Boiler flame safeguard (Fireye YB110) via ProtoAir gateway · BACnet points list

Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir) BACnet points list

Updated 7 November 2026

Short answer

The ProtoAir Universal Gateway reads a Fireye YB110 flame safeguard over Modbus and serves it on BACnet IP or BACnet MS/TP. The profile is monitoring only apart from the Com Status object: burner status and message numbers, flame signal, run minutes, cycles, a 10-entry lockout history, and binary objects for the safety relay, valves, ignition, blower, limits and interlocks (water level, oil and gas pressure, air flow).

This page lists 97 BACnet objects for the Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermal Solutions’s own free documentation, linked below.

Manufacturer
Thermal Solutions
Model
Fireye YB110 flame safeguard (Universal Gateway ProtoAir)
Equipment
Boiler flame safeguard (Fireye YB110) via ProtoAir gateway
Equipment type
Boilers & water heaters
BACnet objects
97 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
YB110, Fireye YB110, BurnerPRO, Fireye, ProtoAir FPA-W44, Universal Gateway 106417-04
Source document
Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus · PN 106417-04 Rev A · rev. 2024-05
Download CSV 97 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermal Solutions’s current documentation and the live device before use. Not official Thermal Solutions information. Terms of use.

BMS integration notes: Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir)

Integration in brief

Add the YB110 as a profile in the ProtoAir Web Configurator with a unique Node-ID and discover it at 50000 + Node-ID. It is a monitoring profile: read burner status, message number, flame signal, the alarm output and the lockout count and history.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1StatusBurner status codeRead
AI 2MsgnCurrent Fireye message numberRead
AI 5FlameFlame signalRead
BI 20Main_Valve_OutMain fuel valve energizedRead
BI 26Alarm_OutAlarm outputRead
AI 11Lockout1_MsgMost recent lockout messageRead
BV 1Com StatusModbus link between ProtoAir and the YB110Read

Enable & remote start

None: the YB110 profile has no command objects.

Network setup

Watch out for

Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

97 of 97 shown
Type
Analog
Show
Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir) BACnet Points List
DescriptionStates
BVmin1Com StatusModbus link from the ProtoAir to the controllerRead
BI1Safety_RelaySafety RelayRead
BI2Main_Valve_InMain Valve InRead
BI3Delayed_Valve_InDelayed Valve InRead
BI4Pilot_Valve_InPilot Valve InRead
BI5Ignition_InIgnition InRead
BI6Blower_InBlower InRead
BI7Op_CntrlOp CntrlRead
BI8Run_IntlckRun IntlckRead
BI9Purge_DamperPurge DamperRead
BI10Term_23Term 23Read
BI11Remote_ResetRemote ResetRead
BI12Start_InputStart InputRead
BI13FVES_POCFVES POCRead
BI14Pilot_HoldPilot HoldRead
BI15Low_Fire_StartLow Fire StartRead
BI16Ref_AC_LineRef AC LineRead
BI17Ignition_OutIgnition OutRead
BI18Pilot_Valve_OutPilot Valve OutRead
BI19Blower_OutBlower OutRead
BImin20Main_Valve_OutMain Valve OutRead
BI21Delayed_Valve_OutDelayed Valve OutRead
BI22Internal_Safety_OutInternal Safety OutRead
BI23Low_Fire_OutLow Fire OutRead
BI24High_Fire_OutHigh Fire OutRead
BI25Auto_OutAuto OutRead
BImin26Alarm_OutAlarm OutRead
AImin1StatusBurner statusRead
AImin2MsgnCurrent message numberRead
AI3GstatBurner sequence statusRead
AI4TimerSequence timerRead
AImin5FlameFlame signalRead
AI6LogstatLogic statusRead
AI7SysminsSystem on time, minutesRead
AI8BnrminsBurner run time, minutesRead
AI9CyclesBurner cyclesRead
AI10Lockout_CountNumber of lockoutsRead
AImin11Lockout1_MsgLockout history 1: messageRead
AI12Lockout1_ModuleLockout history 1: moduleRead
AI13Lockout1_BnrHrsLockout history 1: burner hoursRead
AI14Lockout1_BnrCycsLockout history 1: burner cyclesRead
AI15Lockout2_MsgLockout history 2: messageRead
AI16Lockout2_ModuleLockout history 2: moduleRead
AI17Lockout2_BnrHrsLockout history 2: burner hoursRead
AI18Lockout2_BnrCycsLockout history 2: burner cyclesRead
AI19Lockout3_MsgLockout history 3: messageRead
AI20Lockout3_ModuleLockout history 3: moduleRead
AI21Lockout3_BnrHrsLockout history 3: burner hoursRead
AI22Lockout3_BnrCycsLockout history 3: burner cyclesRead
AI23Lockout4_MsgLockout history 4: messageRead
AI24Lockout4_ModuleLockout history 4: moduleRead
AI25Lockout4_BnrHrsLockout history 4: burner hoursRead
AI26Lockout4_BnrCycsLockout history 4: burner cyclesRead
AI27Lockout5_MsgLockout history 5: messageRead
AI28Lockout5_ModuleLockout history 5: moduleRead
AI29Lockout5_BnrHrsLockout history 5: burner hoursRead
AI30Lockout5_BnrCycsLockout history 5: burner cyclesRead
AI31Lockout6_MsgLockout history 6: messageRead
AI32Lockout6_ModuleLockout history 6: moduleRead
AI33Lockout6_BnrHrsLockout history 6: burner hoursRead
AI34Lockout6_BnrCycsLockout history 6: burner cyclesRead
AI35Lockout7_MsgLockout history 7: messageRead
AI36Lockout7_ModuleLockout history 7: moduleRead
AI37Lockout7_BnrHrsLockout history 7: burner hoursRead
AI38Lockout7_BnrCycsLockout history 7: burner cyclesRead
AI39Lockout8_MsgLockout history 8: messageRead
AI40Lockout8_ModuleLockout history 8: moduleRead
AI41Lockout8_BnrHrsLockout history 8: burner hoursRead
AI42Lockout8_BnrCycsLockout history 8: burner cyclesRead
AI43Lockout9_MsgLockout history 9: messageRead
AI44Lockout9_ModuleLockout history 9: moduleRead
AI45Lockout9_BnrHrsLockout history 9: burner hoursRead
AI46Lockout9_BnrCycsLockout history 9: burner cyclesRead
AI47Lockout10_MsgLockout history 10: messageRead
AI48Lockout10_ModuleLockout history 10: moduleRead
AI49Lockout10_BnrHrsLockout history 10: burner hoursRead
AI50Lockout10_BnrCycsLockout history 10: burner cyclesRead
BI27Op_ControlOp ControlRead
BI28Aux_1Aux 1Read
BI29Aux_2Aux 2Read
BI30Aux_3Aux 3Read
BI31High_waterHigh waterRead
BI32Low_WaterLow WaterRead
BI33High_Oil_TempHigh Oil TempRead
BI34Low_Oil_TempLow Oil TempRead
BI35Low_Oil_PressLow Oil PressRead
BI36Low_Atom_MediaLow Atom MediaRead
BI37Low_Gas_PressLow Gas PressRead
BI38High_Gas_PressHigh Gas PressRead
BI39Aux_GasAux GasRead
BI40High_PressHigh PressRead
BI41High_TempHigh TempRead
BI42Aux_4Aux 4Read
BI43Aux_5Aux 5Read
BI44Aux_6Aux 6Read
BI45Aux_7Aux 7Read
BI46Air_FlowAir FlowRead
Object ID lookup: Thermal Solutions Fireye YB110 flame safeguard point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Fireye YB110 flame safeguard (Universal Gateway ProtoAir) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir)

How many BACnet points does the Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir) have?

This list has 97 BACnet objects: 50 analog inputs, 46 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir) BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir) BACnet documentation?

The source is Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus (PN 106417-04 Rev A), revision 2024-05, published free by Thermal Solutions at https://s3-us-west-2.amazonaws.com/catsy.782/Universal+Gateway+ProtoAir+BACnet+Instruction+Manual.pdf.

What are the minimum BACnet points to integrate the Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir)?

Start with AI 1 Status (Burner status code); AI 2 Msgn (Current Fireye message number); AI 5 Flame (Flame signal); BI 20 Main_Valve_Out (Main fuel valve energized); BI 26 Alarm_Out (Alarm output); AI 11 Lockout1_Msg (Most recent lockout message); BV 1 Com Status (Modbus link between ProtoAir and the YB110).

How do I enable BMS control of the Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir)?

None: the YB110 profile has no command objects.

How do I check these points on the real Fireye YB110 flame safeguard (Universal Gateway ProtoAir)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermal Solutions BACnet points lists

Source: Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus · PN 106417-04 Rev A · rev. 2024-05. Object names, instances and units are reproduced as published; descriptions are our own.