VAV / zone controller · BACnet points list

AAON VAV/Zone BACnet Controller (VAVZB) BACnet points list

Updated 28 October 2026

Short answer

The VAVZB is AAON's VAV box and zone damper controller, used on AAON VAV and zoning systems with an AAON unit controller. It has an on-board BACnet MS/TP port next to the AAON communication loop. Over BACnet it exposes 11 analog inputs, 24 setpoint and configuration analog values, 17 binary status and alarm inputs and 3 multi-state status inputs.

This page lists 55 BACnet objects for the AAON VAV/Zone BACnet Controller (VAVZB) — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.

Manufacturer
AAON
Model
VAV/Zone BACnet Controller (VAVZB)
Equipment
VAV / zone controller
Equipment type
VAV boxes & fan coils
BACnet objects
55 (24 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
VAVZB, VAV/Zone Controller, ASM02426, ASM02427, ASM02661, ASM02662, SS1116, SS1146, G067750
Source document
VAV/Zone BACnet Controller Package Technical Guide (Appendix B: BACnet MS/TP Parameters) · G067750 · rev. Rev. C, December 21, 2022
Download CSV 55 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: AAON VAV/Zone BACnet Controller (VAVZB)

Integration in brief

Set the MAC address, device ID and MS/TP baud on the controller's LCD Settings screens. The BMS can then read zone temperature, airflow, damper position and alarms and write the occupied heating and cooling setpoints and damper/airflow limits. Occupancy itself still comes from the AAON unit controller or GPC-XP over the AAON communication loop.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1Occupied Cooling SetpointOccupied cooling setpoint, 50-90 °FWrite
AV 2Occupied Heating SetpointOccupied heating setpoint, 50-90 °FWrite
MI 1Scheduled Mode of OperationOccupancy/operating mode in effectRead
MI 2Space Temperature HVAC ModeNo demand, cooling, heating or sensor failureRead
AI 2Space TemperatureZone temperatureRead
AI 9Pressure Independent AirflowMeasured airflow (pressure-independent boxes)Read
AI 8Damper PositionCurrent damper positionRead
AI 7Discharge TemperatureBox discharge air temp (if sensor fitted)Read
BI 11Bad or Missing Space SensorSpace sensor failed or missingRead
BI 12Bad or Missing Airflow SensorAirflow sensor failed or missingRead

Enable & remote start

There is no BACnet occupancy or enable point. The VAVZB takes its occupied/unoccupied command from the AAON unit controller or a GPC-XP over the AAON communication loop, and push-button overrides on the room sensor return it to occupied for 0-8 hours (AV 8). Damper force modes (including AV 21 Force Damper to Fixed Position) stay active until cancelled or power is removed.

Network setup

Watch out for

AAON VAV/Zone BACnet Controller (VAVZB) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

55 of 55 shown
Type
BinaryMulti-state
Access
Show
AAON VAV/Zone BACnet Controller (VAVZB) BACnet Points List
DescriptionStates
AI1Application Software VersionSoftware version in the controllerRead
AImin2Space TemperatureZone temperature from the room sensor°FRead
AI3Active Cooling SetpointCooling setpoint in effect°FRead
AI4Active Heating SetpointHeating setpoint in effect°FRead
AI5Slide Offset EffectSetpoint adjustment from the room sensor slide°FRead
AI6Duct TemperatureSupply duct air temperature°FRead
AImin7Discharge TemperatureBox discharge air temperature (if sensor fitted)°FRead
AImin8Damper PositionDamper positionRead
AImin9Pressure Independent AirflowMeasured airflow (pressure-independent boxes)Read
AI10Active Heat StagesHeat stages currently onRead
AI11Modulating Heat SignalModulating heat output signalRead
AVmin1Occupied Cooling Setpoint50-90 °F°FWrite
AVmin2Occupied Heating Setpoint50-90 °F°FWrite
AV3Unoccupied Cooling Setpoint Offset0-30 °F above occupied°FWrite
AV4Unoccupied Heating Setpoint Offset-30-0 °F below occupied°FWrite
AV5Cooling Alarm Limit OffsetHigh space alarm offset, 1-50 °F°FWrite
AV6Heating Alarm Limit OffsetLow space alarm offset, -50 to -1 °F°FWrite
AV7Maximum Slide Offset EffectMaximum slide adjustment, 0-5 °F°FWrite
AV8Push-Button Override DurationOverride duration, 0-8 hhWrite
AV9Heating Setpoints to Call on Main HeatHeating setpoint that calls the main unit for heat, 50-90 °F°FWrite
AV10Auxiliary Heat SetpointBox auxiliary heat setpoint, 50-90 °F°FWrite
AV11Maximum Damper/Airflow SettingMaximum damper position or airflow (0-30000)Write
AV12Vent Mode Damper/Airflow SettingMinimum damper/airflow in vent modeWrite
AV13Cooling Mode Damper/Airflow SettingMinimum damper/airflow in coolingWrite
AV14Heating Mode Damper/Airflow SettingMinimum damper/airflow in heatingWrite
AV15Unoccupied Damper/Airflow SettingDamper/airflow in unoccupied modeWrite
AV16Parallel Fan On Damper/Airflow SettingDamper/airflow where the parallel fan startsWrite
AV17Damper Force Mode Fixed PositionFixed damper/airflow used by the force modeWrite
AV18Box Heating Min Damper/Airflow SettingMinimum damper/airflow when the box heatsWrite
AV19Requires Main Fan Status for HeatingBox heat needs main fan proof (0/1)Write
AV20Force Damper to Fixed PositionForce damper to the fixed position (0/1)Write
AV21Space Sensor Calibration OffsetSpace sensor offset, -100 to 100 °F°FWrite
AV22Discharge Sensor Calibration OffsetDischarge sensor offset, -100 to 100 °F°FWrite
AV23Vacant Room Cooling Mode OffsetCooling offset when the room is empty, 0-30 °F°FWrite
AV24Vacant Room Heating Mode OffsetHeating offset when the room is empty, -30-0 °F°FWrite
BI1Box Fan StatusBox fan statusRead
BI2Heating Relay #1Heat relay 1 statusRead
BI3Heating Relay #2Heat relay 2 statusRead
BI4Main Fan RequiredBox is asking for the main unit fanRead
BI5Main Fan StatusMain unit fan statusRead
BI6Airflow Too Low for HeatingAirflow too low for box heatRead
BI7Box Allowed to VoteBox is a voting zoneRead
BI8Box Fan Starting Delay ActiveBox fan start delay runningRead
BI9Auxiliary Heat Relay StatusAuxiliary heat relay statusRead
BI10Occupancy StatusOccupied/unoccupied statusRead
BImin11Bad or Missing Space SensorSpace sensor alarmRead
BImin12Bad or Missing Airflow SensorAirflow (CFM) sensor alarmRead
BI13Damper Failed to Move ClockwiseDamper opening/closing alarmRead
BI14Damper Failed to Move Counter-ClockwiseDamper opening/closing alarmRead
BI15High Space Temperature AlarmHigh space temperature alarmRead
BI16Low Space Temperature AlarmLow space temperature alarmRead
BI17Damper Feedback FailureDamper feedback failure alarmRead
MImin1Scheduled Mode of OperationCurrent occupancy/operating modeRead1=Unoccupied Mode, 2=Occupied Mode, 3=Override Mode, 4=Calibrating Damper Feedback, 5=Group Override, 6=Open Window Forced Off, 7=Lost Communication with RTU, 8=Occupied Room is Empty
MImin2Space Temperature HVAC ModeSpace demand modeRead1=No Space Demand, 2=Space Cooling Mode, 3=Space Heating Mode, 4=Sensor Failure Mode
MI3Type of VAV BoxConfigured box typeRead1=Cooling Only Box, 2=Heat/Cool Changeover Box, 3=Series Fan Powered Box, 4=Parallel Fan Powered Box

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VAV/Zone BACnet Controller (VAVZB) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AAON VAV/Zone BACnet Controller (VAVZB)

How many BACnet points does the AAON VAV/Zone BACnet Controller (VAVZB) have?

This list has 55 BACnet objects: 11 analog inputs, 24 analog values, 17 binary inputs, 3 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AAON VAV/Zone BACnet Controller (VAVZB) BACnet points are writable?

24 of the 55 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official AAON VAV/Zone BACnet Controller (VAVZB) BACnet documentation?

The source is VAV/Zone BACnet Controller Package Technical Guide (Appendix B: BACnet MS/TP Parameters) (G067750), revision Rev. C, December 21, 2022, published free by AAON at https://www.aaon.com/hubfs/Controls%20Literature/G067750-VAVZP-BACNET-RevC%20221221.pdf.

What are the minimum BACnet points to integrate the AAON VAV/Zone BACnet Controller (VAVZB)?

Start with AV 1 Occupied Cooling Setpoint (Occupied cooling setpoint, 50-90 °F); AV 2 Occupied Heating Setpoint (Occupied heating setpoint, 50-90 °F); MI 1 Scheduled Mode of Operation (Occupancy/operating mode in effect); MI 2 Space Temperature HVAC Mode (No demand, cooling, heating or sensor failure); AI 2 Space Temperature (Zone temperature); AI 9 Pressure Independent Airflow (Measured airflow (pressure-independent boxes)); AI 8 Damper Position (Current damper position); AI 7 Discharge Temperature (Box discharge air temp (if sensor fitted)); BI 11 Bad or Missing Space Sensor (Space sensor failed or missing); BI 12 Bad or Missing Airflow Sensor (Airflow sensor failed or missing).

How do I enable BMS control of the AAON VAV/Zone BACnet Controller (VAVZB)?

There is no BACnet occupancy or enable point. The VAVZB takes its occupied/unoccupied command from the AAON unit controller or a GPC-XP over the AAON communication loop, and push-button overrides on the room sensor return it to occupied for 0-8 hours (AV 8). Damper force modes (including AV 21 Force Damper to Fixed Position) stay active until cancelled or power is removed.

How do I check these points on the real VAV/Zone BACnet Controller (VAVZB)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AAON BACnet points lists

Source: VAV/Zone BACnet Controller Package Technical Guide (Appendix B: BACnet MS/TP Parameters) · G067750 · rev. Rev. C, December 21, 2022. Object names, instances and units are reproduced as published; descriptions are our own.