Reverse osmosis water treatment unit · BACnet points list
Condair Condair RO-E BACnet points list
Updated 28 October 2026
The Condair RO-E makes demineralised water for humidifiers. Its Integrated Controller exposes BACnet IP and MS/TP on-board with status, maintenance and disinfection countdowns, inlet/tank/membrane pressures, permeate quality and flow, valve states and writable tank pressure start/stop limits.
This page lists 24 BACnet objects for the Condair Condair RO-E — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.
- Manufacturer
- Condair
- Model
- Condair RO-E
- Equipment
- Reverse osmosis water treatment unit
- Equipment type
- Humidifiers
- BACnet objects
- 24 (4 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1001
- Also known as
- Condair RO-E+, RO-E reverse osmosis
BMS integration notes: Condair Condair RO-E
The RO-E is monitoring-focused: enable BACnet in its Integrated Controller and read status, service status, error code, pressures and permeate quality. The only writable items are the tank pressure start/stop limits and an error/warning reset.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 30002 | Error/Warning Reset | Clears active errors and warnings | Write |
| MI 121 | RO Device Status | RO operating status | Read |
| AI 10144 | RO Permeate Conductivity | Permeate conductivity (water quality) | Read |
| AI 10142 | RO Tank Pressure | Product water tank pressure | Read |
| AI 10210 | RO Next Disinfection | Days to next disinfection | Read |
| MI 122 | RO Service Status | Maintenance/warning/error status | Read |
| AI 10020 | ErrorWarning Code | Active error or warning code | Read |
Network setup
- BACnet settings are under Menu > password 8808 > Network > BACnet Settings; the BACnet Protocol parameter ships Off (options MS/TP Master, MS/TP Slave, BACnet/IP) and the controller restarts after changing it.
- Node ID (device instance) defaults to 1001 (range 1-4194303); BACnet IP port defaults to 47808.
- IP addressing defaults to DHCP; if no DHCP server answers the controller falls back to an APIPA 169.254.x.x address.
- Foreign Device registration to a BBMD is Off by default; BBMD port 47808 and re-register time 10 are the factory values.
Watch out for
- Permeate conductivity and drain valve are optional on RO-E and standard on RO-E+; the permeate valve is RO-E+ only.
- AV 10127/10128 set the tank refill start/stop pressures.
- Pressure, temperature and flow units follow the Metric/Imperial setting.
Condair Condair RO-E BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| DEV | 1001 | Condair Controller | Water treatment | Read | ||
| Other | 1 | Network Port IPv4 | Network-Port for BACnet IPv4 Communication | Write | ||
| MI | 88 | RO Type | RO Type | Read | 1=RO-E, 2=RO-E+ | |
| MImin | 121 | RO Device Status | RO Status | Read | 1=Initializing, 2=Diagnostic, 3=Stopped, 4=Hold, 5=Filling, 6=Standby, 7=Flushing, 8=Draining | |
| MImin | 122 | RO Service Status | UO Maintenance status | Read | 1=No Info, 2=Warning, 3=Warning Sys, 4=Warning Commissioning, 5=Warning Activation, 6=Error, 7=Warning Disinfection | |
| MI | 134 | RO Capacity | UO Capacity | Read | 1=20 l/h 5.3 gal/hr, 2=40 l/h 10.6 gal/hr, 3=100 l/h 26.4 gal/hr, 4=200 l/h 52.8 gal/hr, 5=300 l/h 79.3 gal/hr | |
| AImin | 10020 | ErrorWarning Code | Error Warning Code | Read | 0=No Error | |
| AImin | 10210 | RO Next Disinfection | Next Disinfection | days | Read | |
| AI | 10141 | RO Inlet Pressure | Inlet pressure | bar or psi | Read | |
| AImin | 10142 | RO Tank Pressure | Tank pressure | bar or psi | Read | |
| AI | 10143 | RO Membrane Pressure | Membrane pressure | bar or psi | Read | |
| AImin | 10144 | RO Permeate Conductivity | Permeate conductivity | µS/cm | Read | |
| AI | 10145 | RO Water Temperature | Permeate temperature (optional) | °C or °F | Read | |
| AI | 10146 | RO Permeate Volume Flow | Permeat flow (optional) | l/h or gal/h | Read | |
| AI | 10150 | RO Next Maintenance | Next maintenance | h | Read | |
| AI | 10238 | RO Operating Hours | Operating hours | h | Read | |
| BI | 78 | RO Inlet Valve | Y11 Inlet valve | Read | 0=Closed, 1=Open | |
| BI | 79 | RO Drain Valve | Y12 Drain valve | Read | 0=Open, 1=Closed | |
| BI | 80 | RO Outlet Valve | Y13 Outlet valve (optional) | Read | 0=Open, 1=Closed | |
| BI | 81 | RO Permeate Valve | Y15 Permeate valve | Read | 0=Drain, 1=Tank | |
| BI | 82 | RO Concentrate Valve | Y16 Concentrate valve (optional) | Read | 0=Closed, 1=Open | |
| AV | 10127 | RO Start Tank Pressure | Minimum tank pressure | bar or psi | Write | |
| AV | 10128 | RO End Tank Pressure | Maximum tank pressure | bar or psi | Write | |
| AVmin | 30002 | Error/Warning Reset | Error/Warning Reset | Write |
No points match these filters.
Integration notes
- BACnet is built into the Integrated Controller (RJ45 for BACnet IP, RS485 for MS/TP master or slave); it ships with the BACnet protocol set to Off.
- Factory Node ID (device instance) is 1001 and the MS/TP MAC is 127; BACnet IP uses UDP 47808 and supports registering with a BBMD.
- Some points are RO-E+ only or optional on the RO-E (permeate conductivity, drain valve, permeate valve).
- Pressure, temperature and flow units follow the controller's Metric/Imperial setting.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair RO-E and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Condair Condair RO-E
How many BACnet points does the Condair Condair RO-E have?
This list has 24 BACnet objects: 10 analog inputs, 3 analog values, 5 binary inputs, 1 device, 4 multi-state inputs, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Condair Condair RO-E BACnet points are writable?
4 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Condair Condair RO-E BACnet documentation?
The source is BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) (2603582-F), revision 2026-07, published free by Condair at https://www.condair.co.uk/consense/bms-communication-ic-2.0/am_bms_interface_bacnet_on_board_2603582_en.pdf.
What are the minimum BACnet points to integrate the Condair Condair RO-E?
Start with AV 30002 Error/Warning Reset (Clears active errors and warnings); MI 121 RO Device Status (RO operating status); AI 10144 RO Permeate Conductivity (Permeate conductivity (water quality)); AI 10142 RO Tank Pressure (Product water tank pressure); AI 10210 RO Next Disinfection (Days to next disinfection); MI 122 RO Service Status (Maintenance/warning/error status); AI 10020 ErrorWarning Code (Active error or warning code).
How do I check these points on the real Condair RO-E?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Condair BACnet points lists
- Hybrid (spray + evaporative) humidifier
Condair Condair DL
Condair DL / DL II hybrid in-duct humidifiers with the Integrated Controller.
Also known as: Condair DL II, DL hybrid humidifier, Integrated Controller DL - Hybrid humidifier BACnet gateway
Condair Condair DL (BACnet gateway board)
Condair DL hybrid humidifiers (Integrated Controller 5.9.x.x) fitted with the optional BACnet/LonWorks gateway board.
Also known as: Virtual_BCU_DL, DL ProtoCessor gateway, BMS DL BACnet - Gas-fired steam humidifier
Condair Condair GS II
Condair GS II gas-fired steam humidifiers with the Integrated Controller (software 5.10.1.14 or later).
Also known as: Condair GS, Nortec GS II, GS gas-fired humidifier - Evaporative humidifier / cooler
Condair Condair ME
Condair ME / ME II in-duct evaporative humidifiers and evaporative coolers.
Also known as: Condair ME II, ME evaporative humidifier - Evaporative humidifier BACnet gateway
Condair Condair ME (BACnet gateway board)
Condair ME evaporative humidifiers (Integrated Controller 5.9.x.x and 5.10.x.x) with the optional BACnet/LonWorks gateway board.
Also known as: Virtual_BCU_ME, ME ProtoCessor gateway - Reverse osmosis water treatment unit
Condair Condair RO-A
Condair RO-A reverse osmosis units connected through the Integrated Controller.
Also known as: RO-A reverse osmosis - Electric resistive steam humidifier
Condair Condair RS
Condair RS / RS II single and dual cylinder (A/B) resistive steam humidifiers.
Also known as: Condair RS II, RS resistive steam humidifier, Nortec RS - Resistive steam humidifier BACnet gateway
Condair Condair RS (BACnet gateway board)
Condair RS resistive steam humidifiers (Integrated Controller 5.9.x.x) with the optional BACnet/LonWorks gateway board.
Also known as: Virtual_BCU_RS, RS ProtoCessor gateway - High-pressure nozzle humidification system
Condair Condair Vita
Condair Vita high-pressure nozzle humidification systems with up to 50 areas.
Also known as: Condair Vita high-pressure, Vita System Master
Source: BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) · 2603582-F · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.