Room CO2 sensor (wall) · BACnet points list

Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The CWLP/CWXP is the older Veris wall CO2 sensor with a relay output and an RS-485 port that runs BACnet MS/TP or Modbus (DIP switch 1). It reports CO2 plus optional humidity, temperature and slider position, and has writable relay setpoint/deadband, ABC calibration mode, offsets, units and an override button flag. It is the predecessor of the CW2 Protocol series and uses a different object set.

This page lists 15 BACnet objects for the Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Veris’s documentation hosted by Kele, not by Veris itself, so treat it as unofficial.

Manufacturer
Veris
Model
CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation)
Equipment
Room CO2 sensor (wall)
Equipment type
Thermostats, sensors & meters
BACnet objects
15 (10 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
133nnn (nnn = MS/TP address)
Also known as
CWLP, CWXP, CWxP, CWLP2TX3, CWxPxxx, Veris CWxP Environmental Sensor, Z205597
Source document
CWLP, CWXP Installation Guide · Z205597-0G · rev. 2016-03 (unofficial copy, hosted by Kele)
Download CSV 15 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Veris’s current documentation and the live device before use. Not official Veris information. Terms of use.

BMS integration notes: Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation)

Integration in brief

Set DIP switch 1 down for BACnet, set the MS/TP address on switches 2-8 and the baud rate on the configuration switches, then read CO2_Level and any fitted humidity, temperature or slider values.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1CO2_LevelRoom CO2, ppmRead
AI 3TemperatureRoom temperature (if fitted)Read
AI 2HumidityRoom relative humidity, % (if fitted)Read
AI 4SliderOccupant slider position, % (if fitted)Read
BV 4OverrideOverride button pressed; write 0 to clearWrite
BI 1Relay_OnCO2 relay energizedRead

Network setup

Watch out for

Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

15 of 15 shown
Type
Access
Show
Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation) BACnet Points List
DescriptionStates
AImin1CO2_LevelCO2 concentrationppmRead
AImin2HumidityRelative humidity (if sensor installed)%RHRead
AImin3TemperatureTemperature (if sensor installed)°F or °CRead
AImin4SliderSlider position (if fitted)%Read
AV1Device_InstanceAlternative way to set the device instance; negative restores 133nnnWrite
AV2CO2_SetpointCO2 relay setpoint, default 800ppmWrite
AV3CO2_DeadbandCO2 relay deadband, default 50ppmWrite
AV4Auto_CalABC auto-calibration: 0 normal, 1 low, 2 offWrite0=Normal; 1=Low; 2=Off
AV5Temp_OffsetTemperature offset, current units (if present)Write
AV6RH_OffsetHumidity offset (if present)%RHWrite
BImin1Relay_OnRelay energized by gas level (ignores BV 2)Read1=Energized
BV1FahrenheitTemperature units, default 1Write0=Celsius; 1=Fahrenheit
BV2Relay_OverrideForces relay on; volatile, default 0Write1=Force relay on
BV3Cal_LockoutLocks out calibration, default 1Write1=Locked
BVmin4OverrideOverride button pressed; write 0 to reset (if present)Write1=Pressed
Object ID lookup: Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation)

How many BACnet points does the Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation) have?

This list has 15 BACnet objects: 4 analog inputs, 6 analog values, 1 binary input, 4 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation) BACnet points are writable?

10 of the 15 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation) BACnet documentation?

Veris does not publish it on its own website. This list comes from CWLP, CWXP Installation Guide (Z205597-0G), revision 2016-03, a copy hosted by Kele at https://assets.kele.com/product-assets/veris-industries/skus/cwlp2tx3/related/installsheet_1024_cwlp2tx3.pdf. Ask Veris or its representative for the current revision.

What are the minimum BACnet points to integrate the Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation)?

Start with AI 1 CO2_Level (Room CO2, ppm); AI 3 Temperature (Room temperature (if fitted)); AI 2 Humidity (Room relative humidity, % (if fitted)); AI 4 Slider (Occupant slider position, % (if fitted)); BV 4 Override (Override button pressed; write 0 to clear); BI 1 Relay_On (CO2 relay energized).

How do I check these points on the real CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Veris BACnet points lists

Source: CWLP, CWXP Installation Guide · Z205597-0G · rev. 2016-03. Object names, instances and units are reproduced as published; descriptions are our own.