  4. Condair ME

Evaporative humidifier / cooler · BACnet points list

Condair Condair ME BACnet points list

Updated 28 October 2026

Short answer

The Condair ME is a multi-stage evaporative humidifier and adiabatic cooler. The Integrated Controller exposes BACnet IP and MS/TP on-board. Points include operating and error status, per-stage capacity and pump speeds, tank level, water quality, separate humidity and cooling PI loops, and writable humidity/demand and temperature inputs.

This page lists 61 BACnet objects for the Condair Condair ME — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.

Manufacturer
Condair
Model
Condair ME
Equipment
Evaporative humidifier / cooler
Equipment type
Humidifiers
BACnet objects
61 (12 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1001
Also known as
Condair ME II, ME evaporative humidifier
Source document
BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) · 2603582-F · rev. 2026-07
Download CSV 61 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Condair Condair ME

Integration in brief

Enable BACnet in the Integrated Controller, set the signal source to BACnet, and write humidity demand (or measured RH) to AO 15044 within the signal timeout. When the ME runs as an evaporative cooler in system mode, also write the temperature to AO 15045. Monitor status, error status and the error code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 15044RH or DemandDemand or measured RH from the BMSCommand
AV 15054Setpoint HumidifyingHumidity setpoint used in RH P/PI modeWrite
AO 15045TemperatureAir temperature from the BMS (cooling system mode)Command
AV 30002Error/Warning ResetReset errors and warnings (1 = reset)Write
MI 5050Device StatusOperating statusRead
AI 15112Actual StagesNumber of stages runningRead
MI 5051Error StatusMaintenance/error statusRead
AI 10020Error/Warning CodeActive error or warning codeRead

Enable & remote start

Set Menu > password 8808 > Controls > Signal Settings > Source to BACnet and pick the Control Mode (Demand, RH P or RH PI; On/Off also exists). With Source left at Analog the unit ignores BACnet control values.

Heartbeat & communication loss

When the signal source is not Analog, the demand/humidity value written over BACnet must be refreshed within the Signal Timeout (1-300 s, default 300 s). If it is not, warning W35 Signal Timeout is raised and the unit stops until a new value arrives, so the BMS must keep rewriting the AO.

Sensors & values from the BMS

In Demand mode the BMS writes the required output (0-100 %) to the RH/Demand AO. In RH P or RH PI mode the BMS writes the measured humidity there and the controller's own setpoint, P-band and I-time AVs do the control. Do not connect a hard-wired demand or sensor signal while the BACnet signal is used. For cooling, AO 15045 carries the air temperature (relinquish default 20 °C) and is only active when the ME is operated in system mode.

Network setup

Watch out for

Condair Condair ME BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

61 of 61 shown
Type
BinaryMulti-state
Access
Show
Condair Condair ME BACnet Points List
DescriptionStates
DEV1001Condair ControllerHumidifierRead
Other1Network Port IPv4Network-Port for BACnet IPv4 CommunicationWrite
MImin5050Device StatusActual device statusRead1=Initializing, 2=Diagnostic, 3=Stopped, 4=Humidifying, 5=Cooling, 6=Holding, 7=Draining, 8=Refreshing, 9=Filling, 10=Standby, 11=Diluting, 12=Assisted Draining, 13=Bleeding, 14=Softstart, 15=Switched Off, 16=Remote Off, 17=Purging, 18=Drain Check
MImin5051Error StatusMaintenance and error statusRead1=No Info, 2=Warning, 3=Maintenance, 4=WET Tank empty, 5=Replace PureFlo Cartridge, 6=Replace UV Lamp, 7=Matrix Wash Over, 8=Out of Commissioning, 9=Activation Code, 10=Error, 11=Disinfection Tank empty
AI15176Water Level TankWater level tankRead0=Level 0, 1=Level 1, 2=Level 2, 3=Level 3, 4=Level 4, 5=Level 5, 6=Level 6, 7=Level 7
AImin10020Error/Warning CodeCode of the latest pending error or warningRead0=no Error
AI10044Operating HoursTotal hours of operation since commissioninghRead
AI10060Next MaintenanceDue date of next maintenance in operating hourshRead
AI15171Next UV Lamp ExchangeDue date of next UV Lamp exchange in days (optional)daysRead
AI15172Next PureFlo ExchangeDue date of next Pure-Flo exchange in days (optional)daysRead
AI15047Humidity ControlActual humidity or demand%Read
AI15048Temperature ControlActual air temperature°C or °FRead
AI15019UV CurrentActual UV current (optional)ARead
AImin15112Actual StagesNumber of running stagesRead
AI15086Capacity 1Water capacity stage 1kg/h or lb/hRead
AI15087Capacity 2Water capacity stage 2kg/h or lb/hRead
AI15088Capacity 3Water capacity stage 3kg/h or lb/hRead
AI15089Capacity 4Water capacity stage 4kg/h or lb/hRead
AI15090Capacity 5Water capacity stage 5kg/h or lb/hRead
AI15091Capacity 6Water capacity stage 6kg/h or lb/hRead
AI15092Capacity 7Water capacity stage 7kg/h or lb/hRead
AI15130Speed Pump 1Actual speed pump 1%Read
AI15131Speed Pump 2Actual speed pump 2%Read
AI15132Speed Pump 3Actual speed pump 3%Read
AI15133Speed Pump 4Actual speed pump 4%Read
AI15134Speed Pump 5Actual speed pump 5%Read
AI15135Speed Pump 6Actual speed pump 6%Read
AI15136Speed Pump 7Actual speed pump 7%Read
AI15077Water ConductivityWater conductivity tank (optional)µS/cmRead
AI15075Water TemperatureActual water temperature (optional)°C or °FRead
AI15049Incoming Air TemperatureIncoming air temperature (optional)°C or °FRead
AVmin15054Setpoint HumidifyingSetpoint humidity control%Write
AV15055P-Band HumidifyingProportional band humidity control%Write
AV15056I-Time HumidifyingIntegral time humidity controlminWrite
AV15057Setpoint CoolingSetpoint temperature control°C or °FWrite
AV15058P-Band CoolingProportional band temperature control°C or °FWrite
AV15059I-Time CoolingIntegral time temperature controlminWrite
AV30507DrainingRemote draining%WriteRead: 100=Off, 0 - 99=Progress draining in %, Write: 0=Stop draining, 1=Start draining
AV30505Matrix Wash OverRemote matrix wash over%WriteRead: 100=Off, 0 - 99=Progress matrix wash over in %, Write: 0=Stop matrix wash over, 1=Start matrix wash over
AVmin30002Error/Warning ResetRemote Error/Warning ResetWrite0=Off, 1=On
AOmin15044RH or DemandActual humidity or demand via BACnet%Command
AOmin15045TemperatureActual temperature via BACnet°C or °FCommand
BI5002Safety LoopSafety loopRead0=Open, 1=Closed (ok)
BI5034Drain ValveDrain valveRead0=Open, 1=Closed
BI5033Inlet ValveInlet valveRead0=Closed, 1=Open
BI5091Drain PumpDrain pumpRead0=Off, 1=On
BI5111Pump 1 ErrorFault pump 1Read0=Fault, 1=Ok
BI5112Pump 2 ErrorFault pump 2Read0=Fault, 1=Ok
BI5113Pump 3 ErrorFault pump 3Read0=Fault, 1=Ok
BI5114Pump 4 ErrorFault pump 4Read0=Fault, 1=Ok
BI5115Pump 5 ErrorFault pump 5Read0=Fault, 1=Ok
BI5116Pump 6 ErrorFault pump 6Read0=Fault, 1=Ok
BI5117Pump 7 ErrorFault pump 7Read0=Fault, 1=Ok
BI5118Water Inlet ErrorFault water inletRead0=Fault, 1=Ok
BI5119Water Outlet ErrorFault water outletRead0=Fault, 1=Ok
BI5120Water Temperature ErrorFault water temperature (optional)Read0=Fault, 1=Ok
BI5122Level Sensor ErrorFault level sensorRead0=Fault, 1=Ok
BI5121Water Conductivity ErrorFault water conductivity (optional)Read0=Fault, 1=Ok
BI5009Leak MonitoringLeakage sensor (optional)Read0=Leak, 1=Ok
BI5007WET Tank LevelWET tank level (optional)Read0=Empty, 1=Ok
BI5008Disinfection Tank LevelDisinfection tank level (optional)Read0=Empty, 1=Ok

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair ME and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Condair Condair ME

How many BACnet points does the Condair Condair ME have?

This list has 61 BACnet objects: 27 analog inputs, 2 analog outputs, 9 analog values, 19 binary inputs, 1 device, 2 multi-state inputs, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Condair Condair ME BACnet points are writable?

12 of the 61 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Condair Condair ME BACnet documentation?

The source is BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) (2603582-F), revision 2026-07, published free by Condair at https://www.condair.co.uk/consense/bms-communication-ic-2.0/am_bms_interface_bacnet_on_board_2603582_en.pdf.

What are the minimum BACnet points to integrate the Condair Condair ME?

Start with AO 15044 RH or Demand (Demand or measured RH from the BMS); AV 15054 Setpoint Humidifying (Humidity setpoint used in RH P/PI mode); AO 15045 Temperature (Air temperature from the BMS (cooling system mode)); AV 30002 Error/Warning Reset (Reset errors and warnings (1 = reset)); MI 5050 Device Status (Operating status); AI 15112 Actual Stages (Number of stages running); MI 5051 Error Status (Maintenance/error status); AI 10020 Error/Warning Code (Active error or warning code).

How do I enable BMS control of the Condair Condair ME?

Set Menu > password 8808 > Controls > Signal Settings > Source to BACnet and pick the Control Mode (Demand, RH P or RH PI; On/Off also exists). With Source left at Analog the unit ignores BACnet control values.

Does the Condair Condair ME need a BACnet heartbeat or have a communication timeout?

When the signal source is not Analog, the demand/humidity value written over BACnet must be refreshed within the Signal Timeout (1-300 s, default 300 s). If it is not, warning W35 Signal Timeout is raised and the unit stops until a new value arrives, so the BMS must keep rewriting the AO.

Can the BMS supply sensor values to the Condair Condair ME?

In Demand mode the BMS writes the required output (0-100 %) to the RH/Demand AO. In RH P or RH PI mode the BMS writes the measured humidity there and the controller's own setpoint, P-band and I-time AVs do the control. Do not connect a hard-wired demand or sensor signal while the BACnet signal is used. For cooling, AO 15045 carries the air temperature (relinquish default 20 °C) and is only active when the ME is operated in system mode.

How do I check these points on the real Condair ME?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Condair BACnet points lists

Source: BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) · 2603582-F · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.