Boiler plant sequencer · BACnet points list

Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) BACnet points list

Updated 12 November 2026

Short answer

Conductor EMS is the master boiler sequencer for Thermal Solutions and Bryan Steam plants. Through the ProtoAir FPA-W44 gateway it reports plant load, sequencer status and setpoint, system supply/return/outdoor temperatures, steam pressure, discrete outputs and system alarms, plus a block of 23 points for each of up to eight boilers. The BMS can enable the sequencer (BV 0) and write its setpoint (AV 0); everything else is read-only Analog Inputs, including on/off states and alarm flags.

This page lists 222 BACnet objects for the Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermal Solutions’s own free documentation, linked below.

Manufacturer
Thermal Solutions
Model
Conductor EMS boiler sequencer (ProtoAir FPA-W44)
Equipment
Boiler plant sequencer
Equipment type
Boilers & water heaters
BACnet objects
222 (2 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
Conductor, Conductor EMS, Bryan Steam Conductor, ProtoAir FPA-W44, 106417-02, Thermal Solutions master sequencer
Source document
Operating Manual, ProtoAir FPA-W44 for Interfacing Bryan Steam & Thermal Solutions Products · 106417-02 Rev 13 · rev. 2022-10
Download CSV 222 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Thermal Solutions’s current documentation and the live device before use. Not official Thermal Solutions information. Terms of use.

BMS integration notes: Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44)

Integration in brief

Cut jumper 1 on PCB-10 so BV 0 can enable the sequencer, then enable it and write the plant setpoint to AV 0. Read the active setpoint, firing rate, system temperatures, sequencer status and the per-boiler alarm flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0EMS_EnableEnable master sequencerWrite
AV 0EMS_SetpointSequencer setpoint, 60-230 °FWrite
AI 2Active_SetpointSetpoint in use, °FRead
AI 3StatusSequencer status codeRead
AI 1Firing_RatePlant firing rate, %Read
AI 7SYSTEM_SUPPLYSystem supply temperature, °FRead
AI 8SYSTEM_RETURNSystem return temperature, °FRead
AI 42BLR1_General_AlarmBoiler 1 general alarm (1 = fault)Read
AI 53ALR_BLR1LockoutBoiler 1 lockout (1 = fault)Read

Enable & remote start

BV 0 EMS_Enable turns the master sequencer on; jumper 1 on PCB-10 must be cut first.

Network setup

Watch out for

Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

222 of 222 shown
Type
Binary
Access
Show
Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) BACnet Points List
DescriptionStates
AI0Plant_loadLoad monitoring statuskBTU/hRead
BVmin0EMS_EnableEnable the master sequencer (cut jumper 1 on PCB-10)Write0=Disable, 1=Enable
AVmin0EMS_SetpointSequencer setpoint, 60-230 °F or pressure range°FWrite
AImin1Firing_RateMaster sequencer modulation rate%Read
AImin2Active_SetpointSetpoint in use°FRead
AI4Master_SP_SourceMaster setpoint sourceRead0=Normal, 1=Remote, 2=DHW, 3=Reset, 4=Reset/Setback, 5=Setback
AImin3StatusSequencer statusRead0=Standby, 1=Start Lead, 2=Start 1st Lag, 3=Start 2nd Lag, 4=Start 3rd Lag, 5=Start 4th Lag, 6=Start 5th Lag, 7=Start 6th Lag, 8=Start 7th Lag
AI5PrioritySequencer priorityRead0=Disabled, 1=Sequence Off, 2=WWSD Both, 3=WWSD Boiler, 4=Non-Condensing, 5=Condensing
AI6LeadNumber of lead boilerRead
AImin7SYSTEM_SUPPLYSystem supply temperature°FRead
AImin8SYSTEM_RETURNSystem return temperature°FRead
AI9OUTDOOR_AIROutdoor air temperature°FRead
AI10UAI5_EMS_SETPOINTEMS setpoint input°FRead
AI11UAI7_PUMP_FEEDBACKPump feedback input%Read
AI12STEAM_PRESSURESteam pressurepsiRead
AI13BLR_A_SHELLBoiler A shell temperature°FRead
AI14BLR_B_SHELLBoiler B shell temperature°FRead
AI15BLR_C_SHELLBoiler C shell temperature°FRead
AI16BLR_D_SHELLBoiler D shell temperature°FRead
AI17UDO1_CONFIGURABLEDiscrete output configurableRead0=Off, 1=On
AI18UDO2_ALARMDiscrete output alarmRead0=Off, 1=On
AI19UDO7_BLR_D_ISOLATION_VALVEDiscrete output blr d isolation valveRead0=Off, 1=On
AI20UDO8_PUMP_ADiscrete output pump aRead0=Off, 1=On
AI21UDO9_BLR_A_ISOLATION_VALVEDiscrete output blr a isolation valveRead0=Off, 1=On
AI22UDO10_BLR_B_ISOLATION_VALVEDiscrete output blr b isolation valveRead0=Off, 1=On
AI23UDO11_BLR_C_ISOLATION_VALVEDiscrete output blr c isolation valveRead0=Off, 1=On
AI24UDO12_PUMP_BDiscrete output pump bRead0=Off, 1=On
AI25ALR_Press_HighHigh steam pressureRead0=Normal, 1=High
AI26ALR_Press_LowLow steam pressureRead0=Normal, 1=Low
AI27ALR_Temp_HighHigh supply water temperatureRead0=Normal, 1=High
AI28ALR_Temp_LowLow supply water temperatureRead0=Normal, 1=Low
AI29ALR_Return_Temp_LowLow return water temperatureRead0=Normal, 1=Low
AI30ALR_Pump_A_FaultSystem pump A faultRead0=Normal, 1=Fault
AI31ALR_Pump_B_FaultSystem pump B faultRead0=Normal, 1=Fault
AI32ALR_Shell_1_HighBoiler 1 high shell temperature (steam)Read0=Normal, 1=High
AI33ALR_Shell_2_HighBoiler 2 high shell temperature (steam)Read0=Normal, 1=High
AI34ALR_Shell_3_HighBoiler 3 high shell temperature (steam)Read0=Normal, 1=High
AI35ALR_Shell_4_HighBoiler 4 high shell temperature (steam)Read0=Normal, 1=High
AI36BLR1_SupplyBoiler 1: supply temperature°FRead
AI37BLR1_ReturnBoiler 1: return temperature°FRead
AI38BLR1_StackBoiler 1: stack temperature°FRead
AI39BLR1_CH_Mod_RateBoiler 1: firing rate%Read
AI40BLR1_Rate_CommandedBoiler 1: firing rate feedback%Read
AI41BLR1_CH_Mod_StatBoiler 1: cH Modbus statusRead0=No Demand, 1=Demand
AImin42BLR1_General_AlarmBoiler 1: general alarmRead0=Normal, 1=Fault
AI43BLR1_Boiler_PumpBoiler 1: boiler pumpRead0=Off, 1=On
AI44BLR1_System_PumpBoiler 1: system pumpRead0=Off, 1=On
AI45BLR1_Pump_StatusBoiler 1: pump statusRead0=Off, 1=On
AI46BLR1_FlameBoiler 1: flame signalmA/VRead
AI47BLR1_StateBoiler 1: burner state code (Sola, TSBC, S7800 or hardwired table)Read
AI48BLR1_Ann_LockoutBoiler 1: lockout code (Sola, TSBC or S7800 table)Read
AI49BLR1_Ann_HoldBoiler 1: hold code (Sola only)Read
AI50ALR_BLR1SupplyHighBoiler 1: high supply water temperatureRead0=Normal, 1=Fault
AI51ALR_LeadBLR1FaultBoiler 1: lead boiler faultRead0=Normal, 1=Fault
AI52ALR_BLR1StartFaultBoiler 1: boiler start faultRead0=Normal, 1=Fault
AImin53ALR_BLR1LockoutBoiler 1: boiler lockoutRead0=Normal, 1=Fault
AI54ALR_BLR1lostBoiler 1: communication lostRead0=Normal, 1=Fault
AI55ALR_BLR1Mod_SourceBoiler 1: modulation source faultRead0=Normal, 1=Fault
AI56ALR_BLR1DMD_SourceBoiler 1: demand source faultRead0=Normal, 1=Fault
AI212BLR1_CyclesBoiler 1: count of boiler startsRead
AI220BLR1_Run_TimeBoiler 1: run timehRead
AI57BLR2_SupplyBoiler 2: supply temperature°FRead
AI58BLR2_ReturnBoiler 2: return temperature°FRead
AI59BLR2_StackBoiler 2: stack temperature°FRead
AI60BLR2_CH_Mod_RateBoiler 2: firing rate%Read
AI61BLR2_Rate_CommandedBoiler 2: firing rate feedback%Read
AI62BLR2_CH_Mod_StatBoiler 2: cH Modbus statusRead0=No Demand, 1=Demand
AI63BLR2_General_AlarmBoiler 2: general alarmRead0=Normal, 1=Fault
AI64BLR2_Boiler_PumpBoiler 2: boiler pumpRead0=Off, 1=On
AI65BLR2_System_PumpBoiler 2: system pumpRead0=Off, 1=On
AI66BLR2_Pump_StatusBoiler 2: pump statusRead0=Off, 1=On
AI67BLR2_FlameBoiler 2: flame signalmA/VRead
AI68BLR2_StateBoiler 2: burner state code (Sola, TSBC, S7800 or hardwired table)Read
AI69BLR2_Ann_LockoutBoiler 2: lockout code (Sola, TSBC or S7800 table)Read
AI70BLR2_Ann_HoldBoiler 2: hold code (Sola only)Read
AI71ALR_BLR2SupplyHighBoiler 2: high supply water temperatureRead0=Normal, 1=Fault
AI72ALR_LeadBLR2FaultBoiler 2: lead boiler faultRead0=Normal, 1=Fault
AI73ALR_BLR2StartFaultBoiler 2: boiler start faultRead0=Normal, 1=Fault
AI74ALR_BLR2LockoutBoiler 2: boiler lockoutRead0=Normal, 1=Fault
AI75ALR_BLR2lostBoiler 2: communication lostRead0=Normal, 1=Fault
AI76ALR_BLR2Mod_SourceBoiler 2: modulation source faultRead0=Normal, 1=Fault
AI77ALR_BLR2DMD_SourceBoiler 2: demand source faultRead0=Normal, 1=Fault
AI213BLR2_CyclesBoiler 2: count of boiler startsRead
AI221BLR2_Run_TimeBoiler 2: run timehRead
AI78BLR3_SupplyBoiler 3: supply temperature°FRead
AI79BLR3_ReturnBoiler 3: return temperature°FRead
AI80BLR3_StackBoiler 3: stack temperature°FRead
AI81BLR3_CH_Mod_RateBoiler 3: firing rate%Read
AI82BLR3_Rate_CommandedBoiler 3: firing rate feedback%Read
AI83BLR3_CH_Mod_StatBoiler 3: cH Modbus statusRead0=No Demand, 1=Demand
AI84BLR3_General_AlarmBoiler 3: general alarmRead0=Normal, 1=Fault
AI85BLR3_Boiler_PumpBoiler 3: boiler pumpRead0=Off, 1=On
AI86BLR3_System_PumpBoiler 3: system pumpRead0=Off, 1=On
AI87BLR3_Pump_StatusBoiler 3: pump statusRead0=Off, 1=On
AI88BLR3_FlameBoiler 3: flame signalmA/VRead
AI89BLR3_StateBoiler 3: burner state code (Sola, TSBC, S7800 or hardwired table)Read
AI90BLR3_Ann_LockoutBoiler 3: lockout code (Sola, TSBC or S7800 table)Read
AI91BLR3_Ann_HoldBoiler 3: hold code (Sola only)Read
AI92ALR_BLR3SupplyHighBoiler 3: high supply water temperatureRead0=Normal, 1=Fault
AI93ALR_LeadBLR3FaultBoiler 3: lead boiler faultRead0=Normal, 1=Fault
AI94ALR_BLR3StartFaultBoiler 3: boiler start faultRead0=Normal, 1=Fault
AI95ALR_BLR3LockoutBoiler 3: boiler lockoutRead0=Normal, 1=Fault
AI96ALR_BLR3lostBoiler 3: communication lostRead0=Normal, 1=Fault
AI97ALR_BLR3Mod_SourceBoiler 3: modulation source faultRead0=Normal, 1=Fault
AI98ALR_BLR3DMD_SourceBoiler 3: demand source faultRead0=Normal, 1=Fault
AI214BLR3_CyclesBoiler 3: count of boiler startsRead
AI222BLR3_Run_TimeBoiler 3: run timehRead
AI99BLR4_SupplyBoiler 4: supply temperature°FRead
AI100BLR4_ReturnBoiler 4: return temperature°FRead
AI101BLR4_StackBoiler 4: stack temperature°FRead
AI102BLR4_CH_Mod_RateBoiler 4: firing rate%Read
AI103BLR4_Rate_CommandedBoiler 4: firing rate feedback%Read
AI104BLR4_CH_Mod_StatBoiler 4: cH Modbus statusRead0=No Demand, 1=Demand
AI105BLR4_General_AlarmBoiler 4: general alarmRead0=Normal, 1=Fault
AI106BLR4_Boiler_PumpBoiler 4: boiler pumpRead0=Off, 1=On
AI107BLR4_System_PumpBoiler 4: system pumpRead0=Off, 1=On
AI108BLR4_Pump_StatusBoiler 4: pump statusRead0=Off, 1=On
AI109BLR4_FlameBoiler 4: flame signalmA/VRead
AI110BLR4_StateBoiler 4: burner state code (Sola, TSBC, S7800 or hardwired table)Read
AI111BLR4_Ann_LockoutBoiler 4: lockout code (Sola, TSBC or S7800 table)Read
AI112BLR4_Ann_HoldBoiler 4: hold code (Sola only)Read
AI113ALR_BLR4SupplyHighBoiler 4: high supply water temperatureRead0=Normal, 1=Fault
AI114ALR_LeadBLR4FaultBoiler 4: lead boiler faultRead0=Normal, 1=Fault
AI115ALR_BLR4StartFaultBoiler 4: boiler start faultRead0=Normal, 1=Fault
AI116ALR_BLR4LockoutBoiler 4: boiler lockoutRead0=Normal, 1=Fault
AI117ALR_BLR4lostBoiler 4: communication lostRead0=Normal, 1=Fault
AI118ALR_BLR4Mod_SourceBoiler 4: modulation source faultRead0=Normal, 1=Fault
AI119ALR_BLR4DMD_SourceBoiler 4: demand source faultRead0=Normal, 1=Fault
AI215BLR4_CyclesBoiler 4: count of boiler startsRead
AI223BLR4_Run_TimeBoiler 4: run timehRead
AI120BLR5_SupplyBoiler 5: supply temperature°FRead
AI121BLR5_ReturnBoiler 5: return temperature°FRead
AI122BLR5_StackBoiler 5: stack temperature°FRead
AI123BLR5_CH_Mod_RateBoiler 5: firing rate%Read
AI124BLR5_Rate_CommandedBoiler 5: firing rate feedback%Read
AI125BLR5_CH_Mod_StatBoiler 5: cH Modbus statusRead0=No Demand, 1=Demand
AI126BLR5_General_AlarmBoiler 5: general alarmRead0=Normal, 1=Fault
AI127BLR5_Boiler_PumpBoiler 5: boiler pumpRead0=Off, 1=On
AI128BLR5_System_PumpBoiler 5: system pumpRead0=Off, 1=On
AI129BLR5_Pump_StatusBoiler 5: pump statusRead0=Off, 1=On
AI130BLR5_FlameBoiler 5: flame signalmA/VRead
AI131BLR5_StateBoiler 5: burner state code (Sola, TSBC, S7800 or hardwired table)Read
AI132BLR5_Ann_LockoutBoiler 5: lockout code (Sola, TSBC or S7800 table)Read
AI133BLR5_Ann_HoldBoiler 5: hold code (Sola only)Read
AI134ALR_BLR5SupplyHighBoiler 5: high supply water temperatureRead0=Normal, 1=Fault
AI135ALR_LeadBLR5FaultBoiler 5: lead boiler faultRead0=Normal, 1=Fault
AI136ALR_BLR5StartFaultBoiler 5: boiler start faultRead0=Normal, 1=Fault
AI137ALR_BLR5LockoutBoiler 5: boiler lockoutRead0=Normal, 1=Fault
AI138ALR_BLR5lostBoiler 5: communication lostRead0=Normal, 1=Fault
AI139ALR_BLR5Mod_SourceBoiler 5: modulation source faultRead0=Normal, 1=Fault
AI140ALR_BLR5DMD_SourceBoiler 5: demand source faultRead0=Normal, 1=Fault
AI216BLR5_CyclesBoiler 5: count of boiler startsRead
AI224BLR5_Run_TimeBoiler 5: run timehRead
AI141BLR6_SupplyBoiler 6: supply temperature°FRead
AI142BLR6_ReturnBoiler 6: return temperature°FRead
AI143BLR6_StackBoiler 6: stack temperature°FRead
AI144BLR6_CH_Mod_RateBoiler 6: firing rate%Read
AI145BLR6_Rate_CommandedBoiler 6: firing rate feedback%Read
AI146BLR6_CH_Mod_StatBoiler 6: cH Modbus statusRead0=No Demand, 1=Demand
AI147BLR6_General_AlarmBoiler 6: general alarmRead0=Normal, 1=Fault
AI148BLR6_Boiler_PumpBoiler 6: boiler pumpRead0=Off, 1=On
AI149BLR6_System_PumpBoiler 6: system pumpRead0=Off, 1=On
AI150BLR6_Pump_StatusBoiler 6: pump statusRead0=Off, 1=On
AI151BLR6_FlameBoiler 6: flame signalmA/VRead
AI152BLR6_StateBoiler 6: burner state code (Sola, TSBC, S7800 or hardwired table)Read
AI153BLR6_Ann_LockoutBoiler 6: lockout code (Sola, TSBC or S7800 table)Read
AI154BLR6_Ann_HoldBoiler 6: hold code (Sola only)Read
AI155ALR_BLR6SupplyHighBoiler 6: high supply water temperatureRead0=Normal, 1=Fault
AI156ALR_LeadBLR6FaultBoiler 6: lead boiler faultRead0=Normal, 1=Fault
AI157ALR_BLR6StartFaultBoiler 6: boiler start faultRead0=Normal, 1=Fault
AI158ALR_BLR6LockoutBoiler 6: boiler lockoutRead0=Normal, 1=Fault
AI159ALR_BLR6lostBoiler 6: communication lostRead0=Normal, 1=Fault
AI160ALR_BLR6Mod_SourceBoiler 6: modulation source faultRead0=Normal, 1=Fault
AI161ALR_BLR6DMD_SourceBoiler 6: demand source faultRead0=Normal, 1=Fault
AI217BLR6_CyclesBoiler 6: count of boiler startsRead
AI225BLR6_Run_TimeBoiler 6: run timehRead
AI162BLR7_SupplyBoiler 7: supply temperature°FRead
AI163BLR7_ReturnBoiler 7: return temperature°FRead
AI164BLR7_StackBoiler 7: stack temperature°FRead
AI165BLR7_CH_Mod_RateBoiler 7: firing rate%Read
AI166BLR7_Rate_CommandedBoiler 7: firing rate feedback%Read
AI167BLR7_CH_Mod_StatBoiler 7: cH Modbus statusRead0=No Demand, 1=Demand
AI168BLR7_General_AlarmBoiler 7: general alarmRead0=Normal, 1=Fault
AI169BLR7_Boiler_PumpBoiler 7: boiler pumpRead0=Off, 1=On
AI170BLR7_System_PumpBoiler 7: system pumpRead0=Off, 1=On
AI171BLR7_Pump_StatusBoiler 7: pump statusRead0=Off, 1=On
AI172BLR7_FlameBoiler 7: flame signalmA/VRead
AI173BLR7_StateBoiler 7: burner state code (Sola, TSBC, S7800 or hardwired table)Read
AI174BLR7_Ann_LockoutBoiler 7: lockout code (Sola, TSBC or S7800 table)Read
AI175BLR7_Ann_HoldBoiler 7: hold code (Sola only)Read
AI176ALR_BLR7SupplyHighBoiler 7: high supply water temperatureRead0=Normal, 1=Fault
AI177ALR_LeadBLR7FaultBoiler 7: lead boiler faultRead0=Normal, 1=Fault
AI178ALR_BLR7StartFaultBoiler 7: boiler start faultRead0=Normal, 1=Fault
AI179ALR_BLR7LockoutBoiler 7: boiler lockoutRead0=Normal, 1=Fault
AI180ALR_BLR7lostBoiler 7: communication lostRead0=Normal, 1=Fault
AI181ALR_BLR7Mod_SourceBoiler 7: modulation source faultRead0=Normal, 1=Fault
AI182ALR_BLR7DMD_SourceBoiler 7: demand source faultRead0=Normal, 1=Fault
AI218BLR7_CyclesBoiler 7: count of boiler startsRead
AI226BLR7_Run_TimeBoiler 7: run timehRead
AI183BLR8_SupplyBoiler 8: supply temperature°FRead
AI184BLR8_ReturnBoiler 8: return temperature°FRead
AI185BLR8_StackBoiler 8: stack temperature°FRead
AI186BLR8_CH_Mod_RateBoiler 8: firing rate%Read
AI187BLR8_Rate_CommandedBoiler 8: firing rate feedback%Read
AI188BLR8_CH_Mod_StatBoiler 8: cH Modbus statusRead0=No Demand, 1=Demand
AI189BLR8_General_AlarmBoiler 8: general alarmRead0=Normal, 1=Fault
AI190BLR8_Boiler_PumpBoiler 8: boiler pumpRead0=Off, 1=On
AI191BLR8_System_PumpBoiler 8: system pumpRead0=Off, 1=On
AI192BLR8_Pump_StatusBoiler 8: pump statusRead0=Off, 1=On
AI193BLR8_FlameBoiler 8: flame signalmA/VRead
AI194BLR8_StateBoiler 8: burner state code (Sola, TSBC, S7800 or hardwired table)Read
AI195BLR8_Ann_LockoutBoiler 8: lockout code (Sola, TSBC or S7800 table)Read
AI196BLR8_Ann_HoldBoiler 8: hold code (Sola only)Read
AI197ALR_BLR8SupplyHighBoiler 8: high supply water temperatureRead0=Normal, 1=Fault
AI198ALR_LeadBLR8FaultBoiler 8: lead boiler faultRead0=Normal, 1=Fault
AI199ALR_BLR8StartFaultBoiler 8: boiler start faultRead0=Normal, 1=Fault
AI200ALR_BLR8LockoutBoiler 8: boiler lockoutRead0=Normal, 1=Fault
AI201ALR_BLR8lostBoiler 8: communication lostRead0=Normal, 1=Fault
AI202ALR_BLR8Mod_SourceBoiler 8: modulation source faultRead0=Normal, 1=Fault
AI203ALR_BLR8DMD_SourceBoiler 8: demand source faultRead0=Normal, 1=Fault
AI219BLR8_CyclesBoiler 8: count of boiler startsRead
AI227BLR8_Run_TimeBoiler 8: run timehRead
Object ID lookup: Thermal Solutions Conductor EMS boiler sequencer point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Conductor EMS boiler sequencer (ProtoAir FPA-W44) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44)

How many BACnet points does the Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) have?

This list has 222 BACnet objects: 220 analog inputs, 1 analog value, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) BACnet points are writable?

2 of the 222 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) BACnet documentation?

The source is Operating Manual, ProtoAir FPA-W44 for Interfacing Bryan Steam & Thermal Solutions Products (106417-02 Rev 13), revision 2022-10, published free by Thermal Solutions at https://www.thermalsolutions.com/wp-content/uploads/2024/06/106417-02-Rev-13-Thermal-Solutions-and-Bryan-ProtoAir-Manual-2022-10-Rev-13.pdf.

What are the minimum BACnet points to integrate the Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44)?

Start with BV 0 EMS_Enable (Enable master sequencer); AV 0 EMS_Setpoint (Sequencer setpoint, 60-230 °F); AI 2 Active_Setpoint (Setpoint in use, °F); AI 3 Status (Sequencer status code); AI 1 Firing_Rate (Plant firing rate, %); AI 7 SYSTEM_SUPPLY (System supply temperature, °F); AI 8 SYSTEM_RETURN (System return temperature, °F); AI 42 BLR1_General_Alarm (Boiler 1 general alarm (1 = fault)); AI 53 ALR_BLR1Lockout (Boiler 1 lockout (1 = fault)).

How do I enable BMS control of the Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44)?

BV 0 EMS_Enable turns the master sequencer on; jumper 1 on PCB-10 must be cut first.

How do I check these points on the real Conductor EMS boiler sequencer (ProtoAir FPA-W44)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Thermal Solutions BACnet points lists

Source: Operating Manual, ProtoAir FPA-W44 for Interfacing Bryan Steam & Thermal Solutions Products · 106417-02 Rev 13 · rev. 2022-10. Object names, instances and units are reproduced as published; descriptions are our own.