Duct humidity and temperature sensor · BACnet points list
Veris HD2 Protocol Series duct humidity / temperature sensor BACnet points list
Updated 12 November 2026
The HD2 Protocol Series is a duct or plant-room humidity and temperature sensor with an RS-485 port for BACnet MS/TP or Modbus. Its BACnet list is three objects: temperature, humidity and a display-units switch for LCD models. It shares object names with the HW2 wall sensor but has none of the HW2 touchscreen objects.
This page lists 3 BACnet objects for the Veris HD2 Protocol Series duct humidity / temperature sensor — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Veris’s own free documentation, linked below.
- Manufacturer
- Veris
- Model
- HD2 Protocol Series duct humidity / temperature sensor
- Equipment
- Duct humidity and temperature sensor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 3 (1 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- Vendor ID + nnn (nnn = MS/TP address)
- Also known as
- HD2, HD2 Protocol, HD2XPXXXX, Plant Room Humidity and Temperature Unit, SpaceLogic SHD2, SHD2 Series, GEX55253, GEX55243
Reference only, provided as-is: verify against Veris’s current documentation and the live device before use. Not official Veris information. Terms of use.
BMS integration notes: Veris HD2 Protocol Series duct humidity / temperature sensor
Set the MS/TP address and protocol, then read AI 1 and AI 2.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
Network setup
- Device instance defaults to Vendor ID followed by the MS/TP address; Object_Identifier is writable.
Veris HD2 Protocol Series duct humidity / temperature sensor BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Room Temperature | Temperature | °C | Read | |
| AImin | 2 | Room Humidity | Relative humidity | %RH | Read | |
| BV | 4 | Temperature Units* | Display units (LCD models) | Write | Active=Fahrenheit; Inactive=Celsius |
No points match these filters.
Object ID lookup: Veris HD2 Protocol Series duct humidity / temperature sensor point IDs by name
Integration notes
- The objects table has no access column; BV 4 is marked writable from its description.
- BV 4 is kept through power outages and applies to LCD models only (as printed).
- Schneider SpaceLogic SHD2 Series (guide GEX55243) prints the same table.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HD2 Protocol Series duct humidity / temperature sensor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Veris HD2 Protocol Series duct humidity / temperature sensor
How many BACnet points does the Veris HD2 Protocol Series duct humidity / temperature sensor have?
This list has 3 BACnet objects: 2 analog inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Veris HD2 Protocol Series duct humidity / temperature sensor BACnet points are writable?
1 of the 3 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Veris HD2 Protocol Series duct humidity / temperature sensor BACnet documentation?
The source is HD2 Protocol Series Installation Guide (GEX55253-03), revision 2026-09, published free by Veris at https://download.schneider-electric.com/files?p_Doc_Ref=GEX55253.
What are the minimum BACnet points to integrate the Veris HD2 Protocol Series duct humidity / temperature sensor?
Start with AI 1 Room Temperature (Air temperature); AI 2 Room Humidity (Relative humidity, %).
How do I check these points on the real HD2 Protocol Series duct humidity / temperature sensor?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Veris BACnet points lists
- Duct air quality sensor (CO2, VOC, PM, humidity, temperature)
Veris CD2 Protocol Series duct / plant-room air quality sensor
Veris CD2 Protocol Series duct and plant-room air quality sensors (and the Schneider SpaceLogic SCD2 twin) set to BACnet MS/TP.
Also known as: CD2, CD2 Protocol, CD2XPXXXX, Plant Room Air Quality Unit, SpaceLogic SCD2, SCD2 Series, GEX55250, GEX55240 - Indoor air quality sensor (CO2, VOC, temperature, humidity)
Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor
Veris CW2 Protocol Series wall air quality sensors, and the identical Schneider SpaceLogic SLP Air Quality Series, on BACnet MS/TP.
Also known as: CW2, CW2 Protocol, SpaceLogic SLP Air Quality, SLP Series Air Quality, Z207902, Living Space Room Unit - Room CO2 sensor (wall)
Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation)
Veris CWLP and CWXP wall CO2 sensors with optional humidity, temperature and slider, set to BACnet MS/TP.
Also known as: CWLP, CWXP, CWxP, CWLP2TX3, CWxPxxx, Veris CWxP Environmental Sensor, Z205597 - Power and energy meter
Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP)
Veris E50H2 and E50H5 DIN-rail power and energy meters with BACnet MS/TP; the E50H5 adds data logging and a real-time clock alert.
Also known as: E50H2, E50H5, E50H2A, E50H5A, Veris E50, E50Hx, ZL0071 - Power and energy meter (bi-directional)
Veris E51H2 / E51H5 bi-directional compact power and energy meter (BACnet MS/TP)
Veris E51H2 and E51H5 DIN-rail three-phase meters with BACnet MS/TP that measure import and export energy; the E51H5 adds data logging.
Also known as: E51H2, E51H5, Veris E51, E51Hx, E51 Series, ZL0109 - Power and energy meter
Veris E71 series energy meter (BACnet IP)
Veris E71 series DIN-rail three-phase energy meters (E71E3, E71E3A, E71E3X, E71E3AX) with dual Ethernet ports.
Also known as: E71, E71E3, E71E3A, E71E3X, E71E3AX, Veris E71, E71 Series Energy Meter - Gas detection sensor (wall platform)
Veris GWNP Series wall gas sensor platform (AG sensors)
Veris GWNP wall-mounted gas platforms fitted with a Veris AG Series gas sensor, on BACnet MS/TP.
Also known as: GWNP, GWNPxx, GWN, Veris gas platform BACnet, AG Series gas sensor - Room humidity and temperature sensor (wall)
Veris HW2 Protocol Series humidity and temperature room sensor
Veris HW2 Protocol Series wall humidity/temperature sensors (optional touchscreen) set to BACnet MS/TP.
Also known as: HW2, HW2 Protocol, HW2TP2A, Living Space Room Unit, Veris HW2 BACnet - Indoor air quality sensor (PM, CO2, VOC, temperature, humidity)
Veris PMW Protocol Series particulate (PM), CO2 and VOC room sensor
Veris PMW Protocol Series wall air quality sensors, and the identical Schneider SpaceLogic SLP PM Series, on BACnet MS/TP.
Also known as: PMW, PMW Protocol, SpaceLogic SLP PM, SLP Series PM, ZL0199, Veris PM sensor BACnet - Room temperature sensor (wall)
Veris TW2 Protocol Series temperature room sensor
Veris TW2 Protocol Series wall temperature sensors (optional touchscreen) set to BACnet MS/TP.
Also known as: TW2, TW2 Protocol, Living Space Room Unit, Veris TW2 BACnet
Source: HD2 Protocol Series Installation Guide · GEX55253-03 · rev. 2026-09. Object names, instances and units are reproduced as published; descriptions are our own.