Reverse osmosis water treatment unit BACnet gateway · BACnet points list

Condair RO-E (BACnet gateway board) BACnet points list

Updated 12 November 2026

Short answer

The Condair RO-E reverse osmosis unit, which feeds water to Condair humidifiers, can be put on BACnet IP or MS/TP with an optional ProtoCessor gateway board. The virtual device reports RO type, operating and service status, capacity, error code, pressures, permeate quality and flow, maintenance hours and valve states, and lets the BMS set the tank pressure band and reset errors.

This page lists 23 BACnet objects for the Condair RO-E (BACnet gateway board) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.

Manufacturer
Condair
Model
Condair RO-E (BACnet gateway board)
Equipment
Reverse osmosis water treatment unit BACnet gateway
Equipment type
Humidifiers
BACnet objects
23 (3 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
300
Also known as
Virtual_BCU_ROE, RO-E ProtoCessor gateway, RO-E+ gateway board, 2611780, 2611783
Source document
Gateway Board for BACnet and LonWorks - Supplemental Installation and Operation Manual (DL II, ME II, RS II and RO-E) · 2603584-F · rev. 2026-07
Download CSV 23 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Condair’s current documentation and the live device before use. Not official Condair information. Terms of use.

BMS integration notes: Condair RO-E (BACnet gateway board)

Integration in brief

The RO-E list is monitoring only, apart from the tank pressure band and an error reset. Map device status, service status and the error code, plus tank and inlet pressure; watch next maintenance and next disinfection for service planning.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 103AV Error/Warning ResetReset errors and warningsWrite
MI 102MI RO Device StatusOperating statusRead
AI 104AI RO Tank PressureTank pressureRead
AI 103AI RO Inlet PressureInlet pressureRead
AI 109AI RO Next MaintenanceHours to next maintenanceRead
MI 103MI RO Service StatusMaintenance/warning/error statusRead
AI 101AI Error Warning CodeActive error/warning codeRead

Network setup

Watch out for

Condair RO-E (BACnet gateway board) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

23 of 23 shown
Type
BinaryMulti-stateOther
Access
Show
Condair RO-E (BACnet gateway board) BACnet Points List
DescriptionStates
DEV300Virtual_BCU_ROEWater treatment RO-E virtual deviceRead
MI101MI RO TypeRO typeRead0=RO-E, 1=RO-E+
MImin102MI RO Device StatusRO operating statusRead1=Initializing, 2=Diagnostic, 3=Stopped, 4=Hold, 5=Filling, 6=Standby, 7=Flushing, 8=Draining
MImin103MI RO Service StatusMaintenance and warning statusRead1=No Info, 2=Warning, 3=Warning Sys, 4=Warning Commissioning, 5=Warning Activation, 6=Error, 7=Warning Disinfection
MI104MI RO CapacityUnit capacityRead1=20 l/h / 5.3 gal/hr, 2=40 l/h / 10.6 gal/hr, 3=100 l/h / 26.4 gal/hr, 4=200 l/h / 52.8 gal/hr, 5=300 l/h / 79.3 gal/hr
AImin101AI Error Warning CodeActive error/warning code, 0 = no errorRead
AI102AI RO Next DisinfectionDays to next disinfection, 0-365daysRead
AImin103AI RO Inlet PressureInlet pressure, 0-6 bar / 0-87 psibar or psiRead
AImin104AI RO Tank PressureTank pressure, 0-6 bar / 0-87 psibar or psiRead
AI105AI RO Membrane PressureMembrane pressure, 0-20 bar / 0-290 psibar or psiRead
AI106AI_ROPermeateConductivityPermeate conductivity, 0-100 µS/cm (RO-E+, option on RO-E)µS/cmRead
AI107AI RO Permeate TemperaturePermeate temperature (optional)°C or °FRead
AI108AI RO Permeate FlowPermeate flow, 0-400 l/h (optional)l/h or gal/hRead
AImin109AI RO Next MaintenanceHours to next maintenance, 0-4000hRead
AI110AI RO Operating HoursOperating hourshRead
AV101AV RO Tank Pressure StartMinimum tank pressure, 0-5 bar / 0-72.5 psibar or psiWrite
AV102AV RO Tank Pressure EndMaximum tank pressure, 0-5 bar / 0-72.5 psibar or psiWrite
AVmin103AV Error/Warning ResetReset errors and warningsWrite
BI101BI Inlet ValveY11 inlet valveRead0=Closed, 1=Open
BI102BI Drain ValveY12 drain valve (RO-E+, option on RO-E)Read0=Open, 1=Closed
BI103BI Outlet ValveY13 outlet valve (optional)Read0=Open, 1=Closed
BI104BI Permeate ValveY15 permeate valve (RO-E+ only)Read0=Drain, 1=Tank
BI105BI Concentrate ValveY16 concentrate valve (optional)Read0=Closed, 1=Open
Object ID lookup: Condair RO-E point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair RO-E (BACnet gateway board) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Condair RO-E (BACnet gateway board)

How many BACnet points does the Condair RO-E (BACnet gateway board) have?

This list has 23 BACnet objects: 10 analog inputs, 3 analog values, 5 binary inputs, 1 device, 4 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Condair RO-E (BACnet gateway board) BACnet points are writable?

3 of the 23 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Condair RO-E (BACnet gateway board) BACnet documentation?

The source is Gateway Board for BACnet and LonWorks - Supplemental Installation and Operation Manual (DL II, ME II, RS II and RO-E) (2603584-F), revision 2026-07, published free by Condair at https://www.condair.com/consense/bms-communication-ic-2.0/am_bms_interface_2603584_en.pdf.

What are the minimum BACnet points to integrate the Condair RO-E (BACnet gateway board)?

Start with AV 103 AV Error/Warning Reset (Reset errors and warnings); MI 102 MI RO Device Status (Operating status); AI 104 AI RO Tank Pressure (Tank pressure); AI 103 AI RO Inlet Pressure (Inlet pressure); AI 109 AI RO Next Maintenance (Hours to next maintenance); MI 103 MI RO Service Status (Maintenance/warning/error status); AI 101 AI Error Warning Code (Active error/warning code).

How do I check these points on the real Condair RO-E (BACnet gateway board)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Condair BACnet points lists

Source: Gateway Board for BACnet and LonWorks - Supplemental Installation and Operation Manual (DL II, ME II, RS II and RO-E) · 2603584-F · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.