Process meter (boiler plant signal) via ProtoAir gateway · BACnet points list

Thermal Solutions Precision Digital Trident PD765 meter (Universal Gateway ProtoAir) BACnet points list

Updated 7 November 2026

Short answer

The Trident PD765 is a panel process meter with two alarm relays and a 4-20 mA output; in these boiler control systems it is read through the ProtoAir Universal Gateway on BACnet IP or BACnet MS/TP. The profile gives the displayed value, relay and alarm states, alarm acknowledge, and the relay set/reset points, delays and 4-20 mA output scaling.

This page lists 32 BACnet objects for the Thermal Solutions Precision Digital Trident PD765 meter (Universal Gateway ProtoAir) — 28 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermal Solutions’s own free documentation, linked below.

Manufacturer
Thermal Solutions
Model
Precision Digital Trident PD765 meter (Universal Gateway ProtoAir)
Equipment
Process meter (boiler plant signal) via ProtoAir gateway
Equipment type
Boilers & water heaters
BACnet objects
32 (28 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
PD765, Trident PD765, Precision Digital PD765, ProtoAir FPA-W44, Universal Gateway 106417-04
Source document
Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus · PN 106417-04 Rev A · rev. 2024-05
Download CSV 32 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermal Solutions’s current documentation and the live device before use. Not official Thermal Solutions information. Terms of use.

BMS integration notes: Thermal Solutions Precision Digital Trident PD765 meter (Universal Gateway ProtoAir)

Integration in brief

Add the PD765 as a profile in the ProtoAir Web Configurator with a unique Node-ID and discover it at 50000 + Node-ID. Read the display value and the alarm states, acknowledge alarms from the BMS, and adjust relay set points if needed.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 6Alarm 1 AcknowledgeAcknowledge alarm 1Write
BV 7Alarm 2 AcknowledgeAcknowledge alarm 2Write
AI 1Display ValueValue shown on the meterRead
BV 2Relay 1 StatusRelay 1 stateWrite
BV 3Relay 2 StatusRelay 2 stateWrite
BI 4Alarm 1 StatusAlarm 1 activeRead
BI 5Alarm 2 StatusAlarm 2 activeRead
BI 1Com StatusModbus link between ProtoAir and the PD765Read

Network setup

Watch out for

Thermal Solutions Precision Digital Trident PD765 meter (Universal Gateway ProtoAir) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

32 of 32 shown
Type
Access
Show
Thermal Solutions Precision Digital Trident PD765 meter (Universal Gateway ProtoAir) BACnet Points List
DescriptionStates
BImin1Com StatusModbus link from the ProtoAir to the controllerRead
AImin1Display ValueValue shown on the meter displayRead
BVmin2Relay 1 StatusRelay 1 StatusWrite
BVmin3Relay 2 StatusRelay 2 StatusWrite
BImin4Alarm 1 StatusAlarm 1 StatusRead
BImin5Alarm 2 StatusAlarm 2 StatusRead
BVmin6Alarm 1 AcknowledgeAlarm 1 AcknowledgeWrite
BVmin7Alarm 2 AcknowledgeAlarm 2 AcknowledgeWrite
AV8Relay 1 Set PointRelay 1 Set PointWrite
AV9Relay 1 Reset PointRelay 1 Reset PointWrite
AV10Relay 1 Turn-on DelayRelay 1 Turn-on DelayWrite
AV11Relay 1 Turn-off DelayRelay 1 Turn-off DelayWrite
BV12Relay 1 Normal/Fail-SafeRelay 1 Normal/Fail-SafeWrite
AV13Relay 1 OperationRelay 1 OperationWrite
AV14Relay 2 Set PointRelay 2 Set PointWrite
AV15Relay 2 Reset PointRelay 2 Reset PointWrite
AV16Relay 2 Turn-on DelayRelay 2 Turn-on DelayWrite
AV17Relay 2 Turn-off DelayRelay 2 Turn-off DelayWrite
BV18Relay 2 Normal/Fail-SafeRelay 2 Normal/Fail-SafeWrite
AV19Relay 2 OperationRelay 2 OperationWrite
BV204-20mA Out-Mode Output Option4-20 mA output: Mode Output OptionWrite
AV214-20mA Out-Mode Data Source4-20 mA output: Mode Data SourceWrite
AV224-20mA Out–Sensor Break Value4-20 mA output: Sensor Break ValueWrite
AV234-20mA Out–Overrange value4-20 mA output: Overrange valueWrite
AV244-20mA Out–Underrange value4-20 mA output: Underrange valueWrite
AV254-20mA Out–Max value Allowed4-20 mA output: Max value AllowedWrite
AV264-20mA Out–Min value Allowed4-20 mA output: Min value AllowedWrite
AV274-20mA Out–Display Value 14-20 mA output: Display Value 1Write
AV284-20mA Out–Display Value 24-20 mA output: Display Value 2Write
AV294-20mA Out–Output 14-20 mA output: Output 1Write
AV304-20mA Out–Output 24-20 mA output: Output 2Write
AV314-20mA Out–Data in mA or Data in bit4-20 mA output: Data in mA or Data in bitWrite
Object ID lookup: Thermal Solutions Precision Digital Trident PD765 meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Precision Digital Trident PD765 meter (Universal Gateway ProtoAir) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermal Solutions Precision Digital Trident PD765 meter (Universal Gateway ProtoAir)

How many BACnet points does the Thermal Solutions Precision Digital Trident PD765 meter (Universal Gateway ProtoAir) have?

This list has 32 BACnet objects: 1 analog input, 21 analog values, 3 binary inputs, 7 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermal Solutions Precision Digital Trident PD765 meter (Universal Gateway ProtoAir) BACnet points are writable?

28 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Thermal Solutions Precision Digital Trident PD765 meter (Universal Gateway ProtoAir) BACnet documentation?

The source is Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus (PN 106417-04 Rev A), revision 2024-05, published free by Thermal Solutions at https://s3-us-west-2.amazonaws.com/catsy.782/Universal+Gateway+ProtoAir+BACnet+Instruction+Manual.pdf.

What are the minimum BACnet points to integrate the Thermal Solutions Precision Digital Trident PD765 meter (Universal Gateway ProtoAir)?

Start with BV 6 Alarm 1 Acknowledge (Acknowledge alarm 1); BV 7 Alarm 2 Acknowledge (Acknowledge alarm 2); AI 1 Display Value (Value shown on the meter); BV 2 Relay 1 Status (Relay 1 state); BV 3 Relay 2 Status (Relay 2 state); BI 4 Alarm 1 Status (Alarm 1 active); BI 5 Alarm 2 Status (Alarm 2 active); BI 1 Com Status (Modbus link between ProtoAir and the PD765).

How do I check these points on the real Precision Digital Trident PD765 meter (Universal Gateway ProtoAir)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.