Easy BACnet
  1. Home
  2. BACnet points lists
  3. Condair
  4. Condair Vita

High-pressure nozzle humidification system · BACnet points list

Condair Condair Vita BACnet points list

Updated 28 October 2026

Short answer

Condair Vita is a high-pressure water atomising system that serves up to 50 humidification areas from one System Master. BACnet on-board reports the reverse osmosis, deionisation and high-pressure stage states, system error category and code, and per-area state, temperature, humidity and a writable per-area humidity setpoint.

This page lists 214 BACnet objects for the Condair Condair Vita — 50 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Condair’s own free documentation, linked below.

Manufacturer
Condair
Model
Condair Vita
Equipment
High-pressure nozzle humidification system
Equipment type
Humidifiers
BACnet objects
214 (50 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
1001
Also known as
Condair Vita high-pressure, Vita System Master
Source document
BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) · 2603582-F · rev. 2026-07
Download CSV 214 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Condair Condair Vita

Integration in brief

Enable BACnet in the Vita System Master and alarm on error categories 1-7 (1 = most severe) plus the error code. Per-area state, temperature and humidity are read from instance blocks offset by area number, and each area's humidity setpoint can be written.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1611600Area Setpoint 1Area 1 humidity setpointWrite
MI 5035Pressure Status HP LineHigh-pressure stage statusRead
MI 5033Reverse Osmosis StateReverse osmosis stage statusRead
MI 603100Area State 1Area 1 state (one per area)Read
AI 1611300Actual Humidity Area 1Measured RH in area 1, %Read
MI 5055Error CategoryError severity; alarm on categories 1-7 (11 = no error)Read
AI 15232Error CodeSystem Master error codeRead

Sensors & values from the BMS

No BMS-fed sensor inputs are listed; the BMS can write each area's humidity setpoint (AV 1611600-1611649, 20-100 %).

Network setup

Watch out for

Condair Condair Vita BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

214 of 214 shown
Type
Multi-stateOther
Access
Show
Condair Condair Vita BACnet Points List
DescriptionStates
DEV1001Condair ControllerWater treatmentRead
MImin5033Reverse Osmosis StateStatus reverse osmosis stageRead1=Stopped, 2=Depressuring, 3=Empty, 4=Flushing, 5=Flushing no water, 6=Producing, 7=Holding, 8=Wait for pressure
MI5034Deionization StateStatus deionization stageRead1=Syn_Idle, 2=Syn_Active
MImin5035Pressure Status HP LineStatus high pressure stageRead1=HP_Stopped, 2=HP_Flushing, 3=HP_Flushing no water, 4=HP_Producing, 5=HP_Producing no water, 6=HP_Holding, 7=HP_Depressuring, 8=HP_Empty, 9=HP_Ventilating
MImin603100Area State 1Area status, area 1Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603101Area State 2Area status, area 2Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603102Area State 3Area status, area 3Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603103Area State 4Area status, area 4Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603104Area State 5Area status, area 5Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603105Area State 6Area status, area 6Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603106Area State 7Area status, area 7Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603107Area State 8Area status, area 8Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603108Area State 9Area status, area 9Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603109Area State 10Area status, area 10Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603110Area State 11Area status, area 11Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603111Area State 12Area status, area 12Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603112Area State 13Area status, area 13Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603113Area State 14Area status, area 14Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603114Area State 15Area status, area 15Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603115Area State 16Area status, area 16Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603116Area State 17Area status, area 17Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603117Area State 18Area status, area 18Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603118Area State 19Area status, area 19Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603119Area State 20Area status, area 20Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603120Area State 21Area status, area 21Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603121Area State 22Area status, area 22Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603122Area State 23Area status, area 23Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603123Area State 24Area status, area 24Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603124Area State 25Area status, area 25Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603125Area State 26Area status, area 26Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603126Area State 27Area status, area 27Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603127Area State 28Area status, area 28Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603128Area State 29Area status, area 29Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603129Area State 30Area status, area 30Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603130Area State 31Area status, area 31Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603131Area State 32Area status, area 32Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603132Area State 33Area status, area 33Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603133Area State 34Area status, area 34Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603134Area State 35Area status, area 35Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603135Area State 36Area status, area 36Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603136Area State 37Area status, area 37Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603137Area State 38Area status, area 38Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603138Area State 39Area status, area 39Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603139Area State 40Area status, area 40Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603140Area State 41Area status, area 41Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603141Area State 42Area status, area 42Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603142Area State 43Area status, area 43Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603143Area State 44Area status, area 44Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603144Area State 45Area status, area 45Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603145Area State 46Area status, area 46Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603146Area State 47Area status, area 47Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603147Area State 48Area status, area 48Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603148Area State 49Area status, area 49Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI603149Area State 50Area status, area 50Read1=Warning, 2=Error, 3=Absent, 4=Inactive, 5=FWA, 6=Active
MI5054Error FlagFlag of System-Master ErrorRead1=No errors and no warnings pending, 2=Errors pending, 3=Warnings pending, 4=Info pending
MImin5055Error CategoryCategory of System-Master ErrorRead1=Fatal error system, 2=Fatal error hp-ring, 3=Error hp-ring (FWA -possible), 4=Error w. impact on water quality, 5=Error (system partially down), 6=Error (limited operation), 7=Warning (action urgently needed), 8=Warning (action may needed), 9=Service due, 10=Service soon due, 11=no error 8)
MI41System Viewer Error StateCategory of System-Viewer ErrorRead1=no error, 2=warning, 3=error
AI15112Number of AreasNumber of areas installedRead
AI10046Serial NumberSerial NumberRead
AI15220UV Lamp ReplacementTimestamp of the last UV lamp replacementsRead
AI15229Micro Filter ReplacementTimestamp of the last microfilter replacementsRead
AI1611400Area Actual Temperature 1Actual temperature of area, area 1°C or °FRead
AI1611401Area Actual Temperature 2Actual temperature of area, area 2°C or °FRead
AI1611402Area Actual Temperature 3Actual temperature of area, area 3°C or °FRead
AI1611403Area Actual Temperature 4Actual temperature of area, area 4°C or °FRead
AI1611404Area Actual Temperature 5Actual temperature of area, area 5°C or °FRead
AI1611405Area Actual Temperature 6Actual temperature of area, area 6°C or °FRead
AI1611406Area Actual Temperature 7Actual temperature of area, area 7°C or °FRead
AI1611407Area Actual Temperature 8Actual temperature of area, area 8°C or °FRead
AI1611408Area Actual Temperature 9Actual temperature of area, area 9°C or °FRead
AI1611409Area Actual Temperature 10Actual temperature of area, area 10°C or °FRead
AI1611410Area Actual Temperature 11Actual temperature of area, area 11°C or °FRead
AI1611411Area Actual Temperature 12Actual temperature of area, area 12°C or °FRead
AI1611412Area Actual Temperature 13Actual temperature of area, area 13°C or °FRead
AI1611413Area Actual Temperature 14Actual temperature of area, area 14°C or °FRead
AI1611414Area Actual Temperature 15Actual temperature of area, area 15°C or °FRead
AI1611415Area Actual Temperature 16Actual temperature of area, area 16°C or °FRead
AI1611416Area Actual Temperature 17Actual temperature of area, area 17°C or °FRead
AI1611417Area Actual Temperature 18Actual temperature of area, area 18°C or °FRead
AI1611418Area Actual Temperature 19Actual temperature of area, area 19°C or °FRead
AI1611419Area Actual Temperature 20Actual temperature of area, area 20°C or °FRead
AI1611420Area Actual Temperature 21Actual temperature of area, area 21°C or °FRead
AI1611421Area Actual Temperature 22Actual temperature of area, area 22°C or °FRead
AI1611422Area Actual Temperature 23Actual temperature of area, area 23°C or °FRead
AI1611423Area Actual Temperature 24Actual temperature of area, area 24°C or °FRead
AI1611424Area Actual Temperature 25Actual temperature of area, area 25°C or °FRead
AI1611425Area Actual Temperature 26Actual temperature of area, area 26°C or °FRead
AI1611426Area Actual Temperature 27Actual temperature of area, area 27°C or °FRead
AI1611427Area Actual Temperature 28Actual temperature of area, area 28°C or °FRead
AI1611428Area Actual Temperature 29Actual temperature of area, area 29°C or °FRead
AI1611429Area Actual Temperature 30Actual temperature of area, area 30°C or °FRead
AI1611430Area Actual Temperature 31Actual temperature of area, area 31°C or °FRead
AI1611431Area Actual Temperature 32Actual temperature of area, area 32°C or °FRead
AI1611432Area Actual Temperature 33Actual temperature of area, area 33°C or °FRead
AI1611433Area Actual Temperature 34Actual temperature of area, area 34°C or °FRead
AI1611434Area Actual Temperature 35Actual temperature of area, area 35°C or °FRead
AI1611435Area Actual Temperature 36Actual temperature of area, area 36°C or °FRead
AI1611436Area Actual Temperature 37Actual temperature of area, area 37°C or °FRead
AI1611437Area Actual Temperature 38Actual temperature of area, area 38°C or °FRead
AI1611438Area Actual Temperature 39Actual temperature of area, area 39°C or °FRead
AI1611439Area Actual Temperature 40Actual temperature of area, area 40°C or °FRead
AI1611440Area Actual Temperature 41Actual temperature of area, area 41°C or °FRead
AI1611441Area Actual Temperature 42Actual temperature of area, area 42°C or °FRead
AI1611442Area Actual Temperature 43Actual temperature of area, area 43°C or °FRead
AI1611443Area Actual Temperature 44Actual temperature of area, area 44°C or °FRead
AI1611444Area Actual Temperature 45Actual temperature of area, area 45°C or °FRead
AI1611445Area Actual Temperature 46Actual temperature of area, area 46°C or °FRead
AI1611446Area Actual Temperature 47Actual temperature of area, area 47°C or °FRead
AI1611447Area Actual Temperature 48Actual temperature of area, area 48°C or °FRead
AI1611448Area Actual Temperature 49Actual temperature of area, area 49°C or °FRead
AI1611449Area Actual Temperature 50Actual temperature of area, area 50°C or °FRead
AImin1611300Actual Humidity Area 1Actual humidity of area, area 1%Read
AI1611301Actual Humidity Area 2Actual humidity of area, area 2%Read
AI1611302Actual Humidity Area 3Actual humidity of area, area 3%Read
AI1611303Actual Humidity Area 4Actual humidity of area, area 4%Read
AI1611304Actual Humidity Area 5Actual humidity of area, area 5%Read
AI1611305Actual Humidity Area 6Actual humidity of area, area 6%Read
AI1611306Actual Humidity Area 7Actual humidity of area, area 7%Read
AI1611307Actual Humidity Area 8Actual humidity of area, area 8%Read
AI1611308Actual Humidity Area 9Actual humidity of area, area 9%Read
AI1611309Actual Humidity Area 10Actual humidity of area, area 10%Read
AI1611310Actual Humidity Area 11Actual humidity of area, area 11%Read
AI1611311Actual Humidity Area 12Actual humidity of area, area 12%Read
AI1611312Actual Humidity Area 13Actual humidity of area, area 13%Read
AI1611313Actual Humidity Area 14Actual humidity of area, area 14%Read
AI1611314Actual Humidity Area 15Actual humidity of area, area 15%Read
AI1611315Actual Humidity Area 16Actual humidity of area, area 16%Read
AI1611316Actual Humidity Area 17Actual humidity of area, area 17%Read
AI1611317Actual Humidity Area 18Actual humidity of area, area 18%Read
AI1611318Actual Humidity Area 19Actual humidity of area, area 19%Read
AI1611319Actual Humidity Area 20Actual humidity of area, area 20%Read
AI1611320Actual Humidity Area 21Actual humidity of area, area 21%Read
AI1611321Actual Humidity Area 22Actual humidity of area, area 22%Read
AI1611322Actual Humidity Area 23Actual humidity of area, area 23%Read
AI1611323Actual Humidity Area 24Actual humidity of area, area 24%Read
AI1611324Actual Humidity Area 25Actual humidity of area, area 25%Read
AI1611325Actual Humidity Area 26Actual humidity of area, area 26%Read
AI1611326Actual Humidity Area 27Actual humidity of area, area 27%Read
AI1611327Actual Humidity Area 28Actual humidity of area, area 28%Read
AI1611328Actual Humidity Area 29Actual humidity of area, area 29%Read
AI1611329Actual Humidity Area 30Actual humidity of area, area 30%Read
AI1611330Actual Humidity Area 31Actual humidity of area, area 31%Read
AI1611331Actual Humidity Area 32Actual humidity of area, area 32%Read
AI1611332Actual Humidity Area 33Actual humidity of area, area 33%Read
AI1611333Actual Humidity Area 34Actual humidity of area, area 34%Read
AI1611334Actual Humidity Area 35Actual humidity of area, area 35%Read
AI1611335Actual Humidity Area 36Actual humidity of area, area 36%Read
AI1611336Actual Humidity Area 37Actual humidity of area, area 37%Read
AI1611337Actual Humidity Area 38Actual humidity of area, area 38%Read
AI1611338Actual Humidity Area 39Actual humidity of area, area 39%Read
AI1611339Actual Humidity Area 40Actual humidity of area, area 40%Read
AI1611340Actual Humidity Area 41Actual humidity of area, area 41%Read
AI1611341Actual Humidity Area 42Actual humidity of area, area 42%Read
AI1611342Actual Humidity Area 43Actual humidity of area, area 43%Read
AI1611343Actual Humidity Area 44Actual humidity of area, area 44%Read
AI1611344Actual Humidity Area 45Actual humidity of area, area 45%Read
AI1611345Actual Humidity Area 46Actual humidity of area, area 46%Read
AI1611346Actual Humidity Area 47Actual humidity of area, area 47%Read
AI1611347Actual Humidity Area 48Actual humidity of area, area 48%Read
AI1611348Actual Humidity Area 49Actual humidity of area, area 49%Read
AI1611349Actual Humidity Area 50Actual humidity of area, area 50%Read
AI15231Error TimeTimestamp of actual System Master ErrorsRead
AImin15232Error CodeError Code of System Master ErrorRead
AI10020System Viewer Err Warn CodeError Code of external control unit errorRead0=no error
AVmin1611600Area Setpoint 1Humidity setpoint of area, area 1%Write
AV1611601Area Setpoint 2Humidity setpoint of area, area 2%Write
AV1611602Area Setpoint 3Humidity setpoint of area, area 3%Write
AV1611603Area Setpoint 4Humidity setpoint of area, area 4%Write
AV1611604Area Setpoint 5Humidity setpoint of area, area 5%Write
AV1611605Area Setpoint 6Humidity setpoint of area, area 6%Write
AV1611606Area Setpoint 7Humidity setpoint of area, area 7%Write
AV1611607Area Setpoint 8Humidity setpoint of area, area 8%Write
AV1611608Area Setpoint 9Humidity setpoint of area, area 9%Write
AV1611609Area Setpoint 10Humidity setpoint of area, area 10%Write
AV1611610Area Setpoint 11Humidity setpoint of area, area 11%Write
AV1611611Area Setpoint 12Humidity setpoint of area, area 12%Write
AV1611612Area Setpoint 13Humidity setpoint of area, area 13%Write
AV1611613Area Setpoint 14Humidity setpoint of area, area 14%Write
AV1611614Area Setpoint 15Humidity setpoint of area, area 15%Write
AV1611615Area Setpoint 16Humidity setpoint of area, area 16%Write
AV1611616Area Setpoint 17Humidity setpoint of area, area 17%Write
AV1611617Area Setpoint 18Humidity setpoint of area, area 18%Write
AV1611618Area Setpoint 19Humidity setpoint of area, area 19%Write
AV1611619Area Setpoint 20Humidity setpoint of area, area 20%Write
AV1611620Area Setpoint 21Humidity setpoint of area, area 21%Write
AV1611621Area Setpoint 22Humidity setpoint of area, area 22%Write
AV1611622Area Setpoint 23Humidity setpoint of area, area 23%Write
AV1611623Area Setpoint 24Humidity setpoint of area, area 24%Write
AV1611624Area Setpoint 25Humidity setpoint of area, area 25%Write
AV1611625Area Setpoint 26Humidity setpoint of area, area 26%Write
AV1611626Area Setpoint 27Humidity setpoint of area, area 27%Write
AV1611627Area Setpoint 28Humidity setpoint of area, area 28%Write
AV1611628Area Setpoint 29Humidity setpoint of area, area 29%Write
AV1611629Area Setpoint 30Humidity setpoint of area, area 30%Write
AV1611630Area Setpoint 31Humidity setpoint of area, area 31%Write
AV1611631Area Setpoint 32Humidity setpoint of area, area 32%Write
AV1611632Area Setpoint 33Humidity setpoint of area, area 33%Write
AV1611633Area Setpoint 34Humidity setpoint of area, area 34%Write
AV1611634Area Setpoint 35Humidity setpoint of area, area 35%Write
AV1611635Area Setpoint 36Humidity setpoint of area, area 36%Write
AV1611636Area Setpoint 37Humidity setpoint of area, area 37%Write
AV1611637Area Setpoint 38Humidity setpoint of area, area 38%Write
AV1611638Area Setpoint 39Humidity setpoint of area, area 39%Write
AV1611639Area Setpoint 40Humidity setpoint of area, area 40%Write
AV1611640Area Setpoint 41Humidity setpoint of area, area 41%Write
AV1611641Area Setpoint 42Humidity setpoint of area, area 42%Write
AV1611642Area Setpoint 43Humidity setpoint of area, area 43%Write
AV1611643Area Setpoint 44Humidity setpoint of area, area 44%Write
AV1611644Area Setpoint 45Humidity setpoint of area, area 45%Write
AV1611645Area Setpoint 46Humidity setpoint of area, area 46%Write
AV1611646Area Setpoint 47Humidity setpoint of area, area 47%Write
AV1611647Area Setpoint 48Humidity setpoint of area, area 48%Write
AV1611648Area Setpoint 49Humidity setpoint of area, area 49%Write
AV1611649Area Setpoint 50Humidity setpoint of area, area 50%Write

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Condair Vita and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Condair Condair Vita

How many BACnet points does the Condair Condair Vita have?

This list has 214 BACnet objects: 107 analog inputs, 50 analog values, 1 device, 56 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Condair Condair Vita BACnet points are writable?

50 of the 214 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Condair Condair Vita BACnet documentation?

The source is BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) (2603582-F), revision 2026-07, published free by Condair at https://www.condair.co.uk/consense/bms-communication-ic-2.0/am_bms_interface_bacnet_on_board_2603582_en.pdf.

What are the minimum BACnet points to integrate the Condair Condair Vita?

Start with AV 1611600 Area Setpoint 1 (Area 1 humidity setpoint); MI 5035 Pressure Status HP Line (High-pressure stage status); MI 5033 Reverse Osmosis State (Reverse osmosis stage status); MI 603100 Area State 1 (Area 1 state (one per area)); AI 1611300 Actual Humidity Area 1 (Measured RH in area 1, %); MI 5055 Error Category (Error severity; alarm on categories 1-7 (11 = no error)); AI 15232 Error Code (System Master error code).

Can the BMS supply sensor values to the Condair Condair Vita?

No BMS-fed sensor inputs are listed; the BMS can write each area's humidity setpoint (AV 1611600-1611649, 20-100 %).

How do I check these points on the real Condair Vita?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Condair BACnet points lists

Source: BACnet on-board - Addendum manual for installation and operation (DL II, ME II, RS II, RO-E and Vita) · 2603582-F · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.