Evaporative humidifier BACnet gateway · BACnet points list

Condair Condair ME (BACnet gateway board) BACnet points list

Updated 28 October 2026

Short answer

Condair ME units can reach BACnet IP or MS/TP through the optional ProtoCessor gateway board. The virtual device reports status, maintenance countdowns, per-stage capacity and pump demand, water and air temperature, faults, and offers writable humidity and temperature loops, wash-over/drain commands and demand inputs.

This page lists 59 BACnet objects for the Condair Condair ME (BACnet gateway board) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.

Manufacturer
Condair
Model
Condair ME (BACnet gateway board)
Equipment
Evaporative humidifier BACnet gateway
Equipment type
Humidifiers
BACnet objects
59 (10 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Integrated Controller 5.9.x.x / 5.10.x.x
Default device instance
410 (BACnet IP); 1001 (MS/TP)
Also known as
Virtual_BCU_ME, ME ProtoCessor gateway
Source document
Gateway Board for BACnet and LonWorks - Supplemental Installation and Operation Manual · 2585293-L · rev. 2022-02
Download CSV 59 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Condair Condair ME (BACnet gateway board)

Integration in brief

Configure the ME controller for Modbus RTU with Signal Source = Modbus and System Mode (Humidifying or Cooling), set up the gateway's BACnet side, and write demand/RH to AO 1 and, for cooling, air temperature to AO 2. Check BI 19 for gateway-to-unit communication.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1AO_RemRHorDemDemand or measured RH from the BMSCommand
AV 1AV_SetPointHumHumidity setpoint used in RH P/PI modeWrite
AO 2AO_RemTempAir temperature from the BMS (cooling system mode)Command
BV 1BV_ResetReset errors and warnings (1 = reset)Write
MI 1MI_HumStatusOperating statusRead
AI 26AI_NumStgActNumber of stages runningRead
BI 19BI_ConnectionGateway-to-humidifier node statusRead
MI 2MI_ServStatusMaintenance/fault statusRead
AI 1AI_ErrorCodeActive error codeRead

Enable & remote start

Set Control Settings (password 0335) > Signal Source to Modbus, choose the Control Mode (Demand, RH P or RH PI), and set the controller's Modbus RTU parameters to match the gateway. On the ME also set System Mode to Humidifying or Cooling.

Heartbeat & communication loss

Controller BMS Timeout (1-300 s, default 300 s): if the control signal is not updated within the timeout, warning W35 BMS Timeout is raised and humidification stops until a valid signal returns. The gateway only forwards the control value to the humidifier when it changes.

Sensors & values from the BMS

In Demand mode the BMS writes the required output (0-100 %) to the AO 1. In RH P or RH PI mode the BMS writes the measured humidity there and the controller's own setpoint, P-band and I-time AVs do the control. Do not connect a hard-wired demand or sensor signal while the BACnet signal is used. AO 2 carries the air temperature for cooling control.

Network setup

Watch out for

Condair Condair ME (BACnet gateway board) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

59 of 59 shown
Type
Multi-stateOther
Access
Show
Condair Condair ME (BACnet gateway board) BACnet Points List
DescriptionStates
DEV410Virtual_BCU_MEHumidifier MERead
MImin1MI_HumStatusOperating statusRead1=Initializing, 2=Diagnostic, 3=Stopped, 4=Humidifying, 5=Cooling, 6=Holding, 7=Draining, 8=Refreshing, 9=Filling, 10=Standby, 11=Diluting, 12=Drain Assisting, 13=Bleeding, 14=Ramping Up, 15=Switched Off, 16=Remote Off, 17=Purging, 18=Drain Check
MImin2MI_ServStatusMaintenance and malfunctions statusRead1=Service Info, 2=Warning, 3=Service, 4=Refill Liquid, 5=Replace Pure- Flow Ag+, 6=Replace UV Bulb, 7=Matrix Wash Over, 8=Out of Comissioning, 9=Activation Code, 10=Fault
AImin1AI_ErrorCodeError codeRead0=no Error
AI2AI_OperatHoursOperating hourshRead
AI3AI_NextSySvcNext servicehRead
AI4AI_NextUVSvcNext UV bulb exchangedaysRead
AI5AI_NextAgSvcNext PureFlo Ag+ exchangedaysRead
AI6AI_RHorDemandActual humidity or demand%Read
AI7AI_TempActual air temperature°C or °FRead
AI8AI_UVCurrAUV currentARead
AI9AI_Stage1CapWater capacity stage 1kg/h or lb/hRead
AI10AI_Stage2CapWater capacity stage 2kg/h or lb/hRead
AI11AI_Stage3CapWater capacity stage 3kg/h or lb/hRead
AI12AI_Stage4CapWater capacity stage 4kg/h or lb/hRead
AI13AI_Stage5CapWater capacity stage 5kg/h or lb/hRead
AI14AI_Stage6CapWater capacity stage 6kg/h or lb/hRead
AI15AI_Stage7CapWater capacity stage 7kg/h or lb/hRead
AI16AI_SpeedPump1Demand pump 1%Read
AI17AI_SpeedPump2Demand pump 2%Read
AI18AI_SpeedPump3Demand pump 3%Read
AI19AI_SpeedPump4Demand pump 4%Read
AI20AI_SpeedPump5Demand pump 5%Read
AI21AI_SpeedPump6Demand pump 6%Read
AI22AI_SpeedPump7Demand pump 7%Read
AI23AI_ConductLpConductivityµS/cmRead
AI24AI_WtrTmpActual water temperature°C or °FRead
AI25AI_AirTmpActual air temperature°C or °FRead
AImin26AI_NumStgActNumber of running stagesRead
AI27AI_LevelWater level in tubRead
AVmin1AV_SetPointHumHumidity setpoint%Write
AV2AV_PropBandHProportional band humidity control%Write
AV3AV_IntTimeHIntegral time humidity controlminWrite
AV4AV_SetPointTmpTemperature setpoint°C or °FWrite
AV5AV_PropBandTProportional band temperature control°C or °FWrite
AV6AV_IntTimeTIntegral time temperatur controlminWrite
AV7AV_WashActMatrix wash over / Tank drainingWriteRead: 0=Off, 1=Initialisierung, 2=Process active, 3=Process completed, Write: 0=Stop active process, 1=Start matrix wash over, 2=Start tank draining
AOmin1AO_RemRHorDemActual humidity or demand via BACnet%Command
AOmin2AO_RemTempActual temperature via BACnet°C or °FCommand
BI1BI_ExtSChLStaSafety loopRead0=Open, 1=Closed (ok)
BI2BI_DosLvlDosing pump levelRead0=Empty, 1=Ok
BI3BI_LeakLeakage sensorRead0=Leakage, 1=Ok
BI4BI_DrainValLpDrain valveRead0=Open, 1=Closed
BI5BI_FillValLpInlet valveRead0=Closed, 1=Open
BI6BI_DrainPumpDrain pumpRead0=Off, 1=On
BI7BI_Pump1ErrFault pump 1Read0=Fault, 1=Ok
BI8BI_Pump2ErrFault pump 2Read0=Fault, 1=Ok
BI9BI_Pump3ErrFault pump 3Read0=Fault, 1=Ok
BI10BI_Pump4ErrFault pump 4Read0=Fault, 1=Ok
BI11BI_Pump5ErrFault pump 5Read0=Fault, 1=Ok
BI12BI_Pump6ErrFault pump 6Read0=Fault, 1=Ok
BI13BI_Pump7ErrFault pump 7Read0=Fault, 1=Ok
BI14BI_InletErrFault water inletRead0=Fault, 1=Ok
BI15BI_TempErrFault water temperatureRead0=Fault, 1=Ok
BI16BI_OutletErrFault water outletRead0=Fault, 1=Ok
BI17BI_LevSenErrFault level sensorRead0=Fault, 1=Ok
BI18BI_CondErrFault water conductivityRead0=Fault, 1=Ok
BImin19BI_ConnectionNode statusRead0=Node offline, 1=Node online
BVmin1BV_ResetRemote resetWrite0=Off, 1=On

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair ME (BACnet gateway board) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Condair Condair ME (BACnet gateway board)

How many BACnet points does the Condair Condair ME (BACnet gateway board) have?

This list has 59 BACnet objects: 27 analog inputs, 2 analog outputs, 7 analog values, 19 binary inputs, 1 binary value, 1 device, 2 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Condair Condair ME (BACnet gateway board) BACnet points are writable?

10 of the 59 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Condair Condair ME (BACnet gateway board) BACnet documentation?

The source is Gateway Board for BACnet and LonWorks - Supplemental Installation and Operation Manual (2585293-L), revision 2022-02, published free by Condair at https://www.condair.com/consense/bms-communication-ic-1.0/am_bms_interface_2585293_en_condairltd.pdf.

What are the minimum BACnet points to integrate the Condair Condair ME (BACnet gateway board)?

Start with AO 1 AO_RemRHorDem (Demand or measured RH from the BMS); AV 1 AV_SetPointHum (Humidity setpoint used in RH P/PI mode); AO 2 AO_RemTemp (Air temperature from the BMS (cooling system mode)); BV 1 BV_Reset (Reset errors and warnings (1 = reset)); MI 1 MI_HumStatus (Operating status); AI 26 AI_NumStgAct (Number of stages running); BI 19 BI_Connection (Gateway-to-humidifier node status); MI 2 MI_ServStatus (Maintenance/fault status); AI 1 AI_ErrorCode (Active error code).

How do I enable BMS control of the Condair Condair ME (BACnet gateway board)?

Set Control Settings (password 0335) > Signal Source to Modbus, choose the Control Mode (Demand, RH P or RH PI), and set the controller's Modbus RTU parameters to match the gateway. On the ME also set System Mode to Humidifying or Cooling.

Does the Condair Condair ME (BACnet gateway board) need a BACnet heartbeat or have a communication timeout?

Controller BMS Timeout (1-300 s, default 300 s): if the control signal is not updated within the timeout, warning W35 BMS Timeout is raised and humidification stops until a valid signal returns. The gateway only forwards the control value to the humidifier when it changes.

Can the BMS supply sensor values to the Condair Condair ME (BACnet gateway board)?

In Demand mode the BMS writes the required output (0-100 %) to the AO 1. In RH P or RH PI mode the BMS writes the measured humidity there and the controller's own setpoint, P-band and I-time AVs do the control. Do not connect a hard-wired demand or sensor signal while the BACnet signal is used. AO 2 carries the air temperature for cooling control.

How do I check these points on the real Condair ME (BACnet gateway board)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Condair BACnet points lists

Source: Gateway Board for BACnet and LonWorks - Supplemental Installation and Operation Manual · 2585293-L · rev. 2022-02. Object names, instances and units are reproduced as published; descriptions are our own.