Rooftop unit / air handler controller · BACnet points list

AAON VCCX-454-GH Controller (grow house) BACnet points list

Updated 12 November 2026

Short answer

The VCCX-454-GH is a version of the VCCX-454 unit controller for indoor agriculture, with grow, dry, fan, cool, heat and purge modes. Its on-board port connects to a BACnet MS/TP network. The object map is much smaller than the standard VCCX-454: about 50 read-only analog inputs, 7 writable analog values, about 100 read-only binary inputs and two multistate input/value pairs for operating mode and HVAC mode.

This page lists 170 BACnet objects for the AAON VCCX-454-GH Controller (grow house) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.

Manufacturer
AAON
Model
VCCX-454-GH Controller (grow house)
Equipment
Rooftop unit / air handler controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
170 (9 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
VCCX-454-GH, VCCX454-GH, ASM07792, SS1207, AAON grow house controller, indoor agriculture HVAC controller
Source document
VCCX-454-GH Controller Technical Guide · ASM07792 Rev. C · rev. 2026-05
Download CSV 170 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.

BMS integration notes: AAON VCCX-454-GH Controller (grow house)

Integration in brief

Wire the on-board port to the MS/TP trunk and set address, device ID and baud on the LCD. The BAS writes the space temperature and RH setpoints, can supply space temperature and RH through AV 3 and AV 4 (with AV 7 toggled as a keep-alive), and selects operating and HVAC mode through MV 1 and MV 2.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1Operating ModeOperating mode: 1 off, 2 operatingWrite
MV 2HVAC ModeHVAC mode: grow, dry, fan, cool, heat, purgeWrite
AV 1Space Temperature SetpointSpace temperature setpoint, °FWrite
AV 2Space RH SetpointSpace RH setpoint, %Write
MI 1Mode of OperationCurrent operating state: off or operatingRead
MI 2HVAC ModeCurrent HVAC modeRead
AI 2Space TemperatureSpace temperatureRead
AI 3Space HumiditySpace humidityRead
BI 43Fan Proving AlarmMain fan airflow failureRead
BI 45Emergency Shutdown AlarmEmergency shutdown activeRead

Enable & remote start

MV 1 Operating Mode (1 = off, 2 = operating) and MV 2 HVAC Mode (grow, dry, fan, cool, heat, purge) are the BACnet mode commands; MI 1 and MI 2 report the active values.

Heartbeat & communication loss

When the controller uses BACnet space temperature and RH (AV 3, AV 4), the BAS must keep toggling AV 7 BACnet Alive Toggle. If it does not change for two minutes the controller falls back to its own sensors (if configured) or raises a space sensor failure alarm.

Sensors & values from the BMS

AV 3 Reference Space Temperature and AV 4 Reference Space RH are used when the controller is configured for BACnet space values; keep AV 7 toggling.

Network setup

Watch out for

AAON VCCX-454-GH Controller (grow house) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

170 of 170 shown
Type
Binary
Access
Show
AAON VCCX-454-GH Controller (grow house) BACnet Points List
DescriptionStates
AI1Application Software VersionCurrent version of the software in the unitRead
AImin2Space TemperatureCurrent value of the Space Temperature SensorRead
AImin3Space HumidityCurrent value of the space humidityRead
AI4Space Dew PointCurrent calculated space dew pointRead
AI5Target Space Dew PointCurrent Space Dew point the unit is controllingRead
AI6Supply Air TemperatureCurrent value of the Supply Air Temperature SensorRead
AI7Outdoor Air TemperatureCurrent value of the Outdoor Air Temperature SensorRead
AI8Modulating Heat PositionCurrent percentage of the modulating heating signal (hot waterRead
AI9Mod Hot Gas Reheat Valve PositionCurrent position of MHGRV Modulating Hot Gas Reheat ValveRead
AI10Main Fan Control SignalCurrent control signal is being sent to the supplyRead
AI11Space Sensor 1 TempCurrent temperature reading from digital Space Sensor #1Read
AI12Space Sensor 1 HumCurrent humidity reading from digital Space Sensor #1Read
AI13Space Sensor 2 TempCurrent temperature reading from digital Space Sensor #2Read
AI14Space Sensor 2 HumCurrent humidity reading from digital Space Sensor #2Read
AI15Space Sensor 3 TempCurrent temperature reading from digital Space Sensor #3Read
AI16Space Sensor 3 HumCurrent humidity reading from digital Space Sensor #3Read
AI17Space Sensor 4 TempCurrent temperature reading from digital Space Sensor #4Read
AI18Space Sensor 4 HumCurrent humidity reading from digital Space Sensor #4Read
AI19Space Sensor 5 TempCurrent temperature reading from digital Space Sensor #5Read
AI20Space Sensor 5 HumCurrent humidity reading from digital Space Sensor #5Read
AI21Space Sensor 6 TempCurrent temperature reading from digital Space Sensor #6Read
AI22Space Sensor 6 HumCurrent humidity reading from digital Space Sensor #6Read
AI23Space Sensor 7 TempCurrent temperature reading from digital Space Sensor #7Read
AI24Space Sensor 7 HumCurrent humidity reading from digital Space Sensor #7Read
AI25Space Sensor 8 TempCurrent temperature reading from digital Space Sensor #8Read
AI26Space Sensor 8 HumCurrent humidity reading from digital Space Sensor #8Read
AI27Space Sensor 9 TempCurrent temperature reading from digital Space Sensor #9Read
AI28Space Sensor 9 HumCurrent humidity reading from digital Space Sensor #9Read
AI29Space Sensor 10 TempCurrent temperature reading from digital Space Sensor #10Read
AI30Space Sensor 10 HumCurrent humidity reading from digital Space Sensor #10Read
AI31Humidifier OutputCurrent value of the signal going to the humidifierRead
AI50A1 Compressor SignalCurrent Compressor A1 modulating cooling signalRead
AI51A Condenser SignalCurrent A Condenser signalRead
AI52A Suction PressureCurrent Compressor A suction pressureRead
AI53A Head PressureCurrent Compressor A head pressureRead
AI54A Saturation TemperatureCurrent Compressor A Coil Saturation TemperatureRead
AI60B1 Compressor SignalCurrent Compressor B1 modulating cooling signalRead
AI61B Condenser SignalCurrent B Condenser signalRead
AI62B Suction PressureCurrent Compressor B suction pressureRead
AI63B Head PressureCurrent Compressor B head pressureRead
AI64B Saturation TemperatureCurrent Compressor B Coil Saturation TemperatureRead
AI70C1 Compressor SignalCurrent Compressor C1 modulating cooling signalRead
AI71C Condenser SignalCurrent C Condenser signalRead
AI72C Suction PressureCurrent Compressor C suction pressureRead
AI73C Head PressureCurrent Compressor C head pressureRead
AI74C Saturation TemperatureCurrent Compressor C Coil Saturation TemperatureRead
AI80D1 Compressor SignalCurrent Compressor D1 modulating cooling signalRead
AI81D Condenser SignalCurrent D Condenser signalRead
AI82D Suction PressureCurrent Compressor D suction pressureRead
AI83D Head PressureCurrent Compressor D head pressureRead
AI84D Saturation TemperatureCurrent Compressor D Coil Saturation TemperatureRead
AI90Mod Gas Heat Valve PositionCurrent position of MODGAS-XWR2 Valve ControlRead
AI91Mod Gas Active StagesCurrent number of gas heat stages activeRead
AVmin1Space Temperature SetpointSpace temperature the controller is trying to control; range 1°F to 110°F°FWrite
AVmin2Space RH SetpointSpace humidity the controller is trying to control; range 0% to 100%%Write
AV3Reference Space TemperatureIf the controller is configured to use a space; range 0°F to 120°F°FWrite
AV4Reference Space RHSpace RH from BACnet, when configured to use it; range 0% to 100%%Write
AV5Humidity Control OutputIf a humidifier is being controlled via BACnet; range 0 V to 10 VVWrite
AV6Supply Fan OverrideOverride to force the VFD to this percentage speed; range 0% to 100%%Write
AV7BACnet Alive ToggleToggle so the controller keeps using BAS space values; range 0 to 1Write
BI1Drying Mode Defrost ActiveA evaporative coil defrost is occurringRead
BI2Main Fan Relay StatusCurrent status of Main Fan Relay #1 on mainRead
BI3Relay #2 StatusCurrent status of Configurable Relay #2 on main boardRead
BI4Relay #3 StatusCurrent status of Configurable Relay #3 on main boardRead
BI5Relay #4 StatusCurrent status of Configurable Relay #4 on main boardRead
BI6Relay #5 StatusCurrent status of Configurable Relay #5 on main boardRead
BI7Relay #6 StatusCurrent status of Configurable Relay #6 on main boardRead
BI8Relay #7 StatusCurrent status of Configurable Relay #7 on main boardRead
BI9Relay #8 StatusCurrent status of Configurable Relay #8 on main boardRead
BI10Expansion Relay #1 StatusCurrent status of Configurable Relay #1 on 12 relayRead
BI11Expansion Relay #2 StatusCurrent status of Configurable Relay #2 on 12 relayRead
BI12Expansion Relay #3 StatusCurrent status of Configurable Relay #3 on 12 relayRead
BI13Expansion Relay #4 StatusCurrent status of Configurable Relay #4 on 12 relayRead
BI14Expansion Relay #5 StatusCurrent status of Configurable Relay #5 on 12 relayRead
BI15Expansion Relay #6 StatusCurrent status of Configurable Relay #6 on 12 relayRead
BI16Expansion Relay #7 StatusCurrent status of Configurable Relay #7 on 12 relayRead
BI17Expansion Relay #8 StatusCurrent status of Configurable Relay #8 on 12 relayRead
BI18Expansion Relay #9 StatusCurrent status of Configurable Relay #9 on 12 relayRead
BI19Expansion Relay #10 StatusCurrent status of Configurable Relay #10 on 12 relayRead
BI20Expansion Relay #11 StatusCurrent status of Configurable Relay #11 on 12 relayRead
BI21Expansion Relay #12 StatusCurrent status of Configurable Relay #12 on 12 relayRead
BI22Reheat EnableCurrent enable status of MHGRV-X series moduleRead
BI23LA Control EnableCurrent enable status of LA Auxiliary moduleRead
BI24Modgas EnableCurrent enable status of MODGAS-XWR2 series moduleRead
BI30Humidifier Forced DeactivatedThe humidifier relay is normally driven via BACnet commandsRead
BI31CO2 Forced DeactivatedThe CO2 relay is normally driven via BACnet commandsRead
BI32Supply Air Sensor FailureThis alarm indicates a failure of the Supply AirRead
BI33Space Sensor 1 FailureThis alarm indicates that the digital Space Sensor #1Read
BI34Space Sensor 2 FailureThis alarm indicates that the digital Space Sensor #2Read
BI35Space Sensor 3 FailureThis alarm indicates that the digital Space Sensor #3Read
BI36Space Sensor 4 FailureThis alarm indicates that the digital Space Sensor #4Read
BI37Space Sensor 5 FailureThis alarm indicates that the digital Space Sensor #5Read
BI38Space Sensor 6 FailureThis alarm indicates that the digital Space Sensor #6Read
BI39Space Sensor 7 FailureThis alarm indicates that the digital Space Sensor #7Read
BI40Space Sensor 8 FailureThis alarm indicates that the digital Space Sensor #8Read
BI41Space Sensor 9 FailureThis alarm indicates that the digital Space Sensor #9Read
BI42Space Sensor 10 FailureThis alarm indicates that the digital Space Sensor #10Read
BImin43Fan Proving AlarmThis alarm indicates an airflow failure from the mainRead
BI44Dirty Filter AlarmThis alarm indicates that the filters are dirtyRead
BImin45Emergency Shutdown AlarmThis alarm indicates that an emergency shutdown has beenRead
BI46High Supply Temp CutoffThe supply air has risen above the High SATRead
BI47Low Supply Temp CutoffThe supply air has fallen below the Low SATRead
BI48Missing Refrigeration Module #1Refrigerant Module #1 is configured but not detectedRead
BI49Missing Refrigeration Module #2Refrigerant Module #2 is configured but not detectedRead
BI50Missing Refrigeration Module #3Refrigerant Module #3 is configured but not detectedRead
BI51Missing Refrigeration Module #4Refrigerant Module #4 is configured but not detectedRead
BI52Missing Reheat BoardThe MHGR board is configured but not detectedRead
BI53Missing LA Control Board #1LA Auxiliary board #1 is configured but not detectedRead
BI54Missing LA Control Board #2LA Auxiliary board #2 is configured but not detectedRead
BI55Missing 12 Relay Expansion BoardThe 12 Relay Expansion Board is configured but notRead
BI56Missing MODGAS BoardThis alarm indicates that the MODGAS-XWR2 series moduleRead
BI57Space Reference Out of ToleranceThe BACnet Space Temperature is 5°F different or HumidityRead
BI60Mechanical Heating FailureA mechanical heating failure alarmRead
BI61Space Sensor Failure ShutdownA Space Sensor failure shutdownRead
BI62High Control Temp FailureA High Control Temp failureRead
BI63Low Control Temp FailureA Low Control Temp failureRead
BI64High Control RH FailureA High Control RH failureRead
BI65Low Control RH FailureA Low Control RH failureRead
BI70A1 Compressor EnableCurrent status of the enable signal to Compressor A1Read
BI71A2 Compressor EnableCurrent status of the enable signal to Compressor A2Read
BI72A1 Compressor AlarmsAn RSM alarm is present on the A1 circuitRead
BI73A2 Compressor AlarmsAn RSM alarm is present on the A2 circuitRead
BI74A Circuit Defrost SwitchCurrent status of the defrost switch on RSM#1Read
BI75A Circuit Water Proof of FlowCurrent status of the water flow switch on RSM#1Read
BI76A Circuit Emergency Shutdown InputCurrent status of the emergency shutdown input on RSM#1Read
BI77A Circuit RSM Relay #1Current status of relay 1 on RSM #1Read
BI78A Circuit RSM Relay #2Current status of relay 2 on RSM #1Read
BI79A Circuit RSM Relay #3Current status of relay 3 on RSM #1Read
BI80A Circuit RSM Relay #4Current status of relay 4 on RSM #1Read
BI81A Circuit RSM Relay #5Current status of relay 5 on RSM #1Read
BI90B1 Compressor EnableCurrent status of the enable signal to Compressor B1Read
BI91B2 Compressor EnableCurrent status of the enable signal to Compressor B2Read
BI92B1 Compressor AlarmsAn RSM alarm is present on the B1 circuitRead
BI93B2 Compressor AlarmsAn RSM alarm is present on the B2 circuitRead
BI94B Circuit Defrost SwitchCurrent status of the defrost switch on RSM #2Read
BI95B Circuit Water Proof of FlowCurrent status of the water flow switch on RSMRead
BI96B Circuit Emergency Shutdown InputCurrent status of the emergency shutdown input on RSMRead
BI97B Circuit RSM Relay #1Current status of relay 1 on RSM #2Read
BI98B Circuit RSM Relay #2Current status of relay 2 on RSM #2Read
BI99B Circuit RSM Relay #3Current status of relay 3 on RSM #2Read
BI100B Circuit RSM Relay #4Current status of relay 4 on RSM #2Read
BI101B Circuit RSM Relay #5Current status of relay 5 on RSM #2Read
BI110C1 Compressor EnableCurrent status of the enable signal to Compressor C1Read
BI111C2 Compressor EnableCurrent status of the enable signal to Compressor C2Read
BI112C1 Compressor AlarmsAn RSM alarm is present on the C1 circuitRead
BI113C2 Compressor AlarmsAn RSM alarm is present on the C2 circuitRead
BI114C Circuit Defrost SwitchCurrent status of defrost switch on RSM #3Read
BI115C Circuit Water Proof of FlowCurrent status of water flow switch on RSM #3Read
BI116C Circuit Emergency Shutdown InputCurrent status of emergency shutdown input on RSM#3Read
BI117C Circuit RSM Relay #1Current status of relay 1 on RSM #3Read
BI118C Circuit RSM Relay #2Current status of relay 2 on RSM #3Read
BI119C Circuit RSM Relay #3Current status of relay 3 on RSM #3Read
BI120C Circuit RSM Relay #4Current status of relay 4 on RSM #3Read
BI121C Circuit RSM Relay #5Current status of relay 5 on RSM #3Read
BI130D1 Compressor EnableCurrent status of the enable signal to Compressor D1Read
BI131D2 Compressor EnableCurrent status of the enable signal to Compressor D2Read
BI132D1 Compressor AlarmsAn RSM alarm is present on the D1 circuitRead
BI133D2 Compressor AlarmsAn RSM alarm is present on the D2 circuitRead
BI134D Circuit Defrost SwitchCurrent status of the defrost switch on RSM #4Read
BI135D Circuit Water Proof of FlowCurrent status of the water flow switch on RSMRead
BI136D Circuit Emergency Shutdown InputCurrent status of the emergency shutdown input on RSMRead
BI137D Circuit RSM Relay #1Current status of relay 1 on RSM #4Read
BI138D Circuit RSM Relay #2Current status of relay 2 on RSM #4Read
BI139D Circuit RSM Relay #3Current status of relay 3 on RSM #4Read
BI140D Circuit RSM Relay #4Current status of relay 4 on RSM #4Read
BI141D Circuit RSM Relay #5Current status of relay 5 on RSM #4Read
MImin1Mode of OperationCurrent operating stateRead1=Off, 2=Operating
MImin2HVAC ModeCurrent HVAC modeRead1=Grow, 2=Dry, 3=Fan, 4=Cool, 5=Heat, 6=Purge
MVmin1Operating ModeOperating mode commandWrite1=Off, 2=Operating
MVmin2HVAC ModeHVAC mode commandWrite1=Grow, 2=Dry, 3=Fan, 4=Cool, 5=Heat, 6=Purge
Object ID lookup: AAON VCCX-454-GH Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VCCX-454-GH Controller (grow house) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AAON VCCX-454-GH Controller (grow house)

How many BACnet points does the AAON VCCX-454-GH Controller (grow house) have?

This list has 170 BACnet objects: 53 analog inputs, 7 analog values, 106 binary inputs, 2 multi-state inputs, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AAON VCCX-454-GH Controller (grow house) BACnet points are writable?

9 of the 170 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official AAON VCCX-454-GH Controller (grow house) BACnet documentation?

The source is VCCX-454-GH Controller Technical Guide (ASM07792 Rev. C), revision 2026-05, published free by AAON at https://www.aaon.com/hubfs/Controls%20Literature/VCCX-454-GH%20Technical%20Guide%20Rev.%20C.pdf.

What are the minimum BACnet points to integrate the AAON VCCX-454-GH Controller (grow house)?

Start with MV 1 Operating Mode (Operating mode: 1 off, 2 operating); MV 2 HVAC Mode (HVAC mode: grow, dry, fan, cool, heat, purge); AV 1 Space Temperature Setpoint (Space temperature setpoint, °F); AV 2 Space RH Setpoint (Space RH setpoint, %); MI 1 Mode of Operation (Current operating state: off or operating); MI 2 HVAC Mode (Current HVAC mode); AI 2 Space Temperature (Space temperature); AI 3 Space Humidity (Space humidity); BI 43 Fan Proving Alarm (Main fan airflow failure); BI 45 Emergency Shutdown Alarm (Emergency shutdown active).

How do I enable BMS control of the AAON VCCX-454-GH Controller (grow house)?

MV 1 Operating Mode (1 = off, 2 = operating) and MV 2 HVAC Mode (grow, dry, fan, cool, heat, purge) are the BACnet mode commands; MI 1 and MI 2 report the active values.

Does the AAON VCCX-454-GH Controller (grow house) need a BACnet heartbeat or have a communication timeout?

When the controller uses BACnet space temperature and RH (AV 3, AV 4), the BAS must keep toggling AV 7 BACnet Alive Toggle. If it does not change for two minutes the controller falls back to its own sensors (if configured) or raises a space sensor failure alarm.

Can the BMS supply sensor values to the AAON VCCX-454-GH Controller (grow house)?

AV 3 Reference Space Temperature and AV 4 Reference Space RH are used when the controller is configured for BACnet space values; keep AV 7 toggling.

How do I check these points on the real VCCX-454-GH Controller (grow house)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AAON BACnet points lists

Source: VCCX-454-GH Controller Technical Guide · ASM07792 Rev. C · rev. 2026-05. Object names, instances and units are reproduced as published; descriptions are our own.