Boiler operating controller (RWF40) via ProtoNode gateway · BACnet points list

Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode) BACnet points list

Updated 28 October 2026

Short answer

Thermal Solutions EVA/EVAW/EVO/EVOW boilers expose their RWF40 controller to BACnet IP or BACnet MS/TP through a ProtoNode FPC-N34 gateway that polls it over Modbus RTU. The RWF40 profile has 15 objects: three analog inputs, setpoint and mode readbacks, and writable process enable, process setpoint, relay enables, step control and modulation values.

This page lists 15 BACnet objects for the Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermal Solutions’s own free documentation, linked below.

Manufacturer
Thermal Solutions
Model
EVA / EVO boiler - RWF40 controller (ProtoNode)
Equipment
Boiler operating controller (RWF40) via ProtoNode gateway
Equipment type
Boilers & water heaters
BACnet objects
15 (8 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000 + the controller's Modbus Node-ID (Node_Offset default 50,000, changeable in the Web Configurator)
Also known as
RWF40, Siemens RWF40, EVA, EVAW, EVO, EVOW, FPC-N34-0643, ProtoNode FPC-N34
Source document
ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up Guide for Interfacing Thermal Solutions Product Models EVA/EVAW/EVO/EVOW with RWF40, RWF55 and RM7800 Controls · Document Revision 7.A (Web Configurator Template Revision 70) · rev. 2018-08
Download CSV 15 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode)

Integration in brief

Wire the RWF40 Modbus port to the ProtoNode, set the RWF40 to 19200 8N1 with a unique Node-ID, add the RWF40 profile in the Web Configurator, then discover the device at 50000 + Node-ID. The writable objects are Process Enable, Process Setpoint, the K1/K2/K3/K6 enables, Step Control and Modulation; the guide does not describe how the boiler uses them.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 7Process EnableProcess enable from the BMSWrite
AV 8Process SetpointProcess setpoint written by the BMSWrite
AV 14ModulationModulation level, %Write
AV 6Operation ModeController operating mode readbackRead
AI 1Input 1Analog input 1 reading; units per controller setupRead
BI 1Com StatusModbus link between ProtoNode and the RWF40Read

Enable & remote start

The guide lists BV 7 Process Enable and AV 8 Process Setpoint as writable but gives no procedure for handing control to the BMS; check the RWF40 configuration.

Network setup

Watch out for

Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

15 of 15 shown
Type
Access
Show
Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode) BACnet Points List
DescriptionStates
BImin1Com StatusProtoNode-to-RWF40 Modbus link statusRead
AImin1Input 1Analog input 1 valueRead
AI2Input 2Analog input 2 valueRead
AI3Input 3Analog input 3 valueRead
AV4First SetpointSetpoint 1 readbackRead
AV5Second SetpointSetpoint 2 readbackRead
AVmin6Operation ModeController operating modeRead
BVmin7Process EnableProcess enable from the BMSWrite
AVmin8Process SetpointProcess setpoint written over the networkWrite
BV9Enable K1Relay K1 enableWrite
BV10Enable K2Relay K2 enableWrite
BV11Enable K3Relay K3 enableWrite
BV12Enable K6Relay K6 enableWrite
AV13Step ControlStep control valueWrite
AVmin14ModulationModulation level%Write

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the EVA / EVO boiler - RWF40 controller (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode)

How many BACnet points does the Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode) have?

This list has 15 BACnet objects: 3 analog inputs, 6 analog values, 1 binary input, 5 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode) BACnet points are writable?

8 of the 15 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode) BACnet documentation?

The source is ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up Guide for Interfacing Thermal Solutions Product Models EVA/EVAW/EVO/EVOW with RWF40, RWF55 and RM7800 Controls (Document Revision 7.A (Web Configurator Template Revision 70)), revision 2018-08, published free by Thermal Solutions at https://boilers-water-heaters.thermalsolutions.com/Asset/Thermal%20Solutions%20EVA,%20EVAW,%20EVO%20&%20EVOW%20ProtoNode%20N34%20&%20N35%20Start-up%20Guide%202018-08.pdf.

What are the minimum BACnet points to integrate the Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode)?

Start with BV 7 Process Enable (Process enable from the BMS); AV 8 Process Setpoint (Process setpoint written by the BMS); AV 14 Modulation (Modulation level, %); AV 6 Operation Mode (Controller operating mode readback); AI 1 Input 1 (Analog input 1 reading; units per controller setup); BI 1 Com Status (Modbus link between ProtoNode and the RWF40).

How do I enable BMS control of the Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode)?

The guide lists BV 7 Process Enable and AV 8 Process Setpoint as writable but gives no procedure for handing control to the BMS; check the RWF40 configuration.

How do I check these points on the real EVA / EVO boiler - RWF40 controller (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermal Solutions BACnet points lists

Source: ProtoNode FPC-N34 and ProtoNode FPC-N35 Start-up Guide for Interfacing Thermal Solutions Product Models EVA/EVAW/EVO/EVOW with RWF40, RWF55 and RM7800 Controls · Document Revision 7.A (Web Configurator Template Revision 70) · rev. 2018-08. Object names, instances and units are reproduced as published; descriptions are our own.