fault High Discharge psi TripFaultRead
BI304B2:C3 Fault Compressor 1 False ActiveFaultRead
BI305B2:C3 Fault Compressor 2 False ActiveFaultRead
BI306B2:C3 Fault No Suction Pressure SensorFaultRead
BI307B2:C3 Fault Emergency ShutdownFaultRead
BI308B2:C3 Fault Modbus Slave TimeoutFaultRead
BI309B2:C3 Fault High SuperheatFaultRead
BI310B2:C3 Fault High Saturation TemperatureFaultRead
BI311B2:C3 Fault Compressor 1 Over CurrentFaultRead
BI312B2:C3 Fault Compressor 2 Over CurrentFaultRead
BI313B2:C3 Fault Compressor 1 Under CurrentFaultRead
BI314B2:C3 Fault Compressor 2 Under CurrentFaultRead
BI315B2:C3 Warning Low Suction PressureWarningRead
BI316B2:C3 Warning Low Suction Pressure StartupWarningRead
BI317B2:C3 Warning High Discharge PressureWarningRead
BI318B2:C3 Warning No Discharge Pressure SensorWarningRead
BI319B2:C3 Warning No Discharge Temperature SensorWarningRead
BI320B2:C3 Warning High SuperheatWarningRead
BI321B2:C3 Warning Condenser FaultWarningRead
BI322B2:C3 Warning No Liquid Line Pressure SensorWarningRead
BI323B2:C3 Warning No Liquid Line Temperature SensorWarningRead
BI324B2:C3 Warning High Discharge Pressure 2WarningRead
BI325B2:C3 Lockout Suction PressureLockoutRead
BI326B2:C3 Lockout Low Discharge PressureLockoutRead
BI327B2:C3 Lockout Compressor 1 Over CurrentLockoutRead
BI328B2:C3 Lockout Compressor 2 Over CurrentLockoutRead
BI329B2:C3 Lockout High Discharge TemperatureLockoutRead
BI330B2:C3 Lockout High Discharge PressureLockoutRead
BI331B2:C3 Lockout Low SuperheatLockoutRead
BI332B2:C3 Lockout High SuperheatLockoutRead
BI333B2:C3 Lockout High Saturation TemperatureLockoutRead
BI334B2:C3 Lockout Compressor 1 Under CurrentLockoutRead
BI335B2:C3 Lockout Compressor 2 Under CurrentLockoutRead
MImin1Operating StatusCurrent unit modeRead1=OFF_MODE, 2=RUN MODE, 3=Holiday OFF MODE, 4=Holiday RUN MODE, 5=Startup Delay, 6=Emergency Shutdown, 7=High Leaving Water
Object ID lookup: AAON Main DX Barrel Chiller Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Main DX Barrel Chiller Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AAON Main DX Barrel Chiller Controller

How many BACnet points does the AAON Main DX Barrel Chiller Controller have?

This list has 524 BACnet objects: 140 analog inputs, 60 analog values, 323 binary inputs, 1 multi-state input. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AAON Main DX Barrel Chiller Controller BACnet points are writable?

60 of the 524 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official AAON Main DX Barrel Chiller Controller BACnet documentation?

The source is Main DX Barrel Chiller Controller Technical Guide (G070300 Rev. B), revision 2021-11, published free by AAON at https://www.aaon.com/hubfs/Controls%20Literature/G070300_DX-Barrel-B_TGD.pdf.

What are the minimum BACnet points to integrate the AAON Main DX Barrel Chiller Controller?

Start with AV 81 Auto/Run/Off Command (Chiller command: 0 auto, 1 run, 2 off); AV 80 Reset Unit Lockout { 1 = Reset } (Write 1 to reset a unit lockout); MI 1 Operating Status (Current unit mode); BI 8 Chiller Running On/Off Status (Chiller running); AI 4 Leaving Water Setpoint (Leaving water setpoint in use); AI 2 Entering Water Temperature (Entering water temperature); AI 3 Leaving Water Temperature (Leaving water temperature); BI 2 Proof of Water Flow #1 (Proof of water flow, barrel 1); BI 4 Emergency Shutdown (Emergency shutdown input).

How do I enable BMS control of the AAON Main DX Barrel Chiller Controller?

AV 81 Auto/Run/Off Command (0 = Auto, 1 = Run, 2 = Off) runs the chiller from the BAS; BI 1 shows the Run/Stop input and BI 6/7 the barrel disable commands. AV 80 resets a unit lockout.

How do I check these points on the real Main DX Barrel Chiller Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AAON BACnet points lists

Source: Main DX Barrel Chiller Controller Technical Guide · G070300 Rev. B · rev. 2021-11. Object names, instances and units are reproduced as published; descriptions are our own.