Boiler burner management system (LMV36) via ProtoAir gateway · BACnet points list

Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir) BACnet points list

Updated 7 November 2026

Short answer

A short profile for a Siemens LMV36 burner control read through the ProtoAir Universal Gateway on BACnet IP or BACnet MS/TP: flame signal, lockout and diagnostic codes, fuel selected and firing rate, plus writable control mode, operating mode and fuel rate.

This page lists 9 BACnet objects for the Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermal Solutions’s own free documentation, linked below.

Manufacturer
Thermal Solutions
Model
Siemens LMV36 burner management (Universal Gateway ProtoAir)
Equipment
Boiler burner management system (LMV36) via ProtoAir gateway
Equipment type
Boilers & water heaters
BACnet objects
9 (3 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
LMV36, Siemens LMV36, LMV3, ProtoAir FPA-W44, Universal Gateway 106417-04
Source document
Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus · PN 106417-04 Rev A · rev. 2024-05
Download CSV 9 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermal Solutions’s current documentation and the live device before use. Not official Thermal Solutions information. Terms of use.

BMS integration notes: Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir)

Integration in brief

Add the LMV36 as a profile in the ProtoAir Web Configurator with a unique Node-ID and discover it at 50000 + Node-ID. Read the firing rate, flame signal and lockout code; the BMS can set control mode, operating mode and fuel rate.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 4Control ModeLocal or remote (BMS) controlWrite
AV 5Operating ModeLMV36 operating modeWrite
AV 6Fuel RateFiring rate command in remote modeWrite
AI 8Firing RateCurrent firing rateRead
AI 1Flame SignalFlame signalRead
AI 2Lockout Error CodeLockout error codeRead
BI 1Com StatusModbus link between ProtoAir and the LMV36Read

Enable & remote start

BV 4 Control Mode and AV 5 Operating Mode select how the LMV36 takes its demand; the manual does not list their values.

Network setup

Watch out for

Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

9 of 9 shown
Type
Access
Show
Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir) BACnet Points List
DescriptionStates
BImin1Com StatusModbus link from the ProtoAir to the controllerRead
AImin1Flame SignalFlame signalRead
AImin2Lockout Error CodeLockout error codeRead
AI3Lockout Diagnostic CodeLockout diagnostic codeRead
BVmin4Control ModeLocal or remote controlWrite
AVmin5Operating ModeOperating modeWrite
AVmin6Fuel RateFiring rate command in remote modeWrite
AI7Fuel SelectedFuel in useRead
AImin8Firing RateCurrent firing rateRead
Object ID lookup: Thermal Solutions Siemens LMV36 burner management point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Siemens LMV36 burner management (Universal Gateway ProtoAir) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir)

How many BACnet points does the Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir) have?

This list has 9 BACnet objects: 5 analog inputs, 2 analog values, 1 binary input, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir) BACnet points are writable?

3 of the 9 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir) BACnet documentation?

The source is Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus (PN 106417-04 Rev A), revision 2024-05, published free by Thermal Solutions at https://s3-us-west-2.amazonaws.com/catsy.782/Universal+Gateway+ProtoAir+BACnet+Instruction+Manual.pdf.

What are the minimum BACnet points to integrate the Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir)?

Start with BV 4 Control Mode (Local or remote (BMS) control); AV 5 Operating Mode (LMV36 operating mode); AV 6 Fuel Rate (Firing rate command in remote mode); AI 8 Firing Rate (Current firing rate); AI 1 Flame Signal (Flame signal); AI 2 Lockout Error Code (Lockout error code); BI 1 Com Status (Modbus link between ProtoAir and the LMV36).

How do I enable BMS control of the Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir)?

BV 4 Control Mode and AV 5 Operating Mode select how the LMV36 takes its demand; the manual does not list their values.

How do I check these points on the real Siemens LMV36 burner management (Universal Gateway ProtoAir)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermal Solutions BACnet points lists

Source: Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus · PN 106417-04 Rev A · rev. 2024-05. Object names, instances and units are reproduced as published; descriptions are our own.