Power and energy meter · BACnet points list

Veris E71 series energy meter (BACnet IP) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

The E71 is a compact three-phase DIN-rail meter with two Ethernet ports and native BACnet IP, Modbus TCP and SNMP. Its object list is read-only Analog Inputs for energy (net, import, export, per quadrant and per phase), power, demand, volts, amps, power factor, frequency, pulse counts, input/relay status and four tariff registers, writable Analog Values for setup, and alert Binary Inputs.

This page lists 131 BACnet objects for the Veris E71 series energy meter (BACnet IP) — 33 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Veris’s documentation hosted by BACnet International, not by Veris itself, so treat it as unofficial.

Manufacturer
Veris
Model
E71 series energy meter (BACnet IP)
Equipment
Power and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
131 (33 writable)
Transport
BACnet IP
Firmware
Firmware 1.9.0, application 111.241.298 (PICS)
Also known as
E71, E71E3, E71E3A, E71E3X, E71E3AX, Veris E71, E71 Series Energy Meter
Source document
E71 - Protocol Implementation Conformance Statement · rev. 2024-08-06 (unofficial copy, hosted by BACnet International)
Download CSV 131 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Veris’s current documentation and the live device before use. Not official Veris information. Terms of use.

BMS integration notes: Veris E71 series energy meter (BACnet IP)

Integration in brief

Give the meter an IP address and device instance, set system type, CT and PT values in the AV setup objects (or on the meter), then trend energy and real power and watch the alert BIs or AI 83 Alarm_Bitmap.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 2KWh_ImportReal energy importRead
AI 1KWh_NetNet real energy (import minus export)Read
AI 11KW_TotalTotal real powerRead
AI 19KW_Present_DemandReal power present demandRead
AI 14PF_TotalTotal power factorRead
AI 15Volts_LL_AvgAverage line-line voltageRead
AI 17Current_AverageAverage currentRead
AI 83Alarm_BitmapAll alert bits as one numberRead

Network setup

Watch out for

Veris E71 series energy meter (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

131 of 131 shown
Type
Binary
Access
Show
Veris E71 series energy meter (BACnet IP) BACnet Points List
DescriptionStates
AImin1KWh_NetNet real energy (import - export)Read
AImin2KWh_ImportReal energy importRead
AI3KWh_ExportReal energy exportRead
AI4KVARh_Q1KVARh Q1Read
AI5KVARh_Q2KVARh Q2Read
AI6KVARh_Q3KVARh Q3Read
AI7KVARh_Q4KVARh Q4Read
AI8Net_KVAhNet apparent energyRead
AI9KVAh_ImportKVAh ImportRead
AI10KVAh_ExportKVAh ExportRead
AImin11KW_TotalTotal real powerRead
AI12KVAR_TotalTotal reactive powerRead
AI13KVA_TotalTotal apparent powerRead
AImin14PF_TotalTotal power factorRead
AImin15Volts_LL_AvgAverage line-line voltageRead
AI16Volts_LN_AvgAverage line-neutral voltageRead
AImin17Current_AverageAverage currentRead
AI18FrequencyFrequencyRead
AImin19KW_Present_DemandReal power present demandRead
AI20KVAR_Present_DemandReactive power present demandRead
AI21KVA_Present_DemandApparent power present demandRead
AI22KW_Max_Demand_ImportReal power max demand, importRead
AI23KVAR_Max_Demand_ImportReactive power max demand, importRead
AI24KVA_Max_Demand_ImportApparent power max demand, importRead
AI29Pulse_Count_1Digital input 1 pulse countRead
AI30Pulse_Count_2Digital input 2 pulse countRead
AI31KWh_Import_AKWh Import ARead
AI32KWh_Import_BKWh Import BRead
AI33KWh_Import_CKWh Import CRead
AI34KWh_Export_AKWh Export ARead
AI35KWh_Export_BKWh Export BRead
AI36KWh_Export_CKWh Export CRead
AI37KVARh_Q1_AKVARh Q1 ARead
AI38KVARh_Q1_BKVARh Q1 BRead
AI39KVARh_Q1_CKVARh Q1 CRead
AI40KVARh_Q2_AKVARh Q2 ARead
AI41KVARh_Q2_BKVARh Q2 BRead
AI42KVARh_Q2_CKVARh Q2 CRead
AI43KVARh_Q3_AKVARh Q3 ARead
AI44KVARh_Q3_BKVARh Q3 BRead
AI45KVARh_Q3_CKVARh Q3 CRead
AI46KVARh_Q4_AKVARh Q4 ARead
AI47KVARh_Q4_BKVARh Q4 BRead
AI48KVARh_Q4_CKVARh Q4 CRead
AI49KVAh_Import_AKVAh Import ARead
AI50KVAh_Import_BKVAh Import BRead
AI51KVAh_Import_CKVAh Import CRead
AI52KVAh_Export_AKVAh Export ARead
AI53KVAh_Export_BKVAh Export BRead
AI54KVAh_Export_CKVAh Export CRead
AI55KW_AKW ARead
AI56KW_BKW BRead
AI57KW_CKW CRead
AI58KVAR_AKVAR ARead
AI59KVAR_BKVAR BRead
AI60KVAR_CKVAR CRead
AI61KVA_AKVA ARead
AI62KVA_BKVA BRead
AI63KVA_CKVA CRead
AI64PF_APF ARead
AI65PF_BPF BRead
AI66PF_CPF CRead
AI67Volts_ABVolts ABRead
AI68Volts_BCVolts BCRead
AI69Volts_ACVolts ACRead
AI70Volts_ANVolts ANRead
AI71Volts_BNVolts BNRead
AI72Volts_CNVolts CNRead
AI73Current_ACurrent ARead
AI74Current_BCurrent BRead
AI75Current_CCurrent CRead
AI76Max_PowerFull-scale powerRead
AI78Energy_ResetsCount of energy resetsRead
AI81Power_Up_CountCount of power-upsRead
AImin83Alarm_BitmapAll alert bits as one numberRead
AI84S1_StatusDigital input 1 statusRead
AI85S2_StatusDigital input 2 statusRead
AI86Relay_CounterRelay operation countRead
AI87Relay_StatusRelay output statusRead
AI88Real_Energy_Import_Tariff1Real energy import, tariff 1Read
AI89Real_Energy_Import_Tariff2Real energy import, tariff 2Read
AI90Real_Energy_Import_Tariff3Real energy import, tariff 3Read
AI91Real_Energy_Import_Tariff4Real energy import, tariff 4Read
AV1ConfigConfiguration registerWrite
AV2System_TypeSystem type (setting)Write
AV3CT_Ratio_PrimaryCt ratio primary (setting)Write
AV4CT_Ratio_SecondaryCt ratio secondary (setting)Write
AV5PT_RatioPt ratio (setting)Write
AV6System_VoltageSystem voltage (setting)Write
AV7Display_UnitsDisplay units (setting)Write
AV8Phase_Loss_Voltage_ThresholdPhase loss voltage threshold (setting)Write
AV9Phase_Loss_Imbalance_ThresholdPhase loss imbalance threshold (setting)Write
AV10SubintervalsSubintervals (setting)Write
AV11Subinterval_LengthSubinterval length (setting)Write
AV12S1_Control_modeS1 control mode (setting)Write
AV13S2_Control_modeS2 control mode (setting)Write
AV14Relay_control_modeRelay control mode (setting)Write
AV15Relay_Behavior_modeRelay behavior mode (setting)Write
AV16Relay_Output_Enable_DisableRelay output enable disable (setting)Write
AV17Applicable_Multi_TariffApplicable multi tariff (setting)Write
AV18Mode_of_LEDMode of led (setting)Write
AV19ChannelChannel (setting)Write
AV20Pulse_weightPulse weight (setting)Write
AV21PT_PrimaryPt primary (setting)Write
AV22PT_SecondaryPt secondary (setting)Write
AV23Demand_MethodDemand method (setting)Write
AV24Demand_Interval_DurationDemand interval duration (setting)Write
AV25Sub_Interval_DurationSub interval duration (setting)Write
AV26Relay_TimedMode_TimeRelay timedmode time (setting)Write
AV27Input_Metering_Ch1_PulseWeightInput metering ch1 pulseweight (setting)Write
AV28Input_Metering_Ch2_PulseWeightInput metering ch2 pulseweight (setting)Write
AV29Nominal_FrequencyNominal frequency (setting)Write
AV30VT_NumberVt number (setting)Write
AV31CT_NumberCt number (setting)Write
AV32VT_Connection_TypeVt connection type (setting)Write
AV33Multi_Tarrif_Control_ModeMulti tarrif control mode (setting)Write
BI1Volts_Error_AVolts Error A alertRead
BI2Volts_Error_BVolts Error B alertRead
BI3Volts_Error_CVolts Error C alertRead
BI4Current_Error_ACurrent Error A alertRead
BI5Current_Error_BCurrent Error B alertRead
BI6Current_Error_CCurrent Error C alertRead
BI7Frequency_ErrorFrequency Error alertRead
BI9Phase_Loss_APhase Loss A alertRead
BI10Phase_Loss_BPhase Loss B alertRead
BI11Phase_Loss_CPhase Loss C alertRead
BI12Low_PF_ALow PF A alertRead
BI13Low_PF_BLow PF B alertRead
BI14Low_PF_CLow PF C alertRead
BI15Energy_OverRunEnergy OverRun alertRead
BI16Energy_Config_ErrEnergy Config Err alertRead
Object ID lookup: Veris E71 series energy meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the E71 series energy meter (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Veris E71 series energy meter (BACnet IP)

How many BACnet points does the Veris E71 series energy meter (BACnet IP) have?

This list has 131 BACnet objects: 83 analog inputs, 33 analog values, 15 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Veris E71 series energy meter (BACnet IP) BACnet points are writable?

33 of the 131 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Veris E71 series energy meter (BACnet IP) BACnet documentation?

Veris does not publish it on its own website. This list comes from E71 - Protocol Implementation Conformance Statement, revision 2024-08-06, a copy hosted by BACnet International at https://www.bacnetinternational.net/catalog/manu/veris%20industries/PICS_e71_pics.pdf. Ask Veris or its representative for the current revision.

What are the minimum BACnet points to integrate the Veris E71 series energy meter (BACnet IP)?

Start with AI 2 KWh_Import (Real energy import); AI 1 KWh_Net (Net real energy (import minus export)); AI 11 KW_Total (Total real power); AI 19 KW_Present_Demand (Real power present demand); AI 14 PF_Total (Total power factor); AI 15 Volts_LL_Avg (Average line-line voltage); AI 17 Current_Average (Average current); AI 83 Alarm_Bitmap (All alert bits as one number).

How do I check these points on the real E71 series energy meter (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Veris BACnet points lists

Source: E71 - Protocol Implementation Conformance Statement · rev. 2024-08-06. Object names, instances and units are reproduced as published; descriptions are our own.