 "manufacturer": "Thermal Solutions",
 "manufacturer_slug": "thermal-solutions",
 "model": "Fireye YB110 flame safeguard (Universal Gateway ProtoAir)",
 "model_slug": "fireye-yb110-universal-gateway-protoair",
 "aliases": [
  "YB110",
  "Fireye YB110",
  "BurnerPRO",
  "Fireye",
  "ProtoAir FPA-W44",
  "Universal Gateway 106417-04"
 ],
 "equipment_type": "Boiler flame safeguard (Fireye YB110) via ProtoAir gateway",
 "applies_to": "Thermal Solutions and Bryan boilers with a Fireye YB110 flame safeguard, connected to the Universal Gateway (ProtoAir FPA-W44).",
 "summary": "The ProtoAir Universal Gateway reads a Fireye YB110 flame safeguard over Modbus and serves it on BACnet IP or BACnet MS/TP. The profile is monitoring only apart from the Com Status object: burner status and message numbers, flame signal, run minutes, cycles, a 10-entry lockout history, and binary objects for the safety relay, valves, ignition, blower, limits and interlocks (water level, oil and gas pressure, air flow).",
 "bacnet_transport": [
  "BACnet IP",
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "All objects are AI or BI except BV 1 Com Status, which is listed as read; the table has no read/write column.",
  "The lockout history repeats message, module, burner hours and burner cycles for lockouts 1-10 (AI 11-50).",
  "Message and status numbers are Fireye codes; the manual gives no code tables."
 ],
 "source": {
  "title": "Universal Gateway Instruction Manual (ProtoAir): BACnet MS/TP, BACnet IP, N2, Modbus",
  "doc_number": "PN 106417-04 Rev A",
  "revision_date": "2024-05",
  "url": "https://s3-us-west-2.amazonaws.com/catsy.782/Universal+Gateway+ProtoAir+BACnet+Instruction+Manual.pdf"
 },
 "integration": {
  "summary": "Add the YB110 as a profile in the ProtoAir Web Configurator with a unique Node-ID and discover it at 50000 + Node-ID. It is a monitoring profile: read burner status, message number, flame signal, the alarm output and the lockout count and history.",
  "minimum_points": [
   {
    "ref": "AI 1",
    "name": "Status",
    "why": "Burner status code"
   },
   {
    "ref": "AI 2",
    "name": "Msgn",
    "why": "Current Fireye message number"
   },
   {
    "ref": "AI 5",
    "name": "Flame",
    "why": "Flame signal"
   },
   {
    "ref": "BI 20",
    "name": "Main_Valve_Out",
    "why": "Main fuel valve energized"
   },
   {
    "ref": "BI 26",
    "name": "Alarm_Out",
    "why": "Alarm output"
   },
   {
    "ref": "AI 11",
    "name": "Lockout1_Msg",
    "why": "Most recent lockout message"
   },
   {
    "ref": "BV 1",
    "name": "Com Status",
    "why": "Modbus link between ProtoAir and the YB110"
   }
  ],
  "enable": "None: the YB110 profile has no command objects.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Device instance = Node_Offset (default 50,000) + the controller's Node-ID (1-255), so Node-ID 1 gives 50001.",
   "ProtoAir default IP address is 192.168.1.24, mask 255.255.255.0.",
   "Add each controller as a profile in the ProtoAir Web Configurator and give it a unique Node-ID."
  ],
  "gotchas": [
   "Decode Status, Msgn and lockout messages with the Fireye YB110 documentation."
  ]
 },
 "points": [
  {
   "type": "BV",
   "instance": 1,
   "name": "Com Status",
   "description": "Modbus link from the ProtoAir to the controller",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "Safety_Relay",
   "description": "Safety Relay",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Main_Valve_In",
   "description": "Main Valve In",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Delayed_Valve_In",
   "description": "Delayed Valve In",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Pilot_Valve_In",
   "description": "Pilot Valve In",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Ignition_In",
   "description": "Ignition In",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "Blower_In",
   "description": "Blower In",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "Op_Cntrl",
   "description": "Op Cntrl",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "Run_Intlck",
   "description": "Run Intlck",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "Purge_Damper",
   "description": "Purge Damper",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "Term_23",
   "description": "Term 23",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "Remote_Reset",
   "description": "Remote Reset",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "Start_Input",
   "description": "Start Input",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 13,
   "name": "FVES_POC",
   "description": "FVES POC",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 14,
   "name": "Pilot_Hold",
   "description": "Pilot Hold",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "Low_Fire_Start",
   "description": "Low Fire Start",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 16,
   "name": "Ref_AC_Line",
   "description": "Ref AC Line",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 17,
   "name": "Ignition_Out",
   "description": "Ignition Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 18,
   "name": "Pilot_Valve_Out",
   "description": "Pilot Valve Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 19,
   "name": "Blower_Out",
   "description": "Blower Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 20,
   "name": "Main_Valve_Out",
   "description": "Main Valve Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 21,
   "name": "Delayed_Valve_Out",
   "description": "Delayed Valve Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 22,
   "name": "Internal_Safety_Out",
   "description": "Internal Safety Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 23,
   "name": "Low_Fire_Out",
   "description": "Low Fire Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 24,
   "name": "High_Fire_Out",
   "description": "High Fire Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 25,
   "name": "Auto_Out",
   "description": "Auto Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 26,
   "name": "Alarm_Out",
   "description": "Alarm Out",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Status",
   "description": "Burner status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Msgn",
   "description": "Current message number",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Gstat",
   "description": "Burner sequence status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Timer",
   "description": "Sequence timer",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Flame",
   "description": "Flame signal",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Logstat",
   "description": "Logic status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "Sysmins",
   "description": "System on time, minutes",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "Bnrmins",
   "description": "Burner run time, minutes",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "Cycles",
   "description": "Burner cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Lockout_Count",
   "description": "Number of lockouts",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Lockout1_Msg",
   "description": "Lockout history 1: message",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "Lockout1_Module",
   "description": "Lockout history 1: module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "Lockout1_BnrHrs",
   "description": "Lockout history 1: burner hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "Lockout1_BnrCycs",
   "description": "Lockout history 1: burner cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "Lockout2_Msg",
   "description": "Lockout history 2: message",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "Lockout2_Module",
   "description": "Lockout history 2: module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "Lockout2_BnrHrs",
   "description": "Lockout history 2: burner hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "Lockout2_BnrCycs",
   "description": "Lockout history 2: burner cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "Lockout3_Msg",
   "description": "Lockout history 3: message",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Lockout3_Module",
   "description": "Lockout history 3: module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Lockout3_BnrHrs",
   "description": "Lockout history 3: burner hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Lockout3_BnrCycs",
   "description": "Lockout history 3: burner cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "Lockout4_Msg",
   "description": "Lockout history 4: message",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "Lockout4_Module",
   "description": "Lockout history 4: module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "Lockout4_BnrHrs",
   "description": "Lockout history 4: burner hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "Lockout4_BnrCycs",
   "description": "Lockout history 4: burner cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "Lockout5_Msg",
   "description": "Lockout history 5: message",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "Lockout5_Module",
   "description": "Lockout history 5: module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "Lockout5_BnrHrs",
   "description": "Lockout history 5: burner hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "Lockout5_BnrCycs",
   "description": "Lockout history 5: burner cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "Lockout6_Msg",
   "description": "Lockout history 6: message",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "Lockout6_Module",
   "description": "Lockout history 6: module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "Lockout6_BnrHrs",
   "description": "Lockout history 6: burner hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "Lockout6_BnrCycs",
   "description": "Lockout history 6: burner cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "Lockout7_Msg",
   "description": "Lockout history 7: message",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "Lockout7_Module",
   "description": "Lockout history 7: module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "Lockout7_BnrHrs",
   "description": "Lockout history 7: burner hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "Lockout7_BnrCycs",
   "description": "Lockout history 7: burner cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "Lockout8_Msg",
   "description": "Lockout history 8: message",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "Lockout8_Module",
   "description": "Lockout history 8: module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "Lockout8_BnrHrs",
   "description": "Lockout history 8: burner hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "Lockout8_BnrCycs",
   "description": "Lockout history 8: burner cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "Lockout9_Msg",
   "description": "Lockout history 9: message",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "Lockout9_Module",
   "description": "Lockout history 9: module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "Lockout9_BnrHrs",
   "description": "Lockout history 9: burner hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "Lockout9_BnrCycs",
   "description": "Lockout history 9: burner cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "Lockout10_Msg",
   "description": "Lockout history 10: message",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "Lockout10_Module",
   "description": "Lockout history 10: module",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "Lockout10_BnrHrs",
   "description": "Lockout history 10: burner hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "Lockout10_BnrCycs",
   "description": "Lockout history 10: burner cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 27,
   "name": "Op_Control",
   "description": "Op Control",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 28,
   "name": "Aux_1",
   "description": "Aux 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 29,
   "name": "Aux_2",
   "description": "Aux 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 30,
   "name": "Aux_3",
   "description": "Aux 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 31,
   "name": "High_water",
   "description": "High water",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 32,
   "name": "Low_Water",
   "description": "Low Water",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 33,
   "name": "High_Oil_Temp",
   "description": "High Oil Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 34,
   "name": "Low_Oil_Temp",
   "description": "Low Oil Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 35,
   "name": "Low_Oil_Press",
   "description": "Low Oil Press",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 36,
   "name": "Low_Atom_Media",
   "description": "Low Atom Media",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 37,
   "name": "Low_Gas_Press",
   "description": "Low Gas Press",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 38,
   "name": "High_Gas_Press",
   "description": "High Gas Press",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 39,
   "name": "Aux_Gas",
   "description": "Aux Gas",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 40,
   "name": "High_Press",
   "description": "High Press",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 41,
   "name": "High_Temp",
   "description": "High Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 42,
   "name": "Aux_4",
   "description": "Aux 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 43,
   "name": "Aux_5",
   "description": "Aux 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 44,
   "name": "Aux_6",
   "description": "Aux 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 45,
   "name": "Aux_7",
   "description": "Aux 7",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 46,
   "name": "Air_Flow",
   "description": "Air Flow",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/thermal-solutions/fireye-yb110-universal-gateway-protoair",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}