Rooftop unit / air handler controller · BACnet points list
AAON Touchscreen Controller BACnet points list
Updated 6 November 2026
The AAON Touchscreen Controller runs the unit sequence (cooling, heating, dehumidification, economizer, heat wheel, fans) and offers BACnet MS/TP or Modbus on its RS-485 port. The list has 116 AVs (sensor readings, outputs and writable setpoints) and 42 BVs (stage, mode and alarm status plus three writable network commands: occupancy, VAV daytime heat and emergency shutdown).
This page lists 158 BACnet objects for the AAON Touchscreen Controller — 69 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.
- Manufacturer
- AAON
- Model
- AAON Touchscreen Controller
- Equipment
- Rooftop unit / air handler controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 158 (69 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- AAON Touchscreen, Touch Screen Controller, AAON TS controller
Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.
BMS integration notes: AAON Touchscreen Controller
Select BACnet on the Network Config screen and set baud, parity and address. Occupancy can come from the internal schedule, the DI1 remote contact or BV 39 Network Occupy; write the occupied setpoints and read mode, fan and alarm status.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 39 | Network Occupy | Occupied command from the BMS | Write |
| BV 41 | Network Emergency Shutdown | Emergency shutdown command | Write |
| AV 59 | Occupied Cooling Spt | Occupied cooling setpoint | Write |
| AV 77 | Occupied Heating Spt | Occupied heating setpoint | Write |
| BV 6 | Occupancy Status | Occupied status | Read |
| BV 7 | Supply Fan Status | Supply fan proven | Read |
| AV 24 | Control Temp | Temperature the unit controls to | Read |
| AV 8 | Supply Air Temp | Supply air temperature | Read |
| BV 23 | Emergency Shutdown Alarm | Emergency shutdown alarm | Read |
| BV 25 | Supply Fan Alarm | Supply fan alarm | Read |
Enable & remote start
Occupied mode comes from the internal schedule, a normally open remote forced-occupied contact on DI1, or the BACnet Network Occupy point (BV 39). BV 41 Network Emergency Shutdown stops the unit; BV 40 VAV Daytime Heat is the only way to start VAV daytime heating.
Network setup
- Menu > Setup > Next > Network Config: Protocol (BACnet or Modbus), baud rate, bits/parity/stop and unit address for RS-485 port 1.
Watch out for
- With the Unoccupied Mode setpoint OFF the unit stays off when unoccupied.
- Space temperature and humidity (AV 114, AV 115) are read-only; there is no BAS sensor input in this list.
AAON Touchscreen Controller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 0 | Discharge Press 1 | Discharge Press 1 | psig | Read | |
| AV | 1 | Discharge Press 2 | Discharge Press 2 | psig | Read | |
| AV | 2 | Suction Press 1 | Suction Press 1 | psig | Read | |
| AV | 3 | Suction Press 2 | Suction Press 2 | psig | Read | |
| AV | 4 | Discharge Temp 1 | Discharge Temp 1 | °F | Read | |
| AV | 5 | Discharge Temp 2 | Discharge Temp 2 | °F | Read | |
| AV | 6 | Mixed Air Temp | Mixed Air Temp | °F | Read | |
| AV | 7 | Return Air Temp | Return Air Temp | °F | Read | |
| AVmin | 8 | Supply Air Temp | Supply Air Temp | °F | Read | |
| AV | 9 | Outside Air Temp | Outside Air Temp | °F | Read | |
| AV | 10 | Return RH | Return RH | %RH | Read | |
| AV | 11 | Outside RH | Outside RH | %RH | Read | |
| AV | 12 | CO2 | CO2 | ppm | Read | |
| AV | 13 | OA Airflow | OA Airflow | CFM | Read | |
| AV | 14 | Duct Press | Duct Press | in. WC | Read | |
| AV | 15 | Building Press | Building Press | in. WC | Read | |
| AV | 16 | Hot Water Valve | Hot Water Valve | % | Read | |
| AV | 17 | Chilled Water Valve | Chilled Water Valve | % | Read | |
| AV | 18 | Condenser Fan 1 | Condenser Fan 1 | % | Read | |
| AV | 19 | Condenser Fan 2 | Condenser Fan 2 | % | Read | |
| AV | 20 | MHGRH | MHGRH | % | Read | |
| AV | 21 | Exhaust Fan | Exhaust Fan | % | Read | |
| AV | 22 | Outside Air Damper | Outside Air Damper | % | Read | |
| AV | 23 | Supply Fan | Supply Fan | % | Read | |
| AVmin | 24 | Control Temp | Control Temp | °F | Read | |
| AV | 25 | Control RH | Control RH | %RH | Read | |
| AV | 26 | Working Clg Spt | Working Clg Spt | °F | Read | |
| AV | 27 | Working Htg Spt | Working Htg Spt | °F | Read | |
| AV | 28 | Clg PID Count | Clg PID Count | Read | ||
| AV | 29 | Digital Comp 1 | Digital Comp 1 | % | Read | |
| AV | 30 | Digital Comp 2 | Digital Comp 2 | % | Read | |
| AV | 31 | Cool PID | Cool PID | Read | ||
| AV | 32 | Heat PID | Heat PID | % | Read | |
| AV | 33 | Clg Supply Reset | Clg Supply Reset | °F | Read | |
| AV | 34 | Htg Supply Reset | Htg Supply Reset | °F | Read | |
| AV | 35 | Econ PID | Econ PID | Read | ||
| AV | 36 | Econ Ramp Count | Econ Ramp Count | min | Read | |
| AV | 37 | Econ Lockout Timer | Econ Lockout Timer | min | Read | |
| AV | 38 | Combustion Blower RPM | Combustion Blower RPM | rpm | Read | |
| AV | 39 | Raw Mod Gas Valve | Raw Mod Gas Valve | % | Read | |
| AV | 40 | Mod Gas Valve | Mod Gas Valve | % | Read | |
| AV | 41 | Raw Mod Gas Valve 2 | Raw Mod Gas Valve 2 | % | Read | |
| AV | 42 | Mod Gas PID | Mod Gas PID | Read | ||
| AV | 43 | Electric Preheat PID | Electric Preheat PID | Read | ||
| AV | 44 | Preheat LAT Probe A | Preheat LAT Probe A | °F | Read | |
| AV | 45 | Preheat LAT Probe B | Preheat LAT Probe B | °F | Read | |
| AV | 46 | Preheat LAT Average | Preheat LAT Average | °F | Read | |
| AV | 47 | Network Address | Network Address | Read | ||
| AV | 48 | Morning Cool-Down Spt | Morning Cool-Down Spt (range 55 to 85), default 78 | °F | Write | |
| AV | 49 | Morning Warm-Up Spt | Morning Warm-Up Spt (range 50 to 85), default 65 | °F | Write | |
| AV | 50 | Preheat OAT Setpoint | Preheat OAT Setpoint (range 10 to 60), default 35 | °F | Write | |
| AV | 51 | Preheat LAT Setpoint | Preheat LAT Setpoint (range 35 to 80), default 50 | °F | Write | |
| AV | 52 | Duct Static Setpoint | Duct Static Setpoint (range 0.25 to 5), default 1 | in. WC | Write | |
| AV | 53 | Supply Fan Unoccupied Config | Supply Fan Unoccupied Config (range 0 to 2), default 0 | Write | ||
| AV | 54 | Supply Fan Occupied Config | Supply Fan Occupied Config (range 0 to 2), default 0 | Write | ||
| AV | 55 | CO2 Spt | CO2 Spt (range 500 to 1500), default 900 | ppm | Write | |
| AV | 56 | Defrost Trigger Spt | Defrost Trigger Spt (range 0 to 40), default 32 | °F | Write | |
| AV | 57 | Defrost Trigger Delay | Defrost Trigger Delay (range 1 to 60), default 30 | min | Write | |
| AV | 58 | Defrost Termination Delay | Defrost Termination Delay (range 1 to 10), default 2 | min | Write | |
| AVmin | 59 | Occupied Cooling Spt | Occupied Cooling Spt (range 55 to 85), default 74 | °F | Write | |
| AV | 60 | Unoccupied Cooling Spt | Unoccupied Cooling Spt (range 55 to 85), default 78 | °F | Write | |
| AV | 61 | Supply Cooling Spt | Supply Cooling Spt (range 45 to 65), default 55 | °F | Write | |
| AV | 62 | Compressor On Time | Compressor On Time (range 120 to 255), default 180 | s | Write | |
| AV | 63 | Compressor Off Time | Compressor Off Time (range 60 to 255), default 180 | s | Write | |
| AV | 64 | Compressor Interstage On Delay | Compressor Interstage On Delay (range 30 to 255), default 60 | s | Write | |
| AV | 65 | Compressor Interstage Off Delay | Compressor Interstage Off Delay (range 30 to 255), default 60 | s | Write | |
| AV | 66 | Outside Air Temp Lockout | Outside Air Temp Lockout (range 0 to 65), default 55 | °F | Write | |
| AV | 67 | Space Cooling Hi Reset | Space Cooling Hi Reset (range 55 to 85), default 76 | °F | Write | |
| AV | 68 | Space Cooling Lo Reset | Space Cooling Lo Reset (range 55 to 85), default 73 | °F | Write | |
| AV | 69 | Supply Cooling Hi Reset | Supply Cooling Hi Reset (range 45 to 65), default 57 | °F | Write | |
| AV | 70 | Supply Cooling Lo Reset | Supply Cooling Lo Reset (range 45 to 65), default 53 | °F | Write | |
| AV | 71 | Sensible Econ Spt | Sensible Econ Spt (range 40 to 80), default 60 | °F | Write | |
| AV | 72 | Econ Lockout Time | Econ Lockout Time (range 1 to 20), default 2 | min | Write | |
| AV | 73 | Econ Min Position | Econ Min Position (range 0 to 100), default 15 | % | Write | |
| AV | 74 | Enthalpy Econ Spt | Enthalpy Econ Spt (range 15 to 25), default 20 | Btu/lb | Write | |
| AV | 75 | Comparative Econ Spt | Comparative Econ Spt (range 1 to 5), default 1 | Btu/lb | Write | |
| AV | 76 | Mixed Air Spt | Mixed Air Spt (range 50 to 80), default 52 | °F | Write | |
| AVmin | 77 | Occupied Heating Spt | Occupied Heating Spt (range 55 to 85), default 70 | °F | Write | |
| AV | 78 | Unoccupied Heating Spt | Unoccupied Heating Spt (range 55 to 85), default 65 | °F | Write | |
| AV | 79 | Supply Heating Spt | Supply Heating Spt (range 55 to 120), default 90 | °F | Write | |
| AV | 80 | Heating On Time | Heating On Time (range 120 to 255), default 180 | s | Write | |
| AV | 81 | Heating Off Time | Heating Off Time (range 120 to 255), default 180 | s | Write | |
| AV | 82 | Heating Interstage On Delay | Heating Interstage On Delay (range 30 to 255), default 30 | s | Write | |
| AV | 83 | Heating Interstage Off Delay | Heating Interstage Off Delay (range 30 to 255), default 30 | s | Write | |
| AV | 84 | OA Heating Lockout | OA Heating Lockout (range 50 to 100), default 75 | °F | Write | |
| AV | 85 | Space Heating Hi Reset | Space Heating Hi Reset (range 55 to 85), default 72 | °F | Write | |
| AV | 86 | Space Heating Lo Reset | Space Heating Lo Reset (range 55 to 85), default 69 | °F | Write | |
| AV | 87 | Supply Heating Hi Reset | Supply Heating Hi Reset (range 55 to 120), default 100 | °F | Write | |
| AV | 88 | Supply Heating Lo Reset | Supply Heating Lo Reset (range 5 to 120), default 90 | °F | Write | |
| AV | 89 | Dehum Enable Spt | Dehum Enable Spt (range 40 to 60), default 50 | %RH | Write | |
| AV | 90 | Suction Temp Spt | Suction Temp Spt (range 38 to 48), default 42 | °F | Write | |
| AV | 91 | MHGRH Purge Time | MHGRH Purge Time (range 60 to 240), default 120 | s | Write | |
| AV | 92 | MHGRH Purge Period | MHGRH Purge Period (range 1 to 120), default 60 | min | Write | |
| AV | 93 | Cooling Head Pressure 1 Spt | Cooling Head Pressure 1 Spt (range 250 to 475), default 340 | psig | Write | |
| AV | 94 | Cooling Head Pressure 1 Spt | Cooling Head Pressure 1 Spt (range 250 to 475), default 340 | psig | Write | |
| AV | 95 | Dehum Head Pressure 1 Spt | Dehum Head Pressure 1 Spt (range 250 to 475), default 390 | psig | Write | |
| AV | 96 | Dehum Head Pressure 2 Spt | Dehum Head Pressure 2 Spt (range 250 to 475), default 390 | psig | Write | |
| AV | 97 | Condenser Valve Min Position | Condenser Valve Min Position (range 0 to 100), default 0 | % | Write | |
| AV | 98 | Exhaust Fan Min Position | Exhaust Fan Min Position (range 0 to 100), default 33 | % | Write | |
| AV | 99 | Building Pressure Spt | Building Pressure Spt (range -.1 to .1), default 0.01 | in. WC | Write | |
| AV | 100 | Heat Wheel Min Run | Heat Wheel Min Run (range 1 to 60), default 1 | s | Write | |
| AV | 101 | Heat Wheel Defrost Spt | Heat Wheel Defrost Spt (range 0 to 35), default 25 | °F | Write | |
| AV | 102 | Heat Wheel Defrost Time | Heat Wheel Defrost Time (range 15 to 255), default 120 | s | Write | |
| AV | 103 | Heat Wheel Defrost Period | Heat Wheel Defrost Period (range 5 to 120), default 30 | min | Write | |
| AV | 104 | Outside Air Flow Spt | Outside Air Flow Spt (range 0 to 15000), default 0 | CFM | Write | |
| AV | 105 | Outside Air Flow Max Spt | Outside Air Flow Max Spt (range 0 to 15000), default 0 | CFM | Write | |
| AV | 106 | Outside Air Flow Min Spt | Outside Air Flow Min Spt (range 0 to 15000), default 0 | CFM | Write | |
| AV | 107 | Dehum Lockout Temp | Dehum Lockout Temp (range 35 to 75), default 55 | °F | Write | |
| AV | 108 | CAV Fan Position | CAV Fan Position (range 33 to 100), default 100 | % | Write | |
| AV | 109 | Supply Fan Max | Supply Fan Max (range 33 to 100), default 100 | % | Write | |
| AV | 110 | SF Cool Min Position | SF Cool Min Position (range 33 to 100), default 33 | % | Write | |
| AV | 111 | SF Deadband | SF Deadband (range 2 to 10), default 4 | °F | Write | |
| AV | 112 | VAV MCD Time | VAV MCD Time (range 5 to 60), default 30 | min | Write | |
| AV | 113 | VAV MWU Time | VAV MWU Time (range 5 to 60), default 30 | min | Write | |
| AV | 114 | Space Temperature | Space Temperature | °F | Read | |
| AV | 115 | Space Relative Humidity | Space Relative Humidity | %RH | Read | |
| BV | 0 | Economizer | Economizer | Read | 0=False, 1=True | |
| BV | 1 | Heat Wheel | Heat Wheel | Read | 0=False, 1=True | |
| BV | 2 | Exhaust Fan | Exhaust Fan | Read | 0=False, 1=True | |
| BV | 3 | Comp 2 | Comp 2 | Read | 0=False, 1=True | |
| BV | 4 | Comp 1 | Comp 1 | Read | 0=False, 1=True | |
| BV | 5 | Supply Fan Command | Supply Fan Command | Read | 0=False, 1=True | |
| BVmin | 6 | Occupancy Status | Occupancy Status | Read | 0=False, 1=True | |
| BVmin | 7 | Supply Fan Status | Supply Fan Status | Read | 0=False, 1=True | |
| BV | 8 | Emergency Shutdown Status | Emergency Shutdown Status | Read | 0=False, 1=True | |
| BV | 9 | Water Flow Status | Water Flow Status | Read | 0=False, 1=True | |
| BV | 10 | Clogged Filter Status | Clogged Filter Status | Read | 0=False, 1=True | |
| BV | 11 | Comp 2 2nd Step | Comp 2 2nd Step | Read | 0=False, 1=True | |
| BV | 12 | Comp 1 2nd Step | Comp 1 2nd Step | Read | 0=False, 1=True | |
| BV | 13 | Heat Stage 4 | Heat Stage 4 | Read | 0=False, 1=True | |
| BV | 14 | Heat Stage 3 | Heat Stage 3 | Read | 0=False, 1=True | |
| BV | 15 | Heat Stage 2 | Heat Stage 2 | Read | 0=False, 1=True | |
| BV | 16 | Heat Stage 1 | Heat Stage 1 | Read | 0=False, 1=True | |
| BV | 17 | Dehum | Dehum | Read | 0=False, 1=True | |
| BV | 18 | Cool | Cool | Read | 0=False, 1=True | |
| BV | 19 | Heat Mode | Heat Mode | Read | 0=False, 1=True | |
| BV | 20 | Vent Mode | Vent Mode | Read | 0=False, 1=True | |
| BV | 21 | On Off Mode | On Off Mode | Read | 0=False, 1=True | |
| BV | 22 | Reversing Valve | Reversing Valve | Read | 0=False, 1=True | |
| BVmin | 23 | Emergency Shutdown Alarm | Emergency Shutdown Alarm | Read | 0=False, 1=True | |
| BV | 24 | Clogged Filter Alarm | Clogged Filter Alarm | Read | 0=False, 1=True | |
| BVmin | 25 | Supply Fan Alarm | Supply Fan Alarm | Read | 0=False, 1=True | |
| BV | 26 | CO2 Alarm | CO2 Alarm | Read | 0=False, 1=True | |
| BV | 27 | Supply Air Temp High Limit | Supply Air Temp High Limit | Read | 0=False, 1=True | |
| BV | 28 | Supply Air Temp Low Limit | Supply Air Temp Low Limit | Read | 0=False, 1=True | |
| BV | 29 | Outside Air Open | Outside Air Open | Read | 0=False, 1=True | |
| BV | 30 | Outside Air Shorted | Outside Air Shorted | Read | 0=False, 1=True | |
| BV | 31 | Supply Air Open | Supply Air Open | Read | 0=False, 1=True | |
| BV | 32 | Supply Air Shorted | Supply Air Shorted | Read | 0=False, 1=True | |
| BV | 33 | Return Air Open | Return Air Open | Read | 0=False, 1=True | |
| BV | 34 | Return Air Shorted | Return Air Shorted | Read | 0=False, 1=True | |
| BV | 35 | Mixed Air Open | Mixed Air Open | Read | 0=False, 1=True | |
| BV | 36 | Mixed Air Shorted | Mixed Air Shorted | Read | 0=False, 1=True | |
| BV | 37 | OA Temp Lockout | OA Temp Lockout | Read | 0=False, 1=True | |
| BV | 38 | Water Flow | Water Flow | Read | 0=False, 1=True | |
| BVmin | 39 | Network Occupy | Network Occupy, default False | Write | 0=False, 1=True | |
| BV | 40 | VAV Daytime Heat | VAV Daytime Heat, default False | Write | 0=False, 1=True | |
| BVmin | 41 | Network Emergency Shutdown | Network Emergency Shutdown, default False | Write | 0=False, 1=True |
No points match these filters.
Object ID lookup: AAON Touchscreen Controller point IDs by name
AV0Discharge Press 1AV1Discharge Press 2AV2Suction Press 1AV3Suction Press 2AV4Discharge Temp 1AV5Discharge Temp 2AV6Mixed Air TempAV7Return Air TempAV8Supply Air TempAV9Outside Air TempAV10Return RHAV11Outside RHAV12CO2AV13OA AirflowAV14Duct PressAV15Building PressAV16Hot Water ValveAV17Chilled Water ValveAV18Condenser Fan 1AV19Condenser Fan 2AV20MHGRHAV21Exhaust FanAV22Outside Air DamperAV23Supply FanAV24Control TempAV25Control RHAV26Working Clg SptAV27Working Htg SptAV28Clg PID CountAV29Digital Comp 1AV30Digital Comp 2AV31Cool PIDAV32Heat PIDAV33Clg Supply ResetAV34Htg Supply ResetAV35Econ PIDAV36Econ Ramp CountAV37Econ Lockout TimerAV38Combustion Blower RPMAV39Raw Mod Gas ValveAV40Mod Gas ValveAV41Raw Mod Gas Valve 2AV42Mod Gas PIDAV43Electric Preheat PIDAV44Preheat LAT Probe AAV45Preheat LAT Probe BAV46Preheat LAT AverageAV47Network AddressAV48Morning Cool-Down SptAV49Morning Warm-Up SptAV50Preheat OAT SetpointAV51Preheat LAT SetpointAV52Duct Static SetpointAV53Supply Fan Unoccupied ConfigAV54Supply Fan Occupied ConfigAV55CO2 SptAV56Defrost Trigger SptAV57Defrost Trigger DelayAV58Defrost Termination DelayAV59Occupied Cooling SptAV60Unoccupied Cooling SptAV61Supply Cooling SptAV62Compressor On TimeAV63Compressor Off TimeAV64Compressor Interstage On DelayAV65Compressor Interstage Off DelayAV66Outside Air Temp LockoutAV67Space Cooling Hi ResetAV68Space Cooling Lo ResetAV69Supply Cooling Hi ResetAV70Supply Cooling Lo ResetAV71Sensible Econ SptAV72Econ Lockout TimeAV73Econ Min PositionAV74Enthalpy Econ SptAV75Comparative Econ SptAV76Mixed Air SptAV77Occupied Heating SptAV78Unoccupied Heating SptAV79Supply Heating SptAV80Heating On TimeAV81Heating Off TimeAV82Heating Interstage On DelayAV83Heating Interstage Off DelayAV84OA Heating LockoutAV85Space Heating Hi ResetAV86Space Heating Lo ResetAV87Supply Heating Hi ResetAV88Supply Heating Lo ResetAV89Dehum Enable SptAV90Suction Temp SptAV91MHGRH Purge TimeAV92MHGRH Purge PeriodAV93Cooling Head Pressure 1 SptAV94Cooling Head Pressure 1 SptAV95Dehum Head Pressure 1 SptAV96Dehum Head Pressure 2 SptAV97Condenser Valve Min PositionAV98Exhaust Fan Min PositionAV99Building Pressure SptAV100Heat Wheel Min RunAV101Heat Wheel Defrost SptAV102Heat Wheel Defrost TimeAV103Heat Wheel Defrost PeriodAV104Outside Air Flow SptAV105Outside Air Flow Max SptAV106Outside Air Flow Min SptAV107Dehum Lockout TempAV108CAV Fan PositionAV109Supply Fan MaxAV110SF Cool Min PositionAV111SF DeadbandAV112VAV MCD TimeAV113VAV MWU TimeAV114Space TemperatureAV115Space Relative HumidityBV0EconomizerBV1Heat WheelBV2Exhaust FanBV3Comp 2BV4Comp 1BV5Supply Fan CommandBV6Occupancy StatusBV7Supply Fan StatusBV8Emergency Shutdown StatusBV9Water Flow StatusBV10Clogged Filter StatusBV11Comp 2 2nd StepBV12Comp 1 2nd StepBV13Heat Stage 4BV14Heat Stage 3BV15Heat Stage 2BV16Heat Stage 1BV17DehumBV18CoolBV19Heat ModeBV20Vent ModeBV21On Off ModeBV22Reversing ValveBV23Emergency Shutdown AlarmBV24Clogged Filter AlarmBV25Supply Fan AlarmBV26CO2 AlarmBV27Supply Air Temp High LimitBV28Supply Air Temp Low LimitBV29Outside Air OpenBV30Outside Air ShortedBV31Supply Air OpenBV32Supply Air ShortedBV33Return Air OpenBV34Return Air ShortedBV35Mixed Air OpenBV36Mixed Air ShortedBV37OA Temp LockoutBV38Water FlowBV39Network OccupyBV40VAV Daytime HeatBV41Network Emergency Shutdown
Integration notes
- The table has no separate object-name column; the description column is used as the object name.
- Access is from the Read/Write column. Binary states are shown from the Min/Max columns (False/True).
- AV 93 and AV 94 are both printed as Cooling Head Pressure 1 Spt; the table does not say which circuit AV 94 covers.
- The manual describes BACnet/Modbus protocol, baud, bits/parity/stop and address settings on the Network Config screen but prints no defaults.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the AAON Touchscreen Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the AAON Touchscreen Controller
How many BACnet points does the AAON Touchscreen Controller have?
This list has 158 BACnet objects: 116 analog values, 42 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which AAON Touchscreen Controller BACnet points are writable?
69 of the 158 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official AAON Touchscreen Controller BACnet documentation?
The source is AAON Touchscreen Controller User's Manual - Tables 3-7 BACnet Points List, revision 2019-07-02, published free by AAON at https://23126496.fs1.hubspotusercontent-na1.net/hubfs/23126496/AAON_TS_Controller_Manual_190702.pdf.
What are the minimum BACnet points to integrate the AAON Touchscreen Controller?
Start with BV 39 Network Occupy (Occupied command from the BMS); BV 41 Network Emergency Shutdown (Emergency shutdown command); AV 59 Occupied Cooling Spt (Occupied cooling setpoint); AV 77 Occupied Heating Spt (Occupied heating setpoint); BV 6 Occupancy Status (Occupied status); BV 7 Supply Fan Status (Supply fan proven); AV 24 Control Temp (Temperature the unit controls to); AV 8 Supply Air Temp (Supply air temperature); BV 23 Emergency Shutdown Alarm (Emergency shutdown alarm); BV 25 Supply Fan Alarm (Supply fan alarm).
How do I enable BMS control of the AAON Touchscreen Controller?
Occupied mode comes from the internal schedule, a normally open remote forced-occupied contact on DI1, or the BACnet Network Occupy point (BV 39). BV 41 Network Emergency Shutdown stops the unit; BV 40 VAV Daytime Heat is the only way to start VAV daytime heating.
How do I check these points on the real AAON Touchscreen Controller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More AAON BACnet points lists
- Rooftop unit controller (zoning)
AAON Auto-Zone 3 (AZ 3) Controller
AAON packaged units run by the Auto-Zone 3 controller, alone or with AZ 3 VAV/zone dampers.
Also known as: AZ 3, AZ3, Auto-Zone 3, AAON AZ3, G071000, SS8014, SS8015, Orion AZ3 - General-purpose BACnet I/O controller
AAON BACnet General Controller (BGC)
AAON BGC general-purpose controller with 8 analog inputs, 8 binary inputs, 8 relays and 4 analog outputs.
Also known as: AAON BGC, BGC Controller, AAON BACnet General Controller, G042460, AAON general purpose I/O controller - DX chiller controller
AAON DX Chiller Controller
AAON packaged DX chillers (non-Turbocor compressors) with the Main DX Chiller Controller, refrigerant modules and optional waterside economizer and evaporative condenser modules.
Also known as: AAON DX Chiller Controller, Main DX Chiller Controller, G054280, SS1149, AAON DX chiller BACnet - DX chiller controller
AAON LF Chiller Controller
AAON LF series one- or two-circuit DX chillers with the LF Chiller Main Controller, optional pumping package and waterside economizer.
Also known as: AAON LF Chiller, LF Chiller Main Controller, G059100, SS1131, DT005683-001, LF chiller BACnet - DX chiller controller
AAON Main DX Barrel Chiller Controller
AAON DX barrel chillers with the Main DX Barrel Chiller Controller, up to two barrels and three refrigerant circuits per barrel, with optional pumping, WSE, evaporative condenser and vestibule modules.
Also known as: AAON DX Barrel Chiller, Main DX Barrel Chiller Controller, G070300, SS1140, DX barrel chiller BACnet - Air handler preheat controller
AAON PREHEAT-X Controller
AAON PREHEAT-X controllers that stage and modulate electric (SCR/SSR) preheat on AAON units and air handlers.
Also known as: PREHEAT-X, PREHEATX, Preheat-X, G086640, AAON preheat controller, Orion PREHEAT-X - Rooftop unit / air handler controller (gateway)
AAON SA Controller (via PT-Link II BACnet gateway)
AAON units with the SA (single-zone) controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: SA controller, AAON SA, PT-Link II, PT-Link BACnet5, G114680 - Rooftop unit / air handler controller
AAON Stratus Unit Manager (Stratus controls)
AAON units built with Stratus controls (Stratus Unit Manager, software 1.3.3).
Also known as: Stratus, AAON Stratus, Stratus Unit Manager, Stratus BACnet Points Guide, Stratus controller, Stratus Series - VAV / zone controller
AAON VAV/Zone BACnet Controller (VAVZB)
Pressure-independent and pressure-dependent VAV boxes and zone dampers controlled by the AAON VAV/Zone BACnet controller.
Also known as: VAVZB, VAV/Zone Controller, ASM02426, ASM02427, ASM02661, ASM02662, SS1116, SS1146, G067750 - Rooftop unit / air handler controller
AAON VCB-X Controller
AAON packaged rooftop units, air handlers, DOAS and water-source units controlled by the Orion VCB-X (OE335-26B-VCBX) unit controller.
Also known as: VCBX, VCB-X, Orion VCB-X, OE335-26B-VCBX, V28940, WattMaster VCB-X, AAON VCB-X BACnet - Rooftop unit / air handler controller
AAON VCCX-454 Controller
AAON rooftop units, air handlers, DOAS and self-contained units built for R-454B and controlled by the VCCX-454 unit controller with RM454 refrigerant modules.
Also known as: VCCX-454, VCCX 454, ASM07503, SS1188, AAON VCCX-454 controller, R-454B unit controller - Rooftop unit / air handler controller
AAON VCCX-454-GH Controller (grow house)
AAON R-454B units for indoor agriculture (grow rooms) controlled by the VCCX-454-GH controller.
Also known as: VCCX-454-GH, VCCX454-GH, ASM07792, SS1207, AAON grow house controller, indoor agriculture HVAC controller - Rooftop unit / air handler controller
AAON VCCX2 Controller
AAON rooftop units, air handlers and DOAS units controlled by the VCCX2 (ASM01698) unit controller.
Also known as: VCC-X2, VCCX, VCC-X, ASM01698, Orion VCCX2, SS1088 - Rooftop unit / air handler controller (gateway)
AAON VCM Controller (legacy, via PT-Link II BACnet gateway)
Older AAON units with the legacy VCM controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: VCM, AAON VCM, PT-Link II, PT-Link BACnet5, G114680 - Rooftop unit / air handler controller (gateway)
AAON VCM-X Controller (via PT-Link II BACnet gateway)
AAON rooftop units, air handlers and other equipment with the VCM-X controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: VCM-X, VCMX, PT-Link II, PT-Link BACnet5, G114680
Source: AAON Touchscreen Controller User's Manual - Tables 3-7 BACnet Points List · rev. 2019-07-02. Object names, instances and units are reproduced as published; descriptions are our own.