Hybrid (spray + evaporative) humidifier · BACnet points list

Condair Condair DL BACnet points list

Updated 28 October 2026

Short answer

The Condair DL is a hybrid humidifier that sprays treated water onto a ceramic evaporator. Its Integrated Controller exposes BACnet IP and MS/TP on-board with no extra card. The object list covers status, silver-ion (Ag-Ion) hygiene data, pressures, valve states, PI control settings and a writable demand/RH input.

This page lists 41 BACnet objects for the Condair Condair DL — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.

Manufacturer
Condair
Model
Condair DL
Equipment
Hybrid (spray + evaporative) humidifier
Equipment type
Humidifiers
BACnet objects
41 (9 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1001
Also known as
Condair DL II, DL hybrid humidifier, Integrated Controller DL
Source document
BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) · 2603582-F · rev. 2026-07
Download CSV 41 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Condair Condair DL

Integration in brief

Turn on BACnet IP or MS/TP in the Integrated Controller, set the signal source to BACnet, then have the BMS write the demand or measured RH to AO 15059 at least every Signal Timeout period. Use BV 5187 for remote enable if Remote Enable is set to BACnet. Monitor the status and error MIs and the error code AI.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 5187Remote EnableRemote enable/disable of the humidifierWrite
AO 15059Rh or DemandDemand or measured RH from the BMSCommand
AV 15050SetpointHumidity setpoint used in RH P/PI modeWrite
MI 5154Device StatusOperating statusRead
AI 15174Actual Hum. CapacityActual spray water outputRead
MI 5155Error StatusMaintenance/error statusRead
AI 10020ErrorWarning CodeActive error or warning codeRead

Enable & remote start

Set Menu > password 8808 > Controls > Signal Settings > Source to BACnet and pick the Control Mode (Demand, RH P or RH PI; On/Off also exists). With Source left at Analog the unit ignores BACnet control values. For BMS start/stop also set Remote Enable to BACnet; BV 5187 then enables the DL (controller software 1.4.0 or later).

Heartbeat & communication loss

When the signal source is not Analog, the demand/humidity value written over BACnet must be refreshed within the Signal Timeout (1-300 s, default 300 s). If it is not, warning W35 Signal Timeout is raised and the unit stops until a new value arrives, so the BMS must keep rewriting the AO.

Sensors & values from the BMS

In Demand mode the BMS writes the required output (0-100 %) to the RH/Demand AO. In RH P or RH PI mode the BMS writes the measured humidity there and the controller's own setpoint, P-band and I-time AVs do the control. Do not connect a hard-wired demand or sensor signal while the BACnet signal is used.

Network setup

Watch out for

Condair Condair DL BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

41 of 41 shown
Type
Multi-state
Access
Show
Condair Condair DL BACnet Points List
DescriptionStates
DEV1001Condair ControllerHumidifierRead
Other1Network Port IPv4Network-Port for BACnet IPv4 CommunicationWrite
MImin5154Device StatusActual device statusRead1=Initializing, 2=Diagnostic, 3=Stopped, 4=Flushing, 5=Standby, 6=Humidifying, 7=Ready, 8=Air Cleaning, 9=Filling, 10=Conductivity Flush, 11=Switched Off, 12=Remote Off, 13=Temperature Flush, 14=Ceramic Wash Over
MImin5155Error StatusMaintenance and error statusRead1=No Info, 2=Warning, 3=Activation Code, 4=Out of Commissioning, 5=Refill Disinfection, 6=Maintenance, 7=Error, 8=Replace Ag Cartridge, 9=Disinfection
MI5089DL TypeCondair DL device assembly configurationRead1=Humidifier, 2=Humidifier + FC, 3=Humidifier + FC - Off
AImin10020ErrorWarning CodeCode of the latest pending error or warningRead0=no Error
AI10044Operating HoursTotal hours of operation since commissioninghRead
AI10060Next MaintenanceDue date of next maintenance in operating hourshRead
AI15068Humidity ControlActual humidity or demand%Read
AI15172Max. Hum. CapacityMaximum possible spray water outputkg/h or lb/hRead
AImin15174Actual Hum. CapacityActual spray water outputkg/h or lb/hRead
AI15154Remain. Ag-Ion CapacityRemaining Ag-Ion capacityAhRead
AI15179Target Ag-Ion CurrentTarget Ag-Ion currentmARead
AI15170PS4 Inlet PressureInlet pressure PS4bar or psiRead
AI15171PS5 Nozzle PressureNozzle pressure PS5bar or psiRead
AI15169Water TemperatureInlet water temperature (optional)°C or °FRead
AI15168Water ConductivityInlet water conductivityµS/cmRead
AI15148Pump CurrentPump currentARead
AI15027Ag-Ion CurrentAg-Ion currentmARead
AVmin15050SetpointHumidity setpoint%Write
AV15051P-BandProportional band%Write
AV15052I-TimeIntegral timeminWrite
AV15058Capacity LimitationLimitation of the maximum possible output%Write
AV30506FlushingRemote flush%WriteRead: 100=Off, 0 - 99=Progress flushing in %, Write: 0=Stop flushing, 1=Start flushing
AV30507Ceramic Wash OverRemote ceramic wash over%WriteRead: 100=Off, 0 - 99=Progress ceramic wash over in %, Write: 0=Stop ceramic wash over, 1=Start ceramic wash over
AOmin15059Rh or DemandActual humidity or demand via BACnet%Command
BI5002Safety LoopSafety loopRead0=Open, 1=Closed (ok)
BI5156Y1 Inlet ValveY1 inlet valveRead0=Closed, 1=Open
BI5157Y2 ReserveY2 valveRead
BI5158Y3 Air CleaningY3 valve air cleaning (optional)Read0=Closed, 1=Open
BI5159Y4 Ext. Pipe FlushY4 valve external pipe flush (optional)Read0=Closed, 1=Open
BI5160Y5 Spray ValveY5 valve for spray circuit 1Read0=Closed, 1=Open
BI5161Y6 Spray ValveY6 valve for spray circuit 2Read0=Closed, 1=Open
BI5162Y7 Spray ValveY7 valve for spray circuit 3Read0=Closed, 1=Open
BI5163Y8 Spray ValveY8 valve for spray circuit 4Read0=Closed, 1=Open
BI5164Y9 Spray ValveY9 valve for spray circuit 5Read0=Closed, 1=Open
BI5165Y10 Drain ValveY10 valve drain (NO)Read0=Open, 1=Closed
BI5166Y11 Aux. Outlet ValveY11 auxiliary outlet valve (optional)Read0=Open, 1=Closed
BI5170FC EnableFrequency converter enableRead0=Off, 1=On
BI5167FC StatusFrequency converter statusRead0=Off, 1=On
BVmin5187Remote EnableRemote enableWrite0=Off, 1=On

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair DL and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Condair Condair DL

How many BACnet points does the Condair Condair DL have?

This list has 41 BACnet objects: 14 analog inputs, 1 analog output, 6 analog values, 14 binary inputs, 1 binary value, 1 device, 3 multi-state inputs, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Condair Condair DL BACnet points are writable?

9 of the 41 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Condair Condair DL BACnet documentation?

The source is BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) (2603582-F), revision 2026-07, published free by Condair at https://www.condair.co.uk/consense/bms-communication-ic-2.0/am_bms_interface_bacnet_on_board_2603582_en.pdf.

What are the minimum BACnet points to integrate the Condair Condair DL?

Start with BV 5187 Remote Enable (Remote enable/disable of the humidifier); AO 15059 Rh or Demand (Demand or measured RH from the BMS); AV 15050 Setpoint (Humidity setpoint used in RH P/PI mode); MI 5154 Device Status (Operating status); AI 15174 Actual Hum. Capacity (Actual spray water output); MI 5155 Error Status (Maintenance/error status); AI 10020 ErrorWarning Code (Active error or warning code).

How do I enable BMS control of the Condair Condair DL?

Set Menu > password 8808 > Controls > Signal Settings > Source to BACnet and pick the Control Mode (Demand, RH P or RH PI; On/Off also exists). With Source left at Analog the unit ignores BACnet control values. For BMS start/stop also set Remote Enable to BACnet; BV 5187 then enables the DL (controller software 1.4.0 or later).

Does the Condair Condair DL need a BACnet heartbeat or have a communication timeout?

When the signal source is not Analog, the demand/humidity value written over BACnet must be refreshed within the Signal Timeout (1-300 s, default 300 s). If it is not, warning W35 Signal Timeout is raised and the unit stops until a new value arrives, so the BMS must keep rewriting the AO.

Can the BMS supply sensor values to the Condair Condair DL?

In Demand mode the BMS writes the required output (0-100 %) to the RH/Demand AO. In RH P or RH PI mode the BMS writes the measured humidity there and the controller's own setpoint, P-band and I-time AVs do the control. Do not connect a hard-wired demand or sensor signal while the BACnet signal is used.

How do I check these points on the real Condair DL?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Condair BACnet points lists

Source: BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) · 2603582-F · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.