Boiler burner management system (LMV2x/3x) via ProtoAir gateway · BACnet points list

Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir) BACnet points list

Updated 7 November 2026

Short answer

The ProtoAir Universal Gateway reads a Siemens LMV2x/3x burner management system over Modbus and serves it on BACnet IP or BACnet MS/TP. It reports burner phase, actuator positions, VSD output, fuel and output, flame signal, counters, the current error and an error history entry, and splits the input and output status words into binary objects (safety loop, pressure switches, alarm, ignition, fan, fuel valves). The BMS can write program stop, Modbus mode and timeout, remote operating mode and target output.

This page lists 81 BACnet objects for the Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermal Solutions’s own free documentation, linked below.

Manufacturer
Thermal Solutions
Model
Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir)
Equipment
Boiler burner management system (LMV2x/3x) via ProtoAir gateway
Equipment type
Boilers & water heaters
BACnet objects
81 (13 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
LMV2_3, LMV2, LMV3, LMV26, LMV37, Siemens LMV2x/3x, ProtoAir FPA-W44, Universal Gateway 106417-04
Source document
Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus · PN 106417-04 Rev A · rev. 2024-05
Download CSV 81 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermal Solutions’s current documentation and the live device before use. Not official Thermal Solutions information. Terms of use.

BMS integration notes: Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir)

Integration in brief

Add the LMV2_3 profile in the ProtoAir Web Configurator with a unique Node-ID and discover it at 50000 + Node-ID. Read burner phase, current output, flame signal, alarm and the current error code. For remote control set Modbus mode to remote and write the remote operating mode and target output, checking the Modbus breakdown time setting (AV 16).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 15Modbus modeLocal or remote (Modbus/BMS) operationWrite
AV 17Operating mode in remote opOperating mode while in remote operationWrite
AV 18Preselect target output mod/multistgTarget output (firing rate) in remote operationWrite
AI 1Burner control phaseBurner sequence phaseRead
AI 6Current outputCurrent burner outputRead
AI 7Flame signalFlame signalRead
BI 17AlarmBurner alarm outputRead
AI 10Current error: Error codeCurrent error codeRead
BV 1Com StatusModbus link between ProtoAir and the LMVRead

Enable & remote start

AV 15 Modbus mode selects local or remote (Modbus) operation; in remote the LMV uses AV 17 and AV 18. The manual does not list the values.

Network setup

Watch out for

Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

81 of 81 shown
Type
Access
Show
Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir) BACnet Points List
DescriptionStates
BVmin1Com StatusModbus link from the ProtoAir to the controllerRead
AImin1Burner control phaseBurner sequence phaseRead
AI2Pos of current fuel actuatorPos of current fuel actuatorRead
AI3Pos of air actuatorPos of air actuatorRead
AI4Manipulated variable VSDManipulated variable VSDRead
AI5Current type of fuelCurrent type of fuelRead
AImin6Current outputCurrent outputRead
AImin7Flame signalFlame signalRead
AI8Current fuel throughputCurrent fuel throughputRead
AI9Startup counter totalStartup counter totalRead
AImin10Current error: Error codeCurrent error: Error codeRead
AI11Current error: Diagnostic codeCurrent error: Diagnostic codeRead
AI12Current error: Error classCurrent error: Error classRead
AI13Current error: Error phaseCurrent error: Error phaseRead
AV14Program stopProgram stopWrite
AVmin15Modbus modeModbus modeWrite
AV16Modbus breakdown timeModbus breakdown timeWrite
AVmin17Operating mode in remote opOperating mode in remote opWrite
AVmin18Preselect target output mod/multistgPreselect target output mod/multistgWrite
AV19Hours run fuel 0 resettableHours run fuel 0 resettableWrite
AV20Hours run fuel 1 resettableHours run fuel 1 resettableWrite
AI21Hours run unit liveHours run unit liveRead
AV22Start counter fuel 0 resettableStart counter fuel 0 resettableWrite
AV23Start counter fuel 1 resettableStart counter fuel 1 resettableWrite
AI24Start counter totalStart counter totalRead
AV25Fuel volume fuel 0 resettableFuel volume fuel 0 resettableWrite
AV26Fuel volume fuel 1 resettableFuel volume fuel 1 resettableWrite
AI27Number of faultsNumber of faultsRead
AV28Preselected output Fuel 0Preselected output Fuel 0Write
AV29Preselected output Fuel 1Preselected output Fuel 1Write
AI30Burner control parameter set codeBurner control parameter set codeRead
AI31Burner control parameter set versionBurner control parameter set versionRead
AI32Burner control identification numberBurner control identification numberRead
AI33SW version burner controlSW version burner controlRead
AI34Min output fuel 0Min output fuel 0Read
AI35Max output fuel 0Max output fuel 0Read
AI36Min output fuel 1Min output fuel 1Read
AI37Max output fuel 1Max output fuel 1Read
AI38Operation mode of burner fuel 0Operation mode of burner fuel 0Read
AI39Operation mode of burner fuel 1Operation mode of burner fuel 1Read
AI40Error History Current ErrorError History Current ErrorRead
AI41Error History Diagnostic CodeError History Diagnostic CodeRead
AI42Error History Error ClassError History Error ClassRead
AI43Error History Error PhaseError History Error PhaseRead
AI44Error History Type of FuelError History Type of FuelRead
AI45Error History OutputError History OutputRead
AI46Error History Start counter totalError History Start counter totalRead
AI47Inputs WordInput status wordRead
BI1Controller On/OffController on/offRead
BI2Inputs Word 1Input word bit 1Read
BI3Inputs Word 2Input word bit 2Read
BI4Inputs Word 3Input word bit 3Read
BI5Inputs Word 4Input word bit 4Read
BI6Inputs Word 5Input word bit 5Read
BI7Inputs Word 6Input word bit 6Read
BI8Pressure Switch Valve ProvingPressure Switch Valve ProvingRead
BI9Safety LoopSafety LoopRead
BI10Inputs Word 9Input word bit 9Read
BI11Pressure Switch MinPressure Switch MinRead
BI12Pressure Switch MaxPressure Switch MaxRead
BI13Inputs Word 12Input word bit 12Read
BI14Air Pressure SwitchAir Pressure SwitchRead
BI15Inputs Word 14Input word bit 14Read
BI16Inputs Word 15Input word bit 15Read
AI60Outputs WordOutput status wordRead
BImin17AlarmAlarm outputRead
BI18Outputs Word 1Output word bit 1Read
BI19Outputs Word 2Output word bit 2Read
BI20Outputs Word 3Output word bit 3Read
BI21IgnitionIgnition outputRead
BI22Outputs Word 5Output word bit 5Read
BI23FanFan outputRead
BI24Outputs Word 7Output word bit 7Read
BI25Outputs Word 8Output word bit 8Read
BI26Outputs Word 9Output word bit 9Read
BI27Outputs Word 10Output word bit 10Read
BI28Outputs Word 11Output word bit 11Read
BI29Outputs Word 12Output word bit 12Read
BI30Fuel Valve 1Fuel Valve 1Read
BI31Fuel Valve 2Fuel Valve 2Read
BI32Fuel Valve 3/PVFuel Valve 3/PVRead
Object ID lookup: Thermal Solutions Siemens LMV2 / LMV3 burner management point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir)

How many BACnet points does the Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir) have?

This list has 81 BACnet objects: 35 analog inputs, 13 analog values, 32 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir) BACnet points are writable?

13 of the 81 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir) BACnet documentation?

The source is Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus (PN 106417-04 Rev A), revision 2024-05, published free by Thermal Solutions at https://s3-us-west-2.amazonaws.com/catsy.782/Universal+Gateway+ProtoAir+BACnet+Instruction+Manual.pdf.

What are the minimum BACnet points to integrate the Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir)?

Start with AV 15 Modbus mode (Local or remote (Modbus/BMS) operation); AV 17 Operating mode in remote op (Operating mode while in remote operation); AV 18 Preselect target output mod/multistg (Target output (firing rate) in remote operation); AI 1 Burner control phase (Burner sequence phase); AI 6 Current output (Current burner output); AI 7 Flame signal (Flame signal); BI 17 Alarm (Burner alarm output); AI 10 Current error: Error code (Current error code); BV 1 Com Status (Modbus link between ProtoAir and the LMV).

How do I enable BMS control of the Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir)?

AV 15 Modbus mode selects local or remote (Modbus) operation; in remote the LMV uses AV 17 and AV 18. The manual does not list the values.

How do I check these points on the real Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermal Solutions BACnet points lists

Source: Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus · PN 106417-04 Rev A · rev. 2024-05. Object names, instances and units are reproduced as published; descriptions are our own.