Easy BACnet
  1. Home
  2. BACnet points lists
  3. Condair
  4. Condair GS II

Gas-fired steam humidifier · BACnet points list

Condair Condair GS II BACnet points list

Updated 28 October 2026

Short answer

The Condair GS II is a natural-gas or propane fired steam humidifier. With Integrated Controller software 5.10.1.14 or later it exposes BACnet IP and MS/TP on-board. Points cover operating and service status, channel 1/2 signals, capacity, exhaust service hours, float levels and inlet valves, plus writable setpoints, P-band and demand inputs.

This page lists 30 BACnet objects for the Condair Condair GS II — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.

Manufacturer
Condair
Model
Condair GS II
Equipment
Gas-fired steam humidifier
Equipment type
Humidifiers
BACnet objects
30 (9 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Integrated Controller 5.10.1.14 or later
Default device instance
1001
Also known as
Condair GS, Nortec GS II, GS gas-fired humidifier
Source document
BACnet on-board - Supplemental Installation and Operation Manual (RS, GS II, DL, ME and RO-A) · 2595492-C · rev. 2022-12
Download CSV 30 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Condair Condair GS II

Integration in brief

Turn on BACnet in the Communication menu, set the control signal source to BACnet, and write demand or RH to AO 10044 (and a limiter value to AO 10045) within the BMS timeout. Read the operating and service status, error code and actual output.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 10044Digital RH/Demand A1Demand or measured RH from the BMSCommand
AO 10045Digital RH/Demand A2Limiter (channel 2) signal from the BMSCommand
AV 10010Setpoint Channel 1Channel 1 humidity setpoint used in RH P/PI modeWrite
MI 614StatusOperating statusRead
AI 10103OutputActual steam outputRead
MI 549Service StatusService/fault statusRead
AI 10730Error CodeActive error codeRead

Enable & remote start

Set Configuration > Control Settings > Source to BACnet (and the BACnet interface to MSTP or BACnet/IP); otherwise control values from BACnet are ignored and the unit follows its driver-board analog input.

Heartbeat & communication loss

BMS Timeout tab (1-300 s, default 300 s): if no valid control signal arrives from the BMS within this time, warning W35 BMS Timeout is raised and the unit stops until a valid signal returns. Only evaluated when the control signal source is not Analog, so keep rewriting the demand AO.

Sensors & values from the BMS

Control Mode Demand uses the AO as an output demand; RH P / RH PI modes use it as a measured humidity and the controller's setpoint/P-band AVs do the control. Setpoint and humidity can only be monitored through the controller in RH P/PI mode.

Network setup

Watch out for

Condair Condair GS II BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

30 of 30 shown
Type
BinaryMulti-stateOther
Access
Show
Condair Condair GS II BACnet Points List
DescriptionStates
DEV1001Integrated ControllerHumidifierRead
MImin614StatusOperating statusRead1=Humidifying, 2=Idle, 3=Idle Drain, 4=Keep Warm, 5=Filling, 6=Draining, 7=Disabled, 8=Safety Loop, 9=Stopped, 10=Blower Pack, 11=Fill Check, 12=FTBD
MImin549Service StatusMaintenance and malfunctions statusRead1=Service Info, 2=Warning, 3=Service, 4=Fault
AI10001Channel 1Input signal channel 1%Read
AI10002Channel 2Limiter signal chanel 2%Read
AI10057System DemandSystem demand%Read
AI10060Operating HoursOperating hourshRead
AI10700Next ServiceNext servicehRead
AI10100Max. CapacityMax. capacitykg/h or lb/hRead
AImin10103OutputActual capacitykg/h or lb/hRead
AImin10730Error CodeError codeRead0=No Error
AI10732Exhaust ServiceTime to exhaust servicehRead
AV10008Manual CapacityManual capacity%Write
AVmin10010Setpoint Channel 1Setpoint channel 1%Write
AV10011Band Channel 1P-band (proportional band)%Write
AV10012ITime Channel 1Integral time channel 1minWrite
AV10013Setpoint Channel 2Setpoint channel 2 limiter%Write
AV10014Band Channel 2P-band (proportional band) limiter%Write
AV10015Damp Channel 2Damp time channel 2sWrite
AOmin10044Digital RH/Demand A1Actual humidity or demand via BACnet%Command
AOmin10045Digital RH/Demand A2Actual humidity or limiter via BACnet%Command
BI3Safety LoopSafety loopRead0=Open, 1=Closed
BI504Drain PumpDrain pumpRead0=Off, 1=On
BI542High Float LevelWater level highRead0=Off, 1=On
BI544Mid Float LevelWater level midRead0=Off, 1=On
BI546Low Float LevelWater level lowRead0=Off, 1=On
BI599Primary Inlet V1Status of Primary inlet valve 1Read0=Closed, 1=Open
BI601Primary Inlet V2Status of Primary inlet valve 2Read0=Closed, 1=Open
BI603Secondary Inlet V1Status of Secondary inlet valve 1Read0=Closed, 1=Open
BI605Secondary Inlet V2Status of Secondary inlet valve 2Read0=Closed, 1=Open

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair GS II and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Condair Condair GS II

How many BACnet points does the Condair Condair GS II have?

This list has 30 BACnet objects: 9 analog inputs, 2 analog outputs, 7 analog values, 9 binary inputs, 1 device, 2 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Condair Condair GS II BACnet points are writable?

9 of the 30 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Condair Condair GS II BACnet documentation?

The source is BACnet on-board - Supplemental Installation and Operation Manual (RS, GS II, DL, ME and RO-A) (2595492-C), revision 2022-12, published free by Condair at https://www.condair.com/consense/bms-communication-ic-1.0/am_bms_interface_bacnet_on_board_2595492_en_condairltd.pdf.

What are the minimum BACnet points to integrate the Condair Condair GS II?

Start with AO 10044 Digital RH/Demand A1 (Demand or measured RH from the BMS); AO 10045 Digital RH/Demand A2 (Limiter (channel 2) signal from the BMS); AV 10010 Setpoint Channel 1 (Channel 1 humidity setpoint used in RH P/PI mode); MI 614 Status (Operating status); AI 10103 Output (Actual steam output); MI 549 Service Status (Service/fault status); AI 10730 Error Code (Active error code).

How do I enable BMS control of the Condair Condair GS II?

Set Configuration > Control Settings > Source to BACnet (and the BACnet interface to MSTP or BACnet/IP); otherwise control values from BACnet are ignored and the unit follows its driver-board analog input.

Does the Condair Condair GS II need a BACnet heartbeat or have a communication timeout?

BMS Timeout tab (1-300 s, default 300 s): if no valid control signal arrives from the BMS within this time, warning W35 BMS Timeout is raised and the unit stops until a valid signal returns. Only evaluated when the control signal source is not Analog, so keep rewriting the demand AO.

Can the BMS supply sensor values to the Condair Condair GS II?

Control Mode Demand uses the AO as an output demand; RH P / RH PI modes use it as a measured humidity and the controller's setpoint/P-band AVs do the control. Setpoint and humidity can only be monitored through the controller in RH P/PI mode.

How do I check these points on the real Condair GS II?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Condair BACnet points lists

Source: BACnet on-board - Supplemental Installation and Operation Manual (RS, GS II, DL, ME and RO-A) · 2595492-C · rev. 2022-12. Object names, instances and units are reproduced as published; descriptions are our own.