DX chiller controller · BACnet points list

AAON DX Chiller Controller BACnet points list

Updated 12 November 2026

Short answer

The Main DX Chiller Controller controls leaving water temperature on AAON DX chillers and has an on-board BACnet MS/TP port. The object map has 54 read-only analog inputs (water and refrigerant temperatures and pressures for circuits A and B, WSE and evaporative condenser data), 39 analog values (setpoints, run command, relay enables) and 86 read-only binary inputs for status, faults, warnings and lockouts, plus one multistate input for the unit mode.

This page lists 180 BACnet objects for the AAON DX Chiller Controller — 39 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from AAON’s own free documentation, linked below.

Manufacturer
AAON
Model
DX Chiller Controller
Equipment
DX chiller controller
Equipment type
Chillers
BACnet objects
180 (39 writable)
Transport
BACnet MS/TP
Firmware
Controller code version 1.00 and later
Also known as
AAON DX Chiller Controller, Main DX Chiller Controller, G054280, SS1149, AAON DX chiller BACnet
Source document
DX Chiller Controller Technical Guide · G054280 Rev. 01B · rev. 2020-02
Download CSV 180 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against AAON’s current documentation and the live device before use. Not official AAON information. Terms of use.

BMS integration notes: AAON DX Chiller Controller

Integration in brief

Connect the on-board MS/TP port and set MAC address, device ID and baud on the LCD. The BAS starts and stops the chiller with AV 34 Auto/Run/Off and sets the leaving water target with AV 1. Monitor the operating status MI, the water temperatures and the system alarm BI.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 34Auto/Run/Off CommandChiller command: 0 auto, 1 run, 2 offWrite
AV 1Chilled Water Target TemperatureChilled water target, 35-75 °FWrite
AV 33Reset Unit Lockout { 1 = Reset }Write 1 to reset a unit lockoutWrite
MI 1Operating StatusCurrent unit modeRead
AI 2Chilled Water In TemperatureEntering chilled water temperatureRead
AI 3Chilled Water Out TemperatureLeaving chilled water temperatureRead
BI 2Proof of Water FlowWater flow switch madeRead
BI 6Active System Alarm StatusActive system alarmRead

Enable & remote start

AV 34 Auto/Run/Off Command (0 = Auto, 1 = Run, 2 = Off) runs the chiller from the BAS; BI 1 shows the Run/Stop input. AV 33 resets a unit lockout.

Network setup

Watch out for

AAON DX Chiller Controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

180 of 180 shown
Type
BinaryMulti-state
Access
Show
AAON DX Chiller Controller BACnet Points List
DescriptionStates
AI1Application VersionRead
AImin2Chilled Water In TemperatureRead
AImin3Chilled Water Out TemperatureRead
AI4Chilled Water Out SetpointRead
AI5Outdoor Air TemperatureRead
AI6Vestibule TemperatureRead
AI7WSE Outlet TemperatureRead
AI8WSE Valve Outlet Mixed TemperatureRead
AI9WSE Primary 3-Way ValveRead
AI10WSE VFD SpeedRead
AI11EVAP Sump TemperatureRead
AI12EVAP Pump AmpsRead
AI13Superheat SetpointRead
AI14Head Pressure SetpointRead
AI15A-Suction PressureRead
AI16A-Discharge PressureRead
AI17A-Liquid Line PressureRead
AI18A-Calculated Saturation TemperatureRead
AI19A-Calculated Discharge TemperatureRead
AI20A-Calculated Liquid Line TemperatureRead
AI21A-Suction Line TemperatureRead
AI22A-Discharge Line TemperatureRead
AI23A-Liquid Line TemperatureRead
AI24A-Superheat TemperatureRead
AI25A-Discharge Superheat TemperatureRead
AI26A-Sub-Cooling TemperatureRead
AI27A-Compressor A1 PercentageRead
AI28A-Compressor A2 PercentageRead
AI29A-Condenser PercentageRead
AI30A-EXV PositionRead
AI31A-Compressor A1 CurrentRead
AI32A-Compressor A2 CurrentRead
AI33A-Condenser A1 CurrentRead
AI34A-Condenser A2 CurrentRead
AI35B-Suction PressureRead
AI36B-Discharge PressureRead
AI37B-Liquid Line PressureRead
AI38B-Calculated Saturation TemperatureRead
AI39B-Calculated Discharge TemperatureRead
AI40B-Calculated Liquid Line TemperatureRead
AI41B-Suction Line TemperatureRead
AI42B-Discharge Line TemperatureRead
AI43B-Liquid Line TemperatureRead
AI44B-Superheat TemperatureRead
AI45B-Discharge Superheat TemperatureRead
AI46B-Sub-Cooling TemperatureRead
AI47B-Compressor B1 PercentageRead
AI48B-Compressor B2 PercentageRead
AI49B-Condenser PercentageRead
AI50B-EXV PositionRead
AI51B-Compressor B1 CurrentRead
AI52B-Compressor B2 CurrentRead
AI53B-Condenser B1 CurrentRead
AI54B-Condenser B2 CurrentRead
AVmin1Chilled Water Target TemperatureRange 35° to 75°°FWrite
AV2Low Chilled Water Out Cutoff TempRange 25° to 45°°FWrite
AV3Ambient Temperature LockoutRange -30° to 40°°FWrite
AV4High Coil Setpoint Reset LimitRange 35° to 60°°FWrite
AV5Low Coil Setpoint Reset LimitRange 35° to 60°°FWrite
AV6Vestibule Cooling SetpointRange 30° to 90°°FWrite
AV7Vestibule Cooling Setpoint DeadbandRange 0.1° to 10°°FWrite
AV8Superheat SetpointRange 1° to 30°°FWrite
AV9Compressor Stage Above WindowRange 1° to 30°°FWrite
AV10Compressor Stage Below WindowRange 1° to 30°°FWrite
AV11Inlet Water Sensor Calibration OffsetRange -100° to 100°°FWrite
AV12Outlet Water Sensor Calibration OffsetRange -100° to 100°°FWrite
AV13Outdoor Air Sensor Calibration OffsetRange -100° to 100°°FWrite
AV14Vestibule Sensor Calibration OffsetRange -100° to 100°°FWrite
AV15Head Pressure SetpointRange 150 PSI to 475 PSIpsiWrite
AV16High Outlet Water Temp Failure TimeRange 5 Sec to 60 SecsWrite
AV17Sump Heater Enable SetpointRange 38° to 80°°FWrite
AV18Sump Heater Setpoint DeadbandRange 1° to 10°°FWrite
AV19EVAP Maximum Rated AmpsRange 0 Amps to 100 AmpsAWrite
AV20EVAP Discharge Control Stage AboveRange 0° to 200°°FWrite
AV21EVAP Discharge Control Stage BelowRange 0° to 200°°FWrite
AV221st Stage Pump/Evap Ambient Enable SPRange 35° to 110°°FWrite
AV23Waterside Economizer Enable DeadbandRange 0° to 75°°FWrite
AV24WSE Freeze Protection SetpointRange 0° to 75°°FWrite
AV25WSE Fan Staging DelayRange 0 Sec to 300 SecsWrite
AV26WSE Startup DelayRange 0 Sec to 300 SecsWrite
AV27WSE Minimum VFD SpeedRange 10% to 50%%Write
AV28WSE Minimum Mixing ValveRange 0% to 95%%Write
AV29WSE Primary 3-Way Valve Slow StartRange 1 Min to 60 MinminWrite
AV30WSE Primary 3-Way Valve Slow StopRange 1 Min to 60 MinminWrite
AV31WSE Reset Alarm History { 1 = Reset }Write0=Log, 1=Reset
AV32Compressor Modulation RateRange 1 Sec to 60 SecsWrite
AVmin33Reset Unit Lockout { 1 = Reset }Write0=Run, 1=Reset
AVmin34Auto/Run/Off CommandWrite0=Auto, 1=Run, 2=Off
AV35Enable/Disable EVAP Drain ValveWrite0=Off, 1=On
AV36Enable/Disable Main Relay #5Write0=Off, 1=On
AV37Enable/Disable Main Relay #6Write0=Off, 1=On
AV38Enable/Disable Main Relay #7Write0=Off, 1=On
AV39Enable/Disable Main Relay #8Write0=Off, 1=On
BI1Run/Stop Input CommandStatusRead
BImin2Proof of Water FlowStatusRead
BI3Phase LossStatusRead
BI4WSE Fan Run StatusStatusRead
BI5WSE at Maximum CapacityStatusRead
BImin6Active System Alarm StatusAlarmRead
BI7WSE Alarm Not OperatingAlarmRead
BI8WSE Alarm Freeze ProtectionAlarmRead
BI9WSE Alarm Valve Outlet Mixed SensorAlarmRead
BI10WSE Alarm Outlet SensorAlarmRead
BI11WSE Alarm Heat Exchange InletAlarmRead
BI12WSE Alarm Heat Exchange OutletAlarmRead
BI13WSE Alarm VFD FaultAlarmRead
BI14EVAP Low Sump Input StatusStatusRead
BI15EVAP Pump Pressure StatusStatusRead
BI16EVAP Condenser PumpStatusRead
BI17EVAP Sump HeaterStatusRead
BI18EVAP Drain ValveStatusRead
BI19EVAP Alarm Low Sump LevelAlarmRead
BI20EVAP Alarm Low Sump TemperatureAlarmRead
BI21EVAP Alarm No Pump Pressure SignalAlarmRead
BI22EVAP Alarm Pump VFD FaultAlarmRead
BI23EVAP Alarm Sump Temp SensorAlarmRead
BI24EVAP Alarm Condenser LockoutAlarmRead
BI25EVAP Alarm Pump Low CurrentAlarmRead
BI26EVAP Alarm Pump High CurrentAlarmRead
BI27A-Fault Low SuctionFaultRead
BI28A-Fault Unsafe SuctionFaultRead
BI29A-Fault Trip High Discharge Pr.FaultRead
BI30A-Fault Compressor A1 Not RunningFaultRead
BI31A-Fault Compressor A2 Not RunningFaultRead
BI32A-Fault No Suction Line Temp SensorFaultRead
BI33A-Fault Low SuperheatFaultRead
BI34A-Fault High Discharge TempFaultRead
BI35A-Fault Compressor A1 False ActiveFaultRead
BI36A-Fault Compressor A2 False ActiveFaultRead
BI37A-Fault No Suction Pr. SensorFaultRead
BI38A-Fault Emergency ShutdownFaultRead
BI39A-Fault MODBUS Slave TimeoutFaultRead
BI40A-Warning Low Suction PressureWarningRead
BI41A-Warning Low Suction Pr. StartupWarningRead
BI42A-Warning High Discharge Pr.WarningRead
BI43A-Warning No Discharge Pr. SensorWarningRead
BI44A-Warning No Discharge Temp SensorWarningRead
BI45A-Warning No Liquid Line Pr. SensorWarningRead
BI46A-Warning No Liquid Line Temp SensorWarningRead
BI47A-Warning High SuperheatWarningRead
BI48A-Warning Condenser FaultWarningRead
BI49A-Warning Condenser A1 Over CurrentWarningRead
BI50A-Warning Condenser A2 Over CurrentWarningRead
BI51A-Lockout Suction PressureLockoutRead
BI52A-Lockout Compressor A1LockoutRead
BI53A-Lockout Compressor A2LockoutRead
BI54A-Lockout Low Discharge PressureLockoutRead
BI55A-Lockout Compressor A1 Over CurrentLockoutRead
BI56A-Lockout Compressor A2 Over CurrentLockoutRead
BI57B-Fault Low SuctionFaultRead
BI58B-Fault Unsafe SuctionFaultRead
BI59B-Fault Trip High Discharge Pr.FaultRead
BI60B-Fault Compressor B1 Not RunningFaultRead
BI61B-Fault Compressor B2 Not RunningFaultRead
BI62B-Fault No Suction Line Temp SensorFaultRead
BI63B-Fault Low SuperheatFaultRead
BI64B-Fault High Discharge TempFaultRead
BI65B-Fault Compressor B1 False ActiveFaultRead
BI66B-Fault Compressor B2 False ActiveFaultRead
BI67B-Fault No Suction Pr. SensorFaultRead
BI68B-Fault Emergency ShutdownFaultRead
BI69B-Fault MODBUS Slave TimeoutFaultRead
BI70B-Warning Low Suction PressureWarningRead
BI71B-Warning Low Suction Pr. StartupWarningRead
BI72B-Warning High Discharge Pr.WarningRead
BI73B-Warning No Discharge Pr. SensorWarningRead
BI74B-Warning No Discharge Temp SensorWarningRead
BI75B-Warning No Liquid Line Pr. SensorWarningRead
BI76B-Warning No Liquid Line Temp SensorWarningRead
BI77B-Warning High SuperheatWarningRead
BI78B-Warning Condenser FaultWarningRead
BI79B-Warning Condenser B1 Over CurrentWarningRead
BI80B-Warning Condenser B2 Over CurrentWarningRead
BI81B-Lockout Suction PressureLockoutRead
BI82B-Lockout Compressor B1LockoutRead
BI83B-Lockout Compressor B2LockoutRead
BI84B-Lockout Low Discharge PressureLockoutRead
BI85B-Lockout Compressor B1 Over CurrentLockoutRead
BI86B-Lockout Compressor B2 Over CurrentLockoutRead
MImin1Operating StatusCurrent unit modeRead1=OFF_MODE, 2=RUN MODE, 3=Holiday OFF MODE, 4=Holiday RUN MODE, 5=Startup Delay, 6=Emergency Shutdown, 7=High Leaving Water
Object ID lookup: AAON DX Chiller Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DX Chiller Controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the AAON DX Chiller Controller

How many BACnet points does the AAON DX Chiller Controller have?

This list has 180 BACnet objects: 54 analog inputs, 39 analog values, 86 binary inputs, 1 multi-state input. The exact set on a given unit depends on its firmware, installed options and configuration.

Which AAON DX Chiller Controller BACnet points are writable?

39 of the 180 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official AAON DX Chiller Controller BACnet documentation?

The source is DX Chiller Controller Technical Guide (G054280 Rev. 01B), revision 2020-02, published free by AAON at https://www.aaon.com/hubfs/Controls%20Literature/G054280-DXCHILLER-01B-200203.pdf.

What are the minimum BACnet points to integrate the AAON DX Chiller Controller?

Start with AV 34 Auto/Run/Off Command (Chiller command: 0 auto, 1 run, 2 off); AV 1 Chilled Water Target Temperature (Chilled water target, 35-75 °F); AV 33 Reset Unit Lockout { 1 = Reset } (Write 1 to reset a unit lockout); MI 1 Operating Status (Current unit mode); AI 2 Chilled Water In Temperature (Entering chilled water temperature); AI 3 Chilled Water Out Temperature (Leaving chilled water temperature); BI 2 Proof of Water Flow (Water flow switch made); BI 6 Active System Alarm Status (Active system alarm).

How do I enable BMS control of the AAON DX Chiller Controller?

AV 34 Auto/Run/Off Command (0 = Auto, 1 = Run, 2 = Off) runs the chiller from the BAS; BI 1 shows the Run/Stop input. AV 33 resets a unit lockout.

How do I check these points on the real DX Chiller Controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More AAON BACnet points lists

Source: DX Chiller Controller Technical Guide · G054280 Rev. 01B · rev. 2020-02. Object names, instances and units are reproduced as published; descriptions are our own.