Boiler controller via ProtoNode gateway · BACnet points list

Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway) BACnet points list

Updated 28 October 2026

Short answer

Apex boilers with the Panasonic display and 4109 software are read over Modbus RTU by the Thermal Solutions Universal Gateway (a ProtoNode) and served as BACnet IP or BACnet MS/TP devices. The 28-object profile has a burner on/off command, writable CH, DHW, lead lag and CH time-of-day setpoints, setpoint sources, sensor temperatures, burner state, lockout and hold codes, and cycle counters.

This page lists 28 BACnet objects for the Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermal Solutions’s own free documentation, linked below.

Manufacturer
Thermal Solutions
Model
Apex with Panasonic display, 4109 software (Universal Gateway)
Equipment
Boiler controller via ProtoNode gateway
Equipment type
Boilers & water heaters
BACnet objects
28 (10 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000 + boiler Modbus address (BACnet IP and MS/TP multiple node); Node_Offset default 50,000
Also known as
Apex, Apex 4109, Panasonic GT02, Universal Gateway, 106417-01, ProtoNode RER, FPC-N34-0816
Source document
Thermal Solutions Universal Gateway Instruction Manual · 106417-01 Rev. 13 · rev. 2017-08-21
Download CSV 28 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway)

Integration in brief

Give each Apex a unique Boiler Address (Adjust > Sequencer Slave), disable Sequencer Master on every boiler, wire the RJ45 boiler-to-boiler port to the gateway, run auto-discovery, then use BV 1 Burner On Off and AV 3 CH Setpoint. Values go to EEPROM, so write them only when they change.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1Burner On OffBurner enable from the BMS (1 = on)Write
AV 3CH SetpointCH setpoint, 79-191 °F; EEPROM, write on changeWrite
AI 21Burner Control StateBurner sequence state; 12 = Run, 14 = LockoutRead
AI 13Supply SensorSupply water temperature, °FRead
AI 8Active CH SetpointCH setpoint in use, °FRead
AI 22Lockout CodeLockout reason; 0 = no lockoutRead

Enable & remote start

BV 1 Burner On Off enables or disables the burner. If only BV 1 is used instead of the boiler's Enable/Disable contact, the boiler stops but the system pump may keep running. For lead/lag, Enable/Disable and the remote firing rate (4-20 mA) must be hard-wired to each boiler, and the Sequencer must be disabled (no master boiler) while the EMS is connected.

Sensors & values from the BMS

When the BMS writes AV 3 CH Setpoint it takes over the boiler's CH setpoint, so disable the boiler's outdoor air reset. There is no writable outdoor or header temperature input.

Network setup

Watch out for

Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

28 of 28 shown
Type
Binary
Access
Show
Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway) BACnet Points List
DescriptionStates
BVmin1Burner On OffEnable / disable the burnerWrite0=Off, 1=On
AI2Demand SourceSource of the current heat demandRead0=Unknown, 1=No source demand, 2=Central heat, 3=Domestic hot water, 4=Lead Lag slave, 5=Lead Lag master, 6=CH frost protection, 7=DHW frost protection, 8=No demand (burner switch off), 9=DHW storage, 11=Warm weather shutdown
AVmin3CH SetpointCentral heat setpoint (79 to 191)°FWrite
AV4DHW SetpointDomestic hot water setpoint (79 to 191)°FWrite
AV5Lead Lag SetpointLead lag setpoint (79 to 191)°FWrite
AV6CH TOD SetpointCentral heat time-of-day setpoint (79 to 191)°FWrite
AI7CH Setpoint SourceWhat sets the active CH setpointRead0=Unknown, 1=Normal setpoint, 2=TOD setpoint, 3=Outdoor reset, 4=Remote control (4-20 mA), 7=Outdoor reset time of day
AImin8Active CH SetpointCH setpoint in use°FRead
AI9DHW Setpoint SourceWhat sets the active DHW setpointRead0=Unknown, 1=Normal setpoint, 2=TOD setpoint, 5=DHW tap setpoint, 6=DHW preheat setpoint
AI10Active DHW SetpointDHW setpoint in use°FRead
AI11LL Master Setpoint SourceWhat sets the lead lag master setpointRead0=Unknown, 1=CH setpoint, 2=CH TOD setpoint, 3=Outdoor reset, 4=Remote control (4-20 mA), 5=DHW setpoint, 6=DHW TOD setpoint, 7=Outdoor reset time of day, 8=Mix setpoint
AI12Active LL SetpointLead lag setpoint in use°FRead
AImin13Supply SensorSupply water temperature (-40 to 266)°FRead
AI14Return SensorReturn water temperature (-40 to 266)°FRead
AI15Header SensorHeader temperature (-40 to 266)°FRead
AI16Stack SensorFlue stack temperature (-40 to 266)°FRead
AI17Outdoor SensorOutdoor air temperature (-40 to 266)°FRead
AI184-20 mA Rem Control Input4-20 mA remote setpoint/modulation inputmARead
AI19Fan SpeedCombustion blower speedrpmRead
AI20Flame SignalFlame signal (0.00-50.00)V or µARead
AImin21Burner Control StateBurner sequence stateRead0=Initiate, 1=Standby Delay, 2=Standby, 3=Safe Startup, 4=Prepurge - Drive to Purge Rate, 5=Prepurge - Measured Purge Time, 6=Prepurge - Drive to Lightoff Rate, 7=Preignition Test, 8=Preignition Time, 9=Pilot Flame Establishing Period, 10=Main Flame Establishing Period, 11=Direct Burner Ignition, 12=Run, 13=Postpurge, 14=Lockout
AImin22Lockout CodeReason for burner lockoutRead0=No lockout, 4=Supply high limit, 5=DHW high limit, 6=Stack high limit, 12=Flame detected out of sequence, 18=Lightoff rate proving failed, 19=Purge rate proving failed, 20=Invalid safety parameters, 21=Invalid modulation parameter, 22=Safety data verification needed, 23=24VAC voltage low/high, 24=Fuel valve error, 25=Hardware fault, 26=Internal fault, 27=Ignition failure
AI23Hold CodeReason for burner holdRead0=None, 1=Anti short cycle, 2=Boiler safety limit open, 3=Boiler safety limit open (ILK off), 7=Return sensor fault, 8=Supply sensor fault, 9=DHW sensor fault, 10=Stack sensor fault, 11=Ignition failure, 13=Flame rod shorted to ground, 14=Delta T inlet/outlet high, 15=Return temp higher than supply, 16=Supply temp has risen too quickly, 17=Fan speed not proved, 23=24VAC voltage low/high, 25=Hardware fault, 27=Ignition failure
AV24Burner Cycle CountBurner cycle counter (0-999,999)Write
AV25Burner Run TimeBurner run time counterhWrite
AV26System Pum Cycle CountSystem pump cycle counterWrite
AV27DHW Pump Cycle CountDHW pump cycle counterWrite
AV28Boiler Pump Cycle CountBoiler pump cycle counterWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Apex with Panasonic display, 4109 software (Universal Gateway) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway)

How many BACnet points does the Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway) have?

This list has 28 BACnet objects: 18 analog inputs, 9 analog values, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway) BACnet points are writable?

10 of the 28 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway) BACnet documentation?

The source is Thermal Solutions Universal Gateway Instruction Manual (106417-01 Rev. 13), revision 2017-08-21, published free by Thermal Solutions at https://boilers-water-heaters.thermalsolutions.com/Asset/106417-01%20Rev%2013%20TS%20Universal%20Gateway%20Instructions.pdf.

What are the minimum BACnet points to integrate the Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway)?

Start with BV 1 Burner On Off (Burner enable from the BMS (1 = on)); AV 3 CH Setpoint (CH setpoint, 79-191 °F; EEPROM, write on change); AI 21 Burner Control State (Burner sequence state; 12 = Run, 14 = Lockout); AI 13 Supply Sensor (Supply water temperature, °F); AI 8 Active CH Setpoint (CH setpoint in use, °F); AI 22 Lockout Code (Lockout reason; 0 = no lockout).

How do I enable BMS control of the Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway)?

BV 1 Burner On Off enables or disables the burner. If only BV 1 is used instead of the boiler's Enable/Disable contact, the boiler stops but the system pump may keep running. For lead/lag, Enable/Disable and the remote firing rate (4-20 mA) must be hard-wired to each boiler, and the Sequencer must be disabled (no master boiler) while the EMS is connected.

Can the BMS supply sensor values to the Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway)?

When the BMS writes AV 3 CH Setpoint it takes over the boiler's CH setpoint, so disable the boiler's outdoor air reset. There is no writable outdoor or header temperature input.

How do I check these points on the real Apex with Panasonic display, 4109 software (Universal Gateway)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.