- Conductor EMS boiler sequencer (ProtoAir FPA-W44)
Boiler plant sequencer · BACnet points list
Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) BACnet points list
Updated 12 November 2026
Conductor EMS is the master boiler sequencer for Thermal Solutions and Bryan Steam plants. Through the ProtoAir FPA-W44 gateway it reports plant load, sequencer status and setpoint, system supply/return/outdoor temperatures, steam pressure, discrete outputs and system alarms, plus a block of 23 points for each of up to eight boilers. The BMS can enable the sequencer (BV 0) and write its setpoint (AV 0); everything else is read-only Analog Inputs, including on/off states and alarm flags.
This page lists 222 BACnet objects for the Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Thermal Solutions’s own free documentation, linked below.
- Manufacturer
- Thermal Solutions
- Model
- Conductor EMS boiler sequencer (ProtoAir FPA-W44)
- Equipment
- Boiler plant sequencer
- Equipment type
- Boilers & water heaters
- BACnet objects
- 222 (2 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- Conductor, Conductor EMS, Bryan Steam Conductor, ProtoAir FPA-W44, 106417-02, Thermal Solutions master sequencer
Reference only, provided as-is: verify against Thermal Solutions’s current documentation and the live device before use. Not official Thermal Solutions information. Terms of use.
BMS integration notes: Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44)
Cut jumper 1 on PCB-10 so BV 0 can enable the sequencer, then enable it and write the plant setpoint to AV 0. Read the active setpoint, firing rate, system temperatures, sequencer status and the per-boiler alarm flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 0 | EMS_Enable | Enable master sequencer | Write |
| AV 0 | EMS_Setpoint | Sequencer setpoint, 60-230 °F | Write |
| AI 2 | Active_Setpoint | Setpoint in use, °F | Read |
| AI 3 | Status | Sequencer status code | Read |
| AI 1 | Firing_Rate | Plant firing rate, % | Read |
| AI 7 | SYSTEM_SUPPLY | System supply temperature, °F | Read |
| AI 8 | SYSTEM_RETURN | System return temperature, °F | Read |
| AI 42 | BLR1_General_Alarm | Boiler 1 general alarm (1 = fault) | Read |
| AI 53 | ALR_BLR1Lockout | Boiler 1 lockout (1 = fault) | Read |
Enable & remote start
BV 0 EMS_Enable turns the master sequencer on; jumper 1 on PCB-10 must be cut first.
Network setup
- The ProtoAir FPA-W44 gateway is set up through its web configurator; see the general sections of the same manual.
Watch out for
- Alarm and on/off points are Analog Inputs (0/1), not Binary objects.
- Repeat the boiler alarm mapping for each installed boiler (blocks of 21 from AI 36).
Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | Plant_load | Load monitoring status | kBTU/h | Read | |
| BVmin | 0 | EMS_Enable | Enable the master sequencer (cut jumper 1 on PCB-10) | Write | 0=Disable, 1=Enable | |
| AVmin | 0 | EMS_Setpoint | Sequencer setpoint, 60-230 °F or pressure range | °F | Write | |
| AImin | 1 | Firing_Rate | Master sequencer modulation rate | % | Read | |
| AImin | 2 | Active_Setpoint | Setpoint in use | °F | Read | |
| AI | 4 | Master_SP_Source | Master setpoint source | Read | 0=Normal, 1=Remote, 2=DHW, 3=Reset, 4=Reset/Setback, 5=Setback | |
| AImin | 3 | Status | Sequencer status | Read | 0=Standby, 1=Start Lead, 2=Start 1st Lag, 3=Start 2nd Lag, 4=Start 3rd Lag, 5=Start 4th Lag, 6=Start 5th Lag, 7=Start 6th Lag, 8=Start 7th Lag | |
| AI | 5 | Priority | Sequencer priority | Read | 0=Disabled, 1=Sequence Off, 2=WWSD Both, 3=WWSD Boiler, 4=Non-Condensing, 5=Condensing | |
| AI | 6 | Lead | Number of lead boiler | Read | ||
| AImin | 7 | SYSTEM_SUPPLY | System supply temperature | °F | Read | |
| AImin | 8 | SYSTEM_RETURN | System return temperature | °F | Read | |
| AI | 9 | OUTDOOR_AIR | Outdoor air temperature | °F | Read | |
| AI | 10 | UAI5_EMS_SETPOINT | EMS setpoint input | °F | Read | |
| AI | 11 | UAI7_PUMP_FEEDBACK | Pump feedback input | % | Read | |
| AI | 12 | STEAM_PRESSURE | Steam pressure | psi | Read | |
| AI | 13 | BLR_A_SHELL | Boiler A shell temperature | °F | Read | |
| AI | 14 | BLR_B_SHELL | Boiler B shell temperature | °F | Read | |
| AI | 15 | BLR_C_SHELL | Boiler C shell temperature | °F | Read | |
| AI | 16 | BLR_D_SHELL | Boiler D shell temperature | °F | Read | |
| AI | 17 | UDO1_CONFIGURABLE | Discrete output configurable | Read | 0=Off, 1=On | |
| AI | 18 | UDO2_ALARM | Discrete output alarm | Read | 0=Off, 1=On | |
| AI | 19 | UDO7_BLR_D_ISOLATION_VALVE | Discrete output blr d isolation valve | Read | 0=Off, 1=On | |
| AI | 20 | UDO8_PUMP_A | Discrete output pump a | Read | 0=Off, 1=On | |
| AI | 21 | UDO9_BLR_A_ISOLATION_VALVE | Discrete output blr a isolation valve | Read | 0=Off, 1=On | |
| AI | 22 | UDO10_BLR_B_ISOLATION_VALVE | Discrete output blr b isolation valve | Read | 0=Off, 1=On | |
| AI | 23 | UDO11_BLR_C_ISOLATION_VALVE | Discrete output blr c isolation valve | Read | 0=Off, 1=On | |
| AI | 24 | UDO12_PUMP_B | Discrete output pump b | Read | 0=Off, 1=On | |
| AI | 25 | ALR_Press_High | High steam pressure | Read | 0=Normal, 1=High | |
| AI | 26 | ALR_Press_Low | Low steam pressure | Read | 0=Normal, 1=Low | |
| AI | 27 | ALR_Temp_High | High supply water temperature | Read | 0=Normal, 1=High | |
| AI | 28 | ALR_Temp_Low | Low supply water temperature | Read | 0=Normal, 1=Low | |
| AI | 29 | ALR_Return_Temp_Low | Low return water temperature | Read | 0=Normal, 1=Low | |
| AI | 30 | ALR_Pump_A_Fault | System pump A fault | Read | 0=Normal, 1=Fault | |
| AI | 31 | ALR_Pump_B_Fault | System pump B fault | Read | 0=Normal, 1=Fault | |
| AI | 32 | ALR_Shell_1_High | Boiler 1 high shell temperature (steam) | Read | 0=Normal, 1=High | |
| AI | 33 | ALR_Shell_2_High | Boiler 2 high shell temperature (steam) | Read | 0=Normal, 1=High | |
| AI | 34 | ALR_Shell_3_High | Boiler 3 high shell temperature (steam) | Read | 0=Normal, 1=High | |
| AI | 35 | ALR_Shell_4_High | Boiler 4 high shell temperature (steam) | Read | 0=Normal, 1=High | |
| AI | 36 | BLR1_Supply | Boiler 1: supply temperature | °F | Read | |
| AI | 37 | BLR1_Return | Boiler 1: return temperature | °F | Read | |
| AI | 38 | BLR1_Stack | Boiler 1: stack temperature | °F | Read | |
| AI | 39 | BLR1_CH_Mod_Rate | Boiler 1: firing rate | % | Read | |
| AI | 40 | BLR1_Rate_Commanded | Boiler 1: firing rate feedback | % | Read | |
| AI | 41 | BLR1_CH_Mod_Stat | Boiler 1: cH Modbus status | Read | 0=No Demand, 1=Demand | |
| AImin | 42 | BLR1_General_Alarm | Boiler 1: general alarm | Read | 0=Normal, 1=Fault | |
| AI | 43 | BLR1_Boiler_Pump | Boiler 1: boiler pump | Read | 0=Off, 1=On | |
| AI | 44 | BLR1_System_Pump | Boiler 1: system pump | Read | 0=Off, 1=On | |
| AI | 45 | BLR1_Pump_Status | Boiler 1: pump status | Read | 0=Off, 1=On | |
| AI | 46 | BLR1_Flame | Boiler 1: flame signal | mA/V | Read | |
| AI | 47 | BLR1_State | Boiler 1: burner state code (Sola, TSBC, S7800 or hardwired table) | Read | ||
| AI | 48 | BLR1_Ann_Lockout | Boiler 1: lockout code (Sola, TSBC or S7800 table) | Read | ||
| AI | 49 | BLR1_Ann_Hold | Boiler 1: hold code (Sola only) | Read | ||
| AI | 50 | ALR_BLR1SupplyHigh | Boiler 1: high supply water temperature | Read | 0=Normal, 1=Fault | |
| AI | 51 | ALR_LeadBLR1Fault | Boiler 1: lead boiler fault | Read | 0=Normal, 1=Fault | |
| AI | 52 | ALR_BLR1StartFault | Boiler 1: boiler start fault | Read | 0=Normal, 1=Fault | |
| AImin | 53 | ALR_BLR1Lockout | Boiler 1: boiler lockout | Read | 0=Normal, 1=Fault | |
| AI | 54 | ALR_BLR1lost | Boiler 1: communication lost | Read | 0=Normal, 1=Fault | |
| AI | 55 | ALR_BLR1Mod_Source | Boiler 1: modulation source fault | Read | 0=Normal, 1=Fault | |
| AI | 56 | ALR_BLR1DMD_Source | Boiler 1: demand source fault | Read | 0=Normal, 1=Fault | |
| AI | 212 | BLR1_Cycles | Boiler 1: count of boiler starts | Read | ||
| AI | 220 | BLR1_Run_Time | Boiler 1: run time | h | Read | |
| AI | 57 | BLR2_Supply | Boiler 2: supply temperature | °F | Read | |
| AI | 58 | BLR2_Return | Boiler 2: return temperature | °F | Read | |
| AI | 59 | BLR2_Stack | Boiler 2: stack temperature | °F | Read | |
| AI | 60 | BLR2_CH_Mod_Rate | Boiler 2: firing rate | % | Read | |
| AI | 61 | BLR2_Rate_Commanded | Boiler 2: firing rate feedback | % | Read | |
| AI | 62 | BLR2_CH_Mod_Stat | Boiler 2: cH Modbus status | Read | 0=No Demand, 1=Demand | |
| AI | 63 | BLR2_General_Alarm | Boiler 2: general alarm | Read | 0=Normal, 1=Fault | |
| AI | 64 | BLR2_Boiler_Pump | Boiler 2: boiler pump | Read | 0=Off, 1=On | |
| AI | 65 | BLR2_System_Pump | Boiler 2: system pump | Read | 0=Off, 1=On | |
| AI | 66 | BLR2_Pump_Status | Boiler 2: pump status | Read | 0=Off, 1=On | |
| AI | 67 | BLR2_Flame | Boiler 2: flame signal | mA/V | Read | |
| AI | 68 | BLR2_State | Boiler 2: burner state code (Sola, TSBC, S7800 or hardwired table) | Read | ||
| AI | 69 | BLR2_Ann_Lockout | Boiler 2: lockout code (Sola, TSBC or S7800 table) | Read | ||
| AI | 70 | BLR2_Ann_Hold | Boiler 2: hold code (Sola only) | Read | ||
| AI | 71 | ALR_BLR2SupplyHigh | Boiler 2: high supply water temperature | Read | 0=Normal, 1=Fault | |
| AI | 72 | ALR_LeadBLR2Fault | Boiler 2: lead boiler fault | Read | 0=Normal, 1=Fault | |
| AI | 73 | ALR_BLR2StartFault | Boiler 2: boiler start fault | Read | 0=Normal, 1=Fault | |
| AI | 74 | ALR_BLR2Lockout | Boiler 2: boiler lockout | Read | 0=Normal, 1=Fault | |
| AI | 75 | ALR_BLR2lost | Boiler 2: communication lost | Read | 0=Normal, 1=Fault | |
| AI | 76 | ALR_BLR2Mod_Source | Boiler 2: modulation source fault | Read | 0=Normal, 1=Fault | |
| AI | 77 | ALR_BLR2DMD_Source | Boiler 2: demand source fault | Read | 0=Normal, 1=Fault | |
| AI | 213 | BLR2_Cycles | Boiler 2: count of boiler starts | Read | ||
| AI | 221 | BLR2_Run_Time | Boiler 2: run time | h | Read | |
| AI | 78 | BLR3_Supply | Boiler 3: supply temperature | °F | Read | |
| AI | 79 | BLR3_Return | Boiler 3: return temperature | °F | Read | |
| AI | 80 | BLR3_Stack | Boiler 3: stack temperature | °F | Read | |
| AI | 81 | BLR3_CH_Mod_Rate | Boiler 3: firing rate | % | Read | |
| AI | 82 | BLR3_Rate_Commanded | Boiler 3: firing rate feedback | % | Read | |
| AI | 83 | BLR3_CH_Mod_Stat | Boiler 3: cH Modbus status | Read | 0=No Demand, 1=Demand | |
| AI | 84 | BLR3_General_Alarm | Boiler 3: general alarm | Read | 0=Normal, 1=Fault | |
| AI | 85 | BLR3_Boiler_Pump | Boiler 3: boiler pump | Read | 0=Off, 1=On | |
| AI | 86 | BLR3_System_Pump | Boiler 3: system pump | Read | 0=Off, 1=On | |
| AI | 87 | BLR3_Pump_Status | Boiler 3: pump status | Read | 0=Off, 1=On | |
| AI | 88 | BLR3_Flame | Boiler 3: flame signal | mA/V | Read | |
| AI | 89 | BLR3_State | Boiler 3: burner state code (Sola, TSBC, S7800 or hardwired table) | Read | ||
| AI | 90 | BLR3_Ann_Lockout | Boiler 3: lockout code (Sola, TSBC or S7800 table) | Read | ||
| AI | 91 | BLR3_Ann_Hold | Boiler 3: hold code (Sola only) | Read | ||
| AI | 92 | ALR_BLR3SupplyHigh | Boiler 3: high supply water temperature | Read | 0=Normal, 1=Fault | |
| AI | 93 | ALR_LeadBLR3Fault | Boiler 3: lead boiler fault | Read | 0=Normal, 1=Fault | |
| AI | 94 | ALR_BLR3StartFault | Boiler 3: boiler start fault | Read | 0=Normal, 1=Fault | |
| AI | 95 | ALR_BLR3Lockout | Boiler 3: boiler lockout | Read | 0=Normal, 1=Fault | |
| AI | 96 | ALR_BLR3lost | Boiler 3: communication lost | Read | 0=Normal, 1=Fault | |
| AI | 97 | ALR_BLR3Mod_Source | Boiler 3: modulation source fault | Read | 0=Normal, 1=Fault | |
| AI | 98 | ALR_BLR3DMD_Source | Boiler 3: demand source fault | Read | 0=Normal, 1=Fault | |
| AI | 214 | BLR3_Cycles | Boiler 3: count of boiler starts | Read | ||
| AI | 222 | BLR3_Run_Time | Boiler 3: run time | h | Read | |
| AI | 99 | BLR4_Supply | Boiler 4: supply temperature | °F | Read | |
| AI | 100 | BLR4_Return | Boiler 4: return temperature | °F | Read | |
| AI | 101 | BLR4_Stack | Boiler 4: stack temperature | °F | Read | |
| AI | 102 | BLR4_CH_Mod_Rate | Boiler 4: firing rate | % | Read | |
| AI | 103 | BLR4_Rate_Commanded | Boiler 4: firing rate feedback | % | Read | |
| AI | 104 | BLR4_CH_Mod_Stat | Boiler 4: cH Modbus status | Read | 0=No Demand, 1=Demand | |
| AI | 105 | BLR4_General_Alarm | Boiler 4: general alarm | Read | 0=Normal, 1=Fault | |
| AI | 106 | BLR4_Boiler_Pump | Boiler 4: boiler pump | Read | 0=Off, 1=On | |
| AI | 107 | BLR4_System_Pump | Boiler 4: system pump | Read | 0=Off, 1=On | |
| AI | 108 | BLR4_Pump_Status | Boiler 4: pump status | Read | 0=Off, 1=On | |
| AI | 109 | BLR4_Flame | Boiler 4: flame signal | mA/V | Read | |
| AI | 110 | BLR4_State | Boiler 4: burner state code (Sola, TSBC, S7800 or hardwired table) | Read | ||
| AI | 111 | BLR4_Ann_Lockout | Boiler 4: lockout code (Sola, TSBC or S7800 table) | Read | ||
| AI | 112 | BLR4_Ann_Hold | Boiler 4: hold code (Sola only) | Read | ||
| AI | 113 | ALR_BLR4SupplyHigh | Boiler 4: high supply water temperature | Read | 0=Normal, 1=Fault | |
| AI | 114 | ALR_LeadBLR4Fault | Boiler 4: lead boiler fault | Read | 0=Normal, 1=Fault | |
| AI | 115 | ALR_BLR4StartFault | Boiler 4: boiler start fault | Read | 0=Normal, 1=Fault | |
| AI | 116 | ALR_BLR4Lockout | Boiler 4: boiler lockout | Read | 0=Normal, 1=Fault | |
| AI | 117 | ALR_BLR4lost | Boiler 4: communication lost | Read | 0=Normal, 1=Fault | |
| AI | 118 | ALR_BLR4Mod_Source | Boiler 4: modulation source fault | Read | 0=Normal, 1=Fault | |
| AI | 119 | ALR_BLR4DMD_Source | Boiler 4: demand source fault | Read | 0=Normal, 1=Fault | |
| AI | 215 | BLR4_Cycles | Boiler 4: count of boiler starts | Read | ||
| AI | 223 | BLR4_Run_Time | Boiler 4: run time | h | Read | |
| AI | 120 | BLR5_Supply | Boiler 5: supply temperature | °F | Read | |
| AI | 121 | BLR5_Return | Boiler 5: return temperature | °F | Read | |
| AI | 122 | BLR5_Stack | Boiler 5: stack temperature | °F | Read | |
| AI | 123 | BLR5_CH_Mod_Rate | Boiler 5: firing rate | % | Read | |
| AI | 124 | BLR5_Rate_Commanded | Boiler 5: firing rate feedback | % | Read | |
| AI | 125 | BLR5_CH_Mod_Stat | Boiler 5: cH Modbus status | Read | 0=No Demand, 1=Demand | |
| AI | 126 | BLR5_General_Alarm | Boiler 5: general alarm | Read | 0=Normal, 1=Fault | |
| AI | 127 | BLR5_Boiler_Pump | Boiler 5: boiler pump | Read | 0=Off, 1=On | |
| AI | 128 | BLR5_System_Pump | Boiler 5: system pump | Read | 0=Off, 1=On | |
| AI | 129 | BLR5_Pump_Status | Boiler 5: pump status | Read | 0=Off, 1=On | |
| AI | 130 | BLR5_Flame | Boiler 5: flame signal | mA/V | Read | |
| AI | 131 | BLR5_State | Boiler 5: burner state code (Sola, TSBC, S7800 or hardwired table) | Read | ||
| AI | 132 | BLR5_Ann_Lockout | Boiler 5: lockout code (Sola, TSBC or S7800 table) | Read | ||
| AI | 133 | BLR5_Ann_Hold | Boiler 5: hold code (Sola only) | Read | ||
| AI | 134 | ALR_BLR5SupplyHigh | Boiler 5: high supply water temperature | Read | 0=Normal, 1=Fault | |
| AI | 135 | ALR_LeadBLR5Fault | Boiler 5: lead boiler fault | Read | 0=Normal, 1=Fault | |
| AI | 136 | ALR_BLR5StartFault | Boiler 5: boiler start fault | Read | 0=Normal, 1=Fault | |
| AI | 137 | ALR_BLR5Lockout | Boiler 5: boiler lockout | Read | 0=Normal, 1=Fault | |
| AI | 138 | ALR_BLR5lost | Boiler 5: communication lost | Read | 0=Normal, 1=Fault | |
| AI | 139 | ALR_BLR5Mod_Source | Boiler 5: modulation source fault | Read | 0=Normal, 1=Fault | |
| AI | 140 | ALR_BLR5DMD_Source | Boiler 5: demand source fault | Read | 0=Normal, 1=Fault | |
| AI | 216 | BLR5_Cycles | Boiler 5: count of boiler starts | Read | ||
| AI | 224 | BLR5_Run_Time | Boiler 5: run time | h | Read | |
| AI | 141 | BLR6_Supply | Boiler 6: supply temperature | °F | Read | |
| AI | 142 | BLR6_Return | Boiler 6: return temperature | °F | Read | |
| AI | 143 | BLR6_Stack | Boiler 6: stack temperature | °F | Read | |
| AI | 144 | BLR6_CH_Mod_Rate | Boiler 6: firing rate | % | Read | |
| AI | 145 | BLR6_Rate_Commanded | Boiler 6: firing rate feedback | % | Read | |
| AI | 146 | BLR6_CH_Mod_Stat | Boiler 6: cH Modbus status | Read | 0=No Demand, 1=Demand | |
| AI | 147 | BLR6_General_Alarm | Boiler 6: general alarm | Read | 0=Normal, 1=Fault | |
| AI | 148 | BLR6_Boiler_Pump | Boiler 6: boiler pump | Read | 0=Off, 1=On | |
| AI | 149 | BLR6_System_Pump | Boiler 6: system pump | Read | 0=Off, 1=On | |
| AI | 150 | BLR6_Pump_Status | Boiler 6: pump status | Read | 0=Off, 1=On | |
| AI | 151 | BLR6_Flame | Boiler 6: flame signal | mA/V | Read | |
| AI | 152 | BLR6_State | Boiler 6: burner state code (Sola, TSBC, S7800 or hardwired table) | Read | ||
| AI | 153 | BLR6_Ann_Lockout | Boiler 6: lockout code (Sola, TSBC or S7800 table) | Read | ||
| AI | 154 | BLR6_Ann_Hold | Boiler 6: hold code (Sola only) | Read | ||
| AI | 155 | ALR_BLR6SupplyHigh | Boiler 6: high supply water temperature | Read | 0=Normal, 1=Fault | |
| AI | 156 | ALR_LeadBLR6Fault | Boiler 6: lead boiler fault | Read | 0=Normal, 1=Fault | |
| AI | 157 | ALR_BLR6StartFault | Boiler 6: boiler start fault | Read | 0=Normal, 1=Fault | |
| AI | 158 | ALR_BLR6Lockout | Boiler 6: boiler lockout | Read | 0=Normal, 1=Fault | |
| AI | 159 | ALR_BLR6lost | Boiler 6: communication lost | Read | 0=Normal, 1=Fault | |
| AI | 160 | ALR_BLR6Mod_Source | Boiler 6: modulation source fault | Read | 0=Normal, 1=Fault | |
| AI | 161 | ALR_BLR6DMD_Source | Boiler 6: demand source fault | Read | 0=Normal, 1=Fault | |
| AI | 217 | BLR6_Cycles | Boiler 6: count of boiler starts | Read | ||
| AI | 225 | BLR6_Run_Time | Boiler 6: run time | h | Read | |
| AI | 162 | BLR7_Supply | Boiler 7: supply temperature | °F | Read | |
| AI | 163 | BLR7_Return | Boiler 7: return temperature | °F | Read | |
| AI | 164 | BLR7_Stack | Boiler 7: stack temperature | °F | Read | |
| AI | 165 | BLR7_CH_Mod_Rate | Boiler 7: firing rate | % | Read | |
| AI | 166 | BLR7_Rate_Commanded | Boiler 7: firing rate feedback | % | Read | |
| AI | 167 | BLR7_CH_Mod_Stat | Boiler 7: cH Modbus status | Read | 0=No Demand, 1=Demand | |
| AI | 168 | BLR7_General_Alarm | Boiler 7: general alarm | Read | 0=Normal, 1=Fault | |
| AI | 169 | BLR7_Boiler_Pump | Boiler 7: boiler pump | Read | 0=Off, 1=On | |
| AI | 170 | BLR7_System_Pump | Boiler 7: system pump | Read | 0=Off, 1=On | |
| AI | 171 | BLR7_Pump_Status | Boiler 7: pump status | Read | 0=Off, 1=On | |
| AI | 172 | BLR7_Flame | Boiler 7: flame signal | mA/V | Read | |
| AI | 173 | BLR7_State | Boiler 7: burner state code (Sola, TSBC, S7800 or hardwired table) | Read | ||
| AI | 174 | BLR7_Ann_Lockout | Boiler 7: lockout code (Sola, TSBC or S7800 table) | Read | ||
| AI | 175 | BLR7_Ann_Hold | Boiler 7: hold code (Sola only) | Read | ||
| AI | 176 | ALR_BLR7SupplyHigh | Boiler 7: high supply water temperature | Read | 0=Normal, 1=Fault | |
| AI | 177 | ALR_LeadBLR7Fault | Boiler 7: lead boiler fault | Read | 0=Normal, 1=Fault | |
| AI | 178 | ALR_BLR7StartFault | Boiler 7: boiler start fault | Read | 0=Normal, 1=Fault | |
| AI | 179 | ALR_BLR7Lockout | Boiler 7: boiler lockout | Read | 0=Normal, 1=Fault | |
| AI | 180 | ALR_BLR7lost | Boiler 7: communication lost | Read | 0=Normal, 1=Fault | |
| AI | 181 | ALR_BLR7Mod_Source | Boiler 7: modulation source fault | Read | 0=Normal, 1=Fault | |
| AI | 182 | ALR_BLR7DMD_Source | Boiler 7: demand source fault | Read | 0=Normal, 1=Fault | |
| AI | 218 | BLR7_Cycles | Boiler 7: count of boiler starts | Read | ||
| AI | 226 | BLR7_Run_Time | Boiler 7: run time | h | Read | |
| AI | 183 | BLR8_Supply | Boiler 8: supply temperature | °F | Read | |
| AI | 184 | BLR8_Return | Boiler 8: return temperature | °F | Read | |
| AI | 185 | BLR8_Stack | Boiler 8: stack temperature | °F | Read | |
| AI | 186 | BLR8_CH_Mod_Rate | Boiler 8: firing rate | % | Read | |
| AI | 187 | BLR8_Rate_Commanded | Boiler 8: firing rate feedback | % | Read | |
| AI | 188 | BLR8_CH_Mod_Stat | Boiler 8: cH Modbus status | Read | 0=No Demand, 1=Demand | |
| AI | 189 | BLR8_General_Alarm | Boiler 8: general alarm | Read | 0=Normal, 1=Fault | |
| AI | 190 | BLR8_Boiler_Pump | Boiler 8: boiler pump | Read | 0=Off, 1=On | |
| AI | 191 | BLR8_System_Pump | Boiler 8: system pump | Read | 0=Off, 1=On | |
| AI | 192 | BLR8_Pump_Status | Boiler 8: pump status | Read | 0=Off, 1=On | |
| AI | 193 | BLR8_Flame | Boiler 8: flame signal | mA/V | Read | |
| AI | 194 | BLR8_State | Boiler 8: burner state code (Sola, TSBC, S7800 or hardwired table) | Read | ||
| AI | 195 | BLR8_Ann_Lockout | Boiler 8: lockout code (Sola, TSBC or S7800 table) | Read | ||
| AI | 196 | BLR8_Ann_Hold | Boiler 8: hold code (Sola only) | Read | ||
| AI | 197 | ALR_BLR8SupplyHigh | Boiler 8: high supply water temperature | Read | 0=Normal, 1=Fault | |
| AI | 198 | ALR_LeadBLR8Fault | Boiler 8: lead boiler fault | Read | 0=Normal, 1=Fault | |
| AI | 199 | ALR_BLR8StartFault | Boiler 8: boiler start fault | Read | 0=Normal, 1=Fault | |
| AI | 200 | ALR_BLR8Lockout | Boiler 8: boiler lockout | Read | 0=Normal, 1=Fault | |
| AI | 201 | ALR_BLR8lost | Boiler 8: communication lost | Read | 0=Normal, 1=Fault | |
| AI | 202 | ALR_BLR8Mod_Source | Boiler 8: modulation source fault | Read | 0=Normal, 1=Fault | |
| AI | 203 | ALR_BLR8DMD_Source | Boiler 8: demand source fault | Read | 0=Normal, 1=Fault | |
| AI | 219 | BLR8_Cycles | Boiler 8: count of boiler starts | Read | ||
| AI | 227 | BLR8_Run_Time | Boiler 8: run time | h | Read |
No points match these filters.
Object ID lookup: Thermal Solutions Conductor EMS boiler sequencer point IDs by name
AI0Plant_loadBV0EMS_EnableAV0EMS_SetpointAI1Firing_RateAI2Active_SetpointAI4Master_SP_SourceAI3StatusAI5PriorityAI6LeadAI7SYSTEM_SUPPLYAI8SYSTEM_RETURNAI9OUTDOOR_AIRAI10UAI5_EMS_SETPOINTAI11UAI7_PUMP_FEEDBACKAI12STEAM_PRESSUREAI13BLR_A_SHELLAI14BLR_B_SHELLAI15BLR_C_SHELLAI16BLR_D_SHELLAI17UDO1_CONFIGURABLEAI18UDO2_ALARMAI19UDO7_BLR_D_ISOLATION_VALVEAI20UDO8_PUMP_AAI21UDO9_BLR_A_ISOLATION_VALVEAI22UDO10_BLR_B_ISOLATION_VALVEAI23UDO11_BLR_C_ISOLATION_VALVEAI24UDO12_PUMP_BAI25ALR_Press_HighAI26ALR_Press_LowAI27ALR_Temp_HighAI28ALR_Temp_LowAI29ALR_Return_Temp_LowAI30ALR_Pump_A_FaultAI31ALR_Pump_B_FaultAI32ALR_Shell_1_HighAI33ALR_Shell_2_HighAI34ALR_Shell_3_HighAI35ALR_Shell_4_HighAI36BLR1_SupplyAI37BLR1_ReturnAI38BLR1_StackAI39BLR1_CH_Mod_RateAI40BLR1_Rate_CommandedAI41BLR1_CH_Mod_StatAI42BLR1_General_AlarmAI43BLR1_Boiler_PumpAI44BLR1_System_PumpAI45BLR1_Pump_StatusAI46BLR1_FlameAI47BLR1_StateAI48BLR1_Ann_LockoutAI49BLR1_Ann_HoldAI50ALR_BLR1SupplyHighAI51ALR_LeadBLR1FaultAI52ALR_BLR1StartFaultAI53ALR_BLR1LockoutAI54ALR_BLR1lostAI55ALR_BLR1Mod_SourceAI56ALR_BLR1DMD_SourceAI212BLR1_CyclesAI220BLR1_Run_TimeAI57BLR2_SupplyAI58BLR2_ReturnAI59BLR2_StackAI60BLR2_CH_Mod_RateAI61BLR2_Rate_CommandedAI62BLR2_CH_Mod_StatAI63BLR2_General_AlarmAI64BLR2_Boiler_PumpAI65BLR2_System_PumpAI66BLR2_Pump_StatusAI67BLR2_FlameAI68BLR2_StateAI69BLR2_Ann_LockoutAI70BLR2_Ann_HoldAI71ALR_BLR2SupplyHighAI72ALR_LeadBLR2FaultAI73ALR_BLR2StartFaultAI74ALR_BLR2LockoutAI75ALR_BLR2lostAI76ALR_BLR2Mod_SourceAI77ALR_BLR2DMD_SourceAI213BLR2_CyclesAI221BLR2_Run_TimeAI78BLR3_SupplyAI79BLR3_ReturnAI80BLR3_StackAI81BLR3_CH_Mod_RateAI82BLR3_Rate_CommandedAI83BLR3_CH_Mod_StatAI84BLR3_General_AlarmAI85BLR3_Boiler_PumpAI86BLR3_System_PumpAI87BLR3_Pump_StatusAI88BLR3_FlameAI89BLR3_StateAI90BLR3_Ann_LockoutAI91BLR3_Ann_HoldAI92ALR_BLR3SupplyHighAI93ALR_LeadBLR3FaultAI94ALR_BLR3StartFaultAI95ALR_BLR3LockoutAI96ALR_BLR3lostAI97ALR_BLR3Mod_SourceAI98ALR_BLR3DMD_SourceAI214BLR3_CyclesAI222BLR3_Run_TimeAI99BLR4_SupplyAI100BLR4_ReturnAI101BLR4_StackAI102BLR4_CH_Mod_RateAI103BLR4_Rate_CommandedAI104BLR4_CH_Mod_StatAI105BLR4_General_AlarmAI106BLR4_Boiler_PumpAI107BLR4_System_PumpAI108BLR4_Pump_StatusAI109BLR4_FlameAI110BLR4_StateAI111BLR4_Ann_LockoutAI112BLR4_Ann_HoldAI113ALR_BLR4SupplyHighAI114ALR_LeadBLR4FaultAI115ALR_BLR4StartFaultAI116ALR_BLR4LockoutAI117ALR_BLR4lostAI118ALR_BLR4Mod_SourceAI119ALR_BLR4DMD_SourceAI215BLR4_CyclesAI223BLR4_Run_TimeAI120BLR5_SupplyAI121BLR5_ReturnAI122BLR5_StackAI123BLR5_CH_Mod_RateAI124BLR5_Rate_CommandedAI125BLR5_CH_Mod_StatAI126BLR5_General_AlarmAI127BLR5_Boiler_PumpAI128BLR5_System_PumpAI129BLR5_Pump_StatusAI130BLR5_FlameAI131BLR5_StateAI132BLR5_Ann_LockoutAI133BLR5_Ann_HoldAI134ALR_BLR5SupplyHighAI135ALR_LeadBLR5FaultAI136ALR_BLR5StartFaultAI137ALR_BLR5LockoutAI138ALR_BLR5lostAI139ALR_BLR5Mod_SourceAI140ALR_BLR5DMD_SourceAI216BLR5_CyclesAI224BLR5_Run_TimeAI141BLR6_SupplyAI142BLR6_ReturnAI143BLR6_StackAI144BLR6_CH_Mod_RateAI145BLR6_Rate_CommandedAI146BLR6_CH_Mod_StatAI147BLR6_General_AlarmAI148BLR6_Boiler_PumpAI149BLR6_System_PumpAI150BLR6_Pump_StatusAI151BLR6_FlameAI152BLR6_StateAI153BLR6_Ann_LockoutAI154BLR6_Ann_HoldAI155ALR_BLR6SupplyHighAI156ALR_LeadBLR6FaultAI157ALR_BLR6StartFaultAI158ALR_BLR6LockoutAI159ALR_BLR6lostAI160ALR_BLR6Mod_SourceAI161ALR_BLR6DMD_SourceAI217BLR6_CyclesAI225BLR6_Run_TimeAI162BLR7_SupplyAI163BLR7_ReturnAI164BLR7_StackAI165BLR7_CH_Mod_RateAI166BLR7_Rate_CommandedAI167BLR7_CH_Mod_StatAI168BLR7_General_AlarmAI169BLR7_Boiler_PumpAI170BLR7_System_PumpAI171BLR7_Pump_StatusAI172BLR7_FlameAI173BLR7_StateAI174BLR7_Ann_LockoutAI175BLR7_Ann_HoldAI176ALR_BLR7SupplyHighAI177ALR_LeadBLR7FaultAI178ALR_BLR7StartFaultAI179ALR_BLR7LockoutAI180ALR_BLR7lostAI181ALR_BLR7Mod_SourceAI182ALR_BLR7DMD_SourceAI218BLR7_CyclesAI226BLR7_Run_TimeAI183BLR8_SupplyAI184BLR8_ReturnAI185BLR8_StackAI186BLR8_CH_Mod_RateAI187BLR8_Rate_CommandedAI188BLR8_CH_Mod_StatAI189BLR8_General_AlarmAI190BLR8_Boiler_PumpAI191BLR8_System_PumpAI192BLR8_Pump_StatusAI193BLR8_FlameAI194BLR8_StateAI195BLR8_Ann_LockoutAI196BLR8_Ann_HoldAI197ALR_BLR8SupplyHighAI198ALR_LeadBLR8FaultAI199ALR_BLR8StartFaultAI200ALR_BLR8LockoutAI201ALR_BLR8lostAI202ALR_BLR8Mod_SourceAI203ALR_BLR8DMD_SourceAI219BLR8_CyclesAI227BLR8_Run_Time
Integration notes
- Object names, types, instances and access are from section 12.11; on/off states and alarm flags are Analog Inputs reading 0 or 1.
- Boiler state, lockout and hold codes (AI 47-49 and the matching objects for boilers 2-8) use the code tables printed for Sola, TSBC, S7800 and hardwired boilers; the tables are not repeated here.
- Boiler 2-8 rows in the manual have no descriptions; they follow the boiler 1 block.
- Boiler cycle counters are AI 212-219 and run times AI 220-227.
- The same manual covers other Thermal Solutions/Bryan controls that are separate lists in this library.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Conductor EMS boiler sequencer (ProtoAir FPA-W44) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44)
How many BACnet points does the Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) have?
This list has 222 BACnet objects: 220 analog inputs, 1 analog value, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) BACnet points are writable?
2 of the 222 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44) BACnet documentation?
The source is Operating Manual, ProtoAir FPA-W44 for Interfacing Bryan Steam & Thermal Solutions Products (106417-02 Rev 13), revision 2022-10, published free by Thermal Solutions at https://www.thermalsolutions.com/wp-content/uploads/2024/06/106417-02-Rev-13-Thermal-Solutions-and-Bryan-ProtoAir-Manual-2022-10-Rev-13.pdf.
What are the minimum BACnet points to integrate the Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44)?
Start with BV 0 EMS_Enable (Enable master sequencer); AV 0 EMS_Setpoint (Sequencer setpoint, 60-230 °F); AI 2 Active_Setpoint (Setpoint in use, °F); AI 3 Status (Sequencer status code); AI 1 Firing_Rate (Plant firing rate, %); AI 7 SYSTEM_SUPPLY (System supply temperature, °F); AI 8 SYSTEM_RETURN (System return temperature, °F); AI 42 BLR1_General_Alarm (Boiler 1 general alarm (1 = fault)); AI 53 ALR_BLR1Lockout (Boiler 1 lockout (1 = fault)).
How do I enable BMS control of the Thermal Solutions Conductor EMS boiler sequencer (ProtoAir FPA-W44)?
BV 0 EMS_Enable turns the master sequencer on; jumper 1 on PCB-10 must be cut first.
How do I check these points on the real Conductor EMS boiler sequencer (ProtoAir FPA-W44)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Thermal Solutions BACnet points lists
- Boiler control (ALTA / Phantom II) via ProtoAir gateway
Thermal Solutions ALTA / Phantom II boiler control (Universal Gateway ProtoAir)
U.S. Boiler ALTA and ALTAC and Velocity Boiler Works Phantom II and Phantom Combi II boilers, connected to the Universal Gateway (ProtoAir FPA-W44) on the control's Modbus 2 port.
Also known as: ALTA, ALTAC, U.S. Boiler ALTA, Phantom II, Phantom Combi II, Velocity Boiler Works Phantom II, ProtoAir FPA-W44, Universal Gateway 106417-04 - Boiler controller via ProtoNode gateway
Thermal Solutions Apex / Arctic with Concert or Panasonic 4716 software (Universal Gateway)
Thermal Solutions Apex and Arctic boilers with the Concert control and display, and Apex boilers with the Panasonic display running 4716 software, through the Universal Gateway.
Also known as: Concert, Concert control, Apex 4716, Arctic, Arctic 1000, Arctic 1500, Universal Gateway, 106417-01, ProtoNode RER, FPC-N34-0816 - Boiler controller via ProtoNode gateway
Thermal Solutions Apex with Panasonic display, 4109 software (Universal Gateway)
Thermal Solutions Apex boilers with the control and Panasonic GT02 display running 4109 software, connected through the Universal Gateway.
Also known as: Apex, Apex 4109, Panasonic GT02, Universal Gateway, 106417-01, ProtoNode RER, FPC-N34-0816 - Boiler flame safeguard (RM7800) via ProtoNode gateway
Thermal Solutions EVA / EVO boiler - RM7800 flame safeguard (ProtoNode)
Thermal Solutions EVA, EVAW, EVO and EVOW boilers with an RM7800 series burner control, connected through a ProtoNode FPC-N34.
Also known as: RM7800, Honeywell RM7800, 7800 Series, EVA, EVAW, EVO, EVOW, FPC-N34-0643, ProtoNode FPC-N34 - Boiler operating controller (RWF40) via ProtoNode gateway
Thermal Solutions EVA / EVO boiler - RWF40 controller (ProtoNode)
Thermal Solutions EVA, EVAW, EVO and EVOW boilers whose operating control is an RWF40, connected through a ProtoNode FPC-N34.
Also known as: RWF40, Siemens RWF40, EVA, EVAW, EVO, EVOW, FPC-N34-0643, ProtoNode FPC-N34 - Boiler operating controller (RWF55) via ProtoNode gateway
Thermal Solutions EVA / EVO boiler - RWF55 controller (ProtoNode)
Thermal Solutions EVA, EVAW, EVO and EVOW boilers whose operating control is an RWF55, connected through a ProtoNode FPC-N34.
Also known as: RWF55, Siemens RWF55, EVA, EVAW, EVO, EVOW, FPC-N34-0643, ProtoNode FPC-N34 - Boiler flame safeguard (Fireye YB110) via ProtoAir gateway
Thermal Solutions Fireye YB110 flame safeguard (Universal Gateway ProtoAir)
Thermal Solutions and Bryan boilers with a Fireye YB110 flame safeguard, connected to the Universal Gateway (ProtoAir FPA-W44).
Also known as: YB110, Fireye YB110, BurnerPRO, Fireye, ProtoAir FPA-W44, Universal Gateway 106417-04 - Process meter (boiler plant signal) via ProtoAir gateway
Thermal Solutions Precision Digital Trident PD765 meter (Universal Gateway ProtoAir)
A Precision Digital Trident PD765 process meter used in Thermal Solutions and Bryan boiler control systems, connected to the Universal Gateway (ProtoAir FPA-W44).
Also known as: PD765, Trident PD765, Precision Digital PD765, ProtoAir FPA-W44, Universal Gateway 106417-04 - Boiler burner management system (LMV2x/3x) via ProtoAir gateway
Thermal Solutions Siemens LMV2 / LMV3 burner management (Universal Gateway ProtoAir)
Thermal Solutions and Bryan boilers fired by a Siemens LMV2x or LMV3x burner management system, connected to the Universal Gateway (ProtoAir FPA-W44).
Also known as: LMV2_3, LMV2, LMV3, LMV26, LMV37, Siemens LMV2x/3x, ProtoAir FPA-W44, Universal Gateway 106417-04 - Boiler burner management system (LMV36) via ProtoAir gateway
Thermal Solutions Siemens LMV36 burner management (Universal Gateway ProtoAir)
Thermal Solutions and Bryan boilers fired by a Siemens LMV36 burner management system, connected to the Universal Gateway (ProtoAir FPA-W44).
Also known as: LMV36, Siemens LMV36, LMV3, ProtoAir FPA-W44, Universal Gateway 106417-04 - Boiler burner management system (LMV52) via ProtoAir gateway
Thermal Solutions Siemens LMV52 burner management (Universal Gateway ProtoAir)
Thermal Solutions and Bryan boilers fired by a Siemens LMV52 burner management system, connected to the Universal Gateway (ProtoAir FPA-W44).
Also known as: LMV52, Siemens LMV52, LMV5, ProtoAir FPA-W44, Universal Gateway 106417-04, Bryan Boiler LMV52 - Boiler operating controller (RWF55) via ProtoAir gateway
Thermal Solutions Siemens RWF55 boiler controller (Universal Gateway ProtoAir)
Thermal Solutions and Bryan boilers that use a Siemens RWF55 temperature/pressure controller, connected to the Universal Gateway (ProtoAir FPA-W44).
Also known as: RWF55, Siemens RWF55, ProtoAir FPA-W44, Universal Gateway 106417-04, Bryan Boiler RWF55 - Boiler controller (TSBC) via ProtoNode gateway
Thermal Solutions TSBC boiler control (Universal Gateway)
Thermal Solutions boilers with the TSBC control (such as EVS and EVCA), connected through the Thermal Solutions Universal Gateway.
Also known as: TSBC, Thermal Solutions Boiler Control, Universal Gateway, 106417-01, ProtoNode RER, FPC-N34-0816, EVS, EVCA
Source: Operating Manual, ProtoAir FPA-W44 for Interfacing Bryan Steam & Thermal Solutions Products · 106417-02 Rev 13 · rev. 2022-10. Object names, instances and units are reproduced as published; descriptions are our own.