- VCCX-454-GH Controller (grow house)
Rooftop unit / air handler controller · BACnet points list
AAON VCCX-454-GH Controller (grow house) BACnet points list
Updated 12 November 2026
The VCCX-454-GH is a version of the VCCX-454 unit controller for indoor agriculture, with grow, dry, fan, cool, heat and purge modes. Its on-board port connects to a BACnet MS/TP network. The object map is much smaller than the standard VCCX-454: about 50 read-only analog inputs, 7 writable analog values, about 100 read-only binary inputs and two multistate input/value pairs for operating mode and HVAC mode.
This page lists 170 BACnet objects for the AAON VCCX-454-GH Controller (grow house) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.
- Manufacturer
- AAON
- Model
- VCCX-454-GH Controller (grow house)
- Equipment
- Rooftop unit / air handler controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 170 (9 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- VCCX-454-GH, VCCX454-GH, ASM07792, SS1207, AAON grow house controller, indoor agriculture HVAC controller
Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.
BMS integration notes: AAON VCCX-454-GH Controller (grow house)
Wire the on-board port to the MS/TP trunk and set address, device ID and baud on the LCD. The BAS writes the space temperature and RH setpoints, can supply space temperature and RH through AV 3 and AV 4 (with AV 7 toggled as a keep-alive), and selects operating and HVAC mode through MV 1 and MV 2.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | Operating Mode | Operating mode: 1 off, 2 operating | Write |
| MV 2 | HVAC Mode | HVAC mode: grow, dry, fan, cool, heat, purge | Write |
| AV 1 | Space Temperature Setpoint | Space temperature setpoint, °F | Write |
| AV 2 | Space RH Setpoint | Space RH setpoint, % | Write |
| MI 1 | Mode of Operation | Current operating state: off or operating | Read |
| MI 2 | HVAC Mode | Current HVAC mode | Read |
| AI 2 | Space Temperature | Space temperature | Read |
| AI 3 | Space Humidity | Space humidity | Read |
| BI 43 | Fan Proving Alarm | Main fan airflow failure | Read |
| BI 45 | Emergency Shutdown Alarm | Emergency shutdown active | Read |
Enable & remote start
MV 1 Operating Mode (1 = off, 2 = operating) and MV 2 HVAC Mode (grow, dry, fan, cool, heat, purge) are the BACnet mode commands; MI 1 and MI 2 report the active values.
Heartbeat & communication loss
When the controller uses BACnet space temperature and RH (AV 3, AV 4), the BAS must keep toggling AV 7 BACnet Alive Toggle. If it does not change for two minutes the controller falls back to its own sensors (if configured) or raises a space sensor failure alarm.
Sensors & values from the BMS
AV 3 Reference Space Temperature and AV 4 Reference Space RH are used when the controller is configured for BACnet space values; keep AV 7 toggling.
Network setup
- MAC address, device ID (up to seven digits) and baud rate are set on the controller's LCD BACnet screens.
- Supported MS/TP baud rates are 9.6K, 19.2K, 38.4K, 57.6K and 76.8K (from the PICS).
Watch out for
- Stop toggling AV 7 and the controller drops the BAS space values after two minutes.
AAON VCCX-454-GH Controller (grow house) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Application Software Version | Current version of the software in the unit | Read | ||
| AImin | 2 | Space Temperature | Current value of the Space Temperature Sensor | Read | ||
| AImin | 3 | Space Humidity | Current value of the space humidity | Read | ||
| AI | 4 | Space Dew Point | Current calculated space dew point | Read | ||
| AI | 5 | Target Space Dew Point | Current Space Dew point the unit is controlling | Read | ||
| AI | 6 | Supply Air Temperature | Current value of the Supply Air Temperature Sensor | Read | ||
| AI | 7 | Outdoor Air Temperature | Current value of the Outdoor Air Temperature Sensor | Read | ||
| AI | 8 | Modulating Heat Position | Current percentage of the modulating heating signal (hot water | Read | ||
| AI | 9 | Mod Hot Gas Reheat Valve Position | Current position of MHGRV Modulating Hot Gas Reheat Valve | Read | ||
| AI | 10 | Main Fan Control Signal | Current control signal is being sent to the supply | Read | ||
| AI | 11 | Space Sensor 1 Temp | Current temperature reading from digital Space Sensor #1 | Read | ||
| AI | 12 | Space Sensor 1 Hum | Current humidity reading from digital Space Sensor #1 | Read | ||
| AI | 13 | Space Sensor 2 Temp | Current temperature reading from digital Space Sensor #2 | Read | ||
| AI | 14 | Space Sensor 2 Hum | Current humidity reading from digital Space Sensor #2 | Read | ||
| AI | 15 | Space Sensor 3 Temp | Current temperature reading from digital Space Sensor #3 | Read | ||
| AI | 16 | Space Sensor 3 Hum | Current humidity reading from digital Space Sensor #3 | Read | ||
| AI | 17 | Space Sensor 4 Temp | Current temperature reading from digital Space Sensor #4 | Read | ||
| AI | 18 | Space Sensor 4 Hum | Current humidity reading from digital Space Sensor #4 | Read | ||
| AI | 19 | Space Sensor 5 Temp | Current temperature reading from digital Space Sensor #5 | Read | ||
| AI | 20 | Space Sensor 5 Hum | Current humidity reading from digital Space Sensor #5 | Read | ||
| AI | 21 | Space Sensor 6 Temp | Current temperature reading from digital Space Sensor #6 | Read | ||
| AI | 22 | Space Sensor 6 Hum | Current humidity reading from digital Space Sensor #6 | Read | ||
| AI | 23 | Space Sensor 7 Temp | Current temperature reading from digital Space Sensor #7 | Read | ||
| AI | 24 | Space Sensor 7 Hum | Current humidity reading from digital Space Sensor #7 | Read | ||
| AI | 25 | Space Sensor 8 Temp | Current temperature reading from digital Space Sensor #8 | Read | ||
| AI | 26 | Space Sensor 8 Hum | Current humidity reading from digital Space Sensor #8 | Read | ||
| AI | 27 | Space Sensor 9 Temp | Current temperature reading from digital Space Sensor #9 | Read | ||
| AI | 28 | Space Sensor 9 Hum | Current humidity reading from digital Space Sensor #9 | Read | ||
| AI | 29 | Space Sensor 10 Temp | Current temperature reading from digital Space Sensor #10 | Read | ||
| AI | 30 | Space Sensor 10 Hum | Current humidity reading from digital Space Sensor #10 | Read | ||
| AI | 31 | Humidifier Output | Current value of the signal going to the humidifier | Read | ||
| AI | 50 | A1 Compressor Signal | Current Compressor A1 modulating cooling signal | Read | ||
| AI | 51 | A Condenser Signal | Current A Condenser signal | Read | ||
| AI | 52 | A Suction Pressure | Current Compressor A suction pressure | Read | ||
| AI | 53 | A Head Pressure | Current Compressor A head pressure | Read | ||
| AI | 54 | A Saturation Temperature | Current Compressor A Coil Saturation Temperature | Read | ||
| AI | 60 | B1 Compressor Signal | Current Compressor B1 modulating cooling signal | Read | ||
| AI | 61 | B Condenser Signal | Current B Condenser signal | Read | ||
| AI | 62 | B Suction Pressure | Current Compressor B suction pressure | Read | ||
| AI | 63 | B Head Pressure | Current Compressor B head pressure | Read | ||
| AI | 64 | B Saturation Temperature | Current Compressor B Coil Saturation Temperature | Read | ||
| AI | 70 | C1 Compressor Signal | Current Compressor C1 modulating cooling signal | Read | ||
| AI | 71 | C Condenser Signal | Current C Condenser signal | Read | ||
| AI | 72 | C Suction Pressure | Current Compressor C suction pressure | Read | ||
| AI | 73 | C Head Pressure | Current Compressor C head pressure | Read | ||
| AI | 74 | C Saturation Temperature | Current Compressor C Coil Saturation Temperature | Read | ||
| AI | 80 | D1 Compressor Signal | Current Compressor D1 modulating cooling signal | Read | ||
| AI | 81 | D Condenser Signal | Current D Condenser signal | Read | ||
| AI | 82 | D Suction Pressure | Current Compressor D suction pressure | Read | ||
| AI | 83 | D Head Pressure | Current Compressor D head pressure | Read | ||
| AI | 84 | D Saturation Temperature | Current Compressor D Coil Saturation Temperature | Read | ||
| AI | 90 | Mod Gas Heat Valve Position | Current position of MODGAS-XWR2 Valve Control | Read | ||
| AI | 91 | Mod Gas Active Stages | Current number of gas heat stages active | Read | ||
| AVmin | 1 | Space Temperature Setpoint | Space temperature the controller is trying to control; range 1°F to 110°F | °F | Write | |
| AVmin | 2 | Space RH Setpoint | Space humidity the controller is trying to control; range 0% to 100% | % | Write | |
| AV | 3 | Reference Space Temperature | If the controller is configured to use a space; range 0°F to 120°F | °F | Write | |
| AV | 4 | Reference Space RH | Space RH from BACnet, when configured to use it; range 0% to 100% | % | Write | |
| AV | 5 | Humidity Control Output | If a humidifier is being controlled via BACnet; range 0 V to 10 V | V | Write | |
| AV | 6 | Supply Fan Override | Override to force the VFD to this percentage speed; range 0% to 100% | % | Write | |
| AV | 7 | BACnet Alive Toggle | Toggle so the controller keeps using BAS space values; range 0 to 1 | Write | ||
| BI | 1 | Drying Mode Defrost Active | A evaporative coil defrost is occurring | Read | ||
| BI | 2 | Main Fan Relay Status | Current status of Main Fan Relay #1 on main | Read | ||
| BI | 3 | Relay #2 Status | Current status of Configurable Relay #2 on main board | Read | ||
| BI | 4 | Relay #3 Status | Current status of Configurable Relay #3 on main board | Read | ||
| BI | 5 | Relay #4 Status | Current status of Configurable Relay #4 on main board | Read | ||
| BI | 6 | Relay #5 Status | Current status of Configurable Relay #5 on main board | Read | ||
| BI | 7 | Relay #6 Status | Current status of Configurable Relay #6 on main board | Read | ||
| BI | 8 | Relay #7 Status | Current status of Configurable Relay #7 on main board | Read | ||
| BI | 9 | Relay #8 Status | Current status of Configurable Relay #8 on main board | Read | ||
| BI | 10 | Expansion Relay #1 Status | Current status of Configurable Relay #1 on 12 relay | Read | ||
| BI | 11 | Expansion Relay #2 Status | Current status of Configurable Relay #2 on 12 relay | Read | ||
| BI | 12 | Expansion Relay #3 Status | Current status of Configurable Relay #3 on 12 relay | Read | ||
| BI | 13 | Expansion Relay #4 Status | Current status of Configurable Relay #4 on 12 relay | Read | ||
| BI | 14 | Expansion Relay #5 Status | Current status of Configurable Relay #5 on 12 relay | Read | ||
| BI | 15 | Expansion Relay #6 Status | Current status of Configurable Relay #6 on 12 relay | Read | ||
| BI | 16 | Expansion Relay #7 Status | Current status of Configurable Relay #7 on 12 relay | Read | ||
| BI | 17 | Expansion Relay #8 Status | Current status of Configurable Relay #8 on 12 relay | Read | ||
| BI | 18 | Expansion Relay #9 Status | Current status of Configurable Relay #9 on 12 relay | Read | ||
| BI | 19 | Expansion Relay #10 Status | Current status of Configurable Relay #10 on 12 relay | Read | ||
| BI | 20 | Expansion Relay #11 Status | Current status of Configurable Relay #11 on 12 relay | Read | ||
| BI | 21 | Expansion Relay #12 Status | Current status of Configurable Relay #12 on 12 relay | Read | ||
| BI | 22 | Reheat Enable | Current enable status of MHGRV-X series module | Read | ||
| BI | 23 | LA Control Enable | Current enable status of LA Auxiliary module | Read | ||
| BI | 24 | Modgas Enable | Current enable status of MODGAS-XWR2 series module | Read | ||
| BI | 30 | Humidifier Forced Deactivated | The humidifier relay is normally driven via BACnet commands | Read | ||
| BI | 31 | CO2 Forced Deactivated | The CO2 relay is normally driven via BACnet commands | Read | ||
| BI | 32 | Supply Air Sensor Failure | This alarm indicates a failure of the Supply Air | Read | ||
| BI | 33 | Space Sensor 1 Failure | This alarm indicates that the digital Space Sensor #1 | Read | ||
| BI | 34 | Space Sensor 2 Failure | This alarm indicates that the digital Space Sensor #2 | Read | ||
| BI | 35 | Space Sensor 3 Failure | This alarm indicates that the digital Space Sensor #3 | Read | ||
| BI | 36 | Space Sensor 4 Failure | This alarm indicates that the digital Space Sensor #4 | Read | ||
| BI | 37 | Space Sensor 5 Failure | This alarm indicates that the digital Space Sensor #5 | Read | ||
| BI | 38 | Space Sensor 6 Failure | This alarm indicates that the digital Space Sensor #6 | Read | ||
| BI | 39 | Space Sensor 7 Failure | This alarm indicates that the digital Space Sensor #7 | Read | ||
| BI | 40 | Space Sensor 8 Failure | This alarm indicates that the digital Space Sensor #8 | Read | ||
| BI | 41 | Space Sensor 9 Failure | This alarm indicates that the digital Space Sensor #9 | Read | ||
| BI | 42 | Space Sensor 10 Failure | This alarm indicates that the digital Space Sensor #10 | Read | ||
| BImin | 43 | Fan Proving Alarm | This alarm indicates an airflow failure from the main | Read | ||
| BI | 44 | Dirty Filter Alarm | This alarm indicates that the filters are dirty | Read | ||
| BImin | 45 | Emergency Shutdown Alarm | This alarm indicates that an emergency shutdown has been | Read | ||
| BI | 46 | High Supply Temp Cutoff | The supply air has risen above the High SAT | Read | ||
| BI | 47 | Low Supply Temp Cutoff | The supply air has fallen below the Low SAT | Read | ||
| BI | 48 | Missing Refrigeration Module #1 | Refrigerant Module #1 is configured but not detected | Read | ||
| BI | 49 | Missing Refrigeration Module #2 | Refrigerant Module #2 is configured but not detected | Read | ||
| BI | 50 | Missing Refrigeration Module #3 | Refrigerant Module #3 is configured but not detected | Read | ||
| BI | 51 | Missing Refrigeration Module #4 | Refrigerant Module #4 is configured but not detected | Read | ||
| BI | 52 | Missing Reheat Board | The MHGR board is configured but not detected | Read | ||
| BI | 53 | Missing LA Control Board #1 | LA Auxiliary board #1 is configured but not detected | Read | ||
| BI | 54 | Missing LA Control Board #2 | LA Auxiliary board #2 is configured but not detected | Read | ||
| BI | 55 | Missing 12 Relay Expansion Board | The 12 Relay Expansion Board is configured but not | Read | ||
| BI | 56 | Missing MODGAS Board | This alarm indicates that the MODGAS-XWR2 series module | Read | ||
| BI | 57 | Space Reference Out of Tolerance | The BACnet Space Temperature is 5°F different or Humidity | Read | ||
| BI | 60 | Mechanical Heating Failure | A mechanical heating failure alarm | Read | ||
| BI | 61 | Space Sensor Failure Shutdown | A Space Sensor failure shutdown | Read | ||
| BI | 62 | High Control Temp Failure | A High Control Temp failure | Read | ||
| BI | 63 | Low Control Temp Failure | A Low Control Temp failure | Read | ||
| BI | 64 | High Control RH Failure | A High Control RH failure | Read | ||
| BI | 65 | Low Control RH Failure | A Low Control RH failure | Read | ||
| BI | 70 | A1 Compressor Enable | Current status of the enable signal to Compressor A1 | Read | ||
| BI | 71 | A2 Compressor Enable | Current status of the enable signal to Compressor A2 | Read | ||
| BI | 72 | A1 Compressor Alarms | An RSM alarm is present on the A1 circuit | Read | ||
| BI | 73 | A2 Compressor Alarms | An RSM alarm is present on the A2 circuit | Read | ||
| BI | 74 | A Circuit Defrost Switch | Current status of the defrost switch on RSM#1 | Read | ||
| BI | 75 | A Circuit Water Proof of Flow | Current status of the water flow switch on RSM#1 | Read | ||
| BI | 76 | A Circuit Emergency Shutdown Input | Current status of the emergency shutdown input on RSM#1 | Read | ||
| BI | 77 | A Circuit RSM Relay #1 | Current status of relay 1 on RSM #1 | Read | ||
| BI | 78 | A Circuit RSM Relay #2 | Current status of relay 2 on RSM #1 | Read | ||
| BI | 79 | A Circuit RSM Relay #3 | Current status of relay 3 on RSM #1 | Read | ||
| BI | 80 | A Circuit RSM Relay #4 | Current status of relay 4 on RSM #1 | Read | ||
| BI | 81 | A Circuit RSM Relay #5 | Current status of relay 5 on RSM #1 | Read | ||
| BI | 90 | B1 Compressor Enable | Current status of the enable signal to Compressor B1 | Read | ||
| BI | 91 | B2 Compressor Enable | Current status of the enable signal to Compressor B2 | Read | ||
| BI | 92 | B1 Compressor Alarms | An RSM alarm is present on the B1 circuit | Read | ||
| BI | 93 | B2 Compressor Alarms | An RSM alarm is present on the B2 circuit | Read | ||
| BI | 94 | B Circuit Defrost Switch | Current status of the defrost switch on RSM #2 | Read | ||
| BI | 95 | B Circuit Water Proof of Flow | Current status of the water flow switch on RSM | Read | ||
| BI | 96 | B Circuit Emergency Shutdown Input | Current status of the emergency shutdown input on RSM | Read | ||
| BI | 97 | B Circuit RSM Relay #1 | Current status of relay 1 on RSM #2 | Read | ||
| BI | 98 | B Circuit RSM Relay #2 | Current status of relay 2 on RSM #2 | Read | ||
| BI | 99 | B Circuit RSM Relay #3 | Current status of relay 3 on RSM #2 | Read | ||
| BI | 100 | B Circuit RSM Relay #4 | Current status of relay 4 on RSM #2 | Read | ||
| BI | 101 | B Circuit RSM Relay #5 | Current status of relay 5 on RSM #2 | Read | ||
| BI | 110 | C1 Compressor Enable | Current status of the enable signal to Compressor C1 | Read | ||
| BI | 111 | C2 Compressor Enable | Current status of the enable signal to Compressor C2 | Read | ||
| BI | 112 | C1 Compressor Alarms | An RSM alarm is present on the C1 circuit | Read | ||
| BI | 113 | C2 Compressor Alarms | An RSM alarm is present on the C2 circuit | Read | ||
| BI | 114 | C Circuit Defrost Switch | Current status of defrost switch on RSM #3 | Read | ||
| BI | 115 | C Circuit Water Proof of Flow | Current status of water flow switch on RSM #3 | Read | ||
| BI | 116 | C Circuit Emergency Shutdown Input | Current status of emergency shutdown input on RSM#3 | Read | ||
| BI | 117 | C Circuit RSM Relay #1 | Current status of relay 1 on RSM #3 | Read | ||
| BI | 118 | C Circuit RSM Relay #2 | Current status of relay 2 on RSM #3 | Read | ||
| BI | 119 | C Circuit RSM Relay #3 | Current status of relay 3 on RSM #3 | Read | ||
| BI | 120 | C Circuit RSM Relay #4 | Current status of relay 4 on RSM #3 | Read | ||
| BI | 121 | C Circuit RSM Relay #5 | Current status of relay 5 on RSM #3 | Read | ||
| BI | 130 | D1 Compressor Enable | Current status of the enable signal to Compressor D1 | Read | ||
| BI | 131 | D2 Compressor Enable | Current status of the enable signal to Compressor D2 | Read | ||
| BI | 132 | D1 Compressor Alarms | An RSM alarm is present on the D1 circuit | Read | ||
| BI | 133 | D2 Compressor Alarms | An RSM alarm is present on the D2 circuit | Read | ||
| BI | 134 | D Circuit Defrost Switch | Current status of the defrost switch on RSM #4 | Read | ||
| BI | 135 | D Circuit Water Proof of Flow | Current status of the water flow switch on RSM | Read | ||
| BI | 136 | D Circuit Emergency Shutdown Input | Current status of the emergency shutdown input on RSM | Read | ||
| BI | 137 | D Circuit RSM Relay #1 | Current status of relay 1 on RSM #4 | Read | ||
| BI | 138 | D Circuit RSM Relay #2 | Current status of relay 2 on RSM #4 | Read | ||
| BI | 139 | D Circuit RSM Relay #3 | Current status of relay 3 on RSM #4 | Read | ||
| BI | 140 | D Circuit RSM Relay #4 | Current status of relay 4 on RSM #4 | Read | ||
| BI | 141 | D Circuit RSM Relay #5 | Current status of relay 5 on RSM #4 | Read | ||
| MImin | 1 | Mode of Operation | Current operating state | Read | 1=Off, 2=Operating | |
| MImin | 2 | HVAC Mode | Current HVAC mode | Read | 1=Grow, 2=Dry, 3=Fan, 4=Cool, 5=Heat, 6=Purge | |
| MVmin | 1 | Operating Mode | Operating mode command | Write | 1=Off, 2=Operating | |
| MVmin | 2 | HVAC Mode | HVAC mode command | Write | 1=Grow, 2=Dry, 3=Fan, 4=Cool, 5=Heat, 6=Purge |
No points match these filters.
Object ID lookup: AAON VCCX-454-GH Controller point IDs by name
AI1Application Software VersionAI2Space TemperatureAI3Space HumidityAI4Space Dew PointAI5Target Space Dew PointAI6Supply Air TemperatureAI7Outdoor Air TemperatureAI8Modulating Heat PositionAI9Mod Hot Gas Reheat Valve PositionAI10Main Fan Control SignalAI11Space Sensor 1 TempAI12Space Sensor 1 HumAI13Space Sensor 2 TempAI14Space Sensor 2 HumAI15Space Sensor 3 TempAI16Space Sensor 3 HumAI17Space Sensor 4 TempAI18Space Sensor 4 HumAI19Space Sensor 5 TempAI20Space Sensor 5 HumAI21Space Sensor 6 TempAI22Space Sensor 6 HumAI23Space Sensor 7 TempAI24Space Sensor 7 HumAI25Space Sensor 8 TempAI26Space Sensor 8 HumAI27Space Sensor 9 TempAI28Space Sensor 9 HumAI29Space Sensor 10 TempAI30Space Sensor 10 HumAI31Humidifier OutputAI50A1 Compressor SignalAI51A Condenser SignalAI52A Suction PressureAI53A Head PressureAI54A Saturation TemperatureAI60B1 Compressor SignalAI61B Condenser SignalAI62B Suction PressureAI63B Head PressureAI64B Saturation TemperatureAI70C1 Compressor SignalAI71C Condenser SignalAI72C Suction PressureAI73C Head PressureAI74C Saturation TemperatureAI80D1 Compressor SignalAI81D Condenser SignalAI82D Suction PressureAI83D Head PressureAI84D Saturation TemperatureAI90Mod Gas Heat Valve PositionAI91Mod Gas Active StagesAV1Space Temperature SetpointAV2Space RH SetpointAV3Reference Space TemperatureAV4Reference Space RHAV5Humidity Control OutputAV6Supply Fan OverrideAV7BACnet Alive ToggleBI1Drying Mode Defrost ActiveBI2Main Fan Relay StatusBI3Relay #2 StatusBI4Relay #3 StatusBI5Relay #4 StatusBI6Relay #5 StatusBI7Relay #6 StatusBI8Relay #7 StatusBI9Relay #8 StatusBI10Expansion Relay #1 StatusBI11Expansion Relay #2 StatusBI12Expansion Relay #3 StatusBI13Expansion Relay #4 StatusBI14Expansion Relay #5 StatusBI15Expansion Relay #6 StatusBI16Expansion Relay #7 StatusBI17Expansion Relay #8 StatusBI18Expansion Relay #9 StatusBI19Expansion Relay #10 StatusBI20Expansion Relay #11 StatusBI21Expansion Relay #12 StatusBI22Reheat EnableBI23LA Control EnableBI24Modgas EnableBI30Humidifier Forced DeactivatedBI31CO2 Forced DeactivatedBI32Supply Air Sensor FailureBI33Space Sensor 1 FailureBI34Space Sensor 2 FailureBI35Space Sensor 3 FailureBI36Space Sensor 4 FailureBI37Space Sensor 5 FailureBI38Space Sensor 6 FailureBI39Space Sensor 7 FailureBI40Space Sensor 8 FailureBI41Space Sensor 9 FailureBI42Space Sensor 10 FailureBI43Fan Proving AlarmBI44Dirty Filter AlarmBI45Emergency Shutdown AlarmBI46High Supply Temp CutoffBI47Low Supply Temp CutoffBI48Missing Refrigeration Module #1BI49Missing Refrigeration Module #2BI50Missing Refrigeration Module #3BI51Missing Refrigeration Module #4BI52Missing Reheat BoardBI53Missing LA Control Board #1BI54Missing LA Control Board #2BI55Missing 12 Relay Expansion BoardBI56Missing MODGAS BoardBI57Space Reference Out of ToleranceBI60Mechanical Heating FailureBI61Space Sensor Failure ShutdownBI62High Control Temp FailureBI63Low Control Temp FailureBI64High Control RH FailureBI65Low Control RH FailureBI70A1 Compressor EnableBI71A2 Compressor EnableBI72A1 Compressor AlarmsBI73A2 Compressor AlarmsBI74A Circuit Defrost SwitchBI75A Circuit Water Proof of FlowBI76A Circuit Emergency Shutdown InputBI77A Circuit RSM Relay #1BI78A Circuit RSM Relay #2BI79A Circuit RSM Relay #3BI80A Circuit RSM Relay #4BI81A Circuit RSM Relay #5BI90B1 Compressor EnableBI91B2 Compressor EnableBI92B1 Compressor AlarmsBI93B2 Compressor AlarmsBI94B Circuit Defrost SwitchBI95B Circuit Water Proof of FlowBI96B Circuit Emergency Shutdown InputBI97B Circuit RSM Relay #1BI98B Circuit RSM Relay #2BI99B Circuit RSM Relay #3BI100B Circuit RSM Relay #4BI101B Circuit RSM Relay #5BI110C1 Compressor EnableBI111C2 Compressor EnableBI112C1 Compressor AlarmsBI113C2 Compressor AlarmsBI114C Circuit Defrost SwitchBI115C Circuit Water Proof of FlowBI116C Circuit Emergency Shutdown InputBI117C Circuit RSM Relay #1BI118C Circuit RSM Relay #2BI119C Circuit RSM Relay #3BI120C Circuit RSM Relay #4BI121C Circuit RSM Relay #5BI130D1 Compressor EnableBI131D2 Compressor EnableBI132D1 Compressor AlarmsBI133D2 Compressor AlarmsBI134D Circuit Defrost SwitchBI135D Circuit Water Proof of FlowBI136D Circuit Emergency Shutdown InputBI137D Circuit RSM Relay #1BI138D Circuit RSM Relay #2BI139D Circuit RSM Relay #3BI140D Circuit RSM Relay #4BI141D Circuit RSM Relay #5MI1Mode of OperationMI2HVAC ModeMV1Operating ModeMV2HVAC Mode
Integration notes
- AI, BI and MI objects are read-only; AV objects are read/write and only AV 3 and AV 4 are sensor values the BAS may write. MV access is not stated; it is shown as writable here because the values mirror the MI points as commands.
- Instances are grouped per refrigeration circuit A-D (analog inputs in blocks from 50, 60, 70 and 80; binary inputs from 70, 90, 110 and 130), so numbering has gaps.
- Points for refrigeration modules, MHGRV reheat, MODGAS and the 12-relay expansion board only report when fitted.
- Source: Appendix C VCCX-454-GH BACnet, guide pages 79-86.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VCCX-454-GH Controller (grow house) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the AAON VCCX-454-GH Controller (grow house)
How many BACnet points does the AAON VCCX-454-GH Controller (grow house) have?
This list has 170 BACnet objects: 53 analog inputs, 7 analog values, 106 binary inputs, 2 multi-state inputs, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which AAON VCCX-454-GH Controller (grow house) BACnet points are writable?
9 of the 170 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official AAON VCCX-454-GH Controller (grow house) BACnet documentation?
The source is VCCX-454-GH Controller Technical Guide (ASM07792 Rev. C), revision 2026-05, published free by AAON at https://www.aaon.com/hubfs/Controls%20Literature/VCCX-454-GH%20Technical%20Guide%20Rev.%20C.pdf.
What are the minimum BACnet points to integrate the AAON VCCX-454-GH Controller (grow house)?
Start with MV 1 Operating Mode (Operating mode: 1 off, 2 operating); MV 2 HVAC Mode (HVAC mode: grow, dry, fan, cool, heat, purge); AV 1 Space Temperature Setpoint (Space temperature setpoint, °F); AV 2 Space RH Setpoint (Space RH setpoint, %); MI 1 Mode of Operation (Current operating state: off or operating); MI 2 HVAC Mode (Current HVAC mode); AI 2 Space Temperature (Space temperature); AI 3 Space Humidity (Space humidity); BI 43 Fan Proving Alarm (Main fan airflow failure); BI 45 Emergency Shutdown Alarm (Emergency shutdown active).
How do I enable BMS control of the AAON VCCX-454-GH Controller (grow house)?
MV 1 Operating Mode (1 = off, 2 = operating) and MV 2 HVAC Mode (grow, dry, fan, cool, heat, purge) are the BACnet mode commands; MI 1 and MI 2 report the active values.
Does the AAON VCCX-454-GH Controller (grow house) need a BACnet heartbeat or have a communication timeout?
When the controller uses BACnet space temperature and RH (AV 3, AV 4), the BAS must keep toggling AV 7 BACnet Alive Toggle. If it does not change for two minutes the controller falls back to its own sensors (if configured) or raises a space sensor failure alarm.
Can the BMS supply sensor values to the AAON VCCX-454-GH Controller (grow house)?
AV 3 Reference Space Temperature and AV 4 Reference Space RH are used when the controller is configured for BACnet space values; keep AV 7 toggling.
How do I check these points on the real VCCX-454-GH Controller (grow house)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More AAON BACnet points lists
- Rooftop unit / air handler controller
AAON Touchscreen Controller
AAON packaged units fitted with the AAON Touchscreen unit controller.
Also known as: AAON Touchscreen, Touch Screen Controller, AAON TS controller - Rooftop unit controller (zoning)
AAON Auto-Zone 3 (AZ 3) Controller
AAON packaged units run by the Auto-Zone 3 controller, alone or with AZ 3 VAV/zone dampers.
Also known as: AZ 3, AZ3, Auto-Zone 3, AAON AZ3, G071000, SS8014, SS8015, Orion AZ3 - General-purpose BACnet I/O controller
AAON BACnet General Controller (BGC)
AAON BGC general-purpose controller with 8 analog inputs, 8 binary inputs, 8 relays and 4 analog outputs.
Also known as: AAON BGC, BGC Controller, AAON BACnet General Controller, G042460, AAON general purpose I/O controller - DX chiller controller
AAON DX Chiller Controller
AAON packaged DX chillers (non-Turbocor compressors) with the Main DX Chiller Controller, refrigerant modules and optional waterside economizer and evaporative condenser modules.
Also known as: AAON DX Chiller Controller, Main DX Chiller Controller, G054280, SS1149, AAON DX chiller BACnet - DX chiller controller
AAON LF Chiller Controller
AAON LF series one- or two-circuit DX chillers with the LF Chiller Main Controller, optional pumping package and waterside economizer.
Also known as: AAON LF Chiller, LF Chiller Main Controller, G059100, SS1131, DT005683-001, LF chiller BACnet - DX chiller controller
AAON Main DX Barrel Chiller Controller
AAON DX barrel chillers with the Main DX Barrel Chiller Controller, up to two barrels and three refrigerant circuits per barrel, with optional pumping, WSE, evaporative condenser and vestibule modules.
Also known as: AAON DX Barrel Chiller, Main DX Barrel Chiller Controller, G070300, SS1140, DX barrel chiller BACnet - Air handler preheat controller
AAON PREHEAT-X Controller
AAON PREHEAT-X controllers that stage and modulate electric (SCR/SSR) preheat on AAON units and air handlers.
Also known as: PREHEAT-X, PREHEATX, Preheat-X, G086640, AAON preheat controller, Orion PREHEAT-X - Rooftop unit / air handler controller (gateway)
AAON SA Controller (via PT-Link II BACnet gateway)
AAON units with the SA (single-zone) controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: SA controller, AAON SA, PT-Link II, PT-Link BACnet5, G114680 - Rooftop unit / air handler controller
AAON Stratus Unit Manager (Stratus controls)
AAON units built with Stratus controls (Stratus Unit Manager, software 1.3.3).
Also known as: Stratus, AAON Stratus, Stratus Unit Manager, Stratus BACnet Points Guide, Stratus controller, Stratus Series - VAV / zone controller
AAON VAV/Zone BACnet Controller (VAVZB)
Pressure-independent and pressure-dependent VAV boxes and zone dampers controlled by the AAON VAV/Zone BACnet controller.
Also known as: VAVZB, VAV/Zone Controller, ASM02426, ASM02427, ASM02661, ASM02662, SS1116, SS1146, G067750 - Rooftop unit / air handler controller
AAON VCB-X Controller
AAON packaged rooftop units, air handlers, DOAS and water-source units controlled by the Orion VCB-X (OE335-26B-VCBX) unit controller.
Also known as: VCBX, VCB-X, Orion VCB-X, OE335-26B-VCBX, V28940, WattMaster VCB-X, AAON VCB-X BACnet - Rooftop unit / air handler controller
AAON VCCX-454 Controller
AAON rooftop units, air handlers, DOAS and self-contained units built for R-454B and controlled by the VCCX-454 unit controller with RM454 refrigerant modules.
Also known as: VCCX-454, VCCX 454, ASM07503, SS1188, AAON VCCX-454 controller, R-454B unit controller - Rooftop unit / air handler controller
AAON VCCX2 Controller
AAON rooftop units, air handlers and DOAS units controlled by the VCCX2 (ASM01698) unit controller.
Also known as: VCC-X2, VCCX, VCC-X, ASM01698, Orion VCCX2, SS1088 - Rooftop unit / air handler controller (gateway)
AAON VCM Controller (legacy, via PT-Link II BACnet gateway)
Older AAON units with the legacy VCM controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: VCM, AAON VCM, PT-Link II, PT-Link BACnet5, G114680 - Rooftop unit / air handler controller (gateway)
AAON VCM-X Controller (via PT-Link II BACnet gateway)
AAON rooftop units, air handlers and other equipment with the VCM-X controller, reached through the AAON PT-Link II BACnet MS/TP gateway.
Also known as: VCM-X, VCMX, PT-Link II, PT-Link BACnet5, G114680
Source: VCCX-454-GH Controller Technical Guide · ASM07792 Rev. C · rev. 2026-05. Object names, instances and units are reproduced as published; descriptions are our own.