Indoor air quality sensor (CO2, VOC, temperature, humidity) · BACnet points list

Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor BACnet points list

Updated 6 November 2026

Short answer

The CW2 wall sensor measures temperature, humidity, CO2 and VOC and computes dew point, reported over BACnet MS/TP or Modbus. Writable values cover touchscreen setpoints, CO2 stoplight limits, offsets, CO2 calibration and display options.

This page lists 27 BACnet objects for the Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor — 22 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Veris’s own free documentation, linked below.

Manufacturer
Veris
Model
CW2 Protocol Series CO2, VOC, humidity and temperature room sensor
Equipment
Indoor air quality sensor (CO2, VOC, temperature, humidity)
Equipment type
Thermostats, sensors & meters
BACnet objects
27 (22 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
Vendor ID + MS/TP address (nnn)
Also known as
CW2, CW2 Protocol, SpaceLogic SLP Air Quality, SLP Series Air Quality, Z207902, Living Space Room Unit
Source document
CW2 Protocol Series Installation Guide · Z207932-0N · rev. 2026-03
Download CSV 27 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Veris’s current documentation and the live device before use. Not official Veris information. Terms of use.

BMS integration notes: Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor

Integration in brief

Set the MS/TP address and BACnet mode on the DIP switches, then read CO2, VOC, temperature and humidity. Offsets and limits are preserved settings to write once.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3CO2 SensorCO2 concentration, ppmRead
AI 1Room TemperatureRoom temperatureRead
AI 2Room HumidityRoom relative humidity, %Read
AI 4VOC SensorVOC levelRead

Network setup

Watch out for

Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

27 of 27 shown
Type
BinaryMulti-state
Access
Show
Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor BACnet Points List
DescriptionStates
AImin1Room TemperatureRoom temperature°C or °FRead
AImin2Room HumidityRoom relative humidity%RHRead
AImin3CO2 SensorCO2 concentrationppmRead
AImin4VOC SensorVOC levelRead
AI9Dew PointDew point temperature°C or °FRead
AV1Temperature Setpoint*Temperature setpoint, 0-50°CWrite
AV2Humidity Setpoint*Humidity setpoint, 0-100%RHWrite
AV3CO2 Yellow Limit*CO2 level for green-to-yellow screen, 400-10000ppmWrite
AV4CO2 Red Limit*CO2 level for yellow-to-red screen, 400-10000ppmWrite
AV7Temperature Offset*Offset added to temperature reading, -5 to 5Write
AV8Humidity Offset*Offset added to humidity reading, -10 to 10Write
AV9CO2 Offset*Offset added to CO2, -250 to 250ppmWrite
AV10VOC Offset*Offset added to VOC, -500 to 500Write
BV1CO2 Stoplight*Enables the CO2 stoplight screen colorsWrite0=Disabled, 1=Enabled
BV2Touch Disable*Disables touch response when activeWrite0=Touch enabled, 1=Touch disabled
BV3CO2 ABC Cal*Enables automatic baseline calibrationWrite0=Disabled, 1=Enabled
BV4Temperature Units*Display unitsWrite0=Celsius, 1=Fahrenheit
BV5Occupancy OverrideOccupancy override (active = room not occupied)Write0=Occupied, 1=Not occupied
BV6Screen Timeout*Enables screen timeoutWrite0=Disabled, 1=Enabled
BV7Display Humidity*Shows humidity on the screenWrite0=Hidden, 1=Shown
BV8Display CO2*Shows CO2 on the screenWrite0=Hidden, 1=Shown
BV9Display VOC*Shows VOC on the screenWrite0=Hidden, 1=Shown
BV10CO2 FRC 400Active sets 400 ppm CO2 baseline (forced calibration)Write0=No action, 1=Set 400 ppm baseline
BV11Select Temperature Display*Main screen shows setpoint (active) or room temperatureWrite0=Room temp on main screen, 1=Setpoint on main screen
BV13Display Setpoint*Shows temperature setpoint on home screenWrite0=Hidden, 1=Shown
MV1Screen Color Set*Screen color theme, 1-4Write
MV2Fan Speed*Fan speed selection, 1-5Write
Object ID lookup: Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CW2 Protocol Series CO2, VOC, humidity and temperature room sensor and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor

How many BACnet points does the Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor have?

This list has 27 BACnet objects: 5 analog inputs, 8 analog values, 12 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor BACnet points are writable?

22 of the 27 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor BACnet documentation?

The source is CW2 Protocol Series Installation Guide (Z207932-0N), revision 2026-03, published free by Veris at https://download.se.com/files?p_Doc_Ref=Z207932.

What are the minimum BACnet points to integrate the Veris CW2 Protocol Series CO2, VOC, humidity and temperature room sensor?

Start with AI 3 CO2 Sensor (CO2 concentration, ppm); AI 1 Room Temperature (Room temperature); AI 2 Room Humidity (Room relative humidity, %); AI 4 VOC Sensor (VOC level).

How do I check these points on the real CW2 Protocol Series CO2, VOC, humidity and temperature room sensor?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.