Room temperature sensor (wall) · BACnet points list
Veris TW2 Protocol Series temperature room sensor BACnet points list
Updated 6 November 2026
The TW2 is a wall temperature sensor on BACnet MS/TP (or Modbus). It reports room temperature; touchscreen models add a temperature setpoint, fan speed, occupancy override and display settings, all writable.
This page lists 11 BACnet objects for the Veris TW2 Protocol Series temperature room sensor — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Veris’s own free documentation, linked below.
- Manufacturer
- Veris
- Model
- TW2 Protocol Series temperature room sensor
- Equipment
- Room temperature sensor (wall)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 11 (10 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- Vendor ID + MS/TP address (nnn)
- Also known as
- TW2, TW2 Protocol, Living Space Room Unit, Veris TW2 BACnet
Reference only, provided as-is: verify against Veris’s current documentation and the live device before use. Not official Veris information. Terms of use.
BMS integration notes: Veris TW2 Protocol Series temperature room sensor
Set the MS/TP address and BACnet mode on the DIP switches, then read room temperature; on touchscreen models also the setpoint, fan speed and override.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Room Temperature | Room temperature | Read |
| AV 1 | Temperature Setpoint* | Occupant temperature setpoint, 0-50 | Write |
| BV 5 | Occupancy Override | Override button state: active = not occupied | Write |
| MV 2 | Fan Speed* | Occupant fan speed selection, 1-5 | Write |
Network setup
- BACnet MS/TP on RS-485: DIP switch ADDRESS positions 1-7 set the MAC (0-127 for BACnet), position 8 selects BACnet or Modbus.
- Baud rates for BACnet: 9600, 19200, 38400, 76800, set on the CONFIG DIP switch.
- Device instance = Vendor_ID followed by the MS/TP address (e.g. 133nnn); it can be rewritten in the device object.
Watch out for
- Occupancy Override logic is inverted: active means not occupied.
Veris TW2 Protocol Series temperature room sensor BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Room Temperature | Room temperature | °C or °F | Read | |
| AVmin | 1 | Temperature Setpoint* | Temperature setpoint, 0-50 | °C | Write | |
| AV | 7 | Temperature Offset | Offset added to temperature reading, -5 to 5 | Write | ||
| BV | 2 | Touch Disable* | Disables touch response when active | Write | 0=Touch enabled, 1=Touch disabled | |
| BV | 4 | Temperature Units* | Display units | Write | 0=Celsius, 1=Fahrenheit | |
| BVmin | 5 | Occupancy Override | Occupancy override (active = room not occupied) | Write | 0=Occupied, 1=Not occupied | |
| BV | 6 | Screen Timeout* | Enables screen timeout | Write | 0=Disabled, 1=Enabled | |
| BV | 11 | Select Temperature Display* | Main screen shows setpoint (active) or room temperature | Write | 0=Room temp on main screen, 1=Setpoint on main screen | |
| BV | 13 | Display Setpoint* | Shows temperature setpoint on home screen | Write | 0=Hidden, 1=Shown | |
| MV | 1 | Screen Color Set* | Screen color theme, 1-4 | Write | ||
| MVmin | 2 | Fan Speed* | Fan speed selection, 1-5 | Write |
No points match these filters.
Object ID lookup: Veris TW2 Protocol Series temperature room sensor point IDs by name
Integration notes
- Names with * are preserved through power outages; avoid writing them cyclically.
- Touchscreen setpoint, fan speed, display and color objects only matter on touchscreen models.
- Occupancy Override is active when the room is NOT occupied (as printed).
- Source: TW2 Protocol Series Installation Guide Z207938-0H, objects table p6-7.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TW2 Protocol Series temperature room sensor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Veris TW2 Protocol Series temperature room sensor
How many BACnet points does the Veris TW2 Protocol Series temperature room sensor have?
This list has 11 BACnet objects: 1 analog input, 2 analog values, 6 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Veris TW2 Protocol Series temperature room sensor BACnet points are writable?
10 of the 11 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Veris TW2 Protocol Series temperature room sensor BACnet documentation?
The source is TW2 Protocol Series Installation Guide (Z207938-0H), revision 2024-06, published free by Veris at https://download.se.com/files?p_Doc_Ref=Z207938.
What are the minimum BACnet points to integrate the Veris TW2 Protocol Series temperature room sensor?
Start with AI 1 Room Temperature (Room temperature); AV 1 Temperature Setpoint* (Occupant temperature setpoint, 0-50); BV 5 Occupancy Override (Override button state: active = not occupied); MV 2 Fan Speed* (Occupant fan speed selection, 1-5).
How do I check these points on the real TW2 Protocol Series temperature room sensor?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Veris BACnet points lists
- Indoor air quality sensor (CO2, VOC, temperature, humidity)
Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor
Veris CW2 Protocol Series wall air quality sensors, and the identical Schneider SpaceLogic SLP Air Quality Series, on BACnet MS/TP.
Also known as: CW2, CW2 Protocol, SpaceLogic SLP Air Quality, SLP Series Air Quality, Z207902, Living Space Room Unit - Power and energy meter
Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP)
Veris E50H2 and E50H5 DIN-rail power and energy meters with BACnet MS/TP; the E50H5 adds data logging and a real-time clock alert.
Also known as: E50H2, E50H5, E50H2A, E50H5A, Veris E50, E50Hx, ZL0071 - Gas detection sensor (wall platform)
Veris GWNP Series wall gas sensor platform (AG sensors)
Veris GWNP wall-mounted gas platforms fitted with a Veris AG Series gas sensor, on BACnet MS/TP.
Also known as: GWNP, GWNPxx, GWN, Veris gas platform BACnet, AG Series gas sensor - Room humidity and temperature sensor (wall)
Veris HW2 Protocol Series humidity and temperature room sensor
Veris HW2 Protocol Series wall humidity/temperature sensors (optional touchscreen) set to BACnet MS/TP.
Also known as: HW2, HW2 Protocol, HW2TP2A, Living Space Room Unit, Veris HW2 BACnet - Indoor air quality sensor (PM, CO2, VOC, temperature, humidity)
Veris PMW Protocol Series particulate (PM), CO2 and VOC room sensor
Veris PMW Protocol Series wall air quality sensors, and the identical Schneider SpaceLogic SLP PM Series, on BACnet MS/TP.
Also known as: PMW, PMW Protocol, SpaceLogic SLP PM, SLP Series PM, ZL0199, Veris PM sensor BACnet
Source: TW2 Protocol Series Installation Guide · Z207938-0H · rev. 2024-06. Object names, instances and units are reproduced as published; descriptions are our own.