Reverse osmosis water treatment unit · BACnet points list

Condair Condair RO-E BACnet points list

Updated 28 October 2026

Short answer

The Condair RO-E makes demineralised water for humidifiers. Its Integrated Controller exposes BACnet IP and MS/TP on-board with status, maintenance and disinfection countdowns, inlet/tank/membrane pressures, permeate quality and flow, valve states and writable tank pressure start/stop limits.

This page lists 24 BACnet objects for the Condair Condair RO-E — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.

Manufacturer
Condair
Model
Condair RO-E
Equipment
Reverse osmosis water treatment unit
Equipment type
Humidifiers
BACnet objects
24 (4 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1001
Also known as
Condair RO-E+, RO-E reverse osmosis
Source document
BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) · 2603582-F · rev. 2026-07
Download CSV 24 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Condair Condair RO-E

Integration in brief

The RO-E is monitoring-focused: enable BACnet in its Integrated Controller and read status, service status, error code, pressures and permeate quality. The only writable items are the tank pressure start/stop limits and an error/warning reset.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 30002Error/Warning ResetClears active errors and warningsWrite
MI 121RO Device StatusRO operating statusRead
AI 10144RO Permeate ConductivityPermeate conductivity (water quality)Read
AI 10142RO Tank PressureProduct water tank pressureRead
AI 10210RO Next DisinfectionDays to next disinfectionRead
MI 122RO Service StatusMaintenance/warning/error statusRead
AI 10020ErrorWarning CodeActive error or warning codeRead

Network setup

Watch out for

Condair Condair RO-E BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

24 of 24 shown
Type
BinaryMulti-state
Access
Show
Condair Condair RO-E BACnet Points List
DescriptionStates
DEV1001Condair ControllerWater treatmentRead
Other1Network Port IPv4Network-Port for BACnet IPv4 CommunicationWrite
MI88RO TypeRO TypeRead1=RO-E, 2=RO-E+
MImin121RO Device StatusRO StatusRead1=Initializing, 2=Diagnostic, 3=Stopped, 4=Hold, 5=Filling, 6=Standby, 7=Flushing, 8=Draining
MImin122RO Service StatusUO Maintenance statusRead1=No Info, 2=Warning, 3=Warning Sys, 4=Warning Commissioning, 5=Warning Activation, 6=Error, 7=Warning Disinfection
MI134RO CapacityUO CapacityRead1=20 l/h 5.3 gal/hr, 2=40 l/h 10.6 gal/hr, 3=100 l/h 26.4 gal/hr, 4=200 l/h 52.8 gal/hr, 5=300 l/h 79.3 gal/hr
AImin10020ErrorWarning CodeError Warning CodeRead0=No Error
AImin10210RO Next DisinfectionNext DisinfectiondaysRead
AI10141RO Inlet PressureInlet pressurebar or psiRead
AImin10142RO Tank PressureTank pressurebar or psiRead
AI10143RO Membrane PressureMembrane pressurebar or psiRead
AImin10144RO Permeate ConductivityPermeate conductivityµS/cmRead
AI10145RO Water TemperaturePermeate temperature (optional)°C or °FRead
AI10146RO Permeate Volume FlowPermeat flow (optional)l/h or gal/hRead
AI10150RO Next MaintenanceNext maintenancehRead
AI10238RO Operating HoursOperating hourshRead
BI78RO Inlet ValveY11 Inlet valveRead0=Closed, 1=Open
BI79RO Drain ValveY12 Drain valveRead0=Open, 1=Closed
BI80RO Outlet ValveY13 Outlet valve (optional)Read0=Open, 1=Closed
BI81RO Permeate ValveY15 Permeate valveRead0=Drain, 1=Tank
BI82RO Concentrate ValveY16 Concentrate valve (optional)Read0=Closed, 1=Open
AV10127RO Start Tank PressureMinimum tank pressurebar or psiWrite
AV10128RO End Tank PressureMaximum tank pressurebar or psiWrite
AVmin30002Error/Warning ResetError/Warning ResetWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair RO-E and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Condair Condair RO-E

How many BACnet points does the Condair Condair RO-E have?

This list has 24 BACnet objects: 10 analog inputs, 3 analog values, 5 binary inputs, 1 device, 4 multi-state inputs, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Condair Condair RO-E BACnet points are writable?

4 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Condair Condair RO-E BACnet documentation?

The source is BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) (2603582-F), revision 2026-07, published free by Condair at https://www.condair.co.uk/consense/bms-communication-ic-2.0/am_bms_interface_bacnet_on_board_2603582_en.pdf.

What are the minimum BACnet points to integrate the Condair Condair RO-E?

Start with AV 30002 Error/Warning Reset (Clears active errors and warnings); MI 121 RO Device Status (RO operating status); AI 10144 RO Permeate Conductivity (Permeate conductivity (water quality)); AI 10142 RO Tank Pressure (Product water tank pressure); AI 10210 RO Next Disinfection (Days to next disinfection); MI 122 RO Service Status (Maintenance/warning/error status); AI 10020 ErrorWarning Code (Active error or warning code).

How do I check these points on the real Condair RO-E?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Condair BACnet points lists

Source: BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) · 2603582-F · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.