Boiler operating controller (RWF55) via ProtoNode gateway · BACnet points list

Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode) BACnet points list

Updated 28 October 2026

Short answer

Thermal Solutions EVA/EVAW/EVO/EVOW boilers with an RWF55 controller are read through a ProtoNode FPC-N34 gateway that polls the RWF55 over Modbus RTU and serves it on BACnet IP or BACnet MS/TP. The profile has 10 objects: three analog inputs, the active setpoint, writable Setpoint 1 and 2, actuator position and a burner alarm value.

This page lists 10 BACnet objects for the Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode) — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermal Solutions’s own free documentation, linked below.

Manufacturer
Thermal Solutions
Model
EVA / EVO boiler - RWF55 controller (ProtoNode)
Equipment
Boiler operating controller (RWF55) via ProtoNode gateway
Equipment type
Boilers & water heaters
BACnet objects
10 (2 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000 + the controller's Modbus Node-ID (Node_Offset default 50,000, changeable in the Web Configurator)
Also known as
RWF55, Siemens RWF55, EVA, EVAW, EVO, EVOW, FPC-N34-0643, ProtoNode FPC-N34
Source document
ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up Guide for Interfacing Thermal Solutions Product Models EVA/EVAW/EVO/EVOW with RWF40, RWF55 and RM7800 Controls · Document Revision 7.A (Web Configurator Template Revision 70) · rev. 2018-08
Download CSV 10 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode)

Integration in brief

Wire the RWF55 R+/R- terminals to the ProtoNode, set it to 19200 8N1 with a unique Node-ID, add the RWF55 profile in the Web Configurator, and discover it at 50000 + Node-ID. Setpoint 1 and Setpoint 2 are the only writable objects; the rest is monitoring.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 5Setpoint 1Setpoint 1 written by the BMSWrite
AI 4Actual SetpointSetpoint currently in useRead
AI 1Analog Input InP1Input InP1 reading; units per controller setupRead
AI 8Actual Angular PositioningActual actuator positionRead
AI 9Burner AlarmBurner alarm; code meanings not given in the guideRead
BI 1Com StatusModbus link between ProtoNode and the RWF55Read

Enable & remote start

The guide gives no remote-enable procedure; only Setpoint 1 (AV 5) and Setpoint 2 (AV 6) are writable.

Network setup

Watch out for

Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

10 of 10 shown
Type
Binary
Access
Show
Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode) BACnet Points List
DescriptionStates
BImin1Com StatusProtoNode-to-RWF55 Modbus link statusRead
AImin1Analog Input InP1Analog input InP1 valueRead
AI2Analog Input InP2Analog input InP2 valueRead
AI3Analog Input InP3Analog input InP3 valueRead
AImin4Actual SetpointSetpoint currently in useRead
AVmin5Setpoint 1Setpoint 1, writableWrite
AV6Setpoint 2Setpoint 2, writableWrite
AI7Analog Input InP3Analog input InP3, unfiltered valueRead
AImin8Actual Angular PositioningActual actuator angular positionRead
AImin9Burner AlarmBurner alarm valueRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EVA / EVO boiler - RWF55 controller (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode)

How many BACnet points does the Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode) have?

This list has 10 BACnet objects: 7 analog inputs, 2 analog values, 1 binary input. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode) BACnet points are writable?

2 of the 10 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode) BACnet documentation?

The source is ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up Guide for Interfacing Thermal Solutions Product Models EVA/EVAW/EVO/EVOW with RWF40, RWF55 and RM7800 Controls (Document Revision 7.A (Web Configurator Template Revision 70)), revision 2018-08, published free by Thermal Solutions at https://boilers-water-heaters.thermalsolutions.com/Asset/Thermal%20Solutions%20EVA,%20EVAW,%20EVO%20&%20EVOW%20ProtoNode%20N34%20&%20N35%20Start-up%20Guide%202018-08.pdf.

What are the minimum BACnet points to integrate the Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode)?

Start with AV 5 Setpoint 1 (Setpoint 1 written by the BMS); AI 4 Actual Setpoint (Setpoint currently in use); AI 1 Analog Input InP1 (Input InP1 reading; units per controller setup); AI 8 Actual Angular Positioning (Actual actuator position); AI 9 Burner Alarm (Burner alarm; code meanings not given in the guide); BI 1 Com Status (Modbus link between ProtoNode and the RWF55).

How do I enable BMS control of the Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode)?

The guide gives no remote-enable procedure; only Setpoint 1 (AV 5) and Setpoint 2 (AV 6) are writable.

How do I check these points on the real EVA / EVO boiler - RWF55 controller (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermal Solutions BACnet points lists

Source: ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up Guide for Interfacing Thermal Solutions Product Models EVA/EVAW/EVO/EVOW with RWF40, RWF55 and RM7800 Controls · Document Revision 7.A (Web Configurator Template Revision 70) · rev. 2018-08. Object names, instances and units are reproduced as published; descriptions are our own.