Rooftop unit / air handler controller · BACnet points list

AAON Touchscreen Controller BACnet points list

Updated 6 November 2026

Short answer

The AAON Touchscreen Controller runs the unit sequence (cooling, heating, dehumidification, economizer, heat wheel, fans) and offers BACnet MS/TP or Modbus on its RS-485 port. The list has 116 AVs (sensor readings, outputs and writable setpoints) and 42 BVs (stage, mode and alarm status plus three writable network commands: occupancy, VAV daytime heat and emergency shutdown).

This page lists 158 BACnet objects for the AAON Touchscreen Controller — 69 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.

Manufacturer
AAON
Model
AAON Touchscreen Controller
Equipment
Rooftop unit / air handler controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
158 (69 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
AAON Touchscreen, Touch Screen Controller, AAON TS controller
Source document
AAON Touchscreen Controller User's Manual - Tables 3-7 BACnet Points List · rev. 2019-07-02
Download CSV 158 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.

BMS integration notes: AAON Touchscreen Controller

Integration in brief

Select BACnet on the Network Config screen and set baud, parity and address. Occupancy can come from the internal schedule, the DI1 remote contact or BV 39 Network Occupy; write the occupied setpoints and read mode, fan and alarm status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 39Network OccupyOccupied command from the BMSWrite
BV 41Network Emergency ShutdownEmergency shutdown commandWrite
AV 59Occupied Cooling SptOccupied cooling setpointWrite
AV 77Occupied Heating SptOccupied heating setpointWrite
BV 6Occupancy StatusOccupied statusRead
BV 7Supply Fan StatusSupply fan provenRead
AV 24Control TempTemperature the unit controls toRead
AV 8Supply Air TempSupply air temperatureRead
BV 23Emergency Shutdown AlarmEmergency shutdown alarmRead
BV 25Supply Fan AlarmSupply fan alarmRead

Enable & remote start

Occupied mode comes from the internal schedule, a normally open remote forced-occupied contact on DI1, or the BACnet Network Occupy point (BV 39). BV 41 Network Emergency Shutdown stops the unit; BV 40 VAV Daytime Heat is the only way to start VAV daytime heating.

Network setup

Watch out for

AAON Touchscreen Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

158 of 158 shown
Type
AnalogBinary
Access
Show
AAON Touchscreen Controller BACnet Points List
DescriptionStates
AV0Discharge Press 1Discharge Press 1psigRead
AV1Discharge Press 2Discharge Press 2psigRead
AV2Suction Press 1Suction Press 1psigRead
AV3Suction Press 2Suction Press 2psigRead
AV4Discharge Temp 1Discharge Temp 1°FRead
AV5Discharge Temp 2Discharge Temp 2°FRead
AV6Mixed Air TempMixed Air Temp°FRead
AV7Return Air TempReturn Air Temp°FRead
AVmin8Supply Air TempSupply Air Temp°FRead
AV9Outside Air TempOutside Air Temp°FRead
AV10Return RHReturn RH%RHRead
AV11Outside RHOutside RH%RHRead
AV12CO2CO2ppmRead
AV13OA AirflowOA AirflowCFMRead
AV14Duct PressDuct Pressin. WCRead
AV15Building PressBuilding Pressin. WCRead
AV16Hot Water ValveHot Water Valve%Read
AV17Chilled Water ValveChilled Water Valve%Read
AV18Condenser Fan 1Condenser Fan 1%Read
AV19Condenser Fan 2Condenser Fan 2%Read
AV20MHGRHMHGRH%Read
AV21Exhaust FanExhaust Fan%Read
AV22Outside Air DamperOutside Air Damper%Read
AV23Supply FanSupply Fan%Read
AVmin24Control TempControl Temp°FRead
AV25Control RHControl RH%RHRead
AV26Working Clg SptWorking Clg Spt°FRead
AV27Working Htg SptWorking Htg Spt°FRead
AV28Clg PID CountClg PID CountRead
AV29Digital Comp 1Digital Comp 1%Read
AV30Digital Comp 2Digital Comp 2%Read
AV31Cool PIDCool PIDRead
AV32Heat PIDHeat PID%Read
AV33Clg Supply ResetClg Supply Reset°FRead
AV34Htg Supply ResetHtg Supply Reset°FRead
AV35Econ PIDEcon PIDRead
AV36Econ Ramp CountEcon Ramp CountminRead
AV37Econ Lockout TimerEcon Lockout TimerminRead
AV38Combustion Blower RPMCombustion Blower RPMrpmRead
AV39Raw Mod Gas ValveRaw Mod Gas Valve%Read
AV40Mod Gas ValveMod Gas Valve%Read
AV41Raw Mod Gas Valve 2Raw Mod Gas Valve 2%Read
AV42Mod Gas PIDMod Gas PIDRead
AV43Electric Preheat PIDElectric Preheat PIDRead
AV44Preheat LAT Probe APreheat LAT Probe A°FRead
AV45Preheat LAT Probe BPreheat LAT Probe B°FRead
AV46Preheat LAT AveragePreheat LAT Average°FRead
AV47Network AddressNetwork AddressRead
AV48Morning Cool-Down SptMorning Cool-Down Spt (range 55 to 85), default 78°FWrite
AV49Morning Warm-Up SptMorning Warm-Up Spt (range 50 to 85), default 65°FWrite
AV50Preheat OAT SetpointPreheat OAT Setpoint (range 10 to 60), default 35°FWrite
AV51Preheat LAT SetpointPreheat LAT Setpoint (range 35 to 80), default 50°FWrite
AV52Duct Static SetpointDuct Static Setpoint (range 0.25 to 5), default 1in. WCWrite
AV53Supply Fan Unoccupied ConfigSupply Fan Unoccupied Config (range 0 to 2), default 0Write
AV54Supply Fan Occupied ConfigSupply Fan Occupied Config (range 0 to 2), default 0Write
AV55CO2 SptCO2 Spt (range 500 to 1500), default 900ppmWrite
AV56Defrost Trigger SptDefrost Trigger Spt (range 0 to 40), default 32°FWrite
AV57Defrost Trigger DelayDefrost Trigger Delay (range 1 to 60), default 30minWrite
AV58Defrost Termination DelayDefrost Termination Delay (range 1 to 10), default 2minWrite
AVmin59Occupied Cooling SptOccupied Cooling Spt (range 55 to 85), default 74°FWrite
AV60Unoccupied Cooling SptUnoccupied Cooling Spt (range 55 to 85), default 78°FWrite
AV61Supply Cooling SptSupply Cooling Spt (range 45 to 65), default 55°FWrite
AV62Compressor On TimeCompressor On Time (range 120 to 255), default 180sWrite
AV63Compressor Off TimeCompressor Off Time (range 60 to 255), default 180sWrite
AV64Compressor Interstage On DelayCompressor Interstage On Delay (range 30 to 255), default 60sWrite
AV65Compressor Interstage Off DelayCompressor Interstage Off Delay (range 30 to 255), default 60sWrite
AV66Outside Air Temp LockoutOutside Air Temp Lockout (range 0 to 65), default 55°FWrite
AV67Space Cooling Hi ResetSpace Cooling Hi Reset (range 55 to 85), default 76°FWrite
AV68Space Cooling Lo ResetSpace Cooling Lo Reset (range 55 to 85), default 73°FWrite
AV69Supply Cooling Hi ResetSupply Cooling Hi Reset (range 45 to 65), default 57°FWrite
AV70Supply Cooling Lo ResetSupply Cooling Lo Reset (range 45 to 65), default 53°FWrite
AV71Sensible Econ SptSensible Econ Spt (range 40 to 80), default 60°FWrite
AV72Econ Lockout TimeEcon Lockout Time (range 1 to 20), default 2minWrite
AV73Econ Min PositionEcon Min Position (range 0 to 100), default 15%Write
AV74Enthalpy Econ SptEnthalpy Econ Spt (range 15 to 25), default 20Btu/lbWrite
AV75Comparative Econ SptComparative Econ Spt (range 1 to 5), default 1Btu/lbWrite
AV76Mixed Air SptMixed Air Spt (range 50 to 80), default 52°FWrite
AVmin77Occupied Heating SptOccupied Heating Spt (range 55 to 85), default 70°FWrite
AV78Unoccupied Heating SptUnoccupied Heating Spt (range 55 to 85), default 65°FWrite
AV79Supply Heating SptSupply Heating Spt (range 55 to 120), default 90°FWrite
AV80Heating On TimeHeating On Time (range 120 to 255), default 180sWrite
AV81Heating Off TimeHeating Off Time (range 120 to 255), default 180sWrite
AV82Heating Interstage On DelayHeating Interstage On Delay (range 30 to 255), default 30sWrite
AV83Heating Interstage Off DelayHeating Interstage Off Delay (range 30 to 255), default 30sWrite
AV84OA Heating LockoutOA Heating Lockout (range 50 to 100), default 75°FWrite
AV85Space Heating Hi ResetSpace Heating Hi Reset (range 55 to 85), default 72°FWrite
AV86Space Heating Lo ResetSpace Heating Lo Reset (range 55 to 85), default 69°FWrite
AV87Supply Heating Hi ResetSupply Heating Hi Reset (range 55 to 120), default 100°FWrite
AV88Supply Heating Lo ResetSupply Heating Lo Reset (range 5 to 120), default 90°FWrite
AV89Dehum Enable SptDehum Enable Spt (range 40 to 60), default 50%RHWrite
AV90Suction Temp SptSuction Temp Spt (range 38 to 48), default 42°FWrite
AV91MHGRH Purge TimeMHGRH Purge Time (range 60 to 240), default 120sWrite
AV92MHGRH Purge PeriodMHGRH Purge Period (range 1 to 120), default 60minWrite
AV93Cooling Head Pressure 1 SptCooling Head Pressure 1 Spt (range 250 to 475), default 340psigWrite
AV94Cooling Head Pressure 1 SptCooling Head Pressure 1 Spt (range 250 to 475), default 340psigWrite
AV95Dehum Head Pressure 1 SptDehum Head Pressure 1 Spt (range 250 to 475), default 390psigWrite
AV96Dehum Head Pressure 2 SptDehum Head Pressure 2 Spt (range 250 to 475), default 390psigWrite
AV97Condenser Valve Min PositionCondenser Valve Min Position (range 0 to 100), default 0%Write
AV98Exhaust Fan Min PositionExhaust Fan Min Position (range 0 to 100), default 33%Write
AV99Building Pressure SptBuilding Pressure Spt (range -.1 to .1), default 0.01in. WCWrite
AV100Heat Wheel Min RunHeat Wheel Min Run (range 1 to 60), default 1sWrite
AV101Heat Wheel Defrost SptHeat Wheel Defrost Spt (range 0 to 35), default 25°FWrite
AV102Heat Wheel Defrost TimeHeat Wheel Defrost Time (range 15 to 255), default 120sWrite
AV103Heat Wheel Defrost PeriodHeat Wheel Defrost Period (range 5 to 120), default 30minWrite
AV104Outside Air Flow SptOutside Air Flow Spt (range 0 to 15000), default 0CFMWrite
AV105Outside Air Flow Max SptOutside Air Flow Max Spt (range 0 to 15000), default 0CFMWrite
AV106Outside Air Flow Min SptOutside Air Flow Min Spt (range 0 to 15000), default 0CFMWrite
AV107Dehum Lockout TempDehum Lockout Temp (range 35 to 75), default 55°FWrite
AV108CAV Fan PositionCAV Fan Position (range 33 to 100), default 100%Write
AV109Supply Fan MaxSupply Fan Max (range 33 to 100), default 100%Write
AV110SF Cool Min PositionSF Cool Min Position (range 33 to 100), default 33%Write
AV111SF DeadbandSF Deadband (range 2 to 10), default 4°FWrite
AV112VAV MCD TimeVAV MCD Time (range 5 to 60), default 30minWrite
AV113VAV MWU TimeVAV MWU Time (range 5 to 60), default 30minWrite
AV114Space TemperatureSpace Temperature°FRead
AV115Space Relative HumiditySpace Relative Humidity%RHRead
BV0EconomizerEconomizerRead0=False, 1=True
BV1Heat WheelHeat WheelRead0=False, 1=True
BV2Exhaust FanExhaust FanRead0=False, 1=True
BV3Comp 2Comp 2Read0=False, 1=True
BV4Comp 1Comp 1Read0=False, 1=True
BV5Supply Fan CommandSupply Fan CommandRead0=False, 1=True
BVmin6Occupancy StatusOccupancy StatusRead0=False, 1=True
BVmin7Supply Fan StatusSupply Fan StatusRead0=False, 1=True
BV8Emergency Shutdown StatusEmergency Shutdown StatusRead0=False, 1=True
BV9Water Flow StatusWater Flow StatusRead0=False, 1=True
BV10Clogged Filter StatusClogged Filter StatusRead0=False, 1=True
BV11Comp 2 2nd StepComp 2 2nd StepRead0=False, 1=True
BV12Comp 1 2nd StepComp 1 2nd StepRead0=False, 1=True
BV13Heat Stage 4Heat Stage 4Read0=False, 1=True
BV14Heat Stage 3Heat Stage 3Read0=False, 1=True
BV15Heat Stage 2Heat Stage 2Read0=False, 1=True
BV16Heat Stage 1Heat Stage 1Read0=False, 1=True
BV17DehumDehumRead0=False, 1=True
BV18CoolCoolRead0=False, 1=True
BV19Heat ModeHeat ModeRead0=False, 1=True
BV20Vent ModeVent ModeRead0=False, 1=True
BV21On Off ModeOn Off ModeRead0=False, 1=True
BV22Reversing ValveReversing ValveRead0=False, 1=True
BVmin23Emergency Shutdown AlarmEmergency Shutdown AlarmRead0=False, 1=True
BV24Clogged Filter AlarmClogged Filter AlarmRead0=False, 1=True
BVmin25Supply Fan AlarmSupply Fan AlarmRead0=False, 1=True
BV26CO2 AlarmCO2 AlarmRead0=False, 1=True
BV27Supply Air Temp High LimitSupply Air Temp High LimitRead0=False, 1=True
BV28Supply Air Temp Low LimitSupply Air Temp Low LimitRead0=False, 1=True
BV29Outside Air OpenOutside Air OpenRead0=False, 1=True
BV30Outside Air ShortedOutside Air ShortedRead0=False, 1=True
BV31Supply Air OpenSupply Air OpenRead0=False, 1=True
BV32Supply Air ShortedSupply Air ShortedRead0=False, 1=True
BV33Return Air OpenReturn Air OpenRead0=False, 1=True
BV34Return Air ShortedReturn Air ShortedRead0=False, 1=True
BV35Mixed Air OpenMixed Air OpenRead0=False, 1=True
BV36Mixed Air ShortedMixed Air ShortedRead0=False, 1=True
BV37OA Temp LockoutOA Temp LockoutRead0=False, 1=True
BV38Water FlowWater FlowRead0=False, 1=True
BVmin39Network OccupyNetwork Occupy, default FalseWrite0=False, 1=True
BV40VAV Daytime HeatVAV Daytime Heat, default FalseWrite0=False, 1=True
BVmin41Network Emergency ShutdownNetwork Emergency Shutdown, default FalseWrite0=False, 1=True
Object ID lookup: AAON Touchscreen Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AAON Touchscreen Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AAON Touchscreen Controller

How many BACnet points does the AAON Touchscreen Controller have?

This list has 158 BACnet objects: 116 analog values, 42 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AAON Touchscreen Controller BACnet points are writable?

69 of the 158 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official AAON Touchscreen Controller BACnet documentation?

The source is AAON Touchscreen Controller User's Manual - Tables 3-7 BACnet Points List, revision 2019-07-02, published free by AAON at https://23126496.fs1.hubspotusercontent-na1.net/hubfs/23126496/AAON_TS_Controller_Manual_190702.pdf.

What are the minimum BACnet points to integrate the AAON Touchscreen Controller?

Start with BV 39 Network Occupy (Occupied command from the BMS); BV 41 Network Emergency Shutdown (Emergency shutdown command); AV 59 Occupied Cooling Spt (Occupied cooling setpoint); AV 77 Occupied Heating Spt (Occupied heating setpoint); BV 6 Occupancy Status (Occupied status); BV 7 Supply Fan Status (Supply fan proven); AV 24 Control Temp (Temperature the unit controls to); AV 8 Supply Air Temp (Supply air temperature); BV 23 Emergency Shutdown Alarm (Emergency shutdown alarm); BV 25 Supply Fan Alarm (Supply fan alarm).

How do I enable BMS control of the AAON Touchscreen Controller?

Occupied mode comes from the internal schedule, a normally open remote forced-occupied contact on DI1, or the BACnet Network Occupy point (BV 39). BV 41 Network Emergency Shutdown stops the unit; BV 40 VAV Daytime Heat is the only way to start VAV daytime heating.

How do I check these points on the real AAON Touchscreen Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AAON BACnet points lists

Source: AAON Touchscreen Controller User's Manual - Tables 3-7 BACnet Points List · rev. 2019-07-02. Object names, instances and units are reproduced as published; descriptions are our own.