  4. VCCX2 Controller

Rooftop unit / air handler controller · BACnet points list

AAON VCCX2 Controller BACnet points list

Updated 28 October 2026

Short answer

The VCCX2 is AAON's main unit controller and has an on-board BACnet MS/TP port. Its object map has about 280 read-only analog inputs (temperatures, pressures, airflow, compressor and refrigerant module data), about 100 writable analog values (setpoints, offsets, overrides and BAS-supplied sensor values) and about 150 read-only binary inputs (alarms, relay and module status).

This page lists 534 BACnet objects for the AAON VCCX2 Controller — 99 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.

Manufacturer
AAON
Model
VCCX2 Controller
Equipment
Rooftop unit / air handler controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
534 (99 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
VCC-X2, VCCX, VCC-X, ASM01698, Orion VCCX2, SS1088
Source document
VCCX2 Controller Technical Guide (Appendix C: BACnet Guide) · G115820 · rev. Rev. AA, January 7, 2025
Download CSV 534 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: AAON VCCX2 Controller

Integration in brief

Connect the on-board MS/TP port and set MAC address, device ID and baud on the controller's LCD BACnet screens. The BAS schedules the unit with AV 67 Schedule Force, adjusts setpoints with the occupied heating/cooling and supply-air AVs, and can supply sensor values through AV 72-79 when the controller is configured for it. Alarms are read from the BI objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 67Schedule ForceOccupied/unoccupied command from the BASWrite
AV 1Occupied Cooling SetpointCooling starts one deadband above this, °FWrite
AV 2Occupied Heating SetpointHeating starts one deadband below this, °FWrite
AV 10Supply Air Cooling SetpointDischarge air temp target in cooling, °FWrite
AI 3Control StatusCurrent occupancy statusRead
AI 4HVAC ModeOff, vent, cool, heat, dehum, purge or defrost modeRead
AI 5Control TemperatureReading from the configured control sensorRead
AI 9Supply Air TemperatureDischarge air temp leaving the unitRead
AI 144Alarm StatusSummary alarmRead

Enable & remote start

Occupancy comes from AV 67 Schedule Force (0 = follow the controller schedule, 1 = forced occupied, 2 = forced unoccupied), the internal week schedule, a GPC-XP broadcast schedule, or the BI4 remote forced occupied contact. AV 68, AV 69, AV 70 and AV 71 override HVAC mode, fan VFD, OA damper and supply setpoint; writing Auto (0 or 65535 as listed) hands control back.

Sensors & values from the BMS

If the controller is configured for it, the BAS can write AV 72 Space Temperature, AV 73 Space Humidity, AV 76 Relief Pressure, AV 77 CO2, AV 78 Outdoor Air Temperature and AV 79 Outdoor Air Humidity; these are the only sensor values the BAS may write. The guide gives no refresh timeout for them. A relief pressure value received over BACnet that is out of range raises an alarm.

Network setup

Watch out for

AAON VCCX2 Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

534 of 534 shown
Type
Binary
Access
Show
AAON VCCX2 Controller BACnet Points List
DescriptionStates
AI1Application Software VersionCurrent version of the software in the unitRead
AI2Control ModeConfigured unit applicationRead0=Supply Air Cooling Only, 1=Supply Air Tempering, 2=Outdoor Temperature Control, 3=Return Air Constant Volume Mode, 4=Space Temp Constant Volume Mode, 5=Space Temp w/ High OA Content, 6=Single Zone VAV
AImin3Control StatusCurrent Occupied/Unoccupied StatusRead0=Unoccupied, 1=Occupied, 2=Override Mode, 3=Holiday Unoccupied, 4=Holiday Occupied, 5=Forced Occupied, 6=Forced Unoccupied, 7=Remote Contact Occupied, 8-10=Reserved, 11=OA Damper Calibration
AImin4HVAC ModeCurrent operational statusRead0=Off, 1=Vent Mode, 2=Cooling Mode, 3=Heating Mode, 4=Vent RH Mode, 5=Cooling RH Mode, 6=Heating RH Mode, 7=Warm Up Mode, 8=Purge Mode, 9=Defrost Mode, 10=Cool Down Mode
AImin5Control TemperatureControl Temperature SensorRead
AI6Mode Cooling SetpointCooling Mode Enable Setpoint Mirror (adjusted by the Space Sensor Slide adjustmentRead
AI7Mode Heating SetpointHeating Mode Enable Setpoint Mirror (adjusted by the Space Sensor Slide adjustmentRead
AI8Sensor Slide Adjust EffectAmount of Current Sensor Slide AdjustRead
AImin9Supply Air TemperatureSupply Air Temperature sensorRead
AI10Supply Air SetpointCurrent SAT Cooling or Heating Setpoint if there is no reset sourceRead
AI11Controlling Coil Temp SetpointCurrent calculated Coil Suction Temperature target during Dehumidification ModeRead
AI12Space TemperatureSpace Temperature SensorRead
AI13Space HumiditySpace HumidityRead
AI14Return Air TemperatureReturn Temperature SensorRead
AI15Return Air HumidityReturn Air HumidityRead
AI16Outdoor Air TemperatureOutdoor Air Temperature SensorRead
AI17Outdoor Air HumidityOutdoor Humidity SensorRead
AI18Outdoor Air WetbulbCurrent calculated Outdoor Wetbulb TemperatureRead
AI19Outdoor Air DewpointCurrent Calculated Outdoor Air Dewpoint TemperatureRead
AI20Supply Air Setpoint Reset VoltageSupply Air Temp Setpoint Reset Input SignalRead
AI21Duct Static PressureCurrent Duct Static PressureRead
AI22Duct Static Control SignalCurrent Duct Static Control Signal (Fan VFD)Read
AI23Building PressureBuilding Pressure SensorRead
AI24Building Pressure Control SignalCurrent Building Pressure Control SignalRead
AI25Outdoor AirflowCurrent Outdoor Airflow MeasurementRead
AI26Supply AirflowCurrent Supply Airflow MeasurementRead
AI27Return AirflowCurrent Return Airflow MeasurementRead
AI28Exhaust AirflowCurrent Exhaust Airflow MeasurementRead
AI29Carbon DioxideCurrent Indoor CO2 LevelRead
AI30Desired Economizer PositionCurrent Modulating Signal to the Economizer DamperRead
AI31Economizer Feedback PositionTitle 24 current position of feedback from Economizer actuatorRead
AI32Return Damper PositionCurrent Signal to the Return Air Damper if using Return Air BypassRead
AI33Return Bypass PositionCurrent Signal to the Return Air Bypass Damper if using Return AirRead
AI34Modulating Cooling PositionCurrent percentage of the Modulating Chilled Water SignalRead
AI35Modulating Heat PositionCurrent percentage of the Modulating Heating signal (Hot Water or SCR heat)Read
AI36Preheater Leaving Air Temp #1Current Preheater Leaving Air Temperature #1Read
AI37Preheater Leaving Air Temp #2Current Preheater Leaving Air Temperature #2Read
AI38Preheater Entering Air TempCurrent Entering Air Temp for PreheaterRead
AI39Preheater Setpoint Reset VoltageCurrent Voltage Reset Input Value for PreheaterRead
AI40Preheater SCR Output SignalCurrent Modulating Heat Signal for PreheaterRead
AI41Preheater PWM Output SignalCurrent PWM Output Signal for PreheaterRead
AI42Mod Hot Gas Reheat Valve PositionCurrent position of MHGRV Modulating Hot Gas Reheat ValveRead
AI43Mod Gas Heat Valve PositionCurrent position of MODGAS Modulating Gas Valve ControlRead
AI44A1 Compressor SignalCurrent Compressor A1 Modulating Cooling SignalRead
AI45A2 Compressor SignalCurrent Compressor A2 Modulating Cooling SignalRead
AI46A1 Condenser SignalCurrent A1 Condenser SignalRead
AI47A2 Condenser SignalCurrent A2 Condenser Signal or WSE Bypass Valve SignalRead
AI48A1 Suction PressureCurrent Compressor A1 Suction PressureRead
AI49A2 Suction PressureCurrent Compressor A2 Suction PressureRead
AI50A1 Head PressureCurrent Compressor A1 Head PressureRead
AI51A2 Head PressureCurrent Compressor A2 Head PressureRead
AI52A1 Saturation TemperatureCurrent Compressor A1 Coil Saturation TemperatureRead
AI53A2 Saturation TemperatureCurrent Compressor A2 Coil Saturation TemperatureRead
AI54A1 Suction Line TemperatureCurrent Compressor A1 Suction Line TemperatureRead
AI55A2 Suction Line TemperatureCurrent Compressor A2Suction Line TemperatureRead
AI56A1 Condenser Suction Temp (Heat Pump)Current Compressor A1 Suction Line Temperature (Heat Pump)Read
AI57A2 Condenser Suction Temp (Heat Pump)Current Compressor A2 Suction Line Temperature (Heat Pump)Read
AI58A1 Superheat TemperatureCurrent Compressor A1 Superheat TemperatureRead
AI59A2 Superheat TemperatureCurrent Compressor A2 Superheat TemperatureRead
AI60Condenser A1 Superheat (Heat Pump)Current Compressor A1 Superheat Temperature (Heat Pump)Read
AI61Condenser A2 Superheat (Heat Pump)Current Compressor A2 Superheat Temperature (Heat Pump)Read
AI62A1 Expansion Valve PositionCurrent position of Compressor A1 Expansion ValveRead
AI63A2 Expansion Valve PositionCurrent position of Compressor A2 Expansion ValveRead
AI64Condenser A1 Expansion Valve PositionCurrent position of Condenser A1 Expansion ValveRead
AI65Condenser A2 Expansion Valve PositionCurrent position of Condenser A2 Expansion ValveRead
AI66A1 Discharge TemperatureCurrent Compressor A1 Discharge TemperatureRead
AI67A2 Discharge TemperatureCurrent Compressor A2 Discharge TemperatureRead
AI68A1 Leaving Water TempCurrent A1 Leaving Water Temperature for WSHPRead
AI69B1 Compressor SignalCurrent Compressor B1 Modulating Cooling SignalRead
AI70B2 Compressor SignalCurrent Compressor B2 Modulating Cooling SignalRead
AI71B1 Condenser SignalCurrent B1 Condenser SignalRead
AI72B2 Condenser SignalCurrent B2 Condenser Signal or WSE Bypass Valve SignalRead
AI73B1 Suction PressureCurrent Compressor B1 Suction PressureRead
AI74B2 Suction PressureCurrent Compressor B2 Suction PressureRead
AI75B1 Head PressureCurrent Compressor B1 Head PressureRead
AI76B2 Head PressureCurrent Compressor B2 Head PressureRead
AI77B1 Saturation TemperatureCurrent Compressor B1 Coil Saturation TemperatureRead
AI78B2 Saturation TemperatureCurrent Compressor B2 Coil Saturation TemperatureRead
AI79B1 Suction Line TemperatureCurrent Compressor B1 Suction Line TemperatureRead
AI80B2 Suction Line TemperatureCurrent Compressor B2 Suction Line TemperatureRead
AI81B1 Condenser Suction Temp (Heat Pump)Current Compressor B1 Suction Line Temperature (Heat Pump)Read
AI82B2 Condenser Suction Temp (Heat Pump)Current Compressor B2 Suction Line Temperature (Heat Pump)Read
AI83B1 Superheat TemperatureCurrent Compressor B1 Superheat TemperatureRead
AI84B2 Superheat TemperatureCurrent Compressor B2 Superheat TemperatureRead
AI85Condenser B1 Superheat (Heat Pump)Current Compressor B1 Superheat Temperature (Heat Pump)Read
AI86Condenser B2 Superheat (Heat Pump)Current Compressor B2 Superheat Temperature (Heat Pump)Read
AI87B1 Expansion Valve PositionCurrent position of Compressor B1 Expansion ValveRead
AI88B2 Expansion Valve PositionCurrent position of Compressor B2 Expansion ValveRead
AI89Condenser B1 Expansion Valve PositionCurrent position of Condenser B1 Expansion ValveRead
AI90Condenser B2 Expansion Valve PositionCurrent position of Condenser B2 Expansion ValveRead
AI91B1 Discharge TemperatureCurrent Compressor B1 Discharge TemperatureRead
AI92B2 Discharge TemperatureCurrent Compressor B2 Discharge TemperatureRead
AI93B1 Leaving Water TempCurrent B1 Leaving Water Temperature for WSHPRead
AI94C1 Compressor SignalCurrent Compressor C1 Modulating Cooling SignalRead
AI95C2 Compressor SignalCurrent Compressor C2 Modulating Cooling SignalRead
AI96C1 Condenser SignalCurrent C1 Condenser SignalRead
AI97C2 Condenser SignalCurrent C2 Condenser Signal or WSE Bypass Valve SignalRead
AI98C1 Suction PressureCurrent Compressor C1 Suction PressureRead
AI99C2 Suction PressureCurrent Compressor C2 Suction PressureRead
AI100C1 Head PressureCurrent Compressor C1 Head PressureRead
AI101C2 Head PressureCurrent Compressor C2 Head PressureRead
AI102C1 Saturation TemperatureCurrent Compressor C1 Coil Saturation TemperatureRead
AI103C2 Saturation TemperatureCurrent Compressor C2 Coil Saturation TemperatureRead
AI104C1 Suction Line TemperatureCurrent Compressor C1 Suction Line TemperatureRead
AI105C2 Suction Line TemperatureCurrent Compressor C2 Suction Line TemperatureRead
AI106C1 Condenser Suction Temp (Heat Pump)Current Compressor C1 Suction Line Temperature (Heat Pump)Read
AI107C2 Condenser Suction Temp (Heat Pump)Current Compressor C2 Suction Line Temperature (Heat Pump)Read
AI108C1 Superheat TemperatureCurrent Compressor C1 Superheat TemperatureRead
AI109C2 Superheat TemperatureCurrent Compressor C2 Superheat TemperatureRead
AI110Condenser C1 Superheat (Heat Pump)Current Compressor C1 Superheat Temperature (Heat Pump)Read
AI111Condenser C2 Superheat (Heat Pump)Current Compressor C2 Superheat Temperature (Heat Pump)Read
AI112C1 Expansion Valve PositionCurrent position of Compressor C1 Expansion ValveRead
AI113C2 Expansion Valve PositionCurrent position of Compressor C2 Expansion ValveRead
AI114Condenser C1 Expansion Valve PositionCurrent position of Condenser C1 Expansion ValveRead
AI115Condenser C2 Expansion Valve PositionCurrent position of Condenser C2 Expansion ValveRead
AI116C1 Discharge TemperatureCurrent Compressor C1 Discharge TemperatureRead
AI117C2 Discharge TemperatureCurrent Compressor C2 Discharge TemperatureRead
AI118C1 Leaving Water TempCurrent C1 Leaving Water Temperature for WSHPRead
AI119D1 Compressor SignalCurrent Compressor D1 Modulating Cooling SignalRead
AI120D2 Compressor SignalCurrent Compressor D2 Modulating Cooling SignalRead
AI121D1 Condenser SignalCurrent D1 Condenser SignalRead
AI122D2 Condenser SignalCurrent D2 Condenser Signal or WSE Bypass Valve SignalRead
AI123D1 Suction PressureCurrent Compressor D1 Suction PressureRead
AI124D2 Suction PressureCurrent Compressor D2 Suction PressureRead
AI125D1 Head PressureCurrent Compressor D1 Head PressureRead
AI126D2 Head PressureCurrent Compressor D2 Head PressureRead
AI127D1 Saturation TemperatureCurrent Compressor D1 Coil Saturation TemperatureRead
AI128D2 Saturation TemperatureCurrent Compressor D2 Coil Saturation TemperatureRead
AI129D1 Suction Line TemperatureCurrent Compressor D1 Suction Line TemperatureRead
AI130D2 Suction Line TemperatureCurrent Compressor D2 Suction Line TemperatureRead
AI131D1 Condenser Suction Temp (Heat Pump)Current Compressor D1 Suction Line Temperature (Heat Pump)Read
AI132D2 Condenser Suction Temp (Heat Pump)Current Compressor D2 Suction Line Temperature (Heat Pump)Read
AI133D1 Superheat TemperatureCurrent Compressor D1 Superheat TemperatureRead
AI134D2 Superheat TemperatureCurrent Compressor D2 Superheat TemperatureRead
AI135Condenser D1 Superheat (Heat Pump)Current Compressor D1 Superheat Temperature (Heat Pump)Read
AI136Condenser D2 Superheat (Heat Pump)Current Compressor D2 Superheat Temperature (Heat Pump)Read
AI137D1 Expansion Valve PositionCurrent position of Compressor D1 Expansion ValveRead
AI138D2 Expansion Valve PositionCurrent position of Compressor D2 Expansion ValveRead
AI139Condenser D1 Expansion Valve PositionCurrent position of Condenser D1 Expansion ValveRead
AI140Condenser D2 Expansion Valve PositionCurrent position of Condenser D2 Expansion ValveRead
AI141D1 Discharge TemperatureCurrent Compressor D1 Discharge TemperatureRead
AI142D2 Discharge TemperatureCurrent Compressor D2 Discharge TemperatureRead
AI143D1 Leaving Water TempCurrent D1 Leaving Water Temperature for WSHPRead
AImin144Alarm StatusAlarm condition summaryRead0=No Alarms, 1=Alarm(s) Present
AI145Outdoor EnthalpyCurrent Outdoor EnthalpyRead
AI146Plenum PressureReservedRead
AI147Return Fan SpeedReservedRead
AI148Plenum Calculated SetpointReservedRead
AI149Return Air Enthalpy StatusReturn Air EnthalpyRead
AI150Current Duct Static SetpointStatus of the duct static setpointRead
AI151RSMZ 1 Condenser FanCurrent RSMZ 1 condenser fan signalRead
AI152RSMZ 1 VFD Comp PercCurrent RSMZ 1 VFD Compressor PercentageRead
AI153RSMZ 1 Discharge PressureCurrent RSMZ 1 discharge pressureRead
AI154RSMZ 1 Suction PressureCurrent RSMZ 1 Suction PressureRead
AI155RSMZ 1 Suction Line TempCurrent RSMZ 1 Suction Line TemperatureRead
AI156RSMZ 1 Saturation TempCurrent RSMZ 1 Saturation TemperatureRead
AI157RSMZ 1 SuperheatCurrent RSMZ 1 Superheat TemperatureRead
AI158RSMZ 1 EEV PositionCurrent RSMZ 1 EEV Valve PositionRead
AI159RSMZ 1 WarningsCurrent RSMZ 1 WarningsRead
AI160RSMZ 1 Comp VFD Alarms 1Current RSMZ 1 Comp VFD Alarms 1Read
AI161RSMZ 1 Comp VFD Alarms 2Current RSMZ 1 Comp VFD Alarms 2Read
AI162RSMZ 1 Comp VFD Drive StatusCurrent RSMZ 1 Comp VFD drive statusRead
AI163RSMZ 1 Compressor CurrentCurrent reading in Amps that the RSMZ 1 compressor is usingRead
AI164RSMZ 1 Discharge Line TempCurrent RSMZ 1 discharge line temperatureRead
AI165RSMZ 1 FaultsCurrent RSMZ 1 FaultsRead
AI166RSMZ 1 LockoutsCurrent RSMZ 1 LockoutsRead
AI167RSMZ 2 Condenser FanCurrent RSMZ 2 condenser fan signalRead
AI168RSMZ 2 VFD Comp PercCurrent RSMZ 2 VFD Compressor PercentageRead
AI169RSMZ 2 Discharge PressureCurrent RSMZ 2 discharge pressureRead
AI170RSMZ 2 Suction PressureCurrent RSMZ 2 Suction PressureRead
AI171RSMZ 2 Suction Line TempCurrent RSMZ 2 Suction Line TemperatureRead
AI172RSMZ 2 Saturation TempCurrent RSMZ 2 Saturation TemperatureRead
AI173RSMZ 2 SuperheatCurrent RSMZ 2 Superheat temperatureRead
AI174RSMZ 2 EEV PositionCurrent RSMZ 2 EEV valve positionRead
AI175RSMZ 2 WarningsCurrent RSMZ 2 WarningsRead
AI176RSMZ 2 Comp VFD Alarms 1Current RSMZ 2 Comp VFD Alarms 1Read
AI177RSMZ 2 Comp VFD Alarms 2Current RSMZ 2 Comp VFD Alarms 2Read
AI178RSMZ 2 Comp VFD Drive StatusCurrent RSMZ 2 Comp VFD drive statusRead
AI179RSMZ 2 Compressor CurrentCurrent reading in Amps that the RSMZ 2 compressor is usingRead
AI180RSMZ 2 Discharge Line TempCurrent RSMZ 2 discharge line temperatureRead
AI181RSMZ 2 FaultsCurrent RSMZ 2 FaultsRead
AI182RSMZ 2 LockoutsCurrent RSMZ 2 LockoutsRead
AI183RSMZ 3 Condenser FanCurrent RSMZ 3 condenser fan signalRead
AI184RSMZ 3 Reheat Valve 1Current RSMZ 3 Reheat Valve 1 positionRead
AI185RSMZ 3 Discharge PressureCurrent RSMZ 3 discharge pressureRead
AI186RSMZ 3 Suction PressureCurrent RSMZ 3 Suction PressureRead
AI187RSMZ 3 Suction Line TempCurrent RSMZ 3 Suction Line TemperatureRead
AI188RSMZ 3 Saturation TempCurrent RSMZ 3 Saturation TemperatureRead
AI189RSMZ 3 SuperheatCurrent RSMZ 3 Superheat temperatureRead
AI190RSMZ 3 EEV PositionCurrent RSMZ 3 EEV valve positionRead
AI191RSMZ 3 Suction Pressure 2Current RSMZ 3 Suction pressure 2Read
AI192RSMZ 3 Suction Line Temp 2Current RSMZ 3 Suction Line Temperature 2Read
AI193RSMZ 3 Saturation Temp 2Current RSMZ 3 Saturation Temperature 2Read
AI194RSMZ 3 Superheat 2Current RSMZ 3 Superheat Temperature 2Read
AI195RSMZ 3 EEV Position 2Current RSMZ 3 EEV valve position 2Read
AI196RSMZ 3 WarningsCurrent RSMZ 3 WarningsRead
AI197RSMZ 3 Discharge Line TempCurrent RSMZ 3 discharge line temperatureRead
AI198RSMZ 3 FaultsCurrent RSMZ 3 FaultsRead
AI199RSMZ 3 LockoutsCurrent RSMZ 3 LockoutsRead
AI200RSMZ 4 Condenser FanCurrent RSMZ 4 Condenser Fan SignalRead
AI201RSMZ 4 VFD Comp PercCurrent RSMZ 4 VFD Compressor PercentageRead
AI202RSMZ 4 Discharge PressureCurrent RSMZ 4 Discharge PressureRead
AI203RSMZ 4 Suction PressureCurrent RSMZ 4 Suction PressureRead
AI204RSMZ 4 Suction Line TempCurrent RSMZ 4 Suction Line TemperatureRead
AI205RSMZ 4 Saturation TempCurrent RSMZ 4 Saturation TemperatureRead
AI206RSMZ 4 SuperheatCurrent RSMZ 4 Superheat TemperatureRead
AI207RSMZ 4 EEV PositionCurrent RSMZ 4 EEV valve positionRead
AI208RSMZ 4 WarningsCurrent RSMZ 4 WarningsRead
AI209RSMZ 4 Comp VFD Alarms 1Current RSMZ 4 Comp VFD Alarms 1Read
AI210RSMZ 4 Comp VFD Alarms 2Current RSMZ 4 Comp VFD Alarms 2Read
AI211RSMZ 4 Comp VFD Drive StatusCurrent RSMZ 4 Comp VFD drive statusRead
AI212RSMZ 4 Comp VFD Compressor CurrentCurrent reading in Amps that the RSMZ 4 compressor is usingRead
AI213RSMZ 4 Discharge Line TempCurrent RSMZ 4 discharge line temperatureRead
AI214RSMZ 4 FaultsCurrent RSMZ 4 FaultsRead
AI215RSMZ 4 LockoutsCurrent RSMZ 4 LockoutsRead
AI216RSMZ 5 Condenser FanCurrent RSMZ 5 Condenser Fan SignalRead
AI217RSMZ 5 VFD Comp PercCurrent RSMZ 5 VFD Compressor PercentageRead
AI218RSMZ 5 Discharge PressureCurrent RSMZ 5 discharge pressureRead
AI219RSMZ 5 Suction PressureCurrent RSMZ 5 Suction pressureRead
AI220RSMZ 5 Suction Line TempCurrent RSMZ 5 Suction Line TemperatureRead
AI221RSMZ 5 Saturation TempCurrent RSMZ 5 Saturation TemperatureRead
AI222RSMZ 5 SuperheatCurrent RSMZ5 Superheat temperatureRead
AI223RSMZ 5 EEV PositionCurrent RSMZ 5 EEV valve positionRead
AI224RSMZ 5 WarningsCurrent RSMZ 5 WarningsRead
AI225RSMZ 5 Comp VFD Alarms 1Current RSMZ 5 Comp VFD Alarms 1Read
AI226RSMZ 5 Comp Alarms 2Current RSMZ 5 Comp VFD Alarms 2Read
AI227RSMZ 5 Comp VFD Drive StatusCurrent RSMZ 5 Comp VFD drive statusRead
AI228RSMZ 5 Compressor CurrentCurrent reading in Amps that the RSMZ 5 compressor is usingRead
AI229RSMZ 5 Discharge Line TempCurrent RSMZ 5 discharge line temperatureRead
AI230RSMZ 5 FaultsCurrent RSMZ 5 FaultsRead
AI231RSMZ 5 LockoutsCurrent RSMZ 5LockoutsRead
AI232RSMZ 6 Condenser FanCurrent RSMZ 6 condenser fan signalRead
AI233RSMZ 6 Reheat Valve 1Current RSMZ 6 Reheat Valve 1 positionRead
AI234RSMZ 6 Discharge PressureCurrent RSMZ 6 discharge pressureRead
AI235RSMZ 6 Suction PressureCurrent RSMZ 6 Suction PressureRead
AI236RSMZ 6 Suction Line TempCurrent RSMZ 6 Suction Line TemperatureRead
AI237RSMZ 6 Saturation TempCurrent RSMZ 6 Saturation TemperatureRead
AI238RSMZ 6 SuperheatCurrent RSMZ 6 Superheat TemperatureRead
AI239RSMZ 6 EEV PositionCurrent RSMZ 6 EEV valve positionRead
AI240RSMZ 6 Suction Pressure 2Current RSMZ 6 Suction pressure 2Read
AI241RSMZ 6 Suction Line Temp 2Current RSMZ 6 Suction Line Temperature 2Read
AI242RSMZ 6 Saturation Temp 2Current RSMZ 6 Saturation Temperature 2Read
AI243RSMZ 6 Superheat 2Current RSMZ 6 Superheat Temperature 2Read
AI244RSMZ 6 EEV Position 2Current RSMZ 6 EEV valve position 2Read
AI245RSMZ 6 WarningsCurrent RSMZ 6 WarningsRead
AI246RSMZ 6 Discharge Line TempCurrent RSMZ 6 discharge line temperatureRead
AI247RSMZ 6 FaultsCurrent RSMZ 6 FaultsRead
AI248RSMZ 6 LockoutsCurrent RSMZ 6 LockoutsRead
AI249Not usedNot usedRead
AI250Not usedNot usedRead
AI251Not usedNot usedRead
AI252Not usedNot usedRead
AI253SUB 1 Sub Cool 1Current Subcooling Module 1 Sub Cool 1 readingRead
AI254SUB 1 Sub Cool 2Current Subcooling Module 1 Sub Cool 2 readingRead
AI255SUB 1 Sub Cool 3Current Subcooling Module 1 Sub Cool 3 readingRead
AI256SUB 1 Pressure 1Current Subcooling Module 1 liquid line pressure 1 readingRead
AI257SUB 1 Pressure 2Current Subcooling Module 1 liquid line pressure 2 readingRead
AI258SUB 1 Pressure 3Current Subcooling Module 1 liquid line pressure 3 readingRead
AI259SUB 1 Saturation 1Subcooling Module 1 saturation temperature 1 readingRead
AI260SUB 1 Saturation 2Subcooling Module 1 saturation temperature 2 readingRead
AI261SUB 1 Saturation 3Subcooling Module 1 saturation temperature 3 readingRead
AI262SUB 1 Line Temp 1Subcooling Module 1 liquid line temperature 1 readingRead
AI263SUB 1 Line Temp 2Subcooling Module 1 liquid line temperature 2 readingRead
AI264SUB 1 Line Temp 3Subcooling Module 1 liquid line temperature 3 readingRead
AI265SUB 2 Sub Cool 1Current Subcooling Module 2 Sub Cool 1 readingRead
AI266SUB 2 Sub Cool 2Current Subcooling Module 2 Sub Cool 2 readingRead
AI267SUB 2 Sub Cool 3Current Subcooling Module 2 Sub Cool 3 readingRead
AI268SUB 2 Pressure 1Current Subcooling Module 2 liquid line pressure 1 readingRead
AI269SUB 2 Pressure 2Subcooling Module 2 liquid line pressure 2 readingRead
AI270SUB 2 Pressure 3Subcooling Module 2 liquid line pressure 3 readingRead
AI271SUB 2 Saturation 1Subcooling Module 2 saturation temperature 1 readingRead
AI272SUB 2 Saturation 2Subcooling Module 2 saturation temperature 2 readingRead
AI273SUB 2 Saturation 3Subcooling Module 2 saturation temperature 3 readingRead
AI274SUB 2 Line Temp 1Subcooling Module 2 liquid line temperature 1 readingRead
AI275SUB 2 Line Temp 2Subcooling Module 2 liquid line temperature 2 readingRead
AI276SUB 2 Line Temp 3Subcooling Module 2 liquid line temperature 3 readingRead
AI277Enter Water PumpStatus of Entering Water TemperatureRead
AI278Return Plenum Pressure StatusReturn Plenum Pressure SensorRead
AI279Return Plenum Control SignalCurrent Return Plenum Control Signal (Motorized Exhaust Damper)Read
AI280Mixed Air TempMixed air temperature sensor statusRead
AI281Actual Heat RiseDifference between supply air temperature and mixed air temperature on unitsRead
AI282Calculated Heat RiseThe heat rise limit determined by how open the Outside Damper isRead
AI283Supply Air Relative HumidityIf an EBUS Supply Air Sensor is being used this showsRead
AI284Supply Air Dew PointIf an EBUS Supply Air Sensor is being used this showsRead
AI285Space Dew PointCalculated Space Dew PointRead
AI286Return Dew PointCalculated Return Dew PointRead
AVmin1Occupied Cooling SetpointIf the control temperature rises one deadband above this setpoint, the control°FWrite
AVmin2Occupied Heating SetpointIf the control temperature drops one deadband below this setpoint, the control°FWrite
AV3Hood On Cooling SetpointCooling Mode Enable Setpoint used only in Hood On Mode or Space°FWrite
AV4Hood On Heating SetpointHeating Mode Enable Setpoint used only in Hood On Mode or Space°FWrite
AV5Unoccupied Cooling OffsetDuring the Unoccupied Mode of Operation, this Setpoint offsets the Occupied Cooling°FWrite
AV6Unoccupied Heating OffsetDuring the Unoccupied Mode of Operation, this Setpoint offsets the Occupied Heating°FWrite
AV7Mode Select DeadbandThis value is added to and subtracted from the HVAC Mode Setpoints°FWrite
AV8Max Coil Setpoint Reset LimitHighest that the Coil Temperature resets to during Space Humidity Reset°FWrite
AV9Min Coil Setpoint Reset LimitLowest the Coil Temperature resets to during Space Humidity Reset°FWrite
AVmin10Supply Air Cooling SetpointSupply Air Cooling Setpoint°FWrite
AV11Supply Air Heating SetpointSupply Air Heating Setpoint°FWrite
AV12Max SAT Cooling Setpoint Reset LimitIf Supply Air Reset is configured this is the High SAT Cooling°FWrite
AV13Max SAT Heating Setpoint Reset LimitIf Supply Air Reset is configured this is the High SAT Heating°FWrite
AV14Supply Air Cooling Staging WindowIn Cooling Mode, if the Supply Air Temperature drops below the Active°FWrite
AV15Supply Air Heating Staging WindowIn Heating Mode, if the Supply Air Temperature rises above the Active°FWrite
AV16Warm-Up Target TemperatureIf Morning Warm-Up is configured, then upon entering occupied mode, the Warm-Up°FWrite
AV17Warm-Up Mode Supply Air SetpointDuring Morning Warm-Up, the Supply Air Temperature is controlled to this Setpoint°FWrite
AV18Cool-Down Mode Supply Air SetpointDuring Morning Cool-Down, the Supply Air Temperature is controlled to this Setpoint°FWrite
AV19Mechanical Cooling Outdoor Air LockoutMechanical Cooling is locked out when the Outdoor Air Temperature is below°FWrite
AV20Mechanical Heating Outdoor Air LockoutMechanical Heating is locked out when the Outdoor Air Temperature is above°FWrite
AV21Low Supply Temp Cutoff AlarmCooling is disabled if the Supply Air Temperature falls below this value°FWrite
AV22High Supply Temp Cutoff AlarmHeating is disabled if the Supply Air Temperature rises above this value°FWrite
AV23Preheater Cooling Mode SetpointIf the Preheater is enabled, and the unit is in the Cooling°FWrite
AV24Preheater Venting Mode SetpointIf the Preheater is enabled, and the unit is in the Vent°FWrite
AV25Preheater Heating Mode SetpointIf the Preheater is enabled, and the unit is in the Heating°FWrite
AV26Outdoor Air Dewpoint SetpointOn an MUA unit, if the OA dewpoint rises above this setpoint°FWrite
AV27Economizer Enable SetpointThe economizer is enabled if the outdoor drybulb, dewpoint, or wetbulb temperature°FWrite
AV28Heat Wheel Defrost Enable SetpointThe unit goes into Heat Wheel Defrost if the Outdoor Air°FWrite
AV29PreHeat Enable SetpointIf the Supply Fan is energized, this is the temperature at which°FWrite
AV30Sensor Slide Offset Max EffectIf the space sensor has the optional slide adjustment feature°FWrite
AV31Space Sensor Calibration OffsetIf the Space Temperature Sensor is reading incorrectly, use this option°FWrite
AV32Supply Air Sensor Calibration OffsetIf the Supply Air Temperature Sensor is reading incorrectly, use this option°FWrite
AV33Return Air Sensor Calibration OffsetIf the Return Temperature Sensor is reading incorrectly, use this option°FWrite
AV34Outdoor Air Sensor Calibration OffsetIf the Outdoor Temperature Sensor is reading incorrectly, use this option°FWrite
AV35Carbon Dioxide Sensor Calibration OffsetIf the CO2 Sensor is reading incorrectly, use this option to -500Write
AV36Low Ambient Protection SetpointTemperature at which the Low Ambient Relay activates in the Occupied°FWrite
AV37SAT Cool Setpoint Reset Source Low LimitIf doing Supply Air Setpoint Reset, this is the Low Reset Source°FWrite
AV38SAT Cool Setpoint Reset Source High LimitIf doing Supply Air Setpoint Reset, this is the High Reset Source°FWrite
AV39SAT Heat Setpoint Reset Source Low LimitIf doing Supply Air Setpoint Reset, this is the Low Reset Source°FWrite
AV40SAT Heat Setpoint Reset Source High LimitIf doing Supply Air Setpoint Reset, this is the High Reset Source°FWrite
AV41Control Temperature High Alarm OffsetIf the temperature of the controlling sensor rises above the Occupied Cooling°FWrite
AV42Control Temperature Low Alarm OffsetIf the temperature of the controlling sensor falls below the Occupied Heating°FWrite
AV43Heat Pump Compressor Heat LockoutCompressor Heat is locked out below this setpoint°FWrite
AV44Maximum Main Fan VFD in SZ VAV Heating ModeIn Single Zone VAV configuration, this is the max fan speedWrite
AV45Minimum Main Fan VFD in Cooling ModeIn Single Zone VAV configuration, this is the fan speed at whichWrite
AV46Minimum Main Fan VFD in Heating ModeIn Single Zone VAV configuration, this is the fan speed at whichWrite
AV47Minimum Main Fan VFD in Vent ModeSpeed at which the VFD operates in the Vent Mode in SingleWrite
AV48Maximum Economizer in Heating ModeMax position the Economizer Damper opens to in Supply Air Tempering duringWrite
AV49Minimum Economizer PositionThe minimum position of the Outdoor Air damper in the Occupied ModeWrite
AV50Maximum Economizer CO2 Reset LimitThe maximum value the Economizer Minimum Position can be reset upWrite
AV51Minimum Carbon Dioxide SetpointThreshold CO2 level at which the Economizer Min Damper Position Setpoint beginsWrite
AV52Maximum Carbon Dioxide SetpointCO2 level at which the Economizer Min Damper Position resetsWrite
AV53Indoor Humidity Setpoint Low Reset LimitOn indoor controlled (non-MUA) units, this is the Humidity setpoint at whichWrite
AV54Indoor Humidity Setpoint High Reset LimitOn indoor controlled (non-MUA) units, this is the Humidity setpoint at whichWrite
AV55Duct Static Pressure SetpointCurrent Static Pressure SetpointWrite
AV56Duct Static Pressure Control DeadbandValue above and below the Duct Static Pressure Setpoint where no controlWrite
AV57Building Pressure Control SetpointBuilding Pressure Setpoint or Exhaust Duct Static Pressure SetpointWrite
AV58Building Pressure Control DeadbandValue above and below the Building Pressure Setpoint or the Exhaust DuctWrite
AV59Minimum Outdoor CFM RequirementMinimum Outdoor Airflow CFM SetpointWrite
AV60Outdoor CFM Control DeadbandControls rate of change for damper signalWrite
AV61Single Zone VAV Fan Speed IntegralThe Integral Constant for Single Zone VAV Fan ControlWrite
AV62Relay Run-time Hours Warning LimitIf any configured relay’s run time exceeds this number of hoursWrite
AV63Cooling Mode Head Pressure SetpointHead Pressure Setpoint in the Cooling ModeWrite
AV64Dehum Mode Head Pressure SetpointHead Pressure Setpoint in the Dehumidification ModeWrite
AV65Superheat SetpointSuperheat Setpoint°FWrite
AV66Maximum Outdoor CFM RequirementMaximum Outdoor Airflow CFM Setpoint in High CO2Write
AVmin67Schedule ForceForces occupancy or follows the controller scheduleWrite0=Auto (controller schedule), 1=Forced Occupied, 2=Forced Unoccupied
AV68HVAC Mode OverrideForces the unit into a mode; Auto restores normal controlWrite0=Auto, 1=Vent, 2=Cool, 3=Heat, 4=Vent Dehum, 5=Cool Dehum, 6=Heat Dehum
AV69Fan VFD OverrideOverrides main fan VFD speed; 65535 returns to autoWrite
AV70Outdoor Air Damper OverrideOverrides outdoor air damper position; 65535 returns to autoWrite
AV71Supply Setpoint OverrideOverrides the supply air temperature setpoint; 0 = no override°FWrite
AV72Space Temperature ValueIf the controller is configured for this operation, the user can write°FWrite
AV73Space Humidity ValueIf the controller is configured for this operation, the user can writeWrite
AV74Indoor RH Calibration OffsetIf the Space Humidity Sensor is reading incorrectly, use -1 this optionWrite
AV75Relief Fan VFDOverrides relief fan VFD speed; 65535 returns to autoWrite
AV76Relief Pressure ValueIf the controller is configured for this operation, the user can writeWrite
AV77Carbon Dioxide ValueIf the controller is configured for this operation, the user can writeWrite
AV78Outdoor Air Temperature ValueIf the controller is configured for this operation, the user can write°FWrite
AV79Outdoor Air Humidity ValueIf the controller is configured for this operation, the user can writeWrite
AV80High Level Enthalpy (Reserved)ReservedWrite
AV81Low Level Enthalpy (Reserved)ReservedWrite
AV82Max Plenum Pressure Setpoint Reset LimitReservedWrite
AV83Min Plenum Pressure Setpoint Reset LimitReservedWrite
AV84Enthalpy Enable SetpointIf configured for Comparative Enthalpy Economizer Control, the OA Enthalpy mustBTU/lbWrite
AV85EnthalpyEnable DeadbandThe OA Enthalpy must be below the Enthalpy Enable SetpointBTU/lbWrite
AV86Maximum Static Setpoint Reset LimitAs the most open VAV damper rises above 80%, the static setpointin. W.C.Write
AV87Minimum Static Setpoint Reset LimitAs the most open VAV damper drops below 80%, the static setpointin. W.C.Write
AV88Static Setpoint Reset IntervalThe Reset Interval is how often the setpoint reset calculation 10 minWrite
AV89Cool-Down Target TemperatureIf Morning Cool-Down is configured then upon entering occupied mode, the Cool-Down°FWrite
AV90Warm-Up OverrideCommands Morning Warm-Up ModeWrite1=Command Warm-Up Mode
AV91Cool Down OverrideCommands Morning Cool-Down ModeWrite1=Command Cool-Down Mode
AV92Return Air High Limit ProtectionReturn air high limit; unit reverts above it (voting/CV units only)Write
AV93Return Air Low Limit ProtectionReturn air low limit; unit reverts below it (voting/CV units only)Write
AV94Sump Drain OverrideTurns the sump drain relay on or back to autoWrite0=Auto, 1=On
AV95Return Plenum Pressure SetpointCurrent Return Plenum Pressure Setpointin. W.C.Write
AV96Return Plenum Pressure DeadbandValue above and below the Return Plenum Pressure Setpoint where no controlin. W.C.Write
AV97Dehum Lockout SetpointIf Outdoor Air temperature is below this setpoint, Dehumidification Mode is locked°FWrite
AV98Emergency Compressor LockoutLets the BMS lock out the compressorsWrite
AV99Supply Air Dew Point SetpointWhen the VCCX2 is configured for DX-DOAS control it modulates the compressorsWrite
BI1Cooling Enabled StatusMechanical Cooling is enabled based on the Cooling LockoutRead
BI2Heating Enabled StatusThat Mechanical Heating is enabled based on the Heating LockoutRead
BI3Economizer Enabled StatusThe Economizer is enabled based on the Economizer Enable SetpointRead
BI4Aux Heat Enabled StatusHeat Pump Auxiliary Heat enabledRead
BI5Emergency Heat Enabled StatusShows the Emergency Heat is enabled based on the Compressor Heating LockoutRead
BI6Fan Proof of Airflow StatusProof of Airflow Binary Input StatusRead
BI7Exhaust Hood On/Off StatusExhaust Hood On/Off Binary Input StatusRead
BI8Remote Forced Occupied StatusRemote Forced Occupied Mode Binary Input StatusRead
BI9Remote Forced Cooling StatusRemote Forced Cooling Mode Binary Input StatusRead
BI10Remote Forced Heating StatusRemote Forced Heating Mode Binary Input StatusRead
BI11Remote Force Dehum StatusRemote Force Dehumidification Mode Binary Input StatusRead
BI12Bad Supply Air SensorAlarm that indicates a failure of the Supply Air SensorRead
BI13Bad Return Air SensorAlarm that indicates a failure of the Return Air SensorRead
BI14Bad Outdoor Air SensorFailure of the Outdoor Air Temperature SensorRead
BI15Bad Space Temp SensorFailure of the Space Temperature SensorRead
BI16Bad Carbon Dioxide SensorFailure of the CO2 SensorRead
BI17Bad Building Pressure SensorAlarm indicating missing or failed Building Pressure SensorRead
BI18Bad Outdoor Airflow SensorAn Outdoor Airflow Sensor is configured, but not detectedRead
BI19Bad Exhaust Airflow SensorAn Exhaust Airflow Sensor is configured, but not detectedRead
BI20Bad Supply Airflow SensorA Supply Airflow Sensor is configured, but not detectedRead
BI21Bad Return Airflow SensorA Return Airflow Sensor is configured, but not detectedRead
BI22Mechanical Cooling AlarmCompressor Relays are enabled but the Supply Air Temperature has not fallenRead
BI23Mechanical Heating AlarmHeating Mode has been initiated but the Supply Air Temperature has notRead
BI24Fan Proving AlarmAlarm that indicates an Airflow failure from the Main FanRead
BI25Dirty Filter AlarmAlarm that indicates the filters are dirtyRead
BI26Emergency Shutdown AlarmAlarm that indicates that Emergency Shutdown has been activatedRead
BI27Relay Runtime WarningWhen any of the configured relays exceeds a configured number of hoursRead
BI28Economizer Missing AlarmTitle 24 operation indicates missing economizer feedbackRead
BI29Economizer Title 24 Failure ATitle 24 Air Temperature Sensor FailureRead
BI30Economizer Title 24 Failure BTitle 24 Not Economizing when it shouldRead
BI31Economizer Title 24 Failure CTitle 24 Economizing when it should notRead
BI32Economizer Title 24 Failure DTitle 24 Damper Not ModulatingRead
BI33Economizer Title 24 Failure ETitle 24 Excess Outdoor AirRead
BI34High Supply Temp CutoffThe Supply Air has risen above the Hi SAT Cutoff SetpointRead
BI35Low Supply Temp CutoffThe Supply Air has fallen below the Low SAT Cutoff SetpointRead
BI36High Control Mode AlarmOccurs when the Controlling Sensor Temperature rises above the Cooling Mode EnableRead
BI37Low Control Mode AlarmOccurs when the Controlling Sensor Temperature falls below the Heating Mode EnableRead
BI38Missing Refrigerant Module #1Refrigerant Module #1 is bad or missingRead
BI39Missing Refrigerant Module #2Refrigerant Module #2 is bad or missingRead
BI40Missing Refrigerant Module #3Refrigerant Module #3 is bad or missingRead
BI41Missing Refrigerant Module #4Refrigerant Module #4 is bad or missingRead
BI42Missing Preheater BoardPreheater Module is bad or missingRead
BI43Missing Reheat BoardThe MHGR board is configured but not detectedRead
BI44Missing Mod Gas BoardThe MODGAS board is configured but not detectedRead
BI45Missing EM1 BoardEM1 Expansion Board is bad or missingRead
BI46Missing 12 Relay Expansion BoardThe 12 Relay Expansion Board is configured but not detectedRead
BI47On Board Relay 1 Main FanCurrent Status of Main Fan Relay #1 on Main BoardRead
BI48On Board Relay 2Current Status of Configurable Relay #2 on Main BoardRead
BI49On Board Relay 3Current Status of Configurable Relay #3 on Main BoardRead
BI50On Board Relay 4Current Status of Configurable Relay #4 on Main BoardRead
BI51On Board Relay 5Current Status of Configurable Relay #5 on Main BoardRead
BI52On Board Relay 6Current Status of Configurable Relay #6 on Main BoardRead
BI53On Board Relay 7Current Status of Configurable Relay #7 on Main BoardRead
BI54On Board Relay 8Current Status of Configurable Relay #8 on Main BoardRead
BI55Expansion Board EM1 Relay 1Current Status of Configurable Relay #1 on EM1 BoardRead
BI56Expansion Board EM1 Relay 2Current Status of Configurable Relay #2 on EM1 BoardRead
BI57Expansion Board EM1 Relay 3Current Status of Configurable Relay #3 on EM1 BoardRead
BI58Expansion Board EM1 Relay 4Current Status of Configurable Relay #4 on EM1 BoardRead
BI59Expansion Board EM1 Relay 5Current Status of Configurable Relay #5 on EM1 BoardRead
BI6012 Relay Expansion Board Relay 1Current Status of Configurable Relay #1 on 12 Relay BoardRead
BI6112 Relay Expansion Board Relay 2Current Status of Configurable Relay #2 on 12 Relay BoardRead
BI6212 Relay Expansion Board Relay 3Current Status of Configurable Relay #3 on 12 Relay BoardRead
BI6312 Relay Expansion Board Relay 4Current Status of Configurable Relay #4 on 12 Relay BoardRead
BI6412 Relay Expansion Board Relay 5Current Status of Configurable Relay #5 on 12 Relay BoardRead
BI6512 Relay Expansion Board Relay 6Current Status of Configurable Relay #6 on 12 Relay BoardRead
BI6612 Relay Expansion Board Relay 7Current Status of Configurable Relay #7 on 12 Relay BoardRead
BI6712 Relay Expansion Board Relay 8Current Status of Configurable Relay #8 on 12 Relay BoardRead
BI6812 Relay Expansion Board Relay 9Current Status of Configurable Relay #9 on 12 Relay BoardRead
BI6912 Relay Expansion Board Relay 10Current Status of Configurable Relay #10 on 12 Relay BoardRead
BI7012 Relay Expansion Board Relay 11Current Status of Configurable Relay #11 on 12 Relay BoardRead
BI7112 Relay Expansion Board Relay 12Current Status of Configurable Relay #12 on 12 Relay BoardRead
BI72Preheater Enable StatusStatus of Preheater Enable InputRead
BI73Preheater Emergency ShutdownStatus of Preheater Emergency Shutdown InputRead
BI74Preheater Spare Binary Input #3Status of Preheater Binary Input #3Read
BI75MODGAS Enable StatusStatus of MODGAS ControllerRead
BI76MHGR Enable StatusStatus of MHGRV ControllerRead
BI77A1 Compressor EnableCurrent Status of Enable Signal to Compressor A1Read
BI78A2 Compressor EnableCurrent Status of Enable Signal to Compressor A2Read
BI79A1 Compressor AlarmsAn RSM alarm is present on the A1 circuitRead
BI80A2 Compressor AlarmsAn RSM alarm is present on the A2 circuitRead
BI81A1-2 Defrost SwitchOutside Coil A1/A2 Temp Switch for Defrost ModeRead
BI82A1-2 Water Proof of FlowA1/A2 Water Proof of Flow SwitchRead
BI83A1-4 Emergency Shutdown (RSMD)Emergency Shutdown Input on Module ARead
BI84Refrigerant Module 1 Relay 1Current Status of Compressor A1 Enable RelayRead
BI85Refrigerant Module 1 Relay 2Current Status of Compressor A2 Enable RelayRead
BI86Refrigerant Module 1 Relay 3Current Status of Condenser 1 Enable RelayRead
BI87Refrigerant Module 1 Relay 4Current Status of Relay #4Read
BI88Refrigerant Module 1 Relay 5Current Status of Relay #5Read
BI89B1 Compressor EnableCurrent Status of Enable Signal to Compressor B1Read
BI90B2 Compressor EnableCurrent Status of Enable Signal to Compressor B2Read
BI91B1 Compressor AlarmsAn RSM alarm is present on the B1 circuitRead
BI92B2 Compressor AlarmsAn RSM alarm is present on the B2 circuitRead
BI93B1-2 Defrost SwitchOutside Coil B1/B2 Temp Switch for Defrost ModeRead
BI94B1-2 Water Proof of FlowB1/B2 Switch for Water Proof of FlowRead
BI95B1-4 Emergency Shutdown (RSMD)Emergency Shutdown Input on Module BRead
BI96Refrigerant Module 2 Relay 1Current Status of Compressor 1 Enable RelayRead
BI97Refrigerant Module 2 Relay 2Current Status of Compressor 2 Enable RelayRead
BI98Refrigerant Module 2 Relay 3Current Status of Condenser 1 Enable RelayRead
BI99Refrigerant Module 2 Relay 4Current Status of Relay #4Read
BI100Refrigerant Module 2 Relay 5Current Status of Relay #5Read
BI101C1 Compressor EnableCurrent Status of Enable Signal to Compressor C1Read
BI102C2 Compressor EnableCurrent Status of Enable Signal to Compressor C2Read
BI103C1 Compressor AlarmsAn RSM alarm is present on the C1 circuitRead
BI104C2 Compressor AlarmsAn RSM alarm is present on the C2 circuitRead
BI105C1-2 Defrost SwitchOutside Coil C1/C2Temp Switch for Defrost ModeRead
BI106C1-2 Water Proof of FlowC1/C2 Switch for Water Proof of FlowRead
BI107C1-4 Emergency Shutdown (RSMD)Emergency Shutdown Input on Module CRead
BI108Refrigerant Module 3 Relay 1Current Status of Compressor 1 Enable RelayRead
BI109Refrigerant Module 3 Relay 2Current Status of Compressor 2 Enable RelayRead
BI110Refrigerant Module 3 Relay 3Current Status Condenser 1 Enable RelayRead
BI111Refrigerant Module 3 Relay 4Current Status of Relay #4Read
BI112Refrigerant Module 3 Relay 5Current Status of Relay #5Read
BI113D1 Compressor EnableCurrent Status of Enable Signal to Compressor D1Read
BI114D2 Compressor EnableCurrent Status of Enable Signal to Compressor D2Read
BI115D1 Compressor AlarmsAn RSM alarm is present on the D1 circuitRead
BI116D2 Compressor AlarmsAn RSM alarm is present on the D2 circuitRead
BI117D1-2 Defrost SwitchOutside Coil D1/D2 Temp Switch for Defrost ModeRead
BI118D1-2 Water Proof of FlowD1/D2 Switch for Water Proof of FlowRead
BI119D1-4 Emergency Shutdown (RSMD)Emergency Shutdown Input on Module DRead
BI120Refrigerant Module 4 Relay 1Current Status of Compressor 1 Enable RelayRead
BI121Refrigerant Module 4 Relay 2Current Status of Compressor 2 Enable RelayRead
BI122Refrigerant Module 4 Relay 3Current Status of Condenser 1 Enable RelayRead
BI123Refrigerant Module 4 Relay 4Current Status of Relay #4Read
BI124Refrigerant Module 4 Relay 5Current Status of Relay #5Read
BI125Preheater AlarmPreheater Alarm IndicatorRead
BI126Return Fan Proving AlarmExhaust Fan / Return Fan Proof of Flow AlarmRead
BI127Compressor Running ACurrent Run Status of Compressor ARead
BI128Compressor Running BCurrent Run Status of Compressor BRead
BI129Compressor Running CCurrent Run Status of Compressor CRead
BI130Compressor Running C2Current Run Status of Compressor C2Read
BI131Compressor Running DCurrent Run Status of Compressor DRead
BI132Compressor Running ECurrent Run Status of Compressor ERead
BI133Compressor Running E2Current Run Status of Compressor E2Read
BI134Compressor Running FCurrent Run Status of Compressor FRead
BI135Compressor Running F2Current Run Status of Compressor F2Read
BI136Return Fan Proving StatusProof of Return Fan Airflow Binary Input StatusRead
BI137IAQ Mode ActiveIAQ Mode is activeRead
BI138Heat Wheel Defrost ActiveHeat Wheel Defrost is activeRead
BI139Direct Fire StatusSignal on EM1 binary input 2 from Direct Fire Module that indicatesRead
BI140Direct Fire Alarm StatusSignal on EM1 binary input 3 that indicates there is an activeRead
BI141Temp Rise WarningThe heat rise when direct fire heat is active has exceededRead
BI142Temp Rise AlarmThe heat rise when direct fire heat is active has exceededRead
BI143Temp Rise LockoutThree High Temp Rise alarms occurred within a 1-hour spanRead
BI144High CO2 Rise WarningHigh return CO2 was detected when running direct fire heatRead
BI145High CO2 Rise AlarmHigh return CO2 was detected and direct fire heat has been temporarilyRead
BI146High CO2 Rise LockoutThree CO2 warning alarms occurred within a 1-hour span and direct fireRead
BI147Ignition LockoutAn active alarm on the Direct Fire ModuleRead
BI148Direct Fire Status LockoutDirect Fire Status Signal is not active within 10 minutesRead
BI149Direct Fire Setpoint OverrideThe max calculated heat rise is limiting the Supply Air SetpointRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VCCX2 Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AAON VCCX2 Controller

How many BACnet points does the AAON VCCX2 Controller have?

This list has 534 BACnet objects: 286 analog inputs, 99 analog values, 149 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AAON VCCX2 Controller BACnet points are writable?

99 of the 534 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AAON VCCX2 Controller BACnet documentation?

The source is VCCX2 Controller Technical Guide (Appendix C: BACnet Guide) (G115820), revision Rev. AA, January 7, 2025, published free by AAON at https://www.aaon.com/hubfs/G039840-VCCX2-T.pdf.

What are the minimum BACnet points to integrate the AAON VCCX2 Controller?

Start with AV 67 Schedule Force (Occupied/unoccupied command from the BAS); AV 1 Occupied Cooling Setpoint (Cooling starts one deadband above this, °F); AV 2 Occupied Heating Setpoint (Heating starts one deadband below this, °F); AV 10 Supply Air Cooling Setpoint (Discharge air temp target in cooling, °F); AI 3 Control Status (Current occupancy status); AI 4 HVAC Mode (Off, vent, cool, heat, dehum, purge or defrost mode); AI 5 Control Temperature (Reading from the configured control sensor); AI 9 Supply Air Temperature (Discharge air temp leaving the unit); AI 144 Alarm Status (Summary alarm).

How do I enable BMS control of the AAON VCCX2 Controller?

Occupancy comes from AV 67 Schedule Force (0 = follow the controller schedule, 1 = forced occupied, 2 = forced unoccupied), the internal week schedule, a GPC-XP broadcast schedule, or the BI4 remote forced occupied contact. AV 68, AV 69, AV 70 and AV 71 override HVAC mode, fan VFD, OA damper and supply setpoint; writing Auto (0 or 65535 as listed) hands control back.

Can the BMS supply sensor values to the AAON VCCX2 Controller?

If the controller is configured for it, the BAS can write AV 72 Space Temperature, AV 73 Space Humidity, AV 76 Relief Pressure, AV 77 CO2, AV 78 Outdoor Air Temperature and AV 79 Outdoor Air Humidity; these are the only sensor values the BAS may write. The guide gives no refresh timeout for them. A relief pressure value received over BACnet that is out of range raises an alarm.

How do I check these points on the real VCCX2 Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AAON BACnet points lists

Source: VCCX2 Controller Technical Guide (Appendix C: BACnet Guide) · G115820 · rev. Rev. AA, January 7, 2025. Object names, instances and units are reproduced as published; descriptions are our own.