Resistive steam humidifier BACnet gateway · BACnet points list

Condair Condair RS (BACnet gateway board) BACnet points list

Updated 28 October 2026

Short answer

Condair RS units can reach BACnet IP or MS/TP through the optional ProtoCessor gateway board. The virtual device reports unit A/B status, water level, capacity, service hours and safety inputs, and offers writable setpoints, P-band, manual capacity, remote drain commands and demand inputs for channel 1 and the limiter.

This page lists 61 BACnet objects for the Condair Condair RS (BACnet gateway board) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.

Manufacturer
Condair
Model
Condair RS (BACnet gateway board)
Equipment
Resistive steam humidifier BACnet gateway
Equipment type
Humidifiers
BACnet objects
61 (10 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Integrated Controller 5.9.x.x
Default device instance
710 (BACnet IP); 1001 (MS/TP)
Also known as
Virtual_BCU_RS, RS ProtoCessor gateway
Source document
Gateway Board for BACnet and LonWorks - Supplemental Installation and Operation Manual · 2585293-L · rev. 2022-02
Download CSV 61 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Condair Condair RS (BACnet gateway board)

Integration in brief

Configure the RS controller for Modbus RTU with Signal Source = Modbus, set the gateway's BACnet side, and write demand/RH to AO 1 (plus a limiter value to AO 2 if used). Watch unit A/B status and BI 29 node status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1AO_RemRHorDemA1Channel 1 demand or RH from the BMSCommand
AO 2AO_RemRHorDemA2Channel 2 limiter signal (dual signal control)Command
AV 1AV_SetPointA1Channel 1 humidity setpoint used in RH P/PI modeWrite
MI 1MI_UnitStatusAUnit A statusRead
MI 2MI_UnitStatusBUnit B status (dual units)Read
AI 11AI_ActCapHumActual steam outputRead
BI 29BI_ConnectionGateway-to-humidifier node statusRead
MI 3MI_ServStatusAUnit A maintenance/fault statusRead
AI 1AI_ErrorCodeActive error codeRead

Enable & remote start

Set Control Settings (password 0335) > Signal Source to Modbus, choose the Control Mode (Demand, RH P or RH PI), and set the controller's Modbus RTU parameters to match the gateway.

Heartbeat & communication loss

Controller BMS Timeout (1-300 s, default 300 s): if the control signal is not updated within the timeout, warning W35 BMS Timeout is raised and humidification stops until a valid signal returns. The gateway only forwards the control value to the humidifier when it changes.

Sensors & values from the BMS

In Demand mode the BMS writes the required output (0-100 %) to the AO 1. In RH P or RH PI mode the BMS writes the measured humidity there and the controller's own setpoint, P-band and I-time AVs do the control. Do not connect a hard-wired demand or sensor signal while the BACnet signal is used.

Network setup

Watch out for

Condair Condair RS (BACnet gateway board) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

61 of 61 shown
Type
BinaryMulti-stateOther
Access
Show
Condair Condair RS (BACnet gateway board) BACnet Points List
DescriptionStates
DEV710Virtual_BCU_RSHumidifier RSRead
MImin1MI_UnitStatusAOperating status unit ARead1=Initializing, 2=Diagnostic, 3=Stopped, 4=Break, 5=Level test, 6=Standby, 7=Humidifying, 8=Filling, 9=Idle, 10=Draining, 11=Remote off, 12=Keep Warm
MImin2MI_UnitStatusBOperating status unit BRead1=Initializing, 2=Diagnostic, 3=Stopped, 4=Break, 5=Level test, 6=Standby, 7=Humidifying, 8=Filling, 9=Idle, 10=Draining, 11=Remote off, 12=Keep Warm
MImin3MI_ServStatusAMaintenance and malfunctions status unit ARead1=Service Info, 2=Warning, 3=RO Service, 4=Extended Maint., 5=Small Maint., 6=Activation Code, 7=Fault
MI4MI_ServStatusBMaintenance and malfunctions status unit BRead1=Service Info, 2=Warning, 3=RO Service, 4=Extended Maint., 5=Small Maint., 6=Activation Code, 7=Fault
MI5MI_HumTypeDevice typeRead1=RS, 2=RS+ RO, 3=RO
MI6MI_NomVoltageNominal voltageRead1=200 V, 2=208 V, 3=230 V, 4=240 V, 5=400 V, 6=415 V, 7=440 V, 8=460 V, 9=480 V, 10=500 V, 11=550 V, 12=600 V, 13=380 V
MI7MI_LevelAWater level unit ARead1=no level, 2=low, 3=low-mid, 4=mid, 5=mid-high, 6=high
MI8MI_LevelBWater level unit BRead1=no level, 2=low, 3=low-mid, 4=mid, 5=mid-high, 6=high
AImin1AI_ErrorCodeError codeRead0=No Error
AI2AI_OperatHoursOperating hourshRead
AI3AI_HoursToServANext service unit AhRead
AI4AI_HoursToServBNext service unit BRead
AI5AI_SystemDemandSystem demand%Read
AI6AI_InputA1Input signal channel 1 unit A%Read
AI7AI_InputA2Limiter signal channel 2 unit A%Read
AI8AI_MaxHumOutMax. capacitykg/h or lb/hRead
AI9AI_CylMaxCapAMax. capacity unit Akg/h or lb/hRead
AI10AI_CylMaxCapBMax. capacity unit Bkg/h or lb/hRead
AImin11AI_ActCapHumActual capacitykg/h or lb/hRead
AI12AI_CylActCapAActual capacity unit Akg/h or lb/hRead
AI13AI_CylActCapBActual capacity unit Bkg/h or lb/hRead
AVmin1AV_SetPointA1Setpoint channel 1 unit A%Write
AV2AV_SetPointA2Setpoint channel 2 limiter unit A%Write
AV3AV_PropBandA1P-Band unit A (proportional band)%Write
AV4AV_PropBandA2P-Band limiter unit A (Proportional band)%Write
AV5AV_IntTimeA1Integral time channel 1 unit AminWrite
AV6AV_DampTimeA2Damp time channel 2 unit AsWrite
AV7AV_CapLimitAManual capacity unit A%Write
AV8AV_RemoteDrainRemote drainWriteRead: 0=Off, 1=Init, 2=busy, 3=done, Write: 0=Off, 1=RS drain cylinder A, 2=RS drain cylinder B, 3=RS drain cyl. A+B, 4=RO flush, 5=RO fresh water automation
AOmin1AO_RemRHorDemA1Actual humidity or demand via BACnet unit A%Command
AOmin2AO_RemRHorDemA2Actual humidity or limiter via BACnet unit A%Command
BI1BI_BlowerPackABlower ready unit ARead0=Off, 1=On (ready)
BI2BI_BlowerPackBBlower ready unit BRead0=Off, 1=On (ready)
BI3BI_ExtSChStaAExternal safety loop unit ARead0=Open, 1=Closed (ok)
BI4BI_ExtSChStaBExternal safety loop unit BRead0=Open, 1=Closed (ok)
BI5BI_IntSChStaAInternal safety loop unit ARead0=Open, 1=Closed (ok)
BI6BI_IntSChStaBInternal safety loop unit BRead0=Open, 1=Closed (ok)
BI7BI_HeatVoltageAHeating voltage unit ARead0=Off, 1=On
BI8BI_HeatVoltageBHeating voltage unit BRead0=Off, 1=On
BI9BI_LevelSafetyAInternal safety loop unit A (security level)Read0=Off, 1=On (ok)
BI10BI_LevelSafetyBInternal safety loop unit B (security level)Read0=Off, 1=On (ok)
BI11BI_LeakALeakage sensor unit ARead0=Off (Leak), 1=On
BI12BI_LeakBLeakage sensor unit BRead0=Off (Leak), 1=On
BI13BI_MainContactAContactor unit ARead0=Off, 1=On
BI14BI_MainContactBContactor unit BRead0=Off, 1=On
BI15BI_PumpAPump unit ARead0=Off, 1=On
BI16BI_PumpBPump unit BRead0=Off, 1=On
BI17BI_InletA1Inlet valve 1 unit ARead0=Closed, 1=Open
BI18BI_InletB1Inlet valve 1 unit BRead0=Closed, 1=Open
BI19BI_InletA2Inlet valve 2 unit ARead0=Closed, 1=Open
BI20BI_InletB2Inlet valve 2 unit BRead0=Closed, 1=Open
BI21BI_DrainA1Drain cool valve unit ARead0=Closed, 1=Open
BI22BI_DrainB1Drain cool valve unit BRead0=Closed, 1=Open
BI23BI_DrainA2Complete drain valve unit ARead0=Closed, 1=Open
BI24BI_DrainB2Complete drain valve unit BRead0=Closed, 1=Open
BI25BI_FanAExternal fan unit ARead0=Off, 1=On
BI26BI_FanBExternal fan unit BRead0=Off, 1=On
BI27BI_FlushValveAHygiene flush unit ARead0=Closed, 1=Open
BI28BI_FlushValveBHygiene flush unit BRead0=Closed, 1=Open
BImin29BI_ConnectionNode statusRead0=Node offline, 1=Node online

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair RS (BACnet gateway board) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Condair Condair RS (BACnet gateway board)

How many BACnet points does the Condair Condair RS (BACnet gateway board) have?

This list has 61 BACnet objects: 13 analog inputs, 2 analog outputs, 8 analog values, 29 binary inputs, 1 device, 8 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Condair Condair RS (BACnet gateway board) BACnet points are writable?

10 of the 61 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Condair Condair RS (BACnet gateway board) BACnet documentation?

The source is Gateway Board for BACnet and LonWorks - Supplemental Installation and Operation Manual (2585293-L), revision 2022-02, published free by Condair at https://www.condair.com/consense/bms-communication-ic-1.0/am_bms_interface_2585293_en_condairltd.pdf.

What are the minimum BACnet points to integrate the Condair Condair RS (BACnet gateway board)?

Start with AO 1 AO_RemRHorDemA1 (Channel 1 demand or RH from the BMS); AO 2 AO_RemRHorDemA2 (Channel 2 limiter signal (dual signal control)); AV 1 AV_SetPointA1 (Channel 1 humidity setpoint used in RH P/PI mode); MI 1 MI_UnitStatusA (Unit A status); MI 2 MI_UnitStatusB (Unit B status (dual units)); AI 11 AI_ActCapHum (Actual steam output); BI 29 BI_Connection (Gateway-to-humidifier node status); MI 3 MI_ServStatusA (Unit A maintenance/fault status); AI 1 AI_ErrorCode (Active error code).

How do I enable BMS control of the Condair Condair RS (BACnet gateway board)?

Set Control Settings (password 0335) > Signal Source to Modbus, choose the Control Mode (Demand, RH P or RH PI), and set the controller's Modbus RTU parameters to match the gateway.

Does the Condair Condair RS (BACnet gateway board) need a BACnet heartbeat or have a communication timeout?

Controller BMS Timeout (1-300 s, default 300 s): if the control signal is not updated within the timeout, warning W35 BMS Timeout is raised and humidification stops until a valid signal returns. The gateway only forwards the control value to the humidifier when it changes.

Can the BMS supply sensor values to the Condair Condair RS (BACnet gateway board)?

In Demand mode the BMS writes the required output (0-100 %) to the AO 1. In RH P or RH PI mode the BMS writes the measured humidity there and the controller's own setpoint, P-band and I-time AVs do the control. Do not connect a hard-wired demand or sensor signal while the BACnet signal is used.

How do I check these points on the real Condair RS (BACnet gateway board)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Condair BACnet points lists

Source: Gateway Board for BACnet and LonWorks - Supplemental Installation and Operation Manual · 2585293-L · rev. 2022-02. Object names, instances and units are reproduced as published; descriptions are our own.