Reverse osmosis water treatment unit · BACnet points list

Condair Condair RO-A BACnet points list

Updated 28 October 2026

Short answer

The Condair RO-A supplies reverse osmosis water to humidifiers. Through the Integrated Controller's BACnet on-board interface it reports operating and service status, capacity, maintenance and operating hours, inlet and tank pressures, pump overcurrent, leak sensor and valve states. All objects are read-only.

This page lists 13 BACnet objects for the Condair Condair RO-A — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.

Manufacturer
Condair
Model
Condair RO-A
Equipment
Reverse osmosis water treatment unit
Equipment type
Humidifiers
BACnet objects
13 (0 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Integrated Controller 5.9.x.x
Default device instance
1001
Also known as
RO-A reverse osmosis
Source document
BACnet on-board - Supplemental Installation and Operation Manual (RS, GS II, DL, ME and RO-A) · 2595492-C · rev. 2022-12
Download CSV 13 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Condair Condair RO-A

Integration in brief

Read-only monitoring of the RO-A through the Integrated Controller's BACnet on-board interface: map status, service status, fault code, capacity and the leak sensor.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MI 731Status RORO operating statusRead
AI 10779Capacity RORO output capacity, %Read
AI 10825Tank pressure ROPure water tank pressureRead
MI 549Service Status AService/fault statusRead
AI 10823Fault CodeActive fault codeRead
BI 727Leakage ROWater leak when 0 (0 = Fault, 1 = Ok)Read

Network setup

Watch out for

Condair Condair RO-A BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

13 of 13 shown
Type
AnalogBinaryMulti-stateOther
Show
Condair Condair RO-A BACnet Points List
DescriptionStates
DEV1001Integrated ControllerReverse osmosisRead
MImin731Status ROOperating status RORead1=Initializing, 2=Diagnostic, 3=Stopped, 4=Standby, 5=Refreshing, 6=Flushing, 7=Producing, 8=Regeneration
AImin10779Capacity ROCapacity RO%Read
AI10784Next Service RONext Maintenance ROhRead
AI10785Operating HoursOperating hours ROhRead
AI10824Inlet pressure ROInlet pressure (fresh water) RObar or psiRead
AImin10825Tank pressure ROPure water tank RObar or psiRead
BI724Guard ROOvercurrent pump RORead0=Fault, 1=Ok
BImin727Leakage ROLeak sensor RORead0=Fault, 1=Ok
BI768Inlet ROInlet valve RORead0=Closed, 1=Open
BI769Drain RODrain valve RORead0=Closed, 1=Open
MImin549Service Status AMaintenance and malfunctions statusRead1=Service Info, 2=Warning, 3=RO Service, 6=Activation Code, 7=Fault
AImin10823Fault CodeError codeRead0=No Error

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair RO-A and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Condair Condair RO-A

How many BACnet points does the Condair Condair RO-A have?

This list has 13 BACnet objects: 6 analog inputs, 4 binary inputs, 1 device, 2 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Condair Condair RO-A BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Condair Condair RO-A BACnet documentation?

The source is BACnet on-board - Supplemental Installation and Operation Manual (RS, GS II, DL, ME and RO-A) (2595492-C), revision 2022-12, published free by Condair at https://www.condair.com/consense/bms-communication-ic-1.0/am_bms_interface_bacnet_on_board_2595492_en_condairltd.pdf.

What are the minimum BACnet points to integrate the Condair Condair RO-A?

Start with MI 731 Status RO (RO operating status); AI 10779 Capacity RO (RO output capacity, %); AI 10825 Tank pressure RO (Pure water tank pressure); MI 549 Service Status A (Service/fault status); AI 10823 Fault Code (Active fault code); BI 727 Leakage RO (Water leak when 0 (0 = Fault, 1 = Ok)).

How do I check these points on the real Condair RO-A?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.