  3. Veris
  4. E50H2 / E50H5 compact power and energy meter (BACnet MS/TP)

Power and energy meter · BACnet points list

Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The E50H2 and E50H5 are DIN-rail three-phase power meters with a BACnet MS/TP port. Measurements are Analog Inputs (energy, power, demand, volts, amps, power factor, frequency), setup is in eleven writable Analog Values (system type, CT and PT ratios, system voltage, demand intervals), and alerts are Binary Inputs that also roll up into AI 52. The E50H5 also has three Trend_Log objects.

This page lists 78 BACnet objects for the Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Veris’s own free documentation, linked below.

Manufacturer
Veris
Model
E50H2 / E50H5 compact power and energy meter (BACnet MS/TP)
Equipment
Power and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
78 (11 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
E50H2, E50H5, E50H2A, E50H5A, Veris E50, E50Hx, ZL0071
Source document
E50H2, E50H5 Compact Power and Energy Meters with BACnet MS/TP Support, Installation Guide · ZL0071-0F · rev. 2018-08
Download CSV 78 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Veris’s current documentation and the live device before use. Not official Veris information. Terms of use.

BMS integration notes: Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP)

Integration in brief

Set the MS/TP address, baud and device ID on the meter screens, then set system type (AV 2), CT size (AV 3) and system voltage (AV 6) to match the service. Trend total energy (AI 1) and real power (AI 2), and watch the alert BIs or AI 52.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1EnergyTotal real energy, kWhRead
AI 2kW_TotalTotal real power, kWRead
AI 34KW_Present_DemandPresent real power demand, kWRead
AI 5PF_TotalTotal power factorRead
AI 6Volts_LL_AvgAverage line-line voltageRead
AI 8Current_AvgAverage current, ARead
AI 25FrequencyFrequency, HzRead
AI 52Alarm_BitmapAll alert bits as one numberRead

Network setup

Watch out for

Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

78 of 78 shown
Type
Binary
Access
Show
Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1EnergyReal energy consumptionkWhRead
AImin2kW_TotalTotal real powerkWRead
AI3kVAR_TotalTotal reactive powerkVARRead
AI4kVA_TotalTotal apparent powerkVARead
AImin5PF_TotalTotal power factorRead
AImin6Volts_LL_AvgAverage line-line voltageVRead
AI7Volts_LN_AvgAverage line-neutral voltageVRead
AImin8Current_AvgAverage currentARead
AI9kW_AReal power phase AkWRead
AI10kW_BReal power phase BkWRead
AI11kW_CReal power phase CkWRead
AI12PF_APower factor phase ARead
AI13PF_BPower factor phase BRead
AI14PF_CPower factor phase CRead
AI15Volts_ABVoltage A-BVRead
AI16Volts_BCVoltage B-CVRead
AI17Volts_ACVoltage A-CVRead
AI18Volts_ANVoltage A-NVRead
AI19Volts_BNVoltage B-NVRead
AI20Volts_CNVoltage C-NVRead
AI21Current_ACurrent phase AARead
AI22Current_BCurrent phase BARead
AI23Current_CCurrent phase CARead
AI24Reserved_AI24ReservedRead
AImin25FrequencyFrequency (phase A)HzRead
AI26kVAhApparent energy consumptionkVAhRead
AI27kVARhReactive energy consumptionkVARhRead
AI28kVA_AApparent power phase AkVARead
AI29kVA_BApparent power phase BkVARead
AI30kVA_CApparent power phase CkVARead
AI31KVAR_AReactive power phase AkVARRead
AI32KVAR_BReactive power phase BkVARRead
AI33KVAR_CReactive power phase CkVARRead
AImin34KW_Present_DemandReal power present demandkWRead
AI35KVAR_Present_DemandReactive power present demandkVARRead
AI36KVA_Present_DemandApparent power present demandkVARead
AI37KW_Max_DemandReal power maximum demandkWRead
AI38KVAR_Max_DemandReactive power maximum demandkVARRead
AI39KVA_Max_DemandApparent power maximum demandkVARead
AI40Pulse_Count_1Pulse input 1 count (named Pulse Count on the E50H2)Read
AI41Pulse_Count_2Pulse input 2 count (E50H5; reserved on the E50H2)Read
AI42KWH_AReal energy phase AkWhRead
AI43KWH_BReal energy phase BkWhRead
AI44KWH_CReal energy phase CkWhRead
AI45Max_PowerTheoretical maximum system powerkWRead
AI46Reserved_AI46ReservedRead
AI47Energy ResetsCount of energy accumulator resetsRead
AI48Reserved_AI48ReservedRead
AI49Reserved_AI49ReservedRead
AI50Power Up CountPower-up counterRead
AI51Ouput ConfigOutput configuration (E50H2 = 11, E50H5 = 10)Read
AImin52Alarm_BitmapAll BI alerts as one number (BI1 = bit 0)Read
AV1ConfigCommand register: energy, demand and pulse resetsWrite
AV2System_TypeSystem type: 10, 11, 12, 31 or 40 (default 40)Write
AV3CT_Ratio_PrimaryCT primary current (default 100)AWrite
AV4CT_Ratio_SecondaryCT secondary: 1 = 1 V, 3 = 1/3 VWrite
AV5PT_RatioPT ratio (1 = no PT)Write
AV6System_VoltageSystem voltage (default 600)VWrite
AV7Display_UnitsDisplay units: 0 = IEC, 1 = IEEEWrite
AV8Phase_Loss_Voltage_ThresholdPhase loss voltage threshold (default 10)%Write
AV9Phase_Loss_Imbalance_ThresholdPhase loss imbalance threshold (default 25)%Write
AV10SubintervalsSub-intervals per demand interval (default 1)Write
AV11Subinterval_LengthSub-interval length in 0.01 s (default 90000 = 15 min)Write
BI1Volts_Error_AVoltage out of range phase ARead0=INACTIVE, 1=ACTIVE
BI2Volts_Error_BVoltage out of range phase BRead0=INACTIVE, 1=ACTIVE
BI3Volts_Error_CVoltage out of range phase CRead0=INACTIVE, 1=ACTIVE
BI4Current_Error_ACurrent out of range phase ARead0=INACTIVE, 1=ACTIVE
BI5Current_Error_ACurrent out of range phase B (name printed _A)Read0=INACTIVE, 1=ACTIVE
BI6Current_Error_ACurrent out of range phase C (name printed _A)Read0=INACTIVE, 1=ACTIVE
BI7Frequency_ErrorFrequency out of rangeRead0=INACTIVE, 1=ACTIVE
BI8Reserved_BI8Reserved, returns inactiveRead0=INACTIVE, 1=ACTIVE
BI9Phase_Loss_APhase loss phase ARead0=INACTIVE, 1=ACTIVE
BI10Phase_Loss_BPhase loss phase BRead0=INACTIVE, 1=ACTIVE
BI11Phase_Loss_CPhase loss phase CRead0=INACTIVE, 1=ACTIVE
BI12Power_Factor_APower factor below 50 % phase ARead0=INACTIVE, 1=ACTIVE
BI13Power_Factor_BPower factor below 50 % phase BRead0=INACTIVE, 1=ACTIVE
BI14Power_Factor_CPower factor below 50 % phase CRead0=INACTIVE, 1=ACTIVE
BI15RTC_ResetReal-time clock reset (E50H5 only)Read0=INACTIVE, 1=ACTIVE
Object ID lookup: Veris E50H2 / E50H5 Energy Meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the E50H2 / E50H5 compact power and energy meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP)

How many BACnet points does the Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP) have?

This list has 78 BACnet objects: 52 analog inputs, 11 analog values, 15 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP) BACnet points are writable?

11 of the 78 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP) BACnet documentation?

The source is E50H2, E50H5 Compact Power and Energy Meters with BACnet MS/TP Support, Installation Guide (ZL0071-0F), revision 2018-08, published free by Veris at https://www.veris.com/ASSETS/DOCUMENTS/ITEMS/EN/e50hx_full_i0f2.pdf.

What are the minimum BACnet points to integrate the Veris E50H2 / E50H5 compact power and energy meter (BACnet MS/TP)?

Start with AI 1 Energy (Total real energy, kWh); AI 2 kW_Total (Total real power, kW); AI 34 KW_Present_Demand (Present real power demand, kW); AI 5 PF_Total (Total power factor); AI 6 Volts_LL_Avg (Average line-line voltage); AI 8 Current_Avg (Average current, A); AI 25 Frequency (Frequency, Hz); AI 52 Alarm_Bitmap (All alert bits as one number).

How do I check these points on the real E50H2 / E50H5 compact power and energy meter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Veris BACnet points lists

Source: E50H2, E50H5 Compact Power and Energy Meters with BACnet MS/TP Support, Installation Guide · ZL0071-0F · rev. 2018-08. Object names, instances and units are reproduced as published; descriptions are our own.