Power and energy meter · BACnet points list
Veris E71 series energy meter (BACnet IP) BACnet points list
Updated 12 November 2026Unofficial source
The E71 is a compact three-phase DIN-rail meter with two Ethernet ports and native BACnet IP, Modbus TCP and SNMP. Its object list is read-only Analog Inputs for energy (net, import, export, per quadrant and per phase), power, demand, volts, amps, power factor, frequency, pulse counts, input/relay status and four tariff registers, writable Analog Values for setup, and alert Binary Inputs.
This page lists 131 BACnet objects for the Veris E71 series energy meter (BACnet IP) — 33 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Veris’s documentation hosted by BACnet International, not by Veris itself, so treat it as unofficial.
- Manufacturer
- Veris
- Model
- E71 series energy meter (BACnet IP)
- Equipment
- Power and energy meter
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 131 (33 writable)
- Transport
- BACnet IP
- Firmware
- Firmware 1.9.0, application 111.241.298 (PICS)
- Also known as
- E71, E71E3, E71E3A, E71E3X, E71E3AX, Veris E71, E71 Series Energy Meter
- Source document
- E71 - Protocol Implementation Conformance Statement · rev. 2024-08-06 (unofficial copy, hosted by BACnet International)
Reference only, provided as-is: verify against Veris’s current documentation and the live device before use. Not official Veris information. Terms of use.
BMS integration notes: Veris E71 series energy meter (BACnet IP)
Give the meter an IP address and device instance, set system type, CT and PT values in the AV setup objects (or on the meter), then trend energy and real power and watch the alert BIs or AI 83 Alarm_Bitmap.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 2 | KWh_Import | Real energy import | Read |
| AI 1 | KWh_Net | Net real energy (import minus export) | Read |
| AI 11 | KW_Total | Total real power | Read |
| AI 19 | KW_Present_Demand | Real power present demand | Read |
| AI 14 | PF_Total | Total power factor | Read |
| AI 15 | Volts_LL_Avg | Average line-line voltage | Read |
| AI 17 | Current_Average | Average current | Read |
| AI 83 | Alarm_Bitmap | All alert bits as one number | Read |
Network setup
- BACnet IP (Annex J); Object_Identifier, Object_Name and Location of the device object are writable.
Watch out for
- The PICS gives no units; check each AI's Units property after connecting.
Veris E71 series energy meter (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | KWh_Net | Net real energy (import - export) | Read | ||
| AImin | 2 | KWh_Import | Real energy import | Read | ||
| AI | 3 | KWh_Export | Real energy export | Read | ||
| AI | 4 | KVARh_Q1 | KVARh Q1 | Read | ||
| AI | 5 | KVARh_Q2 | KVARh Q2 | Read | ||
| AI | 6 | KVARh_Q3 | KVARh Q3 | Read | ||
| AI | 7 | KVARh_Q4 | KVARh Q4 | Read | ||
| AI | 8 | Net_KVAh | Net apparent energy | Read | ||
| AI | 9 | KVAh_Import | KVAh Import | Read | ||
| AI | 10 | KVAh_Export | KVAh Export | Read | ||
| AImin | 11 | KW_Total | Total real power | Read | ||
| AI | 12 | KVAR_Total | Total reactive power | Read | ||
| AI | 13 | KVA_Total | Total apparent power | Read | ||
| AImin | 14 | PF_Total | Total power factor | Read | ||
| AImin | 15 | Volts_LL_Avg | Average line-line voltage | Read | ||
| AI | 16 | Volts_LN_Avg | Average line-neutral voltage | Read | ||
| AImin | 17 | Current_Average | Average current | Read | ||
| AI | 18 | Frequency | Frequency | Read | ||
| AImin | 19 | KW_Present_Demand | Real power present demand | Read | ||
| AI | 20 | KVAR_Present_Demand | Reactive power present demand | Read | ||
| AI | 21 | KVA_Present_Demand | Apparent power present demand | Read | ||
| AI | 22 | KW_Max_Demand_Import | Real power max demand, import | Read | ||
| AI | 23 | KVAR_Max_Demand_Import | Reactive power max demand, import | Read | ||
| AI | 24 | KVA_Max_Demand_Import | Apparent power max demand, import | Read | ||
| AI | 29 | Pulse_Count_1 | Digital input 1 pulse count | Read | ||
| AI | 30 | Pulse_Count_2 | Digital input 2 pulse count | Read | ||
| AI | 31 | KWh_Import_A | KWh Import A | Read | ||
| AI | 32 | KWh_Import_B | KWh Import B | Read | ||
| AI | 33 | KWh_Import_C | KWh Import C | Read | ||
| AI | 34 | KWh_Export_A | KWh Export A | Read | ||
| AI | 35 | KWh_Export_B | KWh Export B | Read | ||
| AI | 36 | KWh_Export_C | KWh Export C | Read | ||
| AI | 37 | KVARh_Q1_A | KVARh Q1 A | Read | ||
| AI | 38 | KVARh_Q1_B | KVARh Q1 B | Read | ||
| AI | 39 | KVARh_Q1_C | KVARh Q1 C | Read | ||
| AI | 40 | KVARh_Q2_A | KVARh Q2 A | Read | ||
| AI | 41 | KVARh_Q2_B | KVARh Q2 B | Read | ||
| AI | 42 | KVARh_Q2_C | KVARh Q2 C | Read | ||
| AI | 43 | KVARh_Q3_A | KVARh Q3 A | Read | ||
| AI | 44 | KVARh_Q3_B | KVARh Q3 B | Read | ||
| AI | 45 | KVARh_Q3_C | KVARh Q3 C | Read | ||
| AI | 46 | KVARh_Q4_A | KVARh Q4 A | Read | ||
| AI | 47 | KVARh_Q4_B | KVARh Q4 B | Read | ||
| AI | 48 | KVARh_Q4_C | KVARh Q4 C | Read | ||
| AI | 49 | KVAh_Import_A | KVAh Import A | Read | ||
| AI | 50 | KVAh_Import_B | KVAh Import B | Read | ||
| AI | 51 | KVAh_Import_C | KVAh Import C | Read | ||
| AI | 52 | KVAh_Export_A | KVAh Export A | Read | ||
| AI | 53 | KVAh_Export_B | KVAh Export B | Read | ||
| AI | 54 | KVAh_Export_C | KVAh Export C | Read | ||
| AI | 55 | KW_A | KW A | Read | ||
| AI | 56 | KW_B | KW B | Read | ||
| AI | 57 | KW_C | KW C | Read | ||
| AI | 58 | KVAR_A | KVAR A | Read | ||
| AI | 59 | KVAR_B | KVAR B | Read | ||
| AI | 60 | KVAR_C | KVAR C | Read | ||
| AI | 61 | KVA_A | KVA A | Read | ||
| AI | 62 | KVA_B | KVA B | Read | ||
| AI | 63 | KVA_C | KVA C | Read | ||
| AI | 64 | PF_A | PF A | Read | ||
| AI | 65 | PF_B | PF B | Read | ||
| AI | 66 | PF_C | PF C | Read | ||
| AI | 67 | Volts_AB | Volts AB | Read | ||
| AI | 68 | Volts_BC | Volts BC | Read | ||
| AI | 69 | Volts_AC | Volts AC | Read | ||
| AI | 70 | Volts_AN | Volts AN | Read | ||
| AI | 71 | Volts_BN | Volts BN | Read | ||
| AI | 72 | Volts_CN | Volts CN | Read | ||
| AI | 73 | Current_A | Current A | Read | ||
| AI | 74 | Current_B | Current B | Read | ||
| AI | 75 | Current_C | Current C | Read | ||
| AI | 76 | Max_Power | Full-scale power | Read | ||
| AI | 78 | Energy_Resets | Count of energy resets | Read | ||
| AI | 81 | Power_Up_Count | Count of power-ups | Read | ||
| AImin | 83 | Alarm_Bitmap | All alert bits as one number | Read | ||
| AI | 84 | S1_Status | Digital input 1 status | Read | ||
| AI | 85 | S2_Status | Digital input 2 status | Read | ||
| AI | 86 | Relay_Counter | Relay operation count | Read | ||
| AI | 87 | Relay_Status | Relay output status | Read | ||
| AI | 88 | Real_Energy_Import_Tariff1 | Real energy import, tariff 1 | Read | ||
| AI | 89 | Real_Energy_Import_Tariff2 | Real energy import, tariff 2 | Read | ||
| AI | 90 | Real_Energy_Import_Tariff3 | Real energy import, tariff 3 | Read | ||
| AI | 91 | Real_Energy_Import_Tariff4 | Real energy import, tariff 4 | Read | ||
| AV | 1 | Config | Configuration register | Write | ||
| AV | 2 | System_Type | System type (setting) | Write | ||
| AV | 3 | CT_Ratio_Primary | Ct ratio primary (setting) | Write | ||
| AV | 4 | CT_Ratio_Secondary | Ct ratio secondary (setting) | Write | ||
| AV | 5 | PT_Ratio | Pt ratio (setting) | Write | ||
| AV | 6 | System_Voltage | System voltage (setting) | Write | ||
| AV | 7 | Display_Units | Display units (setting) | Write | ||
| AV | 8 | Phase_Loss_Voltage_Threshold | Phase loss voltage threshold (setting) | Write | ||
| AV | 9 | Phase_Loss_Imbalance_Threshold | Phase loss imbalance threshold (setting) | Write | ||
| AV | 10 | Subintervals | Subintervals (setting) | Write | ||
| AV | 11 | Subinterval_Length | Subinterval length (setting) | Write | ||
| AV | 12 | S1_Control_mode | S1 control mode (setting) | Write | ||
| AV | 13 | S2_Control_mode | S2 control mode (setting) | Write | ||
| AV | 14 | Relay_control_mode | Relay control mode (setting) | Write | ||
| AV | 15 | Relay_Behavior_mode | Relay behavior mode (setting) | Write | ||
| AV | 16 | Relay_Output_Enable_Disable | Relay output enable disable (setting) | Write | ||
| AV | 17 | Applicable_Multi_Tariff | Applicable multi tariff (setting) | Write | ||
| AV | 18 | Mode_of_LED | Mode of led (setting) | Write | ||
| AV | 19 | Channel | Channel (setting) | Write | ||
| AV | 20 | Pulse_weight | Pulse weight (setting) | Write | ||
| AV | 21 | PT_Primary | Pt primary (setting) | Write | ||
| AV | 22 | PT_Secondary | Pt secondary (setting) | Write | ||
| AV | 23 | Demand_Method | Demand method (setting) | Write | ||
| AV | 24 | Demand_Interval_Duration | Demand interval duration (setting) | Write | ||
| AV | 25 | Sub_Interval_Duration | Sub interval duration (setting) | Write | ||
| AV | 26 | Relay_TimedMode_Time | Relay timedmode time (setting) | Write | ||
| AV | 27 | Input_Metering_Ch1_PulseWeight | Input metering ch1 pulseweight (setting) | Write | ||
| AV | 28 | Input_Metering_Ch2_PulseWeight | Input metering ch2 pulseweight (setting) | Write | ||
| AV | 29 | Nominal_Frequency | Nominal frequency (setting) | Write | ||
| AV | 30 | VT_Number | Vt number (setting) | Write | ||
| AV | 31 | CT_Number | Ct number (setting) | Write | ||
| AV | 32 | VT_Connection_Type | Vt connection type (setting) | Write | ||
| AV | 33 | Multi_Tarrif_Control_Mode | Multi tarrif control mode (setting) | Write | ||
| BI | 1 | Volts_Error_A | Volts Error A alert | Read | ||
| BI | 2 | Volts_Error_B | Volts Error B alert | Read | ||
| BI | 3 | Volts_Error_C | Volts Error C alert | Read | ||
| BI | 4 | Current_Error_A | Current Error A alert | Read | ||
| BI | 5 | Current_Error_B | Current Error B alert | Read | ||
| BI | 6 | Current_Error_C | Current Error C alert | Read | ||
| BI | 7 | Frequency_Error | Frequency Error alert | Read | ||
| BI | 9 | Phase_Loss_A | Phase Loss A alert | Read | ||
| BI | 10 | Phase_Loss_B | Phase Loss B alert | Read | ||
| BI | 11 | Phase_Loss_C | Phase Loss C alert | Read | ||
| BI | 12 | Low_PF_A | Low PF A alert | Read | ||
| BI | 13 | Low_PF_B | Low PF B alert | Read | ||
| BI | 14 | Low_PF_C | Low PF C alert | Read | ||
| BI | 15 | Energy_OverRun | Energy OverRun alert | Read | ||
| BI | 16 | Energy_Config_Err | Energy Config Err alert | Read |
No points match these filters.
Object ID lookup: Veris E71 series energy meter point IDs by name
AI1KWh_NetAI2KWh_ImportAI3KWh_ExportAI4KVARh_Q1AI5KVARh_Q2AI6KVARh_Q3AI7KVARh_Q4AI8Net_KVAhAI9KVAh_ImportAI10KVAh_ExportAI11KW_TotalAI12KVAR_TotalAI13KVA_TotalAI14PF_TotalAI15Volts_LL_AvgAI16Volts_LN_AvgAI17Current_AverageAI18FrequencyAI19KW_Present_DemandAI20KVAR_Present_DemandAI21KVA_Present_DemandAI22KW_Max_Demand_ImportAI23KVAR_Max_Demand_ImportAI24KVA_Max_Demand_ImportAI29Pulse_Count_1AI30Pulse_Count_2AI31KWh_Import_AAI32KWh_Import_BAI33KWh_Import_CAI34KWh_Export_AAI35KWh_Export_BAI36KWh_Export_CAI37KVARh_Q1_AAI38KVARh_Q1_BAI39KVARh_Q1_CAI40KVARh_Q2_AAI41KVARh_Q2_BAI42KVARh_Q2_CAI43KVARh_Q3_AAI44KVARh_Q3_BAI45KVARh_Q3_CAI46KVARh_Q4_AAI47KVARh_Q4_BAI48KVARh_Q4_CAI49KVAh_Import_AAI50KVAh_Import_BAI51KVAh_Import_CAI52KVAh_Export_AAI53KVAh_Export_BAI54KVAh_Export_CAI55KW_AAI56KW_BAI57KW_CAI58KVAR_AAI59KVAR_BAI60KVAR_CAI61KVA_AAI62KVA_BAI63KVA_CAI64PF_AAI65PF_BAI66PF_CAI67Volts_ABAI68Volts_BCAI69Volts_ACAI70Volts_ANAI71Volts_BNAI72Volts_CNAI73Current_AAI74Current_BAI75Current_CAI76Max_PowerAI78Energy_ResetsAI81Power_Up_CountAI83Alarm_BitmapAI84S1_StatusAI85S2_StatusAI86Relay_CounterAI87Relay_StatusAI88Real_Energy_Import_Tariff1AI89Real_Energy_Import_Tariff2AI90Real_Energy_Import_Tariff3AI91Real_Energy_Import_Tariff4AV1ConfigAV2System_TypeAV3CT_Ratio_PrimaryAV4CT_Ratio_SecondaryAV5PT_RatioAV6System_VoltageAV7Display_UnitsAV8Phase_Loss_Voltage_ThresholdAV9Phase_Loss_Imbalance_ThresholdAV10SubintervalsAV11Subinterval_LengthAV12S1_Control_modeAV13S2_Control_modeAV14Relay_control_modeAV15Relay_Behavior_modeAV16Relay_Output_Enable_DisableAV17Applicable_Multi_TariffAV18Mode_of_LEDAV19ChannelAV20Pulse_weightAV21PT_PrimaryAV22PT_SecondaryAV23Demand_MethodAV24Demand_Interval_DurationAV25Sub_Interval_DurationAV26Relay_TimedMode_TimeAV27Input_Metering_Ch1_PulseWeightAV28Input_Metering_Ch2_PulseWeightAV29Nominal_FrequencyAV30VT_NumberAV31CT_NumberAV32VT_Connection_TypeAV33Multi_Tarrif_Control_ModeBI1Volts_Error_ABI2Volts_Error_BBI3Volts_Error_CBI4Current_Error_ABI5Current_Error_BBI6Current_Error_CBI7Frequency_ErrorBI9Phase_Loss_ABI10Phase_Loss_BBI11Phase_Loss_CBI12Low_PF_ABI13Low_PF_BBI14Low_PF_CBI15Energy_OverRunBI16Energy_Config_Err
Integration notes
- Taken from the E71 PICS, which lists object identifiers and names only; it prints no units or descriptions, so units are left blank and descriptions are our reading of the names.
- Reserved objects (AI 25-28, 77, 79, 80, 82; BI 8, 17) are left out.
- Access per the PICS: Analog Input and Binary Input present values are read-only; Analog Value present values are writable.
- The PICS also lists Trend Log objects without instances or names; they are not listed here.
- AV 33 is printed Multi_Tarrif_Control_Mode (spelling as printed).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the E71 series energy meter (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Veris E71 series energy meter (BACnet IP)
How many BACnet points does the Veris E71 series energy meter (BACnet IP) have?
This list has 131 BACnet objects: 83 analog inputs, 33 analog values, 15 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Veris E71 series energy meter (BACnet IP) BACnet points are writable?
33 of the 131 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Veris E71 series energy meter (BACnet IP) BACnet documentation?
Veris does not publish it on its own website. This list comes from E71 - Protocol Implementation Conformance Statement, revision 2024-08-06, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/veris%20industries/PICS_e71_pics.pdf. Ask Veris or its representative for the current revision.
What are the minimum BACnet points to integrate the Veris E71 series energy meter (BACnet IP)?
Start with AI 2 KWh_Import (Real energy import); AI 1 KWh_Net (Net real energy (import minus export)); AI 11 KW_Total (Total real power); AI 19 KW_Present_Demand (Real power present demand); AI 14 PF_Total (Total power factor); AI 15 Volts_LL_Avg (Average line-line voltage); AI 17 Current_Average (Average current); AI 83 Alarm_Bitmap (All alert bits as one number).
How do I check these points on the real E71 series energy meter (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Veris BACnet points lists
- Duct air quality sensor (CO2, VOC, PM, humidity, temperature)
Veris CD2 Protocol Series duct / plant-room air quality sensor
Veris CD2 Protocol Series duct and plant-room air quality sensors (and the Schneider SpaceLogic SCD2 twin) set to BACnet MS/TP.
Also known as: CD2, CD2 Protocol, CD2XPXXXX, Plant Room Air Quality Unit, SpaceLogic SCD2, SCD2 Series, GEX55250, GEX55240 - Indoor air quality sensor (CO2, VOC, temperature, humidity)
Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor
Veris CW2 Protocol Series wall air quality sensors, and the identical Schneider SpaceLogic SLP Air Quality Series, on BACnet MS/TP.
Also known as: CW2, CW2 Protocol, SpaceLogic SLP Air Quality, SLP Series Air Quality, Z207902, Living Space Room Unit - Room CO2 sensor (wall)
Veris CWLP / CWXP wall CO2 sensor with BACnet MS/TP (older generation)
Veris CWLP and CWXP wall CO2 sensors with optional humidity, temperature and slider, set to BACnet MS/TP.
Also known as: CWLP, CWXP, CWxP, CWLP2TX3, CWxPxxx, Veris CWxP Environmental Sensor, Z205597 - Power and energy meter
Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP)
Veris E50H2 and E50H5 DIN-rail power and energy meters with BACnet MS/TP; the E50H5 adds data logging and a real-time clock alert.
Also known as: E50H2, E50H5, E50H2A, E50H5A, Veris E50, E50Hx, ZL0071 - Power and energy meter (bi-directional)
Veris E51H2 / E51H5 bi-directional compact power and energy meter (BACnet MS/TP)
Veris E51H2 and E51H5 DIN-rail three-phase meters with BACnet MS/TP that measure import and export energy; the E51H5 adds data logging.
Also known as: E51H2, E51H5, Veris E51, E51Hx, E51 Series, ZL0109 - Gas detection sensor (wall platform)
Veris GWNP Series wall gas sensor platform (AG sensors)
Veris GWNP wall-mounted gas platforms fitted with a Veris AG Series gas sensor, on BACnet MS/TP.
Also known as: GWNP, GWNPxx, GWN, Veris gas platform BACnet, AG Series gas sensor - Duct humidity and temperature sensor
Veris HD2 Protocol Series duct humidity / temperature sensor
Veris HD2 Protocol Series duct and plant-room humidity/temperature sensors (and the Schneider SpaceLogic SHD2 twin) set to BACnet MS/TP.
Also known as: HD2, HD2 Protocol, HD2XPXXXX, Plant Room Humidity and Temperature Unit, SpaceLogic SHD2, SHD2 Series, GEX55253, GEX55243 - Room humidity and temperature sensor (wall)
Veris HW2 Protocol Series humidity and temperature room sensor
Veris HW2 Protocol Series wall humidity/temperature sensors (optional touchscreen) set to BACnet MS/TP.
Also known as: HW2, HW2 Protocol, HW2TP2A, Living Space Room Unit, Veris HW2 BACnet - Indoor air quality sensor (PM, CO2, VOC, temperature, humidity)
Veris PMW Protocol Series particulate (PM), CO2 and VOC room sensor
Veris PMW Protocol Series wall air quality sensors, and the identical Schneider SpaceLogic SLP PM Series, on BACnet MS/TP.
Also known as: PMW, PMW Protocol, SpaceLogic SLP PM, SLP Series PM, ZL0199, Veris PM sensor BACnet - Room temperature sensor (wall)
Veris TW2 Protocol Series temperature room sensor
Veris TW2 Protocol Series wall temperature sensors (optional touchscreen) set to BACnet MS/TP.
Also known as: TW2, TW2 Protocol, Living Space Room Unit, Veris TW2 BACnet
Source: E71 - Protocol Implementation Conformance Statement · rev. 2024-08-06. Object names, instances and units are reproduced as published; descriptions are our own.