Rooftop unit / air handler controller · BACnet points list

AAON VCB-X Controller BACnet points list

Updated 28 October 2026

Short answer

The VCB-X is the Orion (WattMaster) unit controller used on AAON rooftop units and air handlers. It has an on-board BACnet MS/TP port and serves 51 read-only Analog Inputs (temperatures, humidity, pressures, airflow, setpoint mirrors, output signals, alarm bits), 73 writable Analog Values (setpoints, lockouts, offsets, calibration, fan and damper limits, BAS overrides) and 72 read-only Binary Inputs (enable status, individual alarms, relay status).

This page lists 196 BACnet objects for the AAON VCB-X Controller — 73 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.

Manufacturer
AAON
Model
VCB-X Controller
Equipment
Rooftop unit / air handler controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
196 (73 writable)
Transport
BACnet MS/TP
Firmware
2.13 (BTL listing, OE335-26B-VCBX)
Also known as
VCBX, VCB-X, Orion VCB-X, OE335-26B-VCBX, V28940, WattMaster VCB-X, AAON VCB-X BACnet
Source document
VCB-X Controller Field Technical Guide (Appendix C - VCB-X BACnet) · OR-VCBX-FIELD-TGD-01X · rev. February 2018 (copyright date)
Download CSV 196 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: AAON VCB-X Controller

Integration in brief

Wire the on-board MS/TP port and set MAC address, device ID and baud on the controller's LCD BACnet screens. Schedule the unit from the BAS with AV 62 Schedule Force, adjust the occupied heating/cooling and supply-air setpoints, and read HVAC mode, control status, temperatures and the alarm BIs. AV 63-65 force the mode, fan speed or OA damper; write Auto to hand control back.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 62Schedule Force0 Auto, 1 forced occupied, 2 forced unoccupiedWrite
AV 1Occupied Cooling SetpointCooling starts one degree above thisWrite
AV 2Occupied Heating SetpointHeating starts one degree below thisWrite
AV 10Supply Air Cooling SetpointDischarge air temp target in coolingWrite
AI 3Control StatusCurrent occupancy statusRead
AI 4HVAC ModeOff, vent, cool, heat, dehum, defrost and other modesRead
AI 5Control TemperatureReading from the configured control sensorRead
AI 7Supply Air TemperatureDischarge air temp leaving the unitRead
AI 40Alarm StatusBit-coded summary of active alarmsRead

Enable & remote start

Occupancy comes from AV 62 Schedule Force (0 = follow the controller's schedule, 1 = forced occupied, 2 = forced unoccupied). AV 63 HVAC Mode Override, AV 64 Fan VFD Override and AV 65 Outdoor Air Damper Override force operation; writing Auto (0 for the mode override, 65535 for fan and damper) returns control to the unit.

Sensors & values from the BMS

Not supported: the guide states sensor inputs can't be written over BACnet.

Network setup

Watch out for

AAON VCB-X Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

196 of 196 shown
Type
Binary
Access
Show
AAON VCB-X Controller BACnet Points List
DescriptionStates
AI1Application Software VersionVersion of the software in the unitRead
AI2Control ModeConfigured unit applicationRead1=Constant Volume, 2=Supply Air Cooling Only, 3=Outdoor Temperature Control, 4=Single Zone VAV, 5=Supply Air Tempering, 6=Space Temperature Control w/ High OA Content
AImin3Control StatusOccupied/ Unoccupied StatusRead0=Unoccupied, 1=Occupied, 2=Override Mode, 3=Holiday Unoccupied, 4=Holiday Occupied, 5=Forced Occupied, 6=Forced Unoccupied, 7=Remote Contact Occupied, 8-10=not applicable on BACnet, 11=Hot Water Lockout (custom code)
AImin4HVAC ModeOperational statusRead0=Off, 1=Vent, 2=Cooling, 3=Heating, 4=Vent RH, 5=Cooling RH, 6=Heating RH, 7=Warm Up, 8=Defrost, 9=Purge, 10=Cool Down, 11=Remote Cooling, 12=Remote Heating, 13=Remote Vent Dehum, 14=Remote Cool Dehum, 15=Remote Heat Dehum
AImin5Control TemperatureControl Temperature SensorRead
AI6Space TemperatureSpace Temperature SensorRead
AImin7Supply Air TemperatureSupply Air Temperature sensorRead
AI8Coil TemperatureCoil Temperature valueRead
AI9Discharge TemperatureDigital Compressor Discharge Air Temperature SensorRead
AI10Outdoor Air TemperatureOutdoor Temperature SensorRead
AI11Return Air TemperatureReturn Temperature SensorRead
AI12Leaving Water TemperatureLeaving Water Temperature SensorRead
AI13Outdoor Air Wetbulb TemperatureCalculated Outdoor Wetbulb TemperatureRead
AI14Outdoor Air Dewpoint TemperatureCalculated Outdoor Air Dewpoint TemperatureRead
AI15Indoor Air HumidityIndoor Humidity SensorRead
AI16Outdoor Air HumidityOutdoor Humidity SensorRead
AI17Duct Static PressureDuct Static PressureRead
AI18Building PressureBuilding Pressure SensorRead
AI19Suction PressureSuction Pressure ValueRead
AI20Head Pressure 1Head Pressure 1 ReadingRead
AI21CO2Indoor CO LevelRead
AI22Outdoor AirflowOutdoor Airflow MeasurementRead
AI23Exhaust AirflowExhaust Airflow MeasurementRead
AI24Supply AirflowSupply Airflow MeasurementRead
AI25Return AirflowReturn Airflow MeasurementRead
AI26Cooling SetpointOccupied Cooling Mode Enable Setpoint MirrorRead
AI27Heating SetpointOccupied Heating Mode Enable Setpoint MirrorRead
AI28Supply Air SetpointActive SAT cooling or heating setpoint, after any resetRead
AI29Coil Temperature SetpointCoil suction temperature target in dehumidificationRead
AI30Head Pressure SetpointHead Pressure SetpointRead
AI31Indoor Humidity SetpointIndoor humidity setpoint (low reset limit value)Read
AI32Economizer PositionSignal percentage to the Economizer DamperRead
AI33Fan VFD SignalSupply Fan VFD SignalRead
AI34Modulating Heating PositionPercentage of the Modulating Heating signal (Hot Water or SCR heat)Read
AI35Modulating Cooling PositionPercentage of the Modulating Cooling Signal (Chilled Water or Digital Compressor)Read
AI36Building Pressure Exhaust Control SignalRelief VFD Fan/ Damper SignalRead
AI37Reheat Valve PositionPosition of MHGRV Modulating Hot Gas Reheat ValveRead
AI38Modulating Gas Valve PositionPosition of MODGAS Modulating Gas Valve ControlRead
AI39Condenser 1 Control SignalCondenser 1 Fan / Water Valve Signal StatusRead
AImin40Alarm StatusBit-coded alarm status (see states)ReadBit string: 0 Bad Supply Air Sensor, 1 Bad Return Air Sensor, 2 Bad Outside Air Sensor, 3 Bad Space Sensor, 4 Missing EM1, 5 Bad Coil Temp Sensor, 6 Bad CO2, 7 Bad Discharge, 8-11 Bad OA/Exhaust/Supply/Return CFM, 12 Reheat module, 13 ModGas module, 14 12-relay module, 15 Mech Cooling Failure, 16 Mech Heating Failure, 17 Fan Proving, 18 Dirty Filter, 19 Emergency Shutdown, 20 High SAT Cutoff, 21 Low SAT Cutoff, 22 High Control Mode, 23 Low Control Mode, 24 Digital Comp Cutoff, 25 Digital Comp Lockout, 26 High Head Pressure, 27 Loop Water Proof of Flow, 28 Low Suction, 29 Unsafe Suction, 30 Low Leaving Water Temp
AI41Return Bypass DamperPosition of Return Bypass DamperRead
AI42Return Air DamperPosition of Return Air Damper if using Return Air Bypass ControlRead
AI43Superheat #1 TemperatureNot UsedRead
AI44Superheat #2 TemperatureNot UsedRead
AI45Expansion Valve #1 PositionNot UsedRead
AI46Expansion Valve #2 PositionNot UsedRead
AI47Return Air HumidityReturn Air Humidity ReadingRead
AI48Sensor Slide Adjust EffectAmount Of Current Sensor Slide OffsetRead
AI49Title 24 Economizer FeedbackPosition of feedback from Economizer actuatorRead
AI50Head Pressure 2Head Pressure 2 ReadingRead
AI51Condenser 2 Control SignalCondenser 2 Fan/Water Valve SignalRead
AVmin1Occupied Cooling SetpointCooling mode starts one degree above this (1 to 110)Write
AVmin2Occupied Heating SetpointHeating mode starts one degree below this (1 to 110)Write
AV3Hood On Outdoor Air Cooling SetpointCooling enable setpoint in Hood On mode (1 to 110)Write
AV4Hood On Outdoor Air Heating SetpointHeating enable setpoint in Hood On mode (1 to 110)Write
AV5Unoccupied Cooling OffsetRaises the cooling setpoint when unoccupied (0 to 30)Write
AV6Unoccupied Heating OffsetLowers the heating setpoint when unoccupied (0 to 30)Write
AV7Mode Select DeadbandDeadband added to/subtracted from the mode setpoints (0 to 10)Write
AV8Max Coil Setpoint Reset LimitHighest coil temperature reset during humidity control (35 to 70)Write
AV9Min Coil Setpoint Reset LimitLowest coil temperature reset during humidity control (35 to 70)Write
AVmin10Supply Air Cooling SetpointSupply air temperature target in cooling (30 to 80)Write
AV11Supply Air Heating SetpointSupply air temperature target in heating (40 to 240)Write
AV12Max SAT Cooling Setpoint Reset LimitHigh SAT cooling limit for supply air reset (0 to 100)Write
AV13Max SAT Heating Setpoint Reset LimitHigh SAT heating limit for supply air reset (0 to 250)Write
AV14Supply Air Cooling Staging WindowCooling staging window around the SAT setpoint (1 to 30)Write
AV15Supply Air Heating Staging WindowHeating staging window around the SAT setpoint (1 to 50)Write
AV16Morning Warm-Up Target TemperatureMorning warm-up target temperature (50 to 90)Write
AV17Mechanical Cooling Outdoor Air LockoutMechanical cooling locked out below this OAT (-30 to 100)Write
AV18Mechanical Heating Outdoor Air LockoutMechanical heating locked out above this OAT (-30 to 150)Write
AV19Low Supply Air Temperature CutoffCooling disabled below this supply air temperature (0 to 100)Write
AV20High Supply Air Temperature CutoffHeating disabled above this supply air temperature (0 to 250)Write
AV21Outdoor Air Dewpoint SetpointMUA dehumidification starts above this OA dewpoint (35 to 80)Write
AV22Economizer Enable SetpointEconomizer enabled below this outdoor condition (-30 to 80)Write
AV23Heat Wheel Defrost Enable SetpointHeat wheel defrost below this outdoor temperature (0 to 50)Write
AV24Preheat SetpointPreheat temperature setpoint (-30 to 70)Write
AV25Space Sensor Calibration OffsetSpace temperature sensor calibration offset (-100 to 100)Write
AV26Supply Air Sensor Calibration OffsetSupply air sensor calibration offset (-100 to 100)Write
AV27Return Air Sensor Calibration OffsetReturn air sensor calibration offset (-100 to 100)Write
AV28Outdoor Air Sensor Calibration OffsetOutdoor air sensor calibration offset (-100 to 100)Write
AV29Coil Temperature Calibration OffsetCoil temperature calibration offset (-100 to 100)Write
AV30Leaving Water Sensor Calibration OffsetLeaving water sensor calibration offset (-100 to 100)Write
AV31CO2 Sensor Calibration OffsetCO2 sensor calibration offset (-500 to 500)Write
AV32Low Ambient Protection SetpointLow ambient relay setpoint (-30 to 70)Write
AV33SAT Cool Setpoint Reset Source Low LimitSAT cooling reset source low limit (-30 to 150)Write
AV34SAT Cool Setpoint Reset Source High LimitSAT cooling reset source high limit (1 to 150)Write
AV35SAT Heat Setpoint Reset Source Low LimitSAT heating reset source low limit (-30 to 150)Write
AV36SAT Heat Setpoint Reset Source High LimitSAT heating reset source high limit (1 to 150)Write
AV37Control Temperature High Alarm OffsetHigh control temperature alarm offset (0 to 50)Write
AV38Control Temperature Low Alarm OffsetLow control temperature alarm offset (0 to 50)Write
AV39Heat Pump Compressor Heat LockoutCompressor heating locked out below this OAT (-30 to 100)Write
AV40Minimum Main Fan VFD in Cooling ModeMinimum SZ VAV fan speed in cooling (0 to 100)Write
AV41Minimum Main Fan VFD in Heating ModeMinimum SZ VAV fan speed in heating (0 to 100)Write
AV42Minimum Main Fan VFD in Vent ModeSZ VAV fan speed in vent mode (0 to 100)Write
AV43Maximum Economizer in Heating ModeMaximum economizer position in heating (0 to 100)Write
AV44Minimum Economizer PositionMinimum OA damper position when occupied (0 to 100)Write
AV45Maximum Economizer CO2 Reset LimitHighest economizer minimum position from CO2 reset (0 to 100)Write
AV46Maximum Main Fan VFD in Heat ModeMaximum SZ VAV fan speed in heating (0 to 100)Write
AV47Heat Pump Defrost Minimum IntervalMinimum time between heat pump defrosts (0 Min. . to 120 Min)Write
AV48Heat Pump Adaptive Defrost IncrementAdaptive defrost interval step (0 to 30)Write
AV49CO2 Minimum SetpointCO2 level where economizer minimum reset starts (0 to 2000)Write
AV50CO2 Maximum SetpointCO2 level for full economizer minimum reset (0 to 2000)Write
AV51Indoor Humidity Setpoint Low Reset LimitIndoor humidity setpoint, low reset limit (0 to 100)Write
AV52Indoor Humidity Setpoint High Reset LimitIndoor humidity setpoint, high reset limit (0 to 100)Write
AV53Duct Static Pressure SetpointDuct static pressure setpoint (.10 to 3.0)Write
AV54Duct Static Pressure Control DeadbandDuct static pressure deadband (.01 to .5)Write
AV55Building Pressure Control SetpointBuilding pressure setpoint (-.20 to .20)Write
AV56Building Pressure Control DeadbandBuilding pressure deadband (.01 to .1)Write
AV57Head Pressure Setpoint in Cooling ModeHead pressure setpoint in cooling (240 PSI to 420 PSI)Write
AV58Head Pressure Setpoint in Reheat ModeHead pressure setpoint in reheat (240 PSI to 420 PSI)Write
AV59Minimum Outdoor Air CFMMinimum outdoor airflow setpoint (.10K to 200K)Write
AV60Outdoor Air CFM Proportional WindowOA CFM control proportional window (10 to 9999)Write
AV61SZ VAV Fan Speed IntegralSZ VAV fan speed integral constant (0 to 10)Write
AVmin62Schedule ForceOccupancy command from the BASWrite0=Auto (controller schedule), 1=Forced Occupied, 2=Forced Unoccupied
AV63HVAC Mode OverrideForces the unit into a mode; Auto returns controlWrite0=Auto, 1=Vent, 2=Cool, 3=Heat, 4=Vent Dehum, 5=Cool Dehum, 6=Heat Dehum
AV64Fan VFD OverrideFixed supply fan VFD speed; Auto returns controlWrite0-100 %, 65535=Auto
AV65Outdoor Air Damper OverrideFixed OA damper position; Auto returns controlWrite0-100 %, 65535=Auto
AV66Warm-Up Supply Air Temperature SetpointSupply air setpoint during warm-up (40 to 240)Write
AV67Cool-Down Supply Air Temperature SetpointSupply air setpoint during cool-down (30 to 80)Write
AV69Minimum Condenser PositionMinimum condenser signal (EM1 head pressure) (0 to 100)Write
AV70Maximum Condenser PositionMaximum condenser signal (EM1 head pressure) (0 to 100)Write
AV71Preheat Cooling SetpointPreheat leaving air setpoint in cooling (35 to 90)Write
AV72Preheat Heating SetpointPreheat leaving air setpoint in heating (35 to 90)Write
AV73Preheat Venting SetpointPreheat leaving air setpoint in vent (35 to 90)Write
AV74Push-Button Override DurationPush-button override duration (0 to 8)Write
BI1Cooling Enabled StatusMechanical Cooling is enabled based on the Cooling LockoutRead
BI2Heating Enabled StatusMechanical heating enabled by the heating lockoutRead
BI3Economizer Enabled StatusThe Economizer is enabled based on the Economizer Enable SetpointRead
BI4Reheat Enabled StatusModulating Hotgas Reheat EnabledRead
BI5Emergency Heat Enabled StatusShows the Emergency Heat is enabled based on the Compressor Heating LockoutRead
BI6Bad Supply Air SensorA failure of the Supply Air SensorRead
BI7Reserved For Bad RAT SensorNot Currently UsedRead
BI8Bad Outdoor Air SensorFailure of the Outdoor Air Temperature SensorRead
BI9Bad Space Temp SensorFailure of the Space Temperature SensorRead
BI10Missing EM1 Expansion ModuleEM1 Module is configured but not detectedRead
BI11Bad Coil Pressure SensorFailure of the Coil Pressure SensorRead
BI12Bad CO2 SensorFailure of the CO2 SensorRead
BI13Bad Discharge SensorFailure of the Digital Compressor Discharge Temperature SensorRead
BI14Bad Outdoor Airflow SensorAn Outdoor Airflow Sensor is configured, but not detectedRead
BI15Bad Exhaust Airflow SensorAn Exhaust Airflow Sensor is configured, but not detectedRead
BI16Bad Supply Airflow SensorA Supply Airflow Sensor is configured, but not detectedRead
BI17Bad Return Airflow SensorA Return Airflow Sensor is configured, but not detectedRead
BI18Bad or Missing Reheat BoardThe MHGR board is configured but not detectedRead
BI19Bad or Missing MODGAS BoardThe MODGAS board is configured but not detectedRead
BI20Bad or Missing 12 Relay Expansion Board.The 12 Relay Expansion Board is configured but not detectedRead
BI21Mechanical Cooling AlarmSupply air did not drop 5°F with compressors onRead
BI22Mechanical Heating AlarmSupply air did not rise 5°F in heating modeRead
BI23Fan Proving AlarmMain fan airflow failureRead
BI24Dirty Filter AlarmDirty filterRead
BI25Emergency Shutdown AlarmEmergency shutdown activeRead
BI26High Supply Temp Cutoff AlarmThe Supply Air has risen above the Hi SAT Cutoff SetpointRead
BI27Low Supply Temp Cutoff AlarmSupply air below the low SAT cutoffRead
BI28High Control Mode AlarmControl temperature above cooling enable plus alarm offsetRead
BI29Low Control Mode AlarmControl temperature below heating enable minus alarm offsetRead
BI30Digital Compressor Cutoff AlarmDigital compressor discharge above 268°F or sensor shortedRead
BI31Digital Compressor Lockout AlarmFive digital compressor cutoffs within four hoursRead
BI32High Head Pressure AlarmOccurs if the Head Pressure exceeds the acceptable limitRead
BI33Loop Water Proof of Flow AlarmWSHP loop water flow not provenRead
BI34Low Suction Pressure AlarmWSHP suction pressure below the low setpointRead
BI35Unsafe Suction Pressure AlarmWSHP suction pressure below the unsafe setpointRead
BI36Low Leaving Water Temperature AlarmWSHP leaving water too cold in heatingRead
BI37On Board Relay 1 Main FanStatus of Relay 1 on VCB-X Main BoardRead
BI38On Board Relay 2Status of Relay 2 on VCB-X Main BoardRead
BI39On Board Relay 3Status of Relay 3 on VCB-X Main BoardRead
BI40On Board Relay 4Status of Relay 4 on VCB-X Main BoardRead
BI41On Board Relay 5Status of Relay 5 on VCB-X Main BoardRead
BI42On Board Relay 6Status of Relay 6 on VCB-X Main BoardRead
BI43Expansion Module Relay 1Status of Relay 1 on the EM1 Expansion ModuleRead
BI44Expansion Module Relay 2Status of Relay 2 on the EM1 Expansion ModuleRead
BI45Expansion Module Relay 3Status of Relay 3 on the EM1 Expansion ModuleRead
BI46Expansion Module Relay 4Status of Relay 4 on the EM1 Expansion ModuleRead
BI47Expansion Module Relay 5Status of Relay 5 on the EM1 Expansion ModuleRead
BI4812 Relay Expansion Module Relay 1Status of Relay 1 on the 12 Relay Expansion ModuleRead
BI4912 Relay Expansion Module Relay 2Status of Relay 2 on the 12 Relay Expansion ModuleRead
BI5012 Relay Expansion Module Relay 3Status of Relay 3 on the 12 Relay Expansion ModuleRead
BI5112 Relay Expansion Module Relay 4Status of Relay 4 on the 12 Relay Expansion ModuleRead
BI5212 Relay Expansion Module Relay 5Status of Relay 5 on the 12 Relay Expansion ModuleRead
BI5312 Relay Expansion Module Relay 6Status of Relay 6 on the 12 Relay Expansion ModuleRead
BI5412 Relay Expansion Module Relay 7Status of Relay 7 on the 12 Relay Expansion ModuleRead
BI5512 Relay Expansion Module Relay 8Status of Relay 8 on the 12 Relay Expansion ModuleRead
BI5612 Relay Expansion Module Relay 9Status of Relay 9 on the 12 Relay Expansion ModuleRead
BI5712 Relay Expansion Module Relay 10Status of Relay 10 on the 12 Relay Expansion ModuleRead
BI5812 Relay Expansion Module Relay 11Status of Relay 11 on the 12 Relay Expansion ModuleRead
BI5912 Relay Expansion Module Relay 12Status of Relay 12 on the 12 Relay Expansion ModuleRead
BI60Reheat Expansion Board FAN RelayStatus of Reheat Board Relay 1Read
BI61Reheat Expansion Board COMP RelayStatus of Reheat Board Relay 2Read
BI62Reheat Expansion Board VALVE RelayStatus of Reheat Board Relay 3Read
BI63Reheat Expansion Board AUX RelayStatus of Reheat Board Relay 4Read
BI64MODGAS-X Controller Fan RelayStatus of the Fan Relay on the MODGAS-X ControllerRead
BI65MODGAS-X Controller Low Speed RelayStatus of the Low Speed Relay on the MODGAS-X ControllerRead
BI66MODGAS-X Controller AUX 1 RelayStatus of the AUX 1 Relay on the MODGAS-X ControllerRead
BI67MODGAS-X Controller AUX 2 RelayStatus of the AUX 2 Relay on the MODGAS-X ControllerRead
BI68Title 24 Sensor AlarmOutside Air or Supply Air Temperature Sensor is shorted or missingRead
BI69Title 24 Not Economizing When It ShouldEconomizer is enabled but not following the desired Economizer position commandedRead
BI70Title 24 Economizing When It Should NotEconomizer open past minimum while not enabledRead
BI71Title 24 Damper FailureEconomizer not within 10% of command in 150 sRead
BI72Title 24 Excess Outdoor AirEconomizer feedback is lost or Economizer is not following commanded positionRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VCB-X Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AAON VCB-X Controller

How many BACnet points does the AAON VCB-X Controller have?

This list has 196 BACnet objects: 51 analog inputs, 73 analog values, 72 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AAON VCB-X Controller BACnet points are writable?

73 of the 196 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AAON VCB-X Controller BACnet documentation?

The source is VCB-X Controller Field Technical Guide (Appendix C - VCB-X BACnet) (OR-VCBX-FIELD-TGD-01X), revision February 2018 (copyright date), published free by AAON at https://www.aaon.com/hubfs/Controls%20Literature/OR-VCBX-FIELD-TGD-01X.pdf.

What are the minimum BACnet points to integrate the AAON VCB-X Controller?

Start with AV 62 Schedule Force (0 Auto, 1 forced occupied, 2 forced unoccupied); AV 1 Occupied Cooling Setpoint (Cooling starts one degree above this); AV 2 Occupied Heating Setpoint (Heating starts one degree below this); AV 10 Supply Air Cooling Setpoint (Discharge air temp target in cooling); AI 3 Control Status (Current occupancy status); AI 4 HVAC Mode (Off, vent, cool, heat, dehum, defrost and other modes); AI 5 Control Temperature (Reading from the configured control sensor); AI 7 Supply Air Temperature (Discharge air temp leaving the unit); AI 40 Alarm Status (Bit-coded summary of active alarms).

How do I enable BMS control of the AAON VCB-X Controller?

Occupancy comes from AV 62 Schedule Force (0 = follow the controller's schedule, 1 = forced occupied, 2 = forced unoccupied). AV 63 HVAC Mode Override, AV 64 Fan VFD Override and AV 65 Outdoor Air Damper Override force operation; writing Auto (0 for the mode override, 65535 for fan and damper) returns control to the unit.

Can the BMS supply sensor values to the AAON VCB-X Controller?

Not supported: the guide states sensor inputs can't be written over BACnet.

How do I check these points on the real VCB-X Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AAON BACnet points lists

Source: VCB-X Controller Field Technical Guide (Appendix C - VCB-X BACnet) · OR-VCBX-FIELD-TGD-01X · rev. February 2018 (copyright date). Object names, instances and units are reproduced as published; descriptions are our own.