Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir) BACnet points list

Updated 7 November 2026

Short answer

The ProtoAir Universal Gateway polls a Siemens RWF55 boiler controller over Modbus RTU and serves it on BACnet IP or BACnet MS/TP. Besides the inputs, setpoints, actuator position and burner alarm, this profile adds remote-operation objects: the BMS can switch the RWF55 to remote mode and then write its setpoint, switching thresholds, burner release, relays K2/K3/K6 and the actuator output.

This page lists 25 BACnet objects for the Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir) — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermal Solutions’s own free documentation, linked below.

Manufacturer
Thermal Solutions
Model
Siemens RWF55 boiler controller (Universal Gateway ProtoAir)
Equipment
Boiler operating controller (RWF55) via ProtoAir gateway
Equipment type
Boilers & water heaters
BACnet objects
25 (17 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
RWF55, Siemens RWF55, ProtoAir FPA-W44, Universal Gateway 106417-04, Bryan Boiler RWF55
Source document
Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus · PN 106417-04 Rev A · rev. 2024-05
Download CSV 25 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermal Solutions’s current documentation and the live device before use. Not official Thermal Solutions information. Terms of use.

BMS integration notes: Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir)

Integration in brief

Add the RWF55 as a profile in the ProtoAir Web Configurator with a unique Node-ID and discover it at 50000 + Node-ID. For monitoring read the analog inputs, actual setpoint, actuator position and burner alarm. For BMS control turn on remote operation (AV 10), then write the remote setpoint and burner release.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 10Activation Remote OperationTurns on remote (BMS) operation of the RWF55Write
AV 16Burner Release Remote OperationBurner release while in remote operationWrite
AV 15Setpoint RemoteSetpoint used in remote operationWrite
AI 1Analog Input InP1Analog input 1 (process value)Read
AI 4Actual SetpointSetpoint in useRead
AI 8Actual Angular PositioningActuator positionRead
AI 9Burner AlarmBurner alarmRead
BI 1Com StatusModbus link between ProtoAir and the RWF55Read

Enable & remote start

Remote (BMS) operation is turned on with AV 10 Activation Remote Operation; the manual gives no values for it.

Network setup

Watch out for

Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

25 of 25 shown
Type
Binary
Access
Show
Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir) BACnet Points List
DescriptionStates
BImin1Com StatusModbus link from the ProtoAir to the controllerRead
AImin1Analog Input InP1Analog input 1Read
AI2Analog Input InP2Analog input 2Read
AI3Analog Input InP3Analog input 3Read
AImin4Actual SetpointSetpoint in useRead
AV5Setpoint 1Setpoint 1Write
AV6Setpoint 2Setpoint 2Write
AI7Analog Input InP3Analog input 3Read
AImin8Actual Angular PositioningCurrent actuator positionRead
AImin9Burner AlarmBurner alarmRead
AVmin10Activation Remote OperationTurn remote (BMS) operation onWrite
AV11Controller Off In Remote SetpointController off in remote operationWrite
AV12Switch-On Threshold RemoteRemote switch-on thresholdWrite
AV13Switch-Off Threshold Down RemoteRemote lower switch-off thresholdWrite
AV14Switch-Off Threshold Up RemoteRemote upper switch-off thresholdWrite
AVmin15Setpoint RemoteSetpoint in remote operationWrite
AVmin16Burner Release Remote OperationBurner release in remote operationWrite
AV17Relay K2 Remote OperationRelay K2 in remote operationWrite
AV18Relay K3 Remote OperationRelay K3 in remote operationWrite
AV19Relay K6 Remote OperationRelay K6 in remote operationWrite
AV20Step-By-Step Control Rem OperationStep control in remote operationWrite
AV21Angular Pos Output Remote OperationActuator position output in remote operationWrite
AV22Switch-On Threshold RemoteRemote switch-on thresholdWrite
AV23Switch-Off Threshold Down RemoteRemote lower switch-off thresholdWrite
AV24Switch-Off Threshold Up RemoteRemote upper switch-off thresholdWrite
Object ID lookup: Thermal Solutions Siemens RWF55 boiler controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Siemens RWF55 boiler controller (Universal Gateway ProtoAir) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir)

How many BACnet points does the Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir) have?

This list has 25 BACnet objects: 7 analog inputs, 17 analog values, 1 binary input. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir) BACnet points are writable?

17 of the 25 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir) BACnet documentation?

The source is Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus (PN 106417-04 Rev A), revision 2024-05, published free by Thermal Solutions at https://s3-us-west-2.amazonaws.com/catsy.782/Universal+Gateway+ProtoAir+BACnet+Instruction+Manual.pdf.

What are the minimum BACnet points to integrate the Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir)?

Start with AV 10 Activation Remote Operation (Turns on remote (BMS) operation of the RWF55); AV 16 Burner Release Remote Operation (Burner release while in remote operation); AV 15 Setpoint Remote (Setpoint used in remote operation); AI 1 Analog Input InP1 (Analog input 1 (process value)); AI 4 Actual Setpoint (Setpoint in use); AI 8 Actual Angular Positioning (Actuator position); AI 9 Burner Alarm (Burner alarm); BI 1 Com Status (Modbus link between ProtoAir and the RWF55).

How do I enable BMS control of the Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir)?

Remote (BMS) operation is turned on with AV 10 Activation Remote Operation; the manual gives no values for it.

How do I check these points on the real Siemens RWF55 boiler controller (Universal Gateway ProtoAir)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermal Solutions BACnet points lists

Source: Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus · PN 106417-04 Rev A · rev. 2024-05. Object names, instances and units are reproduced as published; descriptions are our own.