- EVA / EVO boiler - RM7800 flame safeguard (ProtoNode)
Boiler flame safeguard (RM7800) via ProtoNode gateway · BACnet points list
Thermal Solutions EVA / EVO boiler - RM7800 flame safeguard (ProtoNode) BACnet points list
Updated 28 October 2026
The RM7800 burner control on Thermal Solutions EVA/EVAW/EVO/EVOW boilers is read through a ProtoNode FPC-N34 gateway that polls it over Modbus RTU and serves it on BACnet IP or BACnet MS/TP. All 37 objects are read-only: flame signal, cycle and hour counters, fault and first-out codes, one flag per burner sequence state, and the limit and interlock inputs.
This page lists 37 BACnet objects for the Thermal Solutions EVA / EVO boiler - RM7800 flame safeguard (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermal Solutions’s own free documentation, linked below.
- Manufacturer
- Thermal Solutions
- Model
- EVA / EVO boiler - RM7800 flame safeguard (ProtoNode)
- Equipment
- Boiler flame safeguard (RM7800) via ProtoNode gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 37 (0 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 50000 + the controller's Modbus Node-ID (Node_Offset default 50,000, changeable in the Web Configurator)
- Also known as
- RM7800, Honeywell RM7800, 7800 Series, EVA, EVAW, EVO, EVOW, FPC-N34-0643, ProtoNode FPC-N34
BMS integration notes: Thermal Solutions EVA / EVO boiler - RM7800 flame safeguard (ProtoNode)
Wire the RM7800 display module Modbus terminals to the ProtoNode, set it to 19200 8N1 with a unique Node-ID, add the RM7800 profile in the Web Configurator, and discover it at 50000 + Node-ID. It is a monitoring profile: read the run, alarm and lockout flags, the fault and first-out codes and the flame signal.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 58 | Run | Burner in run (1 = on) | Read |
| AI 1 | Flame Signal | Flame signal strength | Read |
| AI 4 | Burner Fault Code | Current burner fault code | Read |
| AI 62 | Alarm | Flame safeguard alarm (1 = on) | Read |
| AI 64 | Lockout | Burner locked out (1 = on) | Read |
| BI 1 | Com Status | Modbus link between ProtoNode and the RM7800 | Read |
Enable & remote start
None: the RM7800 profile is read-only, so start/stop is not available over BACnet.
Network setup
- Device instance = Node_Offset (default 50,000) + the controller's Modbus Node-ID, so Node-ID 1 gives 50001.
- ProtoNode default IP is 192.168.1.24 (255.255.255.0); change it in the FS-GUI under Setup > Network Settings.
- FPC-N34 S-bank DIP switches pick the protocol: all Off = BACnet IP, S0 On = BACnet MS/TP, S2 On = BACnet MS/TP single node.
- BACnet MS/TP: one MAC address (1-127) for the whole ProtoNode on A-bank DIP switches; baud on B-bank switches, factory default 38400.
- Modbus side: every RWF40, RWF55 and RM7800 must run Modbus RTU at 19200, 8N1 with a unique Node-ID (1-255); add each one as a profile in the Web Configurator.
- With more than one controller on a ProtoNode set BACnet Virtual Server Nodes to Yes; give each ProtoNode on a subnet its own BACnet Network Number (default 50).
Watch out for
- Sequence states are AI objects holding 0/1, not binary objects.
- RM7800 wiring: A to ProtoNode Tx+, B to Rx-, C to GND; a factory terminal strip (AO/BO/SO) may already combine it with the RWF controller.
Thermal Solutions EVA / EVO boiler - RM7800 flame safeguard (ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 1 | Com Status | ProtoNode-to-RM7800 Modbus link status | Read | ||
| AImin | 1 | Flame Signal | Flame signal strength | Read | ||
| AI | 2 | Burner Cycles | Burner cycle count | Read | ||
| AI | 3 | Burner Hours | Burner run hours | h | Read | |
| AImin | 4 | Burner Fault Code | Current burner fault code | Read | ||
| AI | 53 | Initiate | Sequence state: initiate | Read | 0=Off, 1=On | |
| AI | 54 | Standby | Sequence state: standby | Read | 0=Off, 1=On | |
| AI | 55 | Purge | Sequence state: purge | Read | 0=Off, 1=On | |
| AI | 56 | Pilot Ignition | Sequence state: pilot ignition | Read | 0=Off, 1=On | |
| AI | 57 | Main Ignition | Sequence state: main ignition | Read | 0=Off, 1=On | |
| AImin | 58 | Run | Sequence state: run | Read | 0=Off, 1=On | |
| AI | 59 | Postpurge | Sequence state: postpurge | Read | 0=Off, 1=On | |
| AI | 60 | Pre-Ignition | Sequence state: pre-ignition | Read | 0=Off, 1=On | |
| AI | 61 | Valve Proving | Sequence state: valve proving | Read | 0=Off, 1=On | |
| AImin | 62 | Alarm | Flame safeguard alarm active | Read | 0=Off, 1=On | |
| AI | 63 | Hold | Sequence on hold | Read | 0=Off, 1=On | |
| AImin | 64 | Lockout | Flame safeguard in lockout | Read | 0=Off, 1=On | |
| AI | 65 | First Out Code | First-out annunciation code | Read | ||
| BI | 66 | Main Valve Proof of Closure | Main valve proof-of-closure input | Read | ||
| BI | 67 | Burner Switch | Burner switch input | Read | ||
| BI | 68 | Operating Control | Operating control input | Read | ||
| BI | 69 | Auxiliary Limit 1 | Auxiliary limit 1 input | Read | ||
| BI | 70 | Auxiliary Limit 2 | Auxiliary limit 2 input | Read | ||
| BI | 71 | Low Water Cutoff | Low water cutoff input | Read | ||
| BI | 72 | High Limit | High limit input | Read | ||
| BI | 73 | Auxiliary Limit 3 | Auxiliary limit 3 input | Read | ||
| BI | 74 | Oil Select Switch | Oil select switch input | Read | ||
| BI | 75 | High Oil Pressure | High oil pressure switch input | Read | ||
| BI | 76 | Low Oil Pressure | Low oil pressure switch input | Read | ||
| BI | 77 | High Oil Temperature | High oil temperature switch input | Read | ||
| BI | 78 | Low Oil Temperature | Low oil temperature switch input | Read | ||
| BI | 79 | Gas Select Switch | Gas select switch input | Read | ||
| BI | 80 | High Gas Pressure | High gas pressure switch input | Read | ||
| BI | 81 | Low Gas Pressure | Low gas pressure switch input | Read | ||
| BI | 82 | Air Flow Switch | Combustion air flow switch input | Read | ||
| BI | 83 | Auxiliary Interlock 4 | Auxiliary interlock 4 input | Read | ||
| BI | 84 | Auxiliary Interlock 5 | Auxiliary interlock 5 input | Read |
No points match these filters.
Integration notes
- Each connected controller shows up as its own BACnet device on the ProtoNode FPC-N34 gateway.
- Monitoring only: the RM7800 profile has no writable objects.
- The sequence-state points (Initiate to Lockout) are analog inputs that carry a 0/1 on/off value.
- The guide gives no fault-code or first-out-code tables; see the RM7800 documentation.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EVA / EVO boiler - RM7800 flame safeguard (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Thermal Solutions EVA / EVO boiler - RM7800 flame safeguard (ProtoNode)
How many BACnet points does the Thermal Solutions EVA / EVO boiler - RM7800 flame safeguard (ProtoNode) have?
This list has 37 BACnet objects: 17 analog inputs, 20 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Thermal Solutions EVA / EVO boiler - RM7800 flame safeguard (ProtoNode) BACnet points are writable?
None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.
Where is the official Thermal Solutions EVA / EVO boiler - RM7800 flame safeguard (ProtoNode) BACnet documentation?
The source is ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up Guide for Interfacing Thermal Solutions Product Models EVA/EVAW/EVO/EVOW with RWF40, RWF55 and RM7800 Controls (Document Revision 7.A (Web Configurator Template Revision 70)), revision 2018-08, published free by Thermal Solutions at https://boilers-water-heaters.thermalsolutions.com/Asset/Thermal%20Solutions%20EVA,%20EVAW,%20EVO%20&%20EVOW%20ProtoNode%20N34%20&%20N35%20Start-up%20Guide%202018-08.pdf.
What are the minimum BACnet points to integrate the Thermal Solutions EVA / EVO boiler - RM7800 flame safeguard (ProtoNode)?
Start with AI 58 Run (Burner in run (1 = on)); AI 1 Flame Signal (Flame signal strength); AI 4 Burner Fault Code (Current burner fault code); AI 62 Alarm (Flame safeguard alarm (1 = on)); AI 64 Lockout (Burner locked out (1 = on)); BI 1 Com Status (Modbus link between ProtoNode and the RM7800).
How do I enable BMS control of the Thermal Solutions EVA / EVO boiler - RM7800 flame safeguard (ProtoNode)?
None: the RM7800 profile is read-only, so start/stop is not available over BACnet.
How do I check these points on the real EVA / EVO boiler - RM7800 flame safeguard (ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Thermal Solutions BACnet points lists
- Boiler controller via ProtoNode gateway
Thermal Solutions Apex / Arctic with Concert or Panasonic 4716 software (Universal Gateway)
Thermal Solutions Apex and Arctic boilers with the Concert control and display, and Apex boilers with the Panasonic display running 4716 software, through the Universal Gateway.
Also known as: Concert, Concert control, Apex 4716, Arctic, Arctic 1000, Arctic 1500, Universal Gateway, 106417-01, ProtoNode RER, FPC-N34-0816 - Boiler controller via ProtoNode gateway
Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway)
Thermal Solutions Apex boilers with the control and Panasonic GT02 display running 4109 software, connected through the Universal Gateway.
Also known as: Apex, Apex 4109, Panasonic GT02, Universal Gateway, 106417-01, ProtoNode RER, FPC-N34-0816 - Boiler operating controller (RWF40) via ProtoNode gateway
Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode)
Thermal Solutions EVA, EVAW, EVO and EVOW boilers whose operating control is an RWF40, connected through a ProtoNode FPC-N34.
Also known as: RWF40, Siemens RWF40, EVA, EVAW, EVO, EVOW, FPC-N34-0643, ProtoNode FPC-N34 - Boiler operating controller (RWF55) via ProtoNode gateway
Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode)
Thermal Solutions EVA, EVAW, EVO and EVOW boilers whose operating control is an RWF55, connected through a ProtoNode FPC-N34.
Also known as: RWF55, Siemens RWF55, EVA, EVAW, EVO, EVOW, FPC-N34-0643, ProtoNode FPC-N34 - Boiler controller (TSBC) via ProtoNode gateway
Thermal Solutions TSBC boiler control (Universal Gateway)
Thermal Solutions boilers with the TSBC control (such as EVS and EVCA), connected through the Thermal Solutions Universal Gateway.
Also known as: TSBC, Thermal Solutions Boiler Control, Universal Gateway, 106417-01, ProtoNode RER, FPC-N34-0816, EVS, EVCA
Source: ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up Guide for Interfacing Thermal Solutions Product Models EVA/EVAW/EVO/EVOW with RWF40, RWF55 and RM7800 Controls · Document Revision 7.A (Web Configurator Template Revision 70) · rev. 2018-08. Object names, instances and units are reproduced as published; descriptions are our own.