DX chiller controller · BACnet points list

AAON LF Chiller Controller BACnet points list

Updated 12 November 2026

Short answer

The LF Chiller Main Controller runs one- or two-circuit AAON DX chillers, with optional pumping and waterside economizer, and has an on-board BACnet MS/TP port. The object map has 52 read-only analog inputs, 34 analog values (setpoints, reset limits, run command and relay enables), 112 read-only binary inputs for status, faults, warnings and lockouts, and a multistate input for the unit mode.

This page lists 199 BACnet objects for the AAON LF Chiller Controller — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.

Manufacturer
AAON
Model
LF Chiller Controller
Equipment
DX chiller controller
Equipment type
Chillers
BACnet objects
199 (34 writable)
Transport
BACnet MS/TP
Firmware
DT005683-001/SS1131 v1.00 and later
Also known as
AAON LF Chiller, LF Chiller Main Controller, G059100, SS1131, DT005683-001, LF chiller BACnet
Source document
LF Chiller Controller Technical Guide · G059100 Rev. 01D · rev. 2020-11
Download CSV 199 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.

BMS integration notes: AAON LF Chiller Controller

Integration in brief

Connect the on-board MS/TP port and set MAC address, device ID and baud on the LCD. The BAS runs the chiller with AV 31 Auto/Run/Off; AV 1-4 set the leaving water setpoint range and its reset signal limits, and AI 4 shows the setpoint in use. Monitor the operating status MI, leaving water temperature and the fault BIs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 31Auto/Run/Off CommandChiller command: 0 auto, 1 run, 2 offWrite
AV 30Reset Unit Lockout {1 = Reset }Write 1 to reset a unit lockoutWrite
MI 1Operating StatusCurrent unit modeRead
AI 4Active Leaving Water SetpointLeaving water setpoint in useRead
AI 2Entering Water TemperatureEntering water temperatureRead
AI 3Leaving Water TemperatureLeaving water temperatureRead
BI 2Proof of Water FlowWater flow switch madeRead
BI 3Emergency ShutdownEmergency shutdown inputRead

Enable & remote start

AV 31 Auto/Run/Off Command (0 = Auto, 1 = Run, 2 = Off) runs the chiller from the BAS; BI 1 shows the Run/Stop input. AV 30 resets a unit lockout.

Network setup

Watch out for

AAON LF Chiller Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

199 of 199 shown
Type
BinaryMulti-state
Access
Show
AAON LF Chiller Controller BACnet Points List
DescriptionStates
AI1Application VersionRead
AImin2Entering Water TemperatureRead
AImin3Leaving Water TemperatureRead
AImin4Active Leaving Water SetpointRead
AI5Outdoor Air TemperatureRead
AI6WSE Primary Feed TemperatureRead
AI7WSE Primary Outlet TemperatureRead
AI8WSE Primary 3-Way ValveRead
AI9WSE VFD SpeedRead
AI10Pump Discharge PressureRead
AI11Pump Suction PressureRead
AI12Pump Differential PressureRead
AI13Pump VFD SpeedRead
AI14Active Superheat SetpointRead
AI15Active Head Pressure SetpointRead
AI16Active Coil Temperature SetpointRead
AI17A-Suction PressureRead
AI18A-Discharge PressureRead
AI19A-Liquid Line PressureRead
AI20A-Calculated Saturation TemperatureRead
AI21A-Calculated Discharge TemperatureRead
AI22A-Calculated Liquid Line TemperatureRead
AI23A-Suction Line TemperatureRead
AI24A-Discharge Line TemperatureRead
AI25A-Liquid Line TemperatureRead
AI26A-Superheat TemperatureRead
AI27A-Discharge Superheat TemperatureRead
AI28A-Sub-cooling TemperatureRead
AI29A-Compressor A1 PercentageRead
AI30A-Compressor A2 PercentageRead
AI31A-Condenser PercentageRead
AI32A-EXV PositionRead
AI33A-Compressor A1 CurrentRead
AI34A-Compressor A2 CurrentRead
AI35B-Suction PressureRead
AI36B-Discharge PressureRead
AI37B-Liquid Line PressureRead
AI38B-Calculated Saturation TemperatureRead
AI39B-Calculated Discharge TemperatureRead
AI40B-Calculated Liquid Line TemperatureRead
AI41B-Suction Line TemperatureRead
AI42B-Discharge Line TemperatureRead
AI43B-Liquid Line TemperatureRead
AI44B-Superheat TemperatureRead
AI45B-Discharge Superheat TemperatureRead
AI46B-Sub-cooling TemperatureRead
AI47B-Compressor B1 PercentageRead
AI48B-Compressor B2 PercentageRead
AI49B-Condenser PercentageRead
AI50B-EXV PositionRead
AI51B-Compressor B1 CurrentRead
AI52B-Compressor B2 CurrentRead
AV1Leaving Water SP Max Reset VoltsRange 0 to 10Write
AV2Leaving Water Max Temp SetpointRange 35 to 60Write
AV3Leaving Water SP Min Reset VoltsRange 0 to 10Write
AV4Leaving Water Min Temp SetpointRange 12 to 60Write
AV5Low Chilled Water Out Cutoff TempRange 0 to 45Write
AV6Ambient Temperature LockoutRange -20 to 40Write
AV7High Coil Setpoint Reset LimitRange 35 to 60Write
AV8Low Coil Setpoint Reset LimitRange 35 to 60Write
AV9Superheat SetpointRange 10 to 30Write
AV10Compressor Stage Above WindowRange 1 to 30Write
AV11Compressor Stage Below WindowRange 1 to 30Write
AV12Entering Water Sensor CalibrationRange -100 to 100Write
AV13Leaving Water Sensor CalibrationRange -100 to 100Write
AV14Outdoor Air Sensor CalibrationRange -100 to 100Write
AV15Head Pressure SetpointRange 150 to 475Write
AV16High Outlet Water Temp Failure TimeRange 5 to 600Write
AV17Waterside Economizer Enable SetpointRange 0 to 75Write
AV18WSE Primary Outlet SetpointRange 0 to 75Write
AV19WSE Heat Exchange Outlet SetpointRange 0 to 75Write
AV20WSE Freeze Protection SetpointRange 0 to 75Write
AV21WSE Heat Exchange Inlet SetpointRange 0 to 75Write
AV22WSE Fan Staging DelayRange 0 to 300Write
AV23WSE Startup DelayRange 0 to 300Write
AV24WSE Minimum VFD SpeedRange 10 to 50Write
AV25WSE Minimum Mixing ValveRange 0 to 95Write
AV26WSE Primary 3-Way Valve Slow StartRange 1 to 60Write
AV27WSE Primary 3-Way Valve Slow StopRange 1 to 60Write
AV28WSE Reset Alarm History {1 = Reset }Write1=Reset
AV29Compressor Modulation RateRange 1 to 60Write
AVmin30Reset Unit Lockout {1 = Reset }Write1=Reset
AVmin31Auto/Run/Off CommandWrite0=Auto, 1=Run, 2=Off
AV32Enable/Disable Main Relay #6Write0=Off, 1=On
AV33Enable/Disable Main Relay #7Write0=Off, 1=On
AV34Enable/Disable Main Relay #8Write0=Off, 1=On
BI1Run/Stop Input CommandStatusRead
BImin2Proof of Water FlowStatusRead
BImin3Emergency ShutdownStatusRead
BI4Phase LossStatusRead
BI5WSE Fan Run StatusStatusRead
BI6WSE at Maximum CapacityStatusRead
BI7WSE Enable StatusStatusRead
BI8WSE Alarm Not OperatingAlarmRead
BI9WSE Alarm Freeze ProtectionAlarmRead
BI10WSE Alarm Primary Outlet SensorAlarmRead
BI11WSE Alarm Primary Feed SensorAlarmRead
BI12WSE Alarm Heat Exchange InletAlarmRead
BI13WSE Alarm Heat Exchange OutletAlarmRead
BI14WSE Alarm VFD FaultAlarmRead
BI15Primary A Pump 1 StatusStatusRead
BI16Primary A Pump 2 StatusStatusRead
BI17Pump Water Flow StatusStatusRead
BI18For Future UseRead
BI19For Future UseRead
BI20A-Fault Low SuctionFaultRead
BI21A-Fault Unsafe SuctionFaultRead
BI22A-Fault Trip High Discharge Pr.FaultRead
BI23A-Fault Compressor A1 Not RunningFaultRead
BI24A-Fault Compressor A2 Not RunningFaultRead
BI25A-Fault No Suction Line Temp SensorFaultRead
BI26A-Fault Low SuperheatFaultRead
BI27A-Fault High Discharge TempFaultRead
BI28A-Fault Compressor A1 False ActiveFaultRead
BI29A-Fault Compressor A2 False ActiveFaultRead
BI30A-Fault No Suction Pr. SensorFaultRead
BI31A-Fault Emergency ShutdownFaultRead
BI32A-Fault MODBUS Slave TimeoutFaultRead
BI33A-Fault High SuperheatFaultRead
BI34A-Fault High Saturation TemperatureFaultRead
BI35A-Fault Compressor A1 Over CurrentFaultRead
BI36A-Fault Compressor A2 Over CurrentFaultRead
BI37A-Fault Compressor A1 Under CurrentFaultRead
BI38A-Fault Compressor A2 Under CurrentFaultRead
BI39For Future UseRead
BI40A-Warning Low Suction PressureWarningRead
BI41A-Warning Low Suction Pr. StartupWarningRead
BI42A-Warning High Discharge Pressure 1WarningRead
BI43A-Warning No Discharge Pr. SensorWarningRead
BI44A-Warning No Discharge Temp SensorWarningRead
BI45A-Warning High SuperheatWarningRead
BI46A-Warning Condenser FaultWarningRead
BI47A-Warning Condenser Over CurrentWarningRead
BI48A-Warning No Liquid Line Pr. SensorWarningRead
BI49A-Warning No Liquid Line Temp SensorWarningRead
BI50A-Warning High Discharge Pressure 2WarningRead
BI51A-Lockout Suction PressureLockoutRead
BI52A-Lockout Low Discharge PressureLockoutRead
BI53A-Lockout Compressor A1 Over CurrentLockoutRead
BI54A-Lockout Compressor A2 Over CurrentLockoutRead
BI55A-Lockout High Discharge TempLockoutRead
BI56A-Lockout High Discharge PressureLockoutRead
BI57A-Lockout Low SuperheatLockoutRead
BI58A-Lockout High SuperheatLockoutRead
BI59A-Lockout High Saturation TempLockoutRead
BI60A-Lockout Compressor A1 Under CurrentLockoutRead
BI61A-Lockout Compressor A2 Under CurrentLockoutRead
BI62For Future UseRead
BI63For Future UseRead
BI64For Future UseRead
BI65For Future UseRead
BI66For Future UseRead
BI67For Future UseRead
BI68For Future UseRead
BI69For Future UseRead
BI70B-Fault Low SuctionFaultRead
BI71B-Fault Unsafe SuctionFaultRead
BI72B-Fault Trip High Discharge Pr.FaultRead
BI73B-Fault Compressor B1 Not RunningFaultRead
BI74B-Fault Compressor B2 Not RunningFaultRead
BI75B-Fault No Suction Line Temp SensorFaultRead
BI76B-Fault Low SuperheatFaultRead
BI77B-Fault High Discharge TempFaultRead
BI78B-Fault Compressor B1 False ActiveFaultRead
BI79B-Fault Compressor B2 False ActiveFaultRead
BI80B-Fault No Suction Pr. SensorFaultRead
BI81B-Fault Emergency ShutdownFaultRead
BI82B-Fault MODBUS Slave TimeoutFaultRead
BI83B-Fault High SuperheatFaultRead
BI84B-Fault High Saturation TemperatureFaultRead
BI85B-Fault Compressor B1 Over CurrentFaultRead
BI86B-Fault Compressor B2 Over CurrentFaultRead
BI87B-Fault Compressor B1 Under CurrentFaultRead
BI88B-Fault Compressor B2 Under CurrentFaultRead
BI89For Future UseRead
BI90B-Warning Low Suction PressureWarningRead
BI91B-Warning Low Suction Pr. StartupWarningRead
BI92B-Warning High Discharge Pressure 1WarningRead
BI93B-Warning No Discharge Pr. SensorWarningRead
BI94B-Warning No Discharge Temp SensorWarningRead
BI95B-Warning High SuperheatWarningRead
BI96B-Warning Condenser FaultWarningRead
BI97B-Warning Condenser Over CurrentWarningRead
BI98B-Warning No Liquid Line Pr. SensorWarningRead
BI99B-Warning No Liquid Line Temp SensorWarningRead
BI100B-Warning High Discharge Pressure 2WarningRead
BI101B-Lockout Suction PressureLockoutRead
BI102B-Lockout Low Discharge PressureLockoutRead
BI103B-Lockout Compressor B1 Over CurrentLockoutRead
BI104B-Lockout Compressor B2 Over CurrentLockoutRead
BI105B-Lockout High Discharge TempLockoutRead
BI106B-Lockout High Discharge PressureLockoutRead
BI107B-Lockout Low SuperheatLockoutRead
BI108B-Lockout High SuperheatLockoutRead
BI109B-Lockout High Saturation TempLockoutRead
BI110B-Lockout Compressor B1 Under CurrentLockoutRead
BI111B-Lockout Compressor B2 Under CurrentLockoutRead
BI112Chiller Fully LoadedStatusRead
MImin1Operating StatusCurrent unit modeRead1=OFF_MODE, 2=RUN MODE, 3=Holiday OFF MODE, 4=Holiday RUN MODE, 5=Startup Delay, 6=Emergency Shutdown, 7=High Leaving Water
Object ID lookup: AAON LF Chiller Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the LF Chiller Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AAON LF Chiller Controller

How many BACnet points does the AAON LF Chiller Controller have?

This list has 199 BACnet objects: 52 analog inputs, 34 analog values, 112 binary inputs, 1 multi-state input. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AAON LF Chiller Controller BACnet points are writable?

34 of the 199 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official AAON LF Chiller Controller BACnet documentation?

The source is LF Chiller Controller Technical Guide (G059100 Rev. 01D), revision 2020-11, published free by AAON at https://www.aaon.com/hubfs/Controls%20Literature/G059100-LFCHILLER-01C-201106.pdf.

What are the minimum BACnet points to integrate the AAON LF Chiller Controller?

Start with AV 31 Auto/Run/Off Command (Chiller command: 0 auto, 1 run, 2 off); AV 30 Reset Unit Lockout {1 = Reset } (Write 1 to reset a unit lockout); MI 1 Operating Status (Current unit mode); AI 4 Active Leaving Water Setpoint (Leaving water setpoint in use); AI 2 Entering Water Temperature (Entering water temperature); AI 3 Leaving Water Temperature (Leaving water temperature); BI 2 Proof of Water Flow (Water flow switch made); BI 3 Emergency Shutdown (Emergency shutdown input).

How do I enable BMS control of the AAON LF Chiller Controller?

AV 31 Auto/Run/Off Command (0 = Auto, 1 = Run, 2 = Off) runs the chiller from the BAS; BI 1 shows the Run/Stop input. AV 30 resets a unit lockout.

How do I check these points on the real LF Chiller Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AAON BACnet points lists

Source: LF Chiller Controller Technical Guide · G059100 Rev. 01D · rev. 2020-11. Object names, instances and units are reproduced as published; descriptions are our own.